FEC Standard

Hardware
description

Micro
programmable
controller IPC
FEC-Standard with
rapid counter
inputs, flash disk
and powerful
@CHIP processor

Description
525 369
en 0105nh
Contents and general instructions

Author . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R. Müller

Editing . . . . . . . . . . . . . . . . . . . . . Documentation - Beck IPC

Layout . . . . . . . . . . . . . . . . . . . Festo AG & Co., Abtl. KG-GD

Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M. Müller

Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0105 nh

Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MANUAL-EN

Designation . . . . . . . . . . . . . . . . . . . . . . . . . . P.BE-FEC-S-SYS

Order No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525 369

©(Festo AG & Co., D-73726 Esslingen, 2001)


Internet: http://www.festo.com
E-Mail: service_international@festo .com

Transmission as well as reproduction of this document, utilization and communication of its


contents prohibited unless expressly permitted. Any contraventions ensue in the obligation
to compensation. All rights resulting from the entry of a patent, registered pattern or designs
are reserved.

Festo P.BE-FEC-S-SYS en 0105nh I


Contents and general instructions

II Festo P.BE-FEC-S-SYS en 0105nh


Contents and general instructions

Contents

Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Important information for the user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IX
The mechanical system structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X

1. Module overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

1.1 Overview of the module variants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3


1.2 Component description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.2.1 Module IPC FEC FC400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.2.2 Module IPC FEC FC440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1.2.3 Module IPC FEC FC520 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.2.4 Module IPC FEC FC560 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1.2.5 Module IPC FEC FC600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.2.6 Module IPC FEC FC620 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
1.2.7 Module IPC FEC FC640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
1.2.8 Module IPC FEC FC660 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13

2. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

2.1 Mounting the IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3


2.2 Top-hat rail mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.1 Procedure for top-hat rail mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.2 Procedure for top-hat rail dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.3 Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.3.1 Procedure for wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.3.2 Procedure for wall dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2.4 Combined mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.4.1 Procedure for combined mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.4.2 Procedure for combined dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.5 Further information on top-hat rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.6 Earthing the IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12

Festo P.BE-FEC-S-SYS en 0105nh III


Contents and general instructions

2.6.1 Earthing without a top-hat rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12


2.6.2 Prohibited earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.6.3 Top-hat rail earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
2.7 Important installation regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15

3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1

3.1 What you require for the hardware installation . . . . . . . . . . . . . . . . . . . . . . . 3-3


3.2 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.3 Pin assignment of the connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.1 Pin assignment of the digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.2 Pin assignment of the analog inputs and outputs . . . . . . . . . . . . . . . . . . . . . 3-6
3.3.3 Pin assignment of the power supply connector . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.3.4 Pin assignment of the communication interfaces (Ext/Com). . . . . . . . . . . . . 3-8
3.3.5 Pin assignment of the network connection (TP). . . . . . . . . . . . . . . . . . . . . . . 3-9
3.4 The communication interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.4.1 Proper use of the SM14/SM15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.4.2 Pin assignment of the programming cable PS1 ZK14 . . . . . . . . . . . . . . . . . . 3-11
3.5 Connection scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.5.1 Connection assignment of the digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.5.2 Connection assignment of the digital outputs . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.5.3 Connection assignment of the analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.5.4 Connection assignment of the analog outputs. . . . . . . . . . . . . . . . . . . . . . . . 3-18
3.5.5 Connection example for programming the IPC FEC-Standard. . . . . . . . . . . . 3-20
3.5.6 Connection example of a direct network connection (only Ethernet). . . . . . 3-21
3.5.7 Connection example of a network (10Base T) . . . . . . . . . . . . . . . . . . . . . . . . 3-22
3.5.8 Connection example of a power supply wiring. . . . . . . . . . . . . . . . . . . . . . . . 3-23
3.5.9 Options of the function selector switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6 Information on wiring the IPC FEC-Standard. . . . . . . . . . . . . . . . . . . . . . . . . . 3-27

4. First Steps / Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

4.1 First steps IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3


4.1.1 Connecting the IPC FEC-Standard to the power . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.1.2 Using the sensor actuator connector SAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.1.3 Connecting a sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7

IV Festo P.BE-FEC-S-SYS en 0105nh


Contents and general instructions

4.1.4 Connecting an actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11


4.1.5 Installing the programming software on your PC. . . . . . . . . . . . . . . . . . . . . . 4-13
4.1.6 The first project with the IPC FEC-Standard in FST. . . . . . . . . . . . . . . . . . . . . 4-14
4.1.7 Overview of retentive operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.1.8 The first project with the IPC FEC-Standard in MULTIPROG. . . . . . . . . . . . . . 4-24
4.2 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
4.3 Rapid counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
4.4 The incremental encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34

5. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1

5.1 Information on troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3


5.2 Errors / Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

A. Technical appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

A.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3


A.2 Output behavior at overload/shor t-circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
A.3 Block diagrams for digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . A-10
A.4 Block diagrams for analog inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . A-13

B. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

B.1 Accessories detailed information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3

C. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1

Festo P.BE-FEC-S-SYS en 0105nh V


Contents and general instructions

Proper use

The micro PLC (IPC FEC-Standard) documented in this manual


is intended exclusively for the following application:

– Process controlling of plants

– Further processing of digital and analog data

Use the IPC FEC-Standard only as follows:

– Properly

– In technically faultless state

– Without unauthorized changes.

When connecting usual commercial supplementary compo-


nents such as sensors and actuators, observe the specified
limits for pressures, temperatures, electrical data, torques,
etc.

Observe the standards specified in the respective standards


as well as the regulations of the employer’s liability insurance
associations, of the technical surveyance, the VDE specifica-
tions or corresponding national specifications.

Target group

This description is intended exclusively for skilled and quali-


fied personnel in control and automation technology, who are
experienced in installing, commissioning, programming and
diagnosis of programmable logic controllers (PLC systems).

Service

In case of technical problems please contact your local Festo


Service.

VI Festo P.BE-FEC-S-SYS en 0105nh


Contents and general instructions

Important information for the user

Categories of danger
This description contains information on possible dangers
which can occur when the product is used improperly. This
information is identified by a signal word (warning, caution,
etc.), has a shaded background and is furthermore identified
by a pictogram. The following types of danger information
exist:

Warning
... Means that non-obser vance can cause serious injuries
or serious damage to proper ty.

Caution
... Means that non-obser vance can cause injuries or dam-
age to proper ty.

Note
... Means that non-obser vance can cause damage to prop-
erty.

Festo P.BE-FEC-S-SYS en 0105nh VII


Contents and general instructions

Identification of special information


The following pictograms identify texts which contain special
information

Piktograms

Information:
Recommendations, hints and references to further sources of
information.

Accessory:
Information on an accessory for the Festo product which is
necessary or advisable.

Text identifiers

1. Numerals are used for activities which are to be carried


out in the specified sequence.

– Bars are used for general enumerations.

VIII Festo P.BE-FEC-S-SYS en 0105nh


Contents and general instructions

Abbreviations

Abbreviation Meaning

Micro PLC Programmable Logic Controller (the product described in this manual:
IPC FEC-Standard)

I Input
O Output
IO Input and/or Output

LED Light Emitting Diode

TTL Transistor-Transistor-Logic

TP Twisted Pair

Fig. 0/1: Abbreviations

Festo P.BE-FEC-S-SYS en 0105nh IX


Contents and general instructions

The mechanical system structure

1 2

7 6 5 4

1 Side section 5 Top-hat rail clamp


2 Front panel 6 Enclosure profile
3 Top-hat rail 7 Fixing screw
4 Earthing jumper (functional earthing) 8 Cover

Fig. 0/2: System structure

X Festo P.BE-FEC-S-SYS en 0105nh


Module overview

Chapter 1

Festo P.BE-FEC-S-SYS en 0105nh 1-1


1. Module overview

1. Module overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

1.1 Overview of the module variants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3


1.2 Component description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.2.1 Module IPC FEC FC400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.2.2 Module IPC FEC FC440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1.2.3 Module IPC FEC FC520 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.2.4 Module IPC FEC FC560 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1.2.5 Module IPC FEC FC600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.2.6 Module IPC FEC FC620 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
1.2.7 Module IPC FEC FC640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
1.2.8 Module IPC FEC FC660 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13

1-2 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

1.1 Overview of the module variants

The following section provides an overview of all the IPC FEC-Standard devices described
in this manual.

Module Description of the modules

IPC FEC FC400 – 16 inputs, 8 transistor outputs, 24 V DC


– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
0 – Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 115
– Overall dimensions 105 x 35 x 131

IPC FEC FC440 – 16 inputs, 8 transistor outputs, 24 V DC, Ethernet 10 BaseT.


– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 115
– Overall dimensions 105 x 35 x 131

IPC FEC FC520 – 16 inputs, 8 outputs, 24 V DC, with analog section 3 inputs / 1
output all 12 bits
– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 136
– Overall dimensions 105 x 35 x 153

Festo P.BE-FEC-S-SYS en 0105nh 1-3


1. Module overview

Module Description of the modules


IPC FEC FC560 – 16 inputs, 8 outputs, 24 V DC, Ethernet 10 BaseT, with analog
section 3 inputs / 1 output all 12 bits
– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 136
– Overall dimensions 105 x 35 x 153

IPC FEC FC600 – 32 inputs, 16 outputs, 24 V DC


– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
0 – Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 157
– Overall dimensions 105 x 35 x 174

IPC FEC FC620 – 32 inputs, 16 outputs, 24 V DC, with analog section 3 inputs / 1
output all 12 bits
– Processor 80186
– Working memory 512 Kbytes
0 – Program memory 512 Kbytes flash
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 157
– Overall dimensions 105 x 35 x 174

1-4 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

Module Description of the modules

IPC FEC FC640 – 32 inputs, 16 outputs, 24 V DC, Ethernet 10 BaseT.


