Digitrip 1150V / 1150Vi - I T Curves


Range: 1-5 seconds @ 6x Ir

30
7

9
10
2

20

40

60
3

50
.7
.8

5
6

8
.9
.6
.5

10000
9000
2 Hours

8000
7000 Circuit Breaker Time / Current Curves (Phase Current)
6000 Available LONG PU
Settings (Ir)
5000 VCP-T, VCP-TR, T-VAC, T-VACR Medium Voltage Circuit Breakers
0.4 to 1 x In = Ir 4
Response: Long Delay (I T) & Short Delay Trip
1 Hour

4000 in 0.05 increments This curve is for 50Hz or 60Hz applications.

3000
Available Sensors and Matching Rating Plug in Amperes
2000 100A 250A 400A 630A 1000A 1250A 2000A

200A 300A 600A 800A 1200A 1600A 2500A

1000 Notes:
900
800 1. There is a Long MEMORY (if enabled) effect that can act to shorten the Long
700 Delay. The memory effect comes into play if a current above the LONG PU value
600 exists for a time and then is cleared by the tripping of a downstream device or the
circuit breaker itself. A subsequent overload will cause the circuit breaker to trip
500 in shorter time than normal. The amount of time delay reduction is inverse to the
400 amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory.
300 2. This curve is shown as a multiple of LONG PU Setting (Ir).
The actual Pickup point occurs at 110% of the Ir, current, with a ±5% tolerance.
4
200 Long TIME Curve Equation: Trip = Long TIME *1296/I ,where I is a multiple of Ir.

4
3. In this time region, the I T Long TIME function will flatten out and be no faster
than the Short TIME setting.

100 4.SHORT PU has an additional setting, which can extend out where the SHORT
90 PU will be active..
80 Plug Adjustable range M1 setting
1 Minute

70 100A through 1250A 1.5 to 14x Ir M1=14x In


60 1600A, 2000A, 2500A 1.5 to 12x Ir M1=12x In
50
5. The SHORT PU points have conventional 100% ± 5% tolerance.
40
6. SHORT TIME: FLAT only - setting 0.1s through 0.5s, 1s or 2s in .05s increments.
30 Tolerance is +0/ -80 ms of setting except
0.10s setting is 0.06 to 0.13
0.15s setting is 0.10 to 0.17
20 0.20s setting is 0.15 to 0.22

7. With zone interlocking on Short Delay utilized and no restraining signal, the minimum
Adjustable Long TIME SHORT TIME band (0.10s) applies regardless of the SHORT TIME setting.
1-5 seconds
8. The end of the curve is determined by the interrupting rating of the circuit breaker.
10 (+10%, -40%) @ 6x Ir
9
With 0.5s increments 9. Curve applies from -20°C to +55°C ambient. Temperatures above +85°C cause
8
7
(See Note 7) automatic trip.
6
5 5

2 2.0s ST Setting Limit for 600A and Greater Plug


See Note 3
Clearing Time in Seconds

1 1 1.0s ST Setting Limit for 200A through 400A Plug


.9
.8
.7
.6
.5 0.50s ST Setting Limit for 100A Plug
.4

.3

0.20s
.2

0.10s

.1
.09
.08
.07
.06
.05
Adjustable SHORT PU
.04 1.5x to 12x or to 14x Ir Minimum clearing time
With 0.5 increments (See Notes 6, 7)
(See Note 4) Adjustable Short TIME
.03
0.10 to 2.0 seconds
with 0.5s increments
.02

.01
1

7000
8000
9000
3000

6000
5000

10000
1000
800

4000
2000
500

700

900
200

600
300
4

400
100
30

70
80
90
7

9
10
2

20

40

60
3

50
.7
.8

5
6

8
.9
.6
.5

Current in Multiples of LONG PU (Ir)


Dwg. No: 5721B05
September 2006
Printed in the U.S.A.