Académique Documents
Professionnel Documents
Culture Documents
art ic l e i nf o a b s t r a c t
Article history: The concept of building-integrated photovoltaic/thermal (BIPV/T) systems emerged in the early 1990s. It
Received 26 March 2015 has attracted increasing attention since 2000 due to its potential to facilitate the design of net-zero
Received in revised form energy buildings through enhanced solar energy utilisation. This article presents a comprehensive re-
1 February 2016
view of the BIPV/T technology, including major developments of various BIPV/T systems, experimental
Accepted 4 July 2016
Available online 2 September 2016
and numerical studies, and the impact of BIPV/T system on building performance. The BIPV/T systems
reviewed here are: air-based systems, water-based systems, concentrating systems and systems invol-
Keywords: ving a phase change working medium such as BIPV/T with either heat pipe or heat pump evaporator. This
Solar energy work provides an overview of research, development, application and status of BIPV/T systems and
Building-integrated photovoltaic
modules. Finally, research needs and opportunities are identified.
Thermal
& 2016 Elsevier Ltd. All rights reserved.
BIPV/T system
Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 887
2. Integration with the building envelope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 888
3. BIPV/T air system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 890
3.1. Active BIPV/T air system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 890
3.2. Passive BIPV/T air system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 893
4. BIPV/T water system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 895
4.1. PV/T water collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 895
4.2. Investigation of BIPV/T water system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 896
5. Other systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 898
5.1. BIPV/T systems involving phase change process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 898
5.1.1. BIPV/T heat pipe system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 898
5.1.2. BIPV/T evaporator system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 899
5.2. BIPV/T concentrating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 899
6. Research method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900
6.1. Numerical approach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900
6.2. Experimental approach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900
6.2.1. Indoor test in built environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900
6.2.2. Outdoor test in the test chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 901
6.2.3. Building size experiments and demonstrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 901
7. Influence on building energy performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 902
8. Discussion and conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 908
8.1. Summary of BIPV/T systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 908
n
Corresponding author.
E-mail address: pvting_yang@163.com (T. Yang).
http://dx.doi.org/10.1016/j.rser.2016.07.011
1364-0321/& 2016 Elsevier Ltd. All rights reserved.
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912 887
determining the fire rating for each PV module [45]. Some time Air is lightweight and easy to transfer, giving a BIPV/T air sys-
later concerns were raised whether and how PV modules with tem the flexibility for integration with various building elements
lower fire ratings may affect the performance of higher rated such as: roofs, facades, windows and skylights. A BIPV/T air sys-
roofing systems. To address these concerns, tests on various tems can be categorized as active open-loop and passive based on
combinations of PV designs and roof coverings were jointly con- the buoyancy force. Compared with liquid-based systems, open-
ducted by UL and the Solar America Board for Codes and Stan- loop BIPV/T air systems are generally advantageous in terms of less
dards. The test results demonstrated that the fire classification initial cost, moderate maintenance effort, and reduced risks re-
rating of the PV module alone, determined by the standard UL lated to freezing or leaking.
1703, may not predict the fire performance of the PV module, An active BIPV/T system is commonly installed in an open-loop
mounting system, and roof assembly as a whole system. As a re- configuration in which outdoor air is driven by a fan and passes
sult, an updated UL 1703 standard was published in October 2013, through the channel behind the PV panels. Since an open-loop air
treating the PV modules and the roofing materials as an integrated system normally runs at a lower temperature than the close-loop
building element [46]. This change is expected to be included in air system, higher thermal efficiency and better PV performance
newer versions of the International Building Code [47]. The and durability can be achieved. In addition, open-loop systems
adaptation of PV and building standards to BIPV system fire rating have the potential for supplying pre-heated fresh air to a building.