– Processor 80186
– Working memory 512 Kbytes
– Program memory 512 Kbytes flash
0
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 157
– Overall dimensions 105 x 35 x 174

IPC FEC FC660 – 32 inputs, 16 outputs, 24 V DC, Ethernet 10 BaseT, with analog
section 3 inputs / 1 output all 12 bits
– Processor 80186
– Working memory 512 Kbytes
0 – Program memory 512 Kbytes flash
– Interface RS232 via SM14/-15
– Power consumption 200 mA nominal at 24 V
– Operating system Festo FST, Multiprog
– Dimensions 105 x 35 x 157
– Overall dimensions 105 x 35 x 174

Fig. 1/1: Overview of the module variants

Festo P.BE-FEC-S-SYS en 0105nh 1-5


1. Module overview

1.2 Component description

1.2.1 Module IPC FEC FC400

The module contains the following connection and display


elements:

1 2

4
5
9

8 7 6

1 Input E0.0 to E0.7 5 Extension interface (Ext)


2 Power LED (power display) 6 Status LED (Run, Stop, Error)
3 Run/Stop switch / function selector 7 Power supply
switch
8 Output A0.0 to A0.7
4 Communication interface (Com)
9 Input E1.0 to E1.7
Fig. 1/2: Connection and display elements of the module IPC FEC FC400

1-6 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

1.2.2 Module IPC FEC FC440

The module contains the following connection and display


elements:

1 2

3
4
5

6
aA 7

aJ 9 8

1 Input E0.0 to E0.7 7 Extension interface (Ext)


2 Power LED (power display) 8 Status LED (Run, Stop, Error)
3 Link/Traffic LED for network activity 9 Power supply
4 Run/Stop switch / function selector aJ Output A0.0 to A0.7
switch
aA Input E1.0 to E1.7
5 Network connection 10Base T
6 Communication interface (Com)
Fig. 1/3: Connection and display elements of the module IPC FEC FC440

Festo P.BE-FEC-S-SYS en 0105nh 1-7


1. Module overview

1.2.3 Module IPC FEC FC520

The module contains the following connection and display


elements:

1 2

aJ
3

4
9
5

8 7 6

1 Analog inputs/outputs 6 Status LED (Run/Stop/Error)


2 Power LED (power display) 7 Power supply
3 Run/Stop switch / function selector 8 Output A0.0 to A0.7
switch
9 Input E1.0 to E1.7
4 Communication interface (Com)
aJ Input E0.0 to E0.7
5 Extension interface (Ext)

Fig. 1/4: Connection and display elements of the module IPC FEC FC520

1-8 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

1.2.4 Module IPC FEC FC560

The module contains the following connection and display


elements:
1 2
3

4
aB
5

6
7
aA

aJ 9 8

1 Analog inputs/outputs 7 Extension interface (Ext)


2 Power LED (power display) 8 Status LED (Run/Stop/Error)
3 Link/Traffic LED for network activity 9 Power supply
4 Run/Stop switch / function selector aJ Output A0.0 to A0.7
switch
aA Input E1.0 to E1.7
5 Network connection 10Base T
aB Input E0.0 to E0.7
6 Communication interface (Com)
Fig. 1/5: Connection and display elements of the module IPC FEC FC560

Festo P.BE-FEC-S-SYS en 0105nh 1-9


1. Module overview

1.2.5 Module IPC FEC FC600

The module contains the following connection and display


elements:

1 2

aB
3

4
5
aA

aJ 9 8 7 6

1 Input E2.0 to E2.7 7 Power supply


2 Power LED (power display) 8 Output A1.0 to A1.7
3 Run/Stop switch / function selector 9 Output A0.0 to A0.7
switch
aJ Input E3.0 to E3.7
4 Communication interface (Com)
aA Input E1.0 to E1.7
5 Extension interface (Ext)
aB Input E0.0 to E0.7
6 Status LED (Run/Stop/Error)
Fig. 1/6: Connection and display elements of the module IPC FEC FC600

1-10 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

1.2.6 Module IPC FEC FC620

The module contains the following connection and display


elements:

1 2 3

aC
4

5
6
aB

aA aJ 9 8 7

1 Input E2.0 to E2.7 7 Status LED (Run/Stop/Error)


2 Analog inputs/outputs 8 Power supply
3 Power LED (power display) 9 Output A1.0 to A1.7
4 Run/Stop switch / function selector aJ Output A0.0 to A0.7
switch
aA Input E3.0 to E3.7
5 Communication interface (Com)
aB Input E1.0 to E1.7
6 Extension interface (Ext)
aC Input E0.0 to E0.7
Fig. 1/7: Connection and display elements of the module IPC FEC FC620

Festo P.BE-FEC-S-SYS en 0105nh 1-11


1. Module overview

1.2.7 Module IPC FEC FC640

The module contains the following connection and display


elements:

1 2 3

aD
4

5
6
7
aC

aB aA aJ 9 8

1 Input E2.0 to E2.7 8 Status LED (Run/Stop/Error)


2 Power LED (power display) 9 Power supply
3 Link/Traffic LED for network activity aJ Output A1.0 to A1.7
4 Run/Stop switch / function selector aA Output A0.0 to A0.7
switch
aB Input E3.0 to E3.7
5 Network connection 10Base T
aC Input E1.0 to E1.7
6 Communication interface (Com)
aD Input E0.0 to E0.7
7 Extension interface (Ext)
Fig. 1/8: Connection and display elements of the module IPC FEC FC640

1-12 Festo P.BE-FEC-S-SYS en 0105nh


1. Module overview

1.2.8 Module IPC FEC FC660

The module contains the following connection and display


elements:

1 2 3
4

aE
5

6
7
8
aD

aC aB aA aJ 9

1 Input E2.0 to E2.7 8 Extension interface (Ext)


2 Analog inputs/outputs 9 Status LED (Run/Stop/Error)
3 Power LED (power display) aJ Power supply
4 Link/Traffic LED for network activity aA Output A1.0 to A1.7
5 Run/Stop switch / function selector aB Output A0.0 to A0.7
switch
aC Input E3.0 to E3.7
6 Network connection 10Base T
aD Input E1.0 to E1.7
7 Communication interface (Com)
aE Input E0.0 to E0.7

Fig. 1/9: Connection and display elements of the module IPC FEC FC660

Festo P.BE-FEC-S-SYS en 0105nh 1-13


1. Module overview

1-14 Festo P.BE-FEC-S-SYS en 0105nh


Mounting

Chapter 2

Festo P.BE-FEC-S-SYS en 0105nh 2-1


2. Mounting

2. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

2.1 Mounting the IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3


2.2 Top-hat rail mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.1 Procedure for top-hat rail mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.2 Procedure for top-hat rail dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.3 Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.3.1 Procedure for wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.3.2 Procedure for wall dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2.4 Combined mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.4.1 Procedure for combined mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.4.2 Procedure for combined dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.5 Further information on top-hat rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.6 Earthing the IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.6.1 Earthing without a top-hat rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.6.2 Prohibited earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.6.3 Top-hat rail earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
2.7 Important installation regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15

2-2 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

2.1 Mounting the IPC FEC-Standard

The IPC FEC-Standard can be mounted on the top-hat rail as


well as directly to the wall by means of two fixing screws.

Combined mounting using both mounting types is also poss-


ible.

Festo P.BE-FEC-S-SYS en 0105nh 2-3


2. Mounting

2.2 Top-hat rail mounting

The IPC FEC-Standard is suitable for mounting on a top-hat


rail (support rail conforming to EN 50022). To this purpose
the rear of the IPC FEC-Standard has two fixed anchored
top-hat rail clamps with which the IPC FEC-Standard can be
snapped in onto the top-hat rail.

2.2.1 Procedure for top-hat rail mounting

Caution
Do not use additional aids to fasten the IPC FEC-Standard
on the top-hat rail.

1. Incline the IPC FEC-Standard by approx. 85 (see Fig. 2/1)


and lean the IPC FEC-Standard against the rear wall
above the top-hat rail.

2. Now slide the IPC FEC-Standard downwards until the


top-hat rail clamps of the IPC FEC-Standard contacts the
top-hat rail.

3. Then press the lower half of the IPC FEC-Standard


against the top-hat rail. The ball of the thumb is suitable
for latching the IPC FEC-Standard on to the top-hat rail
gently. (see Fig. 2/2).

2-4 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

1 IPC FEC-Standard
2 Top-hat rail

Fig. 2/1: IPC FEC-Standard mounting scheme 1

1 IPC FEC-Standard
2 Top-hatrail

Fig. 2/2: IPC FEC-Standard mounting scheme 2

Festo P.BE-FEC-S-SYS en 0105nh 2-5


2. Mounting

2.2.2 Procedure for top-hat rail dismantling

Caution
Never remove an IPC FEC-Standard from the top-hat rail
while it is wired. All cable connections must have been
removed before the IPC FEC-Standard is removed.

Caution
Avoid using screwdrivers or other levering tools to
separate the IPC FEC-Standard from the top-hat rail. If you
avoid using auxiliary tools, unwanted vibrations or even
damage to the wall and the IPC FEC-Standard is avoided.

1. Clasp around the enclosure of the IPC FEC-Standard by


placing the thumbs of your hand on the lower end and
the other fingers of the same hand on the upper end of
the IPC FEC-Standard.

2. Lever the IPC FEC-Standard from the top-hat rail by


pulling the lower end of the IPC FEC-Standard towards
yourself while exercising moderate pressure with your
thumbs. A clear latching sound then indicates that the
device has been unlatched and can thus be removed
from the top-hat rail.

2-6 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

2.3 Wall mounting

The IPC FEC-Standard is suitable for mounting to a wall. To


this purpose there are fixed integrated fixing brackets on
both ends of the IPC FEC-Standard.

Observe the distances of the holes which have to be set at the


respective IPC FEC types. The required screw diameter
amounts to 4.0 mm. The screw head diameter should not
amount to more than 8.5 mm.

IPC FEC-type hole distance

IPC FEC FC400 114,2 mm

IPC FEC FC440 114,2 mm

IPC FEC FC520 135,7 mm

IPC FEC FC560 135,7 mm

IPC FEC FC600 157,0 mm

IPC FEC FC620 157,0 mm

IPC FEC FC640 157,0 mm

IPC FEC FC660 157,0 mm

2.3.1 Procedure for wall mounting

1. Set the holes to conform to the existing underground


under consideration of the hole distance of your IPC
FEC type.

