Sensor Cable →SIB CSU Setting


Alm.Attr.
Power Cabinet Sensor X5 Door Alarm
Out-Relay:A6
Alm.Attr.
AC Power Off
Out-Relay:A3
Batt.Dischg.
Out-Relay:A4
Alm.Attr.
SMR.In comm.F
Out-Relay:A4
In-Relay Attr.
Battery Cabinet Air condition alarm X4(s4.48vp) state:open
Out-Relay:A2
Alm.Attr.
Batt.loop Broker
Out-Relay:A5
In-RelayAttr.
Battery Cabinet Sensor X4(s3&48VP) state:open
Out-Relay:A1
Hardware
Alarm Cable connection picture
Software
SIB← Alarm Cable Alarm module Alarm Name

X16(COM6.NO6) white and blue SA(0) Door control alarm

X15(COM3.NC3) white and orange SA(1) AC power-cut alarm

X15(COM4.NO4) white and green SA(2) Rectifier module alarm

X14(COM2.NO2) white and blown SA(3) Air condition

X16(COM5.NC5) white and grey SA(4) Battery alarm

X14(COM1.NC1) red and blue SA(5) Door control alarm

FCE(5) Smog

FCE(2) Door alarm

FCE(4) Flooding

FCE(2) Door alarm

FCE(2) Door alarm


ware
SA Alarm status

Alarm when closed

Alarm when open

Alarm when closed

Alarm when closed

Alarm when open

Alarm when open

Alarm when closed

Alarm when open

Alarm when closed

Alarm when open

Alarm when open


Hardware
Sensor Cable CSU Setting Alarm Cable connection picture
Door Sensor Cable(ET support)

Alm.Attr.
AC Power Off
Cable(SIB Board Relay:A2
connect DDF) Bat.Discharge
Relay:A3

Alm.Attr.
Cable(SIB Board SMR Alarm
connect DDF) Relay:A3

AC1 Cable(ET support)


AC2 Cable(ET support)
AC Controller Cable(ET support)
High temperature Cable(ET support)
Smog Cable(ET support)
Softwa
SIB Board DDF Alarm Cable Alarm module Alarm Name
white and blue SA(0) Door control alarm

X15(COM2.NO2) white and orange SA(1) AC power-cut alarm

X16(COM3.N03) white and green SA(2) Rectifier module alarm

DDF

white and blown SA(3) Air condition fault


white and grey SA(4) Air condition fault
red and blue SA(5) self-defined
red and orange SA(6) self-defined
red and green SA(7) Smog
Software
Dry contact description SA Alarm status
Door control alarm Alarm when closed

AC power-cut alarm Alarm when closed

Rectifier module alarm Alarm when closed

Air condition 1 Alarm when closed


Air condition 2 Alarm when closed
Air condition controller Alarm when closed
High Temp Alarm when closed
Smog Alarm when closed
Outdoor Site CSU Setting
System Para Battery Cap. -1#
150AH
Battery Cap. -2#
150AH
Battery Cap. -3#
Para.Set 150AH
Battery Cap. -4#
0AH

Batt.Para. Float Voltage


54.5 V
Equalized Voltage
56.8 V
Pre.Equ.Chg.Dura.
4 Hour
Chg.Curr.Coeff.
0.200C10
LLVD1 Voltage
45.0 V
LLVD2 Voltage
45.0 V
BLVD Voltage
43.2 V
te CSU Setting

This parameter refers to the


nominal battery capacity. It should
be set according to the actual
situation. Otherwise, normal battery
management cannot be performed. If Ctrl Setup Para
no batteries are configured, set
this parameter to 0.
Indoor Site CSU Setting
Sys Para Bat.1.Cap.
400AH This parameter refers to the nominal
Bat.2.Cap. battery capacity. It should be set
0 AH according to the actual situation.
Otherwise, normal battery management
Bat.3.Cap. cannot be performed. If no batteries
0 AH are configured, set this parameter to
Bat.4.Cap. 0.
0 AH

Batt Para Float Vol.


54.5 V
Equal Vol.
56.8 V
Cur. Limited
0.2 C
BatVol Min.
47 V
1-Shut Vol.
45 V
2-Shut Vol.
45 V