codes, illustrated the effort being made to update building stan- In a passive system, extra ducting or moving parts are not
dards to reflect the increasingly widespread BIPV technology. usually required since the heated air is either fed into the indoor
However, as Scott and Zielnik [48] pointed out, BIPV products space or exhausted into the ambient. This type of installation
conform separately to both PV and building standards but there is often called a BIPV system, although significant consideration
are essentially no integrated standards specifically for BIPV pro- is made of the thermal aspects during the design process. A
ducts. Also, current standards primarily address specific safety and passive system usually interacts with the building environment in
electrical issues but do not address long term performance re- regard to heating, cooling and lighting loads, and electricity
quirements as either a PV panel or building material. Bloem [49] production.
suggested that less than optimal tilt angles of BIPV systems and
the lack of convection at the back of the PV for some thermally 3.1. Active BIPV/T air system
insulated BIPV installations may result in significant BIPV perfor-
mance impairments that do not exist for standalone PV under The schematic of a typical open-loop BIPV/T air system is
standard test conditions. Bloem et al. [50] recommended that the shown in Fig. 5 [52]. Depending on the solar cell type, about 6–16%
complete BIPV/T system be tested using a comprehensive assess- of the incoming solar radiation is converted into electricity, with
ment procedure covering: electrical performance, thermal per- the rest either reflected (about 10%) or transferred into heat. This
formance and its seasonal variation, ventilation performance, vi- means that approximately 70% of the incident solar energy has to
sual effect, maintenance and other performance criteria. Further- dissipate in the form of thermal energy. The heat accumulated in
more, building codes impose requirements for PV as a the PV is dissipated via four heat transfer paths: radiative
Fig. 7. (a) Schematic illustration of a BIPV/T system integrated with UTC [26]; (b) Mechanical room of the JMSB building before BIPV/T system installation; (c) Transpired
collector installed as part of the mechanical room facade; (d) PV modules mounted on top of the transpired collector as the outermost layer of the mechanical room façade.
892 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
affect the electricity generation. The addition of the cover glass in low. Further simulation showed that more thermal energy was col-
front of the whole wallboard increased the thermal efficiency from lected by adding a glazing above the PV, while electricity generation
approximately 22% to more than 29%, which echoed the work of was greatly reduced due to diminished solar input through the
Tripanagnostopoulos et al. [55] on PV/T systems. The electrical glazing and higher PV temperature.
efficiency was reduced by the cover glass due to condensation on Assoa et al. [13] developed a BIPV/T system with co-generation
the inner surface of the glass. of hot air and water, which applied adjacent hybrid bi-fluid ther-
It is advantageous to integrate the BIPV/T system with an ex- mal collectors and PV panels above the rib structures. The com-
istent building energy system, such as the unglazed transpired bined thermal efficiency reached approximately 80% under fa-
collector (UTC). A UTC is a perforated, dark-colored and corrugated vourable operating conditions. Assoa et al. [61] extended this de-
metal panel that is usually fixed onto the equator-facing façade of sign with a variant roof-integrated BIPV/T system using a ribbed
a building. With all sides sealed, the ambient air is drawn in sheet steel absorber and using natural ventilation air as the
through the holes and heated along its flow path by the absorbed working fluid (Fig. 8). The system was integrated into the roof of a
solar energy. With a typical thermal efficiency of 65–75% [56], this manufacturing company building and monitored for two years. A
system is able to collect suitable energy for fresh air pre-heating validated numerical model showed that although forced ventila-
[57] or crop drying [58]. Naveed et al. [59] showed that the PV tion achieved higher thermal production than natural ventilation,
module mounted on a UTC is cooled by 3–9 °C on a typical day in the difference between the calculated electrical yields of the two
February compared to a PV module attached to the wall. operating modes was marginal.
Athienitis et al. [26] investigated the performance of a BIPV/T Lin et al. [62] combined phase change materials (PCM) in a
prototype integrated with UTCs (Fig. 7a). The authors selected roof-integrated BIPV/T air system. This system allowed for not only
black PV module backsheet as well as black aluminum frame to electricity generation, solar heating during winter daytime and sky
maximise solar energy absorption and to create a uniform ap- radiative cooling during summer nighttime, but also increased
pearance of the whole system. Figures 2.7b, 2.7c, 2.7d shows how insulation plus thermal energy storage with the PCM component.