2. Fix the IPC FEC-Standard by means of two screws of


the type described at the desired position

Festo P.BE-FEC-S-SYS en 0105nh 2-7


2. Mounting

2.3.2 Procedure for wall dismantling

Warning
Never dismantle an IPC FEC-Standard from the wall while it
is wired. All cable connections must have been removed
before the IPC FEC-Standard is dismantled.

1. Use a suitable screwdriver to remove the two fixing


screws which hold the IPC FEC-Standard to the wall by
means of the fixing brackets.

2. When removing the screws hold the IPC FEC-Standard


with one hand in order to prevent it from falling .

2-8 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

2.4 Combined mounting

The IPC FEC-Standard is suitable for combined mounting


(wall/top-hat rail).

2.4.1 Procedure for combined mounting

1. Observe the points described under Section 2.3 with


regard to the hole distance and the screw type.
Ensure additionally that the two holes are set so that
they can be accessed for mounting through the
oblong holes positioned in the top-hat rail.

2. When you have prepared fixing by wall mounting, the


module can be set on the top-hat rail as described
under Section 2.2.

3. Align the IPC FEC-Standard on the top-hat rail so that


the wall holes correspond with the side fixing brackets
of the IPC FEC-Standard.

4. Fix the IPC FEC-Standard by means of the two screws


of the screw type described under Section 2.3 through
the top-hat rail oblong holes and through the side
fixing brackets of the IPC FEC-Standard to the wall.

Festo P.BE-FEC-S-SYS en 0105nh 2-9


2. Mounting

2.4.2 Procedure for combined dismantling

Warning
Never dismantle an IPC FEC-Standard from the wall or from
the top-hat rail while it is wired. All cable connections must
have been removed before the IPC FEC-Standard is
dismantled.

Caution
Never try to remove the IPC FEC-Standard from the top-hat
rail before the wall mounting screws have been removed .

1. Use a suitable screwdriver to remove the two fixing


screws which hold the IPC FEC-Standard through the
top-hat rail to the wall by means of the fixing brackets.

2. Clasp around the enclosure of the IPC FEC-Standard by


placing the thumbs of your hand on the lower end and the
other fingers of the same hand on the upper end of the
IPC FEC-Standard.

3. Lever the IPC FEC-Standard from the top-hat rail by


pulling the lower end of the IPC FEC-Standard towards
yourself while exercising moderate pressure with your
thumbs. A clear latching sound then indicates that the
device has been unlatched and can thus be removed from
the top-hat rail.

2-10 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

2.5 Further information on top-hat rail mounting

The IPC FEC-Standard should not be slid on the top-hat rail.


The top-hat rail clamp presses the IPC FEC-Standard so firmly
against the top-hat rail that unintentional moving of the IPC
FEC-Standard is not possible.

If the IPC FEC-Standard has to be placed at a different posi-


tion on the top-hat rail, remove the device from the top-hat
rail and place it back onto the rail at the desired position.

Moving the IPC FEC-Standard on the top-hat rail causes high


mechanical wear at the top-hat rail itself.

The correct latching-in method (as described in Section 2.2) is


only subject to a very low degree of wear and can thus be
repeated as often as required.

Festo P.BE-FEC-S-SYS en 0105nh 2-11


2. Mounting

2.6 Earthing the IPC FEC-Standard

Before the IPC FEC-Standard is commissioned it has to be


earthed. The stranded cable required to this purpose has to
have a cross-section of at least 2.5 mm2.

2.6.1 Earthing without a top-hat rail

Slide the clamp-type cable lug of the earthing cable onto one
of the two lug holders positioned on the two sides of the IPC
FEC-Standard. The other end of the earthing cable is
connected to the central star-head earthing point.This
earthing applies for an example without top-hat rail (see Fig.
2/3).

3
1

0 0

1 Functional earthing cable 3 Central star-head earthing point


2 IPC FEC-Standard
Fig. 2/3: Earthing principle for functional earthing

2-12 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

Caution
It is prohibited to connect several devices via the same
earthing cable (see Fig. 2/4).

2.6.2 Prohibited earthing

The earthing shown in Fig. 2/4 is prohibited. When installing


the IPC FEC-Standard always ensure that earthing is
implemented as shown in Fig. 2/3, if the IPC FEC-Standard is
not mounted on the top-hat rail.

4
2
0 0

1 Central star-head earthing point 3 Functional earthing cable


2 IPC FEC-Standard 4 Functional earthing cable
Fig. 2/4: Prohibited earthing

Festo P.BE-FEC-S-SYS en 0105nh 2-13


2. Mounting

2.6.3 Top-hat rail earthing

A further earthing alternative is to earth the top-hat rail itself.


In this case no additional connection is required between the
top-hat rail and the IPC FEC-Standard since the top-hat rail
clamp of the IPC FEC-Standard establishes a conductive
connection.

1
4

0 0

1 Central star-head earthing point 3 Top-hat rail


2 IPC FEC-Standard 4 Functional earthing cable
Fig. 2/5: Top-hat rail earthing

If a top-hat rail/suppor t rail is selected as the fixing alterna-


tive, it has to have an equipotential bonding to the star-head
earthing point of the control cabinet or of the feeder conduc-
tor. If the top-hat rail then becomes an equipotential bonding
strip, several IPC FEC-Standard devices may be fastened to it.
The earthing terminals in the form of lug holders (6.3 mm) are
then defined as a functional earthing and can be used to con-
tact shieldings.

2-14 Festo P.BE-FEC-S-SYS en 0105nh


2. Mounting

2.7 Important installation regulations

Only use power supply units which ensure safe separation of


the operating voltage conforming to IEC 742 / EN60742 / VDE
0551, PELV with at least 4 kV insulation resistance for the 24
V DC power supply (power connections) and for the power
supply of the digital inputs (nominal 24 V DC).

Switched-mode power supply units with safe separation con-


forming to EN 60950 / VDE 0805 are also permitted.

The power supply unit PS1 PSE3 fulfills the specified require-
ments.

The maximum length of the power supply cable amounts to


10 m.

Use exclusively shielded cables for TP and cross-over cables.


TP cables of the type S/STP (min. CAT5) are to be used. The
shieldings are to be applied to an interference-free earth at
both ends, as a large area and as low-resistance. This can be
implemented with the top-hat rail clamp which is part of the
earthing set (Part No.: 526683). The enclosure of the hubs
used also have to be earthed as low-resistance.

The maximum length of the connected cable for signal con-


nections of the digital and analog I/Os amounts to 30 m

Festo P.BE-FEC-S-SYS en 0105nh 2-15


2. Mounting

2-16 Festo P.BE-FEC-S-SYS en 0105nh


Installation

Chapter 3

Festo P.BE-FEC-S-SYS en 0105nh 3-1


3. Installation

3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1

3.1 What you require for the hardware installation . . . . . . . . . . . . . . . . . . . . . . . 3-3


3.2 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.3 Pin assignment of the connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.1 Pin assignment of the digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . 3-5
3.3.2 Pin assignment of the analog inputs and outputs . . . . . . . . . . . . . . . . . . . . . 3-6
3.3.3 Pin assignment of the power supply connector . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.3.4 Pin assignment of the communication interfaces (Ext/Com). . . . . . . . . . . . . 3-8
3.3.5 Pin assignment of the network connection (TP). . . . . . . . . . . . . . . . . . . . . . . 3-9
3.4 The communication interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.4.1 Proper use of the SM14/SM15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.4.2 Pin assignment of the programming cable PS1 ZK14 . . . . . . . . . . . . . . . . . . 3-11
3.5 Connection scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.5.1 Connection assignment of the digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
3.5.2 Connection assignment of the digital outputs . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.5.3 Connection assignment of the analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.5.4 Connection assignment of the analog outputs. . . . . . . . . . . . . . . . . . . . . . . . 3-18
3.5.5 Connection example for programming the IPC FEC-Standard. . . . . . . . . . . . 3-20
3.5.6 Connection example of a direct network connection (only Ethernet). . . . . . 3-21
3.5.7 Connection example of a network (10Base T) . . . . . . . . . . . . . . . . . . . . . . . . 3-22
3.5.8 Connection example of a power supply wiring. . . . . . . . . . . . . . . . . . . . . . . . 3-23
3.5.9 Options of the function selector switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6 Information on wiring the IPC FEC-Standard. . . . . . . . . . . . . . . . . . . . . . . . . . 3-27

3-2 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.1 What you require for the hardware installation

– An IPC FEC-Standard (scope of delivery)

– A power supply unit 24 V DC (e.g. PS1 PSE3)

– A connecting cable (PS1 SM14) in order to establish a


connection between the IPC FEC-Standard and the
external computer.

– An external computer such as a PC or a laptop with a free


communication interface and an installed Windows
operating system.

Festo P.BE-FEC-S-SYS en 0105nh 3-3


3. Installation

3.2 Installation Instructions

When installing the IPC FEC-Standard, take the environmental


conditions into account under which the device normally op-
erates.

Do not install the IPC FEC-Standard

– In areas which are subject to excessive dust, oil mist,


conductive dust or corrosive gas

– Directly in areas which are subject to shock or


vibrations

– In areas which are subject to high temperatures,


direct sun irradiation, humidity or rain

– Near high-voltage devices or lines

Caution
Ensure that no wire pieces, fillings or shavings fall into the
device when holes are drilled or wires connected.

Do not mount the IPC FEC-Standard directly above a


heat-generating source, such as a heater, a current
transformer or a high-wattage resistor.

Caution
If the ambient temperature in the control cabinet exceeds
55 °C, a ventilator has to be installed for forced ventilation.