the layers of the BIPV/T system, namely the transpired collector TRYNSYS simulations showed that the BIPV/T air system main-
and the PV modules, were integrated as the façade of the me- tained indoor air temepratures consistently above 18.9 °C on ty-
chanical room. It can be seen that the BIPV/T system was not ap- pical winter days in Australia.
plied to an existing building façade, but rather constitute itself Using a building simulation tool, Guiavarch and Peuportier [12]
alone as a functional building wall. Furthermore, the corrugations found that the thermal efficiency of the BIPV/T system depended on
of the UTC ran horizontally instead of vertically in order to form which zones the heated air would be directed to. The simulation results
sealed air gaps with the PV to induce turbulent flow in the air also suggested the advantage of using semi-transparent PV modules
gaps. Comparative experiments between a bare UTC and a BIPV/T instead of opaque PV modules because less heat was lost at non-
prototype with 70% PV coverage indicated that the BIPV/T system packing areas with low emissivity and because the transmitted solar
was 7–17% higher in efficiency than the UTC, with the assumption radiation was absorbed at the back of the system. Vats et al. [14] ana-
that electricity is four times more valuable than heat. This in- lytically showed that a decrease in semi-transparent PV module packing
tegration concept was further applied on a newly constructed of- factor (percentage of the total PV module area covered by solar cells)
fice building – the John Molson School of Business (JMSB) at resulted in decreased module temperature and increased system ther-
Concordia University in Montreal, Canada. The BIPV/T installation mal output. Bloem [49] drew the same conclusion through experiments
provided a peak power generation of 24.5 kW electrical and 75 kW performed using a test environment box. It was pointed out that con-
thermal for the building. The authors pointed out that this BIPV/T vective and radiative heat exchanges on the rear side of the PV module
demonstration project could provide a model for retrofit applica- in the building-integrated application were different from those for the
tions where a new BIPV/T façade could be built over the existing open rack mounted PV. This was addressed by the test environment
façade. box that facilitated changing materials (e.g. metal, brick, wood) at the
Using an experimentally calibrated model, Pantic et al. [60] pre- surface facing the rear of the PV. Aste et al. [63] developed a BIPV/T
dicted that a significant outlet air temperature increase would be component using semi-transparent PV modules and implemented this
achieved by connecting a 1.5 m vertical glazed solar air collector in design concept for the Fiat Research Centre at Orbassano, Italy. The
series with the outlet of the conventional BIPV/T system. The air installed system has a power of 20 kWp and the hot air was used for
temperature rise enables coupling with a rockbed heat storage. The preheating air in winter and desiccant cooling in summer.
added vertical solar air collector expands usable roof area and receives Charron and Athienitis [64] carried out an optimization study
high amounts of solar radiation in winter when the solar altitude was of the performance of ventilated double-facades integrated with
PV panels and motorized blinds. Installing PV modules in the and average Reynolds number. The importance of using actual
middle of the glazed cavity was found to enhance the heat re- distributed wind velocities as opposed to an assumed uniform
covery at the cost of reduced electricity generation. Integrating fins velocity in the simulation of building-integrated solar systems was
to the back of the PV resulted in a similar increase in thermal ef- further discussed [72]. The wind velocity distribution on the BIPV/
ficiency without compromising electrical output. It was concluded T façade using a physical model of the JMSB building of Concordia
that optimization strategies depended on the intended use of the University [26] was experimentally measured in an open circuit
façade incorporating both a BIPV/T system and motorized blinds. wind tunnel. It was observed that the velocity near building edges
Kaiser et al. [65] developed semi-empirical correlations for PV could be 50% higher than those above the roof. The surrounding
module temperature and resulting electrical efficiency in relation structures were found to increase the local wind velocities by 20–
to depth-to-length channel aspect ratio, channel air velocity, am- 30% compared with the case when they were removed from the
bient temperature and incident solar radiation. For systems with vicinity of the JMSB building. Full-scale measurements of wind-
forced convection, lower aspect ratios were suggested to enhance induced convective heat transfer coefficients for a flat plate solar
PV cooling. For naturally ventilated systems, a critical channel collector mounted on a pitched roof was conducted by Sharples
aspect ratio of 0.11 was suggested to reduce the overheating of PV and Charlesworth [73].
modules.