3-4 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.3 Pin assignment of the connectors

3.3.1 Pin assignment of the digital inputs and outputs

PS1 SAC31

Distribution strip 24 V (connected internally)

Supply voltage I/O

Input EX.0
Output AX.0

Input EX.1
Output AX.1

Input EX.2
Output AX.2

Input EX.3
Output AX.3

Input EX.4
Output AX.4

Input EX.5
Output AX.5

Input EX.6
Output AX.6

Input EX.7
Output AX.7

0V

Distribution strip 0 V DC (connected internally)

Fig. 3/1: PS1 SAC31 used as a digital connector

Festo P.BE-FEC-S-SYS en 0105nh 3-5


3. Installation

3.3.2 Pin assignment of the analog inputs and outputs

Pin No. Designation PS1 SAC31 as an example

1 +24 V
1
2 OUT0

3 GND OUT0

4 GND IN0

5 IN0

6 GND IN1

7 IN1

8 GND IN2
2
9 IN2

10 0V

1 Distribution strip 24 V
2 Distribution strip 0 V
Fig. 3/2: PS1 SAC31 used as an analog connector

3-6 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.3.3 Pin assignment of the power supply connector

Caution
Ensure that the external power supply is switched off until
the control system has been installed.

PS1 SAC11 as an example Pin No. Designation

1 + 24 V DC

2 + 24 V DC

3 + 24 V DC

4 + 24 V DC

5 + 24 V DC

6 0V

7 0V

8 0V

9 0V

10 0V

Fig. 3/3: Pin assignment of the power supply

The IPC FEC-Standard is to be supplied with a supply voltage


of 24 V DC which is to be applied to the provided ”Power 24 V
DC” connection. The positive pole of the voltage source is
connected to Pin 1 and the negative pole is connected to Pin
10 of the power supply connector.

The + 24 V DC and the 0 V connections are interconnected in


their function group in the control system (not in the con-
nector).

Festo P.BE-FEC-S-SYS en 0105nh 3-7


3. Installation

3.3.4 Pin assignment of the communication interfaces (Ext/Com)

The communication and extension interface of the IPC


FEC-Standard operate with a TTL level (5 V). Only use the
respective accessories offered (PS1 SM14/SM15).

RJ12 connector Pin No Designation

1 + 5V

2 GND

3 TXD

4 RXD

5 CTS

6 RTS

Fig. 3/4: Communication and extension interface

3-8 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.3.5 Pin assignment of the network connection (TP)

The network connection is used both to network several IPC


FEC-Standard units with each other as well as to connect the
IPC FEC-Standard to a higher-level control system or
visualization unit.

RJ45 connector (10Base T) Pin No Designation

1 TD+

2 TD-

3 RD+

4 Not assigned

5 Not assigned

6 RD-

7 Not assigned

8 Not assigned

Fig. 3/5: Network connection (TP)

The Ethernet connection to your control system allows you to

– Communicate between the control systems (send and


receive data)

– Program and maintain the control systems via the


Ethernet

– Transport data of the control system in an office network


(DDE server, OPC server) and use the control system as a
WEB server in order to visualize and/or to operate the
machine process with a browser (only FST)

Festo P.BE-FEC-S-SYS en 0105nh 3-9


3. Installation

3.4 The communication interface

COM and EXT are universal TTL connections. A level controller (e.g. SM14 or
SM15) is required for implementation.

Applications

COM Use as a programming interface or MMI

EXT Use with MMI or other RS232 devices

Please note that the SM14/15 supplies the Transmit, Receive and RTS/CTS sig-
nals.

The cable length (SM14/SM15 interface controller plus zero modem cable) may
not exceed 3 m.
3

1 PS1 SM14: Programming cable + interface converter TTL-RS232


2 PS1 SM15: Interface converter TTL-RS232 without zero modem cable
3 Functional earthing with earthing clamp
Fig. 3/6: Application of the interface cables

3-10 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.4.1 Proper use of the SM14/SM15

The interface converter TTL-RS232 PS1 SM15 was conceived


for the industrial installation of serial communication. The
scope of delivery of the PS1 SM15 does not include a zero
modem cable. A corresponding cable is to be created as
shown in the figure below. The connector pin assignment of
the SM15 corresponds to that of the SM14. The specifications
of the EIA (Electronic Industrial Association) RS232-C are to
be observed when implementing a serial communication con-
nection.

A shielded cable (braided shield, 80% coverage) is required


in order to achieve a sufficient level of immunity to interfer-
ence. The shielding is to be created as a large area and as
low-resistance.

The SM14 programming cable is not to be used in the sense


of an industrial installation. The scope of delivery of the SM14
includes a zero modem cable.

3.4.2 Pin assignment of the programming cable PS1 ZK14

Pin assignment RS232 connector (SUB-D)

Connector A Connector B
Pin 1 and 6 Connect to Pin 4

Pin 2 Connect to Pin 3

Pin 3 Connect to Pin 2

Pin 4 Connect to Pin 1 and 6

Pin 5 Connect to Pin 5

Pin 7 Connect to Pin 8

Pin 8 Connect to Pin 7

Pin 9 Do not connect to Pin 9

Festo P.BE-FEC-S-SYS en 0105nh 3-11


3. Installation

1 2

5
6

1 Pin 5 4 Pin 9
2 Pin 1 5 Connector B (SUB-D)
3 Pin 6 6 Connector A (SUB-D)
Fig. 3/7: Programming cable PS1 ZK14 (zero modem cable)

3-12 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.5 Connection scheme

3.5.1 Connection assignment of the digital inputs

The digital inputs of the IPC FEC-Standard are used to detect


states (e.g. by means of a sensor or switch).

Depending on the version of the IPC FEC-Standard either 2 x 8


or 4 x 8 digital inputs are available. These are connected are
shown below.

1 2
_

1 Jumper 24 V DC from distribution strip 4 Jumper 0 V from distribution strip to


to module supply module supply

2 Supply voltage 0 V 5 Supply voltage 24 V DC


3 Sensor (cable length max. 30 m) 6 PS1 SAC31
Fig. 3/8: Connection example for digital input

Festo P.BE-FEC-S-SYS en 0105nh 3-13


3. Installation

3.5.2 Connection assignment of the digital outputs

The digital outputs of the IPC FEC-Standard are used to out-


put internally processed signals.

Depending on the version of the IPC FEC-Standard either 1 x 8


or 2 x 8 digital outputs are available. These are connected are
shown below.

Caution
Reversing of the polarity at the supply of the digital output
module has to be avoided under all circumstances.
The use of an external protection (4 AF) of the output mo-
dule is recommended.

3-14 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

1
2

3
6

1 Jumper 24 V DC from distribution strip 4 Jumper 0 V from distribution strip to


to module supply module supply

2 Supply voltage 0 V 5 Supply voltage 24 V DC


3 Actuator (cable length max. 30 m) 6 PS1 SAC31
Fig. 3/9: Connections example of digital output

Festo P.BE-FEC-S-SYS en 0105nh 3-15


3. Installation

3.5.3 Connection assignment of the analog inputs

The analog inputs of the IPC FEC-Standard are used to detect


analog states for example of temperature, rotational speed,
speed, pressure or other sensors.

The IPC FEC-Standard types 520, 560, 620 and 660 have 3
analog inputs available. The resolution of the inputs amount
to 12 bits. The input signal can be defined as a current (0-20
mA) or voltage (0-10 V) signal path by means of the software
operating system. Connection to a connector PS1 SAC30 is
implemented as shown below.

The two connectors PS1 SAC11 and PS1 SAC31 are not suit-
able for use in this case since the integrated LEDs can cause a
measuring error in the analog value.

Note
The analog input signal lines are to be implemented with
shielded cables. Cables with braided shielding (80% cover-
age) are suitable. The shielding is to be connected at the
module end, as a large area and as low-resistance.

3-16 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

1 2

-
-
7
+
6 5 4 3

1 PS1 SAC30 5 Sensor +24 V DC


2 Pressure sensor 6 Supply voltage 24 V DC
(cable length max. 30 m)
7 Supply voltage 0 V DC
3 Signal GND
4 Signal IN
Fig. 3/10: Connection example of an analog input

If the analog inputs are to be used exclusively, the analog


output module does not have to be supplied (see block
diagrams for analog inputs and outputs).

Festo P.BE-FEC-S-SYS en 0105nh 3-17


3. Installation

3.5.4 Connection assignment of the analog outputs

The analog output of an IPC FEC-Standard is used to control


analog actuators, for example, pressure regulator, tempera-
ture controller, level controller, etc.

The FEC Standard types 520, 560, 620 and 660 have 1 analog
output. The internal resolution of the output amounts to 12
bits. The signal is a current signal (0-20 mA). The connection
to a connector PS1 SAC10 is shown below using a propor-
tional valve as an example.

Caution
Reversing of the polarity at the supply of the analog output
module has to be avoided under all circumstances. The
use of an external protection (125 mAF) of the output
module is recommended.

Note
The analog output signal lines are to be implemented with
shielded cables. Cables with braided shielding (80%
coverage) are suitable. The shielding is to be connected at
the module end, as a large area and as low-resistance.

3-18 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

+ 1
7

-
5 AC/DC
3
4

1 Signal OUT 4 Signal GND


2 Propor tional valve 5 Supply voltage 0 V
(cable length max. 30 m)
6 PS1 SAC10
3 External power supply
7 Supply voltage 24 V
Fig. 3/11: Connection example of an analog output

Festo P.BE-FEC-S-SYS en 0105nh 3-19


3. Installation

3.5.5 Connection example for programming the IPC FEC-Standard

The following passages show various examples of how to use


the IPC FEC-Standard correctly.

The connection cable PS1 SM14 can be used to establish a


direct connection between the IPC FEC-Standard and the ex-
ternal computer. This enables the IPC FEC-Standard to be
provided with its own application programs. For further in-
formation please refer to the respective description on the
FST or Multiprog CD.

2
3

1 IPC FEC-Standard 3 Connecting cable SM 14(cable length


max. 3 m)
2 External computer
Fig. 3/12: Programming with an external computer

3-20 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.5.6 Connection example of a direct network connection (only Ethernet)

The network connection (TP) can be used to implement a


direct network connection between two PC FEC-Standard de-
vices. The figure below shows the assignment required for
the assignment of the cross cable. The cable length may not
exceed 100 m. TP cables of the type S/STP (min. CAT5) are to
be used.

1 1

8 8

1 TD+ 5 Not assigned


2 TD- 6 RD-
3 RD+ 7 Not assigned
4 Not assigned 8 Not assigned
Fig. 3/13: Network connection via TP interface

Festo P.BE-FEC-S-SYS en 0105nh 3-21


3. Installation

3.5.7 Connection example of a network (10Base T)

The network connection (TP) can be used to set up a network


with more than 2 IPC FEC-Standard devices. The number of
IPC FEC-Standard units which can be connected to each other
depends on the type and number of the hubs used (star
distribution). The cable length of each individual IPC FEC-
Standard which is connected to a hub may not exceed 100
meters. TP cables of the type S/STP (min. CAT 5) are to be
used. A minimum distance between each other does not have
to be observed.

1 2
3

3 3

1 IPC FEC-Standard 3 Twisted Pair cable


2 Hub 4 Programming station (e.g. laptop
with network board)

Fig. 3/14: Network (10Base T)

3-22 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.5.8 Connection example of a power supply wiring

1 Power supply cable 3 Power supply connector


(cable length max. 10 m)
4 IPC FEC-Standard
2 Power supply
Fig. 3/15: Power supply wiring

Festo P.BE-FEC-S-SYS en 0105nh 3-23


3. Installation

Caution
Do not switch on the power supply after you have com-
pleted the wiring of the ”Power 24V DC”, but wait until the
whole installation has been completed.
Depending on the design of the power supply and the con-
nector used a contact overload may occur.
A protection of the feeder cable is to be implemented.

Note
The connections between the Connectors 1 to 5 and 6 to
10 are suitable for the power supply of the outputs or in-
puts. The maximum single contact rating amounts to 8 A at
SAC X 4 A at ZC13 8 A.

3.5.9 Options of the function selector switch

The function selector switch of the IPC FEC-Standard has 2


different functionalities.

– It can be sampled as a Run/Stop switch per software,


whereby the position 0 corresponds to the function
Stop and every other position to the function Run.

– It can be used as a trimmer. Positions 0-15 can be


sampled by an application program. Position 0 of the
function selector switch always means: The program
has been stopped. Before commissioning the switch is
to be set to Position 0 (state of delivery).

3-24 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

Fig. 3/16: Function selector switch in the initial position

Note
In order not to evaluate every intermediate position when
switching from one position to another one across several
intermediate positions, reading out of the switch is
delayed.
The value is not read out until the switch rests for approx.
2 seconds in the same position

The function selector switch as a Run/Stop switch:

In this mode a program can be assigned to each of the switch


positions 1 to 15 of the function selector switch. By default
the switch positions 1 - 15 has the meaning that the FEC or
the program of the FEC is in the state RUN (loaded program).

The switch positions can be read out by the program.

The function selector switch as a trimmer:

The function selector switch of the IPC FEC-Standard can be


used as a trimmer. In this mode a step-by-step control can be
implemented (for example in order to control the speed of a
motor).

The type of use of the function selector switch is determined


by the software. Both functionalities of the function selector
switch cannot be used simultaneously.

Festo P.BE-FEC-S-SYS en 0105nh 3-25


3. Installation

In the state of delivery the switch positions 1 to 15 of the


function selector switch are without action.

Warning
A change in the switch position of the function selector
switch during running operation can have serious conse-
quences depending on the programs which are assigned
to the switch positions.

Corresponding precautionary measures therefore already


have to be taken when programming the switches in order to
prevent accidents.

For further information on the function selector switch please


refer to the respective description on the FST or Multiprog
CD.

Before commissioning the switch is to be set to Position 0


(state of delivery).

As a Run/STOP switch the function selector switch is used to


set the plant to STOP.

By default the position 0 = STOP, the position 1 to F = RUN.

For your information:

A change in the function selector switch while a digital output


is overloaded leads to delayed recognition of the changed
position

3-26 Festo P.BE-FEC-S-SYS en 0105nh


3. Installation

3.6 Information on wiring the IPC FEC-Standard

Note
Separate the signal input and signal output wires in
separate cable ducts and avoid bundling the signals. Do
not use the same multiple-conductor cable to wire the
signal inputs and outputs.

Caution
Check the supply voltage and earthing connections as well
as the input/output connections before switching on the
current.

Ensure that the mounting screws or screw terminals for the


external connection are fixed. External connections may not
have any visible signs of damage.

Warning
Ensure that the supply voltage is separated from the IPC
FEC-Standard before replacing the cable or taking similar
steps.

In case of loads, such as forwards/backwards motor contac-


tors, which can be dangerous when activated simultaneously,
both interlocks outside the IPC FEC-Standard as well as pro-
grammed interlocks should exist. This prevents such loads
from being activated simultaneously.

– Do no connect any of the unused terminals.

Festo P.BE-FEC-S-SYS en 0105nh 3-27


3. Installation

Note
For EMERGENCY-OFF functions the output loads should be
switched off by a switch outside the IPC FEC-Standard
which separates the load voltage from the output ter-
minals.
If you connect an EMERGENCY OFF circuit, please ensure
that national wiring or safety regulations are observed.

The connection of a surge voltage suppresser parallel to an


inductive load reduces the generation of electrical emitted
interference.

Caution
The operating voltage of the IPC FEC-Standard is protected
against reversing of the polarity. Nevertheless, check the
polarity before commissioning.
The output power supply (supply of the outputs) may not
have the polarity reversed. External protection is recom-
mended.

3-28 Festo P.BE-FEC-S-SYS en 0105nh


First Steps / Commissioning

Chapter 4

Festo P.BE-FEC-S-SYS en 0105nh 4-1


4. First Steps / Commissioning

4. First Steps / Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

4.1 First steps IPC FEC-Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3


4.1.1 Connecting the IPC FEC-Standard to the power . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.1.2 Using the sensor actuator connector SAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.1.3 Connecting a sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4.1.4 Connecting an actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4.1.5 Installing the programming software on your PC. . . . . . . . . . . . . . . . . . . . . . 4-13
4.1.6 The first project with the IPC FEC-Standard in FST. . . . . . . . . . . . . . . . . . . . . 4-14
4.1.7 Overview of retentive operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.1.8 The first project with the IPC FEC-Standard in MULTIPROG. . . . . . . . . . . . . . 4-24
4.2 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
4.3 Rapid counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
4.4 The incremental encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34

4-2 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1 First steps IPC FEC-Standard

The following sections contain a brief introduction into the use of the IPC FEC-Standard

You require:

– An IPC FEC-Standard (any type)

– At least 3 connectors PS1 SAC10, PS1 SAC11, PS1 SAC30


or PS1 SAC31

– A power supply 24 V DC at least 1 A

– The programming cable PS1 SM14

– A programming PC with a free serial interface COM1 or


COM2 or COM3 or COM4 (9-pin SUB-D connector) and
Windows 9X, NT, ME or 2000 operating system

– The programming software “FST4.02” or “MULTIPROG


2.01 (04/2001) for FEC” or higher.

4.1.1 Connecting the IPC FEC-Standard to the power

Please use the connector PS1 SAC10 in order to connect the


power supply to the IPC FEC-Standard. Plug the connector
into the connector strip labeled with ”Power 24 V DC”. Con-
nect the 24 V DC of the power supply to one of the upper 5
connections of the connector and the 0 V of the power supply
to one of the lower 5 connections of the connector. Also refer
to the figure below.

Check and ensure that the cable is wired with the correct po-
larity. Also check whether the function selector switch is set to
Position 0 and correct it if necessary. Now switch on the
power supply for test purposes. The Power LED has to light
up.

Festo P.BE-FEC-S-SYS en 0105nh 4-3


4. First Steps / Commissioning

Caution
Before carrying out the further wiring separate the power
supply again from the IPC FEC-Standard.

1 Power supply cable 3 Power supply connector


(cable length max. 10 m)
4 IPC FEC-Standard
2 Power supply
Fig. 4/1: Connection scheme of the power supply

4-4 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1.2 Using the sensor actuator connector SAC

The sensor actuator connector PS1 SAC is equipped with ten-


sion spring technique. There are single-row versions with and
without LEDs and three-row versions with and without LEDs.
The three-row versions of the connectors have two distribu-
tion strips, for + and - each, which are contacted through sep-
arately from each other in the connector.

2 3

1
4

1 PS1 SAC10 3 PS1 SAC30


2 PS1 SAC11 (with LEDs) 4 PS1 SAC31 (with LEDs)
Fig. 4/2: Sensor actuator connector SAC

The wiring of solid wires is carried out in the same way as the
mounting of wires with wire end ferrules. These can be
introduced into the corresponding tension spring terminals of
the PS1 SAC connector.

If you use flexible wires without wire end ferrules, the button
which is assigned clearly by color to the tension spring ter-
minal has to be pressed down by means of a suitable tool
(screwdriver). The cable can be introduced while it is pressed
down.

Festo P.BE-FEC-S-SYS en 0105nh 4-5


4. First Steps / Commissioning

1 Connector
PS1 SAC11
1
2 Cable
3 Screwdriver

Fig. 4/3: Permitted wire cross-sections: 0.5 ... 1.5 mm 2,


stripping length: 7 - 10 mm

4-6 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1.3 Connecting a sensor

Sensors are connected to the connector strips which are


identified by the designation ”Digital Input”.

It is advisable to use a PS1 SAC11 or a PS1 SAC31 since these


connectors are equipped with LEDs for displaying the signal.
These connectors must be supplied expressly with power!

1 24V (red) 1
1 2 3
2 PS1 SAC11
3 PS1 SAC31
4 0 V (blue)
4 4

Fig. 4/4: PS1 SAC11 and PS1 SAC31 with connected power
supply

The power supply connector which was connected under


Section 4.1.1 (Fig. 4/1) can be used as a distribution strip for
the 24 V DC power supply. The upper 5 connections are
connected to each other on the printed circuit board, the
lower 5 as well. The maximum total current which may be led
across a connector contact amounts to:

Connector Imax /Contact

PS1 SACXX 4A

ZC 13-Z 6A

ZC13-S 8A

In order to use the 24 V/0 V distributor strips of the PS1


SAC30/31 these have to be supplied additionally with power.

Festo P.BE-FEC-S-SYS en 0105nh 4-7


4. First Steps / Commissioning

This allows different power supply units to be used or differ-


ent protection circuits for the sensor/actuator equipment and
the control system to be used.