Zogou and Stapountzis [66] assessed typical transient behaviour of 3.2. Passive BIPV/T air system
a BIPV/T air system in outdoor conditions in Greece. The authors
further performed indoor tests to study the air flow field in the BIPV/T Gaillard et al. [74] conducted an experimental evaluation of a
setup, using flow visualization instruments as well as a hot wire an- naturally ventilated full-scale BIPV system under real operating
emometry system [67]. A significant flow entrance effect was ob- conditions. The West-North-West orientation of the BIPV façade
served in the cases studied of their work. It was found that the flow was compensated by designing a series of adjacent prism columns
rate and the heat transfer coefficient between the back of PV module with PV modules installed on west-facing surfaces to optimise PV
and air are critical to the system performance. performance. Monitored data suggested that the system might
Sohel et al. [68] developed a dynamic model capable of simu- contribute to the heating and ventilation needs of the building in
lating the performance of BIPV/T air systems under real operation addition to electrical power generation, especially during the
conditions. The numerical model showed that thermal efficiency spring and autumn. With sheltered air inlets, the air movement
increases with increasing ambient temperature in an approximate behind the PV modules was found to be dominated by buoyancy
linear manner, while electrical and exergy efficiencies decrease effect, whereas no clear correlation was observed between the
with an increase in ambient temperature. Higher air flow rates magnitude of channel air and outdoor wind speed. Using para-
were found to benefit electrical and exergy efficiencies until the metric analysis of the measured data, the authors developed linear
flow rate exceeded 300 L/s at which point the efficiencies were not models composed of a few independent variables to characterise
sensitive to the changes in flow rate. the electrical and thermal performance of the BIPV façade, sug-
Agrawal and Tiwari [69] designed BIPV/T air channels that can gesting that simplified physical models should be appropriate to
be connected in series or parallel for use in the cold climate. Nu- predict system performance despite the complexity of real oper-
merical simulations suggested that the series configuration was ating conditions and unconventional geometries.
more suitable for a constant air mass flow rate in terms of energy Analytical models are useful to predict the thermal behaviour
and exergy production, whereas the parallel configuration was of a passive BIPV system. Brinkworth et al. [75] developed an
better in the case of constant air velocity. Overall, the series con- analytical model to predict the thermal behaviour of a BIPV system
figuration with constant mass flow rate was found to generate the with buoyancy driven laminar flow. The model is straightforward
most annual energy and exergy including thermal and electrical to use either as an Excel spreadsheet or coupled to a building si-
gains. mulation package. Also using analytical expressions of a passive
An unglazed BIPV/T system with PV directly exposed to the BIPV system, Sandberg and Moshfegh [76] found that the max-
ambient air could also result in a peak PV temperature of about imum flow rate was obtained by increasing the height of the air
60 °C on a warm sunny day [22]. Yang and Athienitis [70] proposed channel until a balance between friction and buoyancy was
using multiple air inlets instead of one inlet for the BIPV/T system achieved for a given heat input.
that usually involves large-scale installation. Based on experi- Wong et al. [77] found that semi-transparent PV modules used
ments carried out on a conventional one-inlet BIPV/T system in an as tilted residential skylights reduce the annual building heating
indoor solar simulator, a lumped parameter thermal network load but cause overheating issues in regions with a cooling season
model was developed and verified with experimental data. Si- in Japan. It was proposed to use transparent insulation for cold
mulation results of a BIPV/T system with two inlets showed that regions and opaque movable insulation for moderate temperature
the thermal efficiency was increased by 5% and the peak PV regions to optimise the building energy performance. Varying the
temperature was reduced by about 1.5 °C compared to a one-inlet module packing factor was also found essential to achieve max-
system assuming equal total flow rates were used for each system. imum energy savings in different climate conditions. Xu et al. [78]
The authors pointed out that the local heat transfer coefficients concluded that implementing the optimal packing factor achieved
were higher near the added inlet because the boundary layer had an average energy saving of 13% compared to the least favourable
been broken, and that the air drawn into the second inlet has al- PV packing factor. Yun et al. [79] discussed the optimum trans-
ready been pre-heated by the PV top surface. It was suggested that parent window to opaque PV ratio for different climate, building
for actual roofs of 5–6 m long, the reduction of maximum PV characteristics and façade configurations. In addition, they sug-
temperature would be at least 5–10 °C depending on flow rate and gested that locating the air outlet in a region of wind-induced
wind conditions. negative pressure was essential to enhancing the natural ventila-
Karava et al. [71] pointed out that the Nusselt number corre- tion in the BIPV system.