Caution
If the power supply connector is used as a distribution
strip, the maximum current carrying capacity of the various
connectors available is to be observed.
A digital output group may be subjected to a maximum
total current of 3.2 A (8 x 0.4 A).

1 PS1 SAC31 1 2 3
2 PS1 SAC10
3 Power supply
+24 V DC

OV

Fig. 4/5: Wiring of the distribution list with the power supply

4-8 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

A sensor is connected to a PS1 SAC10/11 as follows.

1 PS1 SAC10 as a 1 2 3 4
digital input
connector

2 Sensor
3 PS1 SAC10 as a
+24 V DC
power supply
connector

4 Power supply

OV

Fig. 4/6: Sensor wiring with PS1 SAC10

Festo P.BE-FEC-S-SYS en 0105nh 4-9


4. First Steps / Commissioning

A sensor is connected to a PS1 SAC30/31 as follows.

1 LED 1 2 3
2 Jumper 24 V DC -
from distribution 4
strip to supply

3 Power supply 0 V
4 Sensor
5 Jumper 0 V DC
from distribution
strip to supply

6 Supply voltage
24 V DC 5
7 SAC 31 as a
digital input 6
connector +
7

Fig. 4/7: Sensor wiring with PS1 SAC31

Since the LEDs of the connectors PS1 SAC11 and PS1 SAC31
are connected in the connector with the signal and 0 V, the
wiring of the sensor equipment can also be tested
irrespective of the control system.

4-10 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1.4 Connecting an actuator

Actuators are connected to the connector strips which are


identified by the designation ”Digital Output”.

It is advisable to use a PS1 SAC11 or a PS1 SAC31 since these


connectors are equipped with LEDs for displaying the signal.

The outputs of the IPC FEC-Standard supply a +24 V DC signal


(PNP) with a maximum rated current of 0.4 A. Ensure that the
24 V DC supply voltage supplies sufficient current for all the
connected loads.

An actuator is connected to a PS1 SAC10/11 as follows.

1 PS1 SAC11 as a 1 2 3 4
digital output
connector
+24 V DC
2 Actuator
3 PS1 SAC10 as a
power supply
connector

4 Power supply OV

Fig. 4/8: Actuator wiring with SAC 10/11

Festo P.BE-FEC-S-SYS en 0105nh 4-11


4. First Steps / Commissioning

An actuator is connected to a PS1 SAC30/31 as follows.

1 LED 1 2 3 4
2 Jumper 24 V DC
from distribution -
strip to supply

3 Supply voltage
0V

4 Actuator
5 PS1 SAC31 as a 5
digital output
connector

6 Jumper 0 V from
distribution strip
to supply
6
7 Supply power
24 V DC
7
+
FIg. 4/9: Actuator wiring with PS1 SAC31

4-12 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1.5 Installing the programming software on your PC

For the programming of the IPC FEC-Standard you require


either the FST4 software in Version 4.02 or higher or the
MULTIPROG 2.01 software release date 04/2001 or later.

Please note that an IPC FEC-Standard can only be


programmed either with FST or MULTIPROG. Please check on
the rating plate of your control system which version you re-
quire.

1 Rating plate for 1 2


FST variation

2 Rating plate for


Multiprog
variation
FEC FC440-FST HW0.5
185205 N452 SW1.3

FEC FC440-MWT HW0.5


185205 N452 SW1.3

Fig. 4/10: Label difference for the FEC language variations

Install the FST4.02 software if you use FST for the


programming.

Install MULTIPROG for FEC Version 2.01 if you use MULTI-


PROG.

Festo P.BE-FEC-S-SYS en 0105nh 4-13


4. First Steps / Commissioning

4.1.6 The first project with the IPC FEC-Standard in FST

Please proceed as follows:

1 Connect your IPC FEC-Standard to the power supply as


described previously. Connect at least one sensor.
Connect the power supply to the output connector (so
that you can check by means of the LEDs whether an
output switches).

2. Install FST 4.02 (or higher) on your programming PC if it


has not been installed yet.

3. Connect the control system and the PC with the


programming cable SM14. Use the connection COM at the
IPC FEC-Standard and COM1 or COM2, etc. at the
programming PC.

4. Start the FST software

5. Open a new project via the menu Project, New

Fig. 4/11:FST Programming, screenshot 1

4-14 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

6. Assign a project name

Fig. 4/12: FST Programming, screenshot 2

Festo P.BE-FEC-S-SYS en 0105nh 4-15


4. First Steps / Commissioning

7. Select the IPC FEC-Standard as the CPU

Fig. 4/13: FST Programming, screenshot 3

8. Assign a comment - if desired.

4-16 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

9. Open the I/O configuration. Insert your control system as


the I/O module (right mouse click, Insert)

Fig. 4/14: FST Programming, screenshot 4

Festo P.BE-FEC-S-SYS en 0105nh 4-17


4. First Steps / Commissioning

10. Insert a new program with the number 0 into your project
(right mouse click on Programs, New Program)

Fig. 4/15: FST Programming, screenshot 5

4-18 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

11. Program as follows:

IF NOP

THEN LOAD IW0

TO OW0

Fig. 4/16: FST Programming, screenshot 6

Festo P.BE-FEC-S-SYS en 0105nh 4-19


4. First Steps / Commissioning

12. If you are prompted for the entry in the assignment list,
you can enter a symbolic name and a comment.

Fig. 4/17: FST Programming, screenshot 7

13. Click on Load Project

Fig. 4/18:FST programming, screenshots 8 and 9

14. Note that COM1 is set by default as the interface at your


programming PC. If you want to use COM2, open the entry
”FST Settings” in the Options menu and then the tab card
”Interface to Control System” and select the desired
interface there.

4-20 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

Fig. 4/19: FST programming, screenshot 10

15. Switch the rotary switch on the IPC FEC-Standard from


Stop (Position 0) to RUN (Position 1 to F). The Run LED on
the IPC FEC-Standard now has to switch over to green.

16. Now enter an input signal on an input of Group E0. The


output at the corresponding position of the output group
A0 then also has to be switched to 1.

Festo P.BE-FEC-S-SYS en 0105nh 4-21


4. First Steps / Commissioning

17. Check your program by switching to online mode: Right


mouse click in your program, Online

Fig. 4/20: FST programming, screenshot 11

18. Check your program by switching the online display

Fig. 4/21: FST programming, screenshot 12

4-22 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.1.7 Overview of retentive operands

Operand Operand Number

Output word (AW) 0...1

Register (Rx) 0...127

Timer preselection (TV) 0...127

Counter (Zx) 0...127

Counter preselection (ZV) 0...127

Counter word (ZW) 0...127

Flag word (MW) 0...255

Operand Range

Input word EWO to EW1 with E0.0 to E0.7 and E1.0 to E1.3

Output word AW0 with A0.0 to A0.7

Error word FW, also as F


Initialization flag Fl, per program
Flag words MW0 to MW9999 with Mx. 0 to Mx.15

Register R0 to R255

Function units FE0 to FE255, FE32 to FE38 per program

Timer T0 to T255 (also TV and TW for every timer TE, TA)

Counter Z0 to Z255 (also as ZV and ZW for every counter)

Programs P0 to P63

Program state PS0 to PS63

Function blocks BAF0 to BAF99 (predefined by Festo)

Program block BAP0 to BAP99 (can be defined by the user)

Festo P.BE-FEC-S-SYS en 0105nh 4-23


4. First Steps / Commissioning

4.1.8 The first project with the IPC FEC-Standard in MULTIPROG

Please proceed as follows:

1. Connect your IPC FEC-Standard to the power supply as


described above. Connect at least one sensor to Input 0 of
Group E0. Connect the power supply to the output
connector (so that you can check by means of the LEDs
whether an output switches).

2. Install MULTIPROG 2.01 Release 2001/04 (or higher) on


your programming PC if it has not been installed yet

3. Connect the control system and the PC with the


programming cable PS1 SM14. Use the connection COM
at the IPC FEC-Standard and COM1 or COM2, etc. at the
programming PC.

4. Start MULTIPROG

5. Open a new project via the menu Project, New

Fig. 4/22: MWT-Programming, screenshot 1

4-24 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

6. Select a template which is suitable for your control


system

Fig. 4/23:MWT-Programming, screenshot 2

7. Save the new project under a name which makes sense

Fig. 4/24:MWT Programming, screenshot 3

Festo P.BE-FEC-S-SYS en 0105nh 4-25


4. First Steps / Commissioning

8. The template contains a complete program which


transfers the signal at Input 0.0 to the Output 0.0. Then
compile your project (menu Code, Generate New Project).

Fig. 4/25: MWT Programming, screenshot 4

9. Check the serial interface for the connection to the control


system. COM1 is entered as the default in your project.
Your PC may require COM2. You can find the setting by
clicking with the right-hand mouse button on the resource
(e.g. FC400 in the subdirectory Config in the directory
Physical Hardware) to open the menu and there the
settings.

4-26 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

Fig. 4/26: MWT-Programming, screenshot 5

Festo P.BE-FEC-S-SYS en 0105nh 4-27


4. First Steps / Commissioning

Fig. 4/27: MWT-Programming, screenshot 6

10. Open the control dialog box

Fig. 4/28: MWT-Programming, screenshot 7

4-28 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

11. Send the project to the control system

Fig. 4/29: MWT-Programming, screenshot 8

Fig. 4/30: MWT Programming, screenshot 9

Festo P.BE-FEC-S-SYS en 0105nh 4-29


4. First Steps / Commissioning

12. Start the control system with a cold start in the control
dialog box

Fig. 4/31: MWT-Programming, screenshot 10

13. Now enter an input signal on Input 0 of Group E0. The


output 0 of Group A0 then also has to be switched to 1.

14. Check your program by switching to on-line mode

Fig. 4/32: MWT-Programming, screenshot 11

15. Note that the template contains such an example program


in each of the IEC 6 1131-3 programming languages. You
can activate the debug mode for the program which is
actually being executed.

4-30 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

To this purpose it has to be entered in Task1 of the subdi-


rectory Tasks.

Fig. 4/33: MWT-Programming, screenshot 12

Festo P.BE-FEC-S-SYS en 0105nh 4-31


4. First Steps / Commissioning

4.2 Display elements

The FEC has a Run LED which can light in the colors green, red
and orange. Each color indicates an operating state of the
FEC.

During starting (Power ON) the LED switches to orange.

In the following sections the states depend on the setting of


the Run/Stop switch.

If the Run/Stop switch is set to Stop (0), the LED light orange.
If the Run/Stop switch is switched to RUN (1-15) and there is
a project on the system, the project is started and the LED
lights up green. If the Run/Stop switch is set to RUN (1-15)
and there is no project on the system, there is a fault and the
LED lights up red. In the Run state the LED indicates an error
with red.

A detailed fault description is contained on the respective


programming system (FST or Multiprog) or in the documenta-
tion on the corresponding product CD.

4-32 Festo P.BE-FEC-S-SYS en 0105nh


4. First Steps / Commissioning

4.3 Rapid counters

The two inputs (see table below) can be configured indepen-


dently of each other as rapid counter inputs with which the
counting pulses can be used to count up to a frequency of 2
kHz. The counters have a depth of 16 bits (0 to 65535). Inputs
which are configured as counters can still be read simulta-
neously as normal digital inputs.

IPC FEC-type Input

FC400 E1.6 and E1.7

FC440 E1.6 and E1.7

FC520 E1.6 and E1.7

FC560 E1.6 and E1.7

FC600 E3.6 and E3.7

FC620 E3.6 and E3.7

FC640 E3.6 and E3.7

FC660 E3.6 and E3.7

1
1 Module
connector

2 Rapid counter
inputs

2
2

Fig. 4/34: Configuring as rapid counter inputs

Festo P.BE-FEC-S-SYS en 0105nh 4-33


4. First Steps / Commissioning

4.4 The incremental encoder

The IPC FEC disposes of a 16-bit-deep software incremental


encoder (also called AB direction recognition) which can pro-
cess counting pulses up to 200 Hz. The connection is implem-
ented via the two inputs provided as listed in the table below.
An optional reference switch can also be connected via the
input listed in the table.

FEC-type Inkremental enkoder inputs Reference switch input

FC400 E1.4 and E1.5 E1.0

FC440 E1.4 and E1.5 E1.0

FC520 E1.4 and E1.5 E1.0

FC560 E1.4 and E1.5 E1.0

FC600 E3.4 and E3.5 E3.0

FC620 E3.4 and E3.5 E3.0

FC640 E3.4 and E3.5 E3.0

FC660 E3.4 and E3.5 E3.0

1 Module 1
connector

2 Inkremental en-
koder 3
3 Reference switch 2
input

Fig. 4/35: Configuration as an incremental encoder

4-34 Festo P.BE-FEC-S-SYS en 0105nh


Troubleshooting

Chapter 5

Festo P.BE-FEC-S-SYS en 0105nh 5-1


5. Troubleshooting

5. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1

5.1 Information on troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3


5.2 Errors / Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

5-2 Festo P.BE-FEC-S-SYS en 0105nh


5. Troubleshooting

5.1 Information on troubleshooting

Note
Ensure that the installation instructions specified in the
manual have been carried out correctly.

Note
Check whether the IPC FEC-Standard has been connected
with undamaged cables conforming to standards.

Note
Ensure that the absolutely correct supply voltage is
available for the IPC FEC-Standard.

Festo P.BE-FEC-S-SYS en 0105nh 5-3


5. Troubleshooting

5.2 Errors / Remedies

Error Remedy

The IPC FEC-Standard does not – Restart the IPC FEC-Standard.


react – To do so interrupt the power
supply to the IPC
FEC-Standard for a few
seconds.

The module does not read any – Check whether the power
values from the inputs or does supply for the inputs and
not write any values to the outputs is applied correctly at
outputs the individual ports [E0, E1,
A0, etc.].

No communication is estab- – Ensure that the cable PS1


lished via the serial interface SM14 is connected at the FEC
from the PC to the IPC FEC-Stan- end to the communication
dard. interface (Com) and not to the
extension interface (Ext).
– No other program may access
the serial interface from your
PC

I have connected my SAC SC31 – Check whether the signal strip


(3-row), but do not see a signal and the distribution strips are
when the sensor supplies a connected to 24 V DC.
signal. – Check whether you are using
a sensor which supplies +24 V
DC as the signal.

5-4 Festo P.BE-FEC-S-SYS en 0105nh


5. Troubleshooting

Error Remedy
The Power LED does not light up – Check whether the power
although I have connected the supply amounts to 24 V DC
power. (not AC).
– Check whether you have
connected +24 V DC to one of
the 5 upper connections and 0
V to one of the 5 lower
connections.
– Check whether the wires have
been stripped correctly.

I cannot establish a connection – Check whether the IPC


to the IPC FEC-Standard. FEC-Standard is connected to
the power supply and whether
the Power LED lights up.
– Check whether the
programming cable SM14 is
inserted in the connection
COM at the IPC FEC-Standard.
– Check whether the
programming cable SM14 is
inserted into a free RS232
connection at your
programming PC and whether
the correct connection is set
in FST or Multiprog (COM1,
COM2, etc.).
– Check whether 9600 baud
8/N/1 is set
– Check whether the control
system is suitable for the
programming software used
by you.

Festo P.BE-FEC-S-SYS en 0105nh 5-5


5. Troubleshooting

Error Remedy
The IPC FEC-Standard does not The power supply is lower than
react after the power supply has 18 V.
been switched on. The TP LED – Use a power supply unit that
lights up, Power and Run LED are supplies 24 V. In the case of a
off. laboratory power supply unit
the current limiting can be
activated due to the higher
making current.

I have loaded the project Only FST:


correctly for the control system, – Check whether you have the
the Run LED lights up after the program 0 in your project.
program has been loaded, but – Check whether the program 0
red is marked in the project
– Check whether the FST has
really loaded the project or
whether a fault message is
displayed in the message win-
dow.
– Check the fault number (menu
Online, Control Panel) and
compare the error number
with the FST manual.

Fig. 5/1: Error number display

5-6 Festo P.BE-FEC-S-SYS en 0105nh


Technical appendix

Appendix A

Festo P.BE-FEC-S-SYS en 0105nh A-1


A. Technical appendix

A. Technical appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

A.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3


A.2 Output behavior at overload/shor t-circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
A.3 Block diagrams for digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . A-10
A.4 Block diagrams for analog inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . A-13

A-2 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

A.1 Technical data

General

Climatic properties

Transportation/Storage (conforming to -25 °C to +70 °C


IEC 68-2-1/2)
Normal operation (conforming to IEC 0 °C to +55 °C
68-2-1/2)
Temperature change (slow change) IEC 68-2-14
Relative humidity 95 % no moisture condensation

Insensitivity test against vibration (EN 10-57 Hz 0,075 mm; 57 - 150 Hz 1 g


60068-2-6 FC)

Insensitivity test against shock (EN 15 g, 11 ms; 2 shocks/direction


600682-27 EA)

Test for dry heat and cold resistance +70 °C, 96 h; -25 °C, 96 h
(EN60068-2-2Bb / 2-1)

Temperature change durability test (IEC -25 °C/+70 °C, 2 cycles each 3 h
60068 2-14 Na/Nb)

Cycles of moist heat durability test +25 °C/+55 °C, 2 cycles each 12 h
(95-100%) EN 60068-2-30Db

Mechanical properties

Weight IPC FEC FC400 380 g


Weight IPC FEC FC440 390 g
Weight IPC FEC FC520 410 g
Weight IPC FEC FC560 425 g
Weight IPC FEC FC600 480 g
Weight IPC FEC FC620 490 g
Weight IPC FEC FC640 500 g
Weight IPC FEC FC660 510 g
Dimensions IPC FEC FC4XX 115 mm x 105 mm x 35 mm (enclosure)
Dimensions IPC FEC FC5XX 136 mm x 105 mm x 35 mm (enclosure)
Dimensions IPC FEC FC6XX 157 mm x 105 mm x 35 mm (enclosure)

Festo P.BE-FEC-S-SYS en 0105nh A-3


A. Technical appendix

General
Electromagnetic properties

Electromagnetic Compatibility (EMC) EN 50081-2 / EN 61000-6-2


Electrostatic discharging (ESD) EN 61000-4-2
High-frequency electromagnetic fields
(HFF) EN 61000-4-3
Bursts EN 61000-4-4
Mains-borne RF disturbances (LHF) EN 61000-4-6
Radio interference voltage / Interference
field strength EN 55022 / Class A

Electrical properties

Maximum power consumption 200 mA nominal at 24 V, 300 mA maximum

Power consumption of the max 5 W + voltage 24 V DC +25%/-15%


IPC-FEC-Standard + Break time <1ms
+ Max. cable length 10 m

Digital inputs
Number 16 to 32 (depending on type)
Of which usable as rapid counters 2, max. of 2 kHz each

Input voltage/current 24 V DC, typ. 5 mA; Type I

Nominal value for TRUE 15 V DC min.

Nominal value for FALSE 5 V DC max.

Input signal delay Typ. 5 ms

Electrical isolation Yes, optocoupler

Status display with LED Optional in the connector

Inkremental-enkoder Max. 200 Hz

Permissible length of the connecting cable Max. 30 m

A-4 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

Digital outputs
Number 8 to 16 (depending on type)

Type Transistor PNP

Voltage/Current 24 V DC, 400 mA

Short-circuit-proof/Overload-proof yes

Lamp-proof yes, up to 5 W

Electrical isolation Yes, optocoupler

Switching frequency Max. 1 kHz

Electrical isolation in groups Yes, each 1 byte

Maximum group current 3,2 A

Status display with LED Optional in the connector

Fusing Fuse internal 10 AF per output group

Permissible length of the connecting cable Max. 30 m

Analog inputs
Number of inputs 3 inputs (depending on the type)
Signal range 0(4)... 20 mA

Resolution 12 Bit ±3 LSB

Conversion time 1 ms/channel

Electrical isolation Yes, optocoupler


Permissible length of the connecting cable Max 30 m

Analog outputs
Number of inputs / outputs 1 output (depending on the type)

Signal range 0(4)... 20 mA

Resolution 12 Bit ±3 LSB

Festo P.BE-FEC-S-SYS en 0105nh A-5


A. Technical appendix

Analog outputs
Conversion time 1 ms

Electrical isolation Yes, optocoupler

Fusing Fuse intern. 375 mAF

Permissible length of the connecting cable Max 30 m

Rotary switch
Number 1

Positions 16

STOP/RUN 0=Stop and 1 ... F=Run

Serial interface
Number 2

Connection RJ12 socket

Properties Serial, asynchronous, TTL level, not isolated

Use as RS232c SM14 or SM15 required

Connection assignment SM14/15A Transmit, Receive, RTS, CTS

Use as universal interface: EXT 300 ... 115000 Baud, 7N1, 7E1, 701, 8N1, 8E1,
801

Permissible length of the connecting cable


FEC SM14/15 + ZK14 Max. 3 m

A-6 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

Ethernet
Number 1/0 (depending on type)

Bus interface IEEE802.3 (10Base T)

Data rate 10 MBit/s

Connector RJ45

Supported protocols TCP/IP, EasylP, http (only FST)

OPC server (on request) Yes, for EasylP

DDE server Yes, for EasylP

Permissible length of the connecting cable Max. 100 m to the next neutral point

Status Display
Combined link/traffic LED Link: Permanently on green (depending
on type)
Traffic: Permanently on green
(depending on type)

Power LED Power supply display - green

Status LED Depending on status


Run green
Stop orange
Error red

Protection information
Degree of protection IP 20

Safety class Safety class III,


Power supply unit conforming to IEC 742/EN
60742/VDE 0551/PELV with at least 4 kV in-
sulation resistance or switched-mode power
supply units with a protective separation con-
forming to EN 60950/VDE 0805 are permitted.
The maximum length of the power supply cable
amounts to 10 m.

Festo P.BE-FEC-S-SYS en 0105nh A-7


A. Technical appendix

Hardware and software properties


Processor 80186 (20 MHz)
Working memory 512 kByte RAM
Working memory for Multiprog Typ. 12000 lines STL
Working memory for FST typ. 14000 lines
Retentive data Max 2 kbytes
Program memory 150 Kbytes available (write/delete cycles min.
10,000)
Operating state display Run LED (green, red, orange, flashing)
Network connection
(FC440/560/640/660) 10Base T (RJ45)
Network communication display
(FC440/560/640/660) Link/Traffic LED

A-8 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

A.2 Output behavior at overload/shor t-circuit

The output ports (A0, A1, etc.) are short-circuit- and overload-
proof independently of each other.

If a short-circuit or overload current is applied, a temperature


rise occurs at the switching transistor. The overtemperature
fuse switches the respective output off so that the switching
transistor can cool down again. The respective output is acti-
vated afterwards again. If an overload current continuous to
exist after the activation, the process begins again.

The cycle length of the process depends on the extent of the


overload. In case of a low overload the cycle length can last
up to several minutes - at a high overload less than 1 second.

This behavior can be influenced, if necessary, by the operat-


ing system (FST, Multiprog).

Festo P.BE-FEC-S-SYS en 0105nh A-9


A. Technical appendix

A.3 Block diagrams for digital inputs and outputs

1 2

+24 V
5 +5 V
3

0V

1 Internal 4 Load
2 External 5 Fuse 10 Amperes fast
3 Power supply
Fig. A/1: Digital output

A-10 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

1 2

4 +5 V +24 V
3

0V

1 Internal 3 Power supply


2 External 4 Fuse 10 Amperes fast
5 Load
Fig. A/2: Digital output

Festo P.BE-FEC-S-SYS en 0105nh A-11


A. Technical appendix

1 2

+24 V

+5 V

0V

5 3

1 Internal 4 Sensor
2 External 5 PS1 SAC
3 Power supply
Fig. A/3: Digital input

A-12 Festo P.BE-FEC-S-SYS en 0105nh


A. Technical appendix

A.4 Block diagrams for analog inputs and outputs

1 Internal 1 2 3
2 External
3 Power supply AV+ +24 V
7
4 Analog current or Ain
voltage source

5 I signal A/D
4

6 A/D converter ‹300R


7 U signal
AGND 0V
6 5

Fig. A/4: Diagram of analog input

1 Internal 3
1 2
2 External
3 Power supply
6 AV+ + 24 V
4 Analog current
signal

5 D/A converter Aout 4


6 Fuse 0,375 AF
D/A
5
AGND 0V

Fig. A/5: Diagram of analog output

Festo P.BE-FEC-S-SYS en 0105nh A-13


A. Technical appendix

A-14 Festo P.BE-FEC-S-SYS en 0105nh


Accessories

Appendix B

Festo P.BE-FEC-S-SYS en 0105nh B-1


Appendix B. Accessories

B. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

B.1 Accessories detailed information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3

B-2 Festo P.BE-FEC-S-SYS en 0105nh


Appendix B. Accessories

B.1 Accessories detailed information

Product Product image

PS1 PSE3 AC/DC converter 230 V AC/ 40 W, 24 V


DC /1.74 A

24 V DC, 40 W is supplied by the PSE3 from 185


to 265 V AC - latches onto the top-hat rail, fits
into the PS1 design

Supplied with screwed connectors

Packaging unit: 1 piece

Order No. 160853

Programming cable PS1 SM14

Programming cable TTL-RS232 in SUB-D housing


+ zero modem cable

Packaging unit: 1 piece

Order No. 188935

Programming cable PS1 SM15

Interface converter TTL-RS232 in SUB-D housing


+ top-hat rail mount with earthing connection

Packaging unit: 1 piece

Order No. 192681

Festo P.BE-FEC-S-SYS en 0105nh B-3


Appendix B. Accessories

Product Product image


Sensor actuator connector PS1 SAC10

Tension spring technique 10-pin, single-row with-


out LEDs

Packaging unit: 1 piece

Order No. 197159

Sensor actuator connector PS1 SAC11

10-pin, single-row with LEDs

Packaging unit: 1 piece

Order No.: 197160

Sensor actuator connector PS1 SAC30

10-pin, three-row with LEDs

Packaging unit: 1 piece

Order No. 197161

Sensor actuator connector PS1 SAC31

Tension spring technique 10-pin, single-row with


LEDs

Packaging unit: 1 piece

Order No. 197162

B-4 Festo P.BE-FEC-S-SYS en 0105nh


Appendix B. Accessories

Product Product image


Screw terminal socket PS1 ZC13-S

Power supply connector 10-pin

Packaging unit: 4 piece

Order No. 160800

Earthing set
*)
As an earthing possibility for analog I/Os and
Ethernet

Packaging unit: 1 piece

Order No. 526683

* Cables are not included in the scope of delivery

Festo P.BE-FEC-S-SYS en 0105nh B-5


Appendix B. Accessories

B-6 Festo P.BE-FEC-S-SYS en 0105nh


Index

Appendix C

Festo P.BE-FEC-S-SYS en 0105nh C-1


C. Index

C. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1

C-2 Festo P.BE-FEC-S-SYS en 0105nh


C. Index

Index

A
AB direction recognition . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
application program . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24

B
Before commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10

C
cable length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
combined dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Combined mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
communication connection . . . . . . . . . . . . . . . . . . . . . . . 3-11
communication interface . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Connecting cable SM 14 . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Connection assignment . . . . . . . . . . . . . . . . . . . . . . 3-13, 3-14
Connection scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
connector pin assignment . . . . . . . . . . . . . . . . . . . . . . . . 3-11
connector strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
control speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25
counting pulses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33

Festo P.BE-FEC-S-SYS en 0105nh C-3


C. Index

cross cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21


cycle length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9

D
debug mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
Digital Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Digital Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
direct network connection . . . . . . . . . . . . . . . . . . . . . . . . 3-21
dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
displaying the signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Distribution strip 24 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
distribution strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
dust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

E
E/As . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
earthing terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Earthing without a top-hat rail . . . . . . . . . . . . . . . . . . . . 2-12
equipotential bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
equipotential bonding strip . . . . . . . . . . . . . . . . . . . . . . . 2-14
Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21

F
FST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
FST Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
function selector . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24, 3-25

C-4 Festo P.BE-FEC-S-SYS en 0105nh


C. Index

functional earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14

G
gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

H
Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

I
Important information for the user . . . . . . . . . . . . . . . . . . . VII
incremental encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
IPC FEC FC400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
IPC FEC FC440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
IPC FEC FC520 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
IPC FEC FC560 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
IPC FEC FC600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
IPC FEC FC620 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
IPC FEC FC640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
IPC FEC FC660 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

L
Load Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20

M
MULTIPROG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13, 4-24

Festo P.BE-FEC-S-SYS en 0105nh C-5


C. Index

MWT-Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24

N
network connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII

O
oil mist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
on-line mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22, 4-30
online display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
operating state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
output group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21

P
Pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Power LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Power supply connector . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
power supply unit PS1 PSE3 . . . . . . . . . . . . . . . . . . . . . . 2-15
Power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
programming cable PS1 SM14 . . . . . . . . . . . . . . . . . . . . 4-24
Programming station . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
project name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
PS1 SAC10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5, 4-11
PS1 SAC11 . . . . . . . . . . . . . . . . . . . . . . . . . 3-7, 4-5, 4-7, 4-11
PS1 SAC30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5

C-6 Festo P.BE-FEC-S-SYS en 0105nh


C. Index

PS1 SAC31 . . . . . . . . . . . . . . . . . . . . . . 3-5, 3-6, 4-5, 4-7, 4-11


PS1 SM14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

R
rain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
rapid counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
rating plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
RJ12 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Run LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32

S
Sensor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
shielded cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
short-circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
single contact rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
star distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
star-head earthing point . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
stranded cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
sun irradiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
switch position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25

T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VI
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
tension spring terminals . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Top-hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14

Festo P.BE-FEC-S-SYS en 0105nh C-7


C. Index

Top-hat rail earthing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14


trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24, 3-25
troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Twisted Pair cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22

V
vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

W
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VII
wire cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27, 4-5, 4-8