lations previously developed for plates subjected to uniform ap- The open-joint ventilated façade employs discontinuous ex-
proach flow should not be used directly for roof surfaces because ternal cladding on ventilated facades, resulting in localized dis-
of the complex wind flow field around buildings. In the context of continuities of the air flow at the joints (Fig. 9). Sanjuan et al. [80]
BIPV/T application, a correlation for Nusselt number was devel- showed that open-joint ventilated facades may achieve significant
oped that included the effect of free stream turbulence intensity energy savings in climates with hot summers and mild winters.
894 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
wall was usually focused on the heat transfer and thermal mod-
eling of the energy system [81–84].
Ji et al. [85] proposed a BIPV/T Trombe wall system and as-
sessed the temperatures of the PV and indoor environment
through numerical modeling. This BIPV/T Trombe wall system was
shown to increase room temperature by a maximum value of
12.3 °C compared to the conventional wall in the winter of Hefei,
China. Later, Ji et al. [86] found that installing a BIPV/T Trombe wall
system in a fenestrated room with heat storage increased the room
temperature by a maximum of 7.7 °C. Sun et al. [87] showed that a
south façade having both a BIPV/T Trombe wall and a window
(Fig. 10) can achieve a higher indoor air temperature than a facade
with a conventional Trombe wall of the same size. Jiang et al. [88]
concluded that the indoor air temperature was increased by 6.8 °C
when the PV packing factor was reduced from 0.873 to 0.207.
Koyunbaba and Yilmaz [89] found that the BIPV/T Trombe wall
system may led to a significant room temperature increase. They
suggested using an automation system for opening and closing the
vents to maintain comfortable conditions in the room. In order to
Fig. 9. Schematic of an open-joint ventilated façade [80]. regulate the indoor temperature, Ji et al. [90] proposed a BIPV/T
Trombe wall system having extra vents to exhaust the heated cavity
There is a possibility of integrating PV as a building material into air to the outdoor environment in summer. In addition, it was sug-
this type of ventilated façade. gested to add thermal insulation, advantageous for both summer and
In a BIPV/T Trombe wall system, the outer glazing of the tra- winter conditions, and append a shading curtain in the summer to
ditional Trombe wall is replaced with the semi-transparent pho- improve system performance. Aelenei et al. [91] studied a BIPV/T
Trombe wall system with the massive wall replaced with a gypsum
tovoltaic module, a-Si or c-Si type. While maintaining the ad-
board incorporating PCM. The PCM absorbed excessive heat during
vantages of Trombe walls such as simple configuration, no moving
the day when solar radiation was abundant, thereby reducing the
parts and zero running cost, the BIPV/T Trombe wall system also
overheating of the indoor environment.
generates electrical energy and reduces solar energy gain in
Semi-transparent PV modules may replace window glazing owing
summer. Furthermore, the front PV panel adds to the aesthetical
to light transmission and electricity generation capability. The inter-
appearance of the building, as compared to the black wall under- action between the BIPV window and the building involves PV elec-
neath the clear glass. tricity generation, thermal loads, lighting consumption and visual
A Trombe wall consists of two solid layers – a glazing pane on comfort of the building. There are generally three forms of BIPV
the exterior and a massive thermal wall on the interior with an air windows in current research: single pane, double-pane with enclosed
cavity in between the layers. Usually there are vents at the top and air cavity, and ventilated double-pane with open air cavity.
the bottom of the wall to allow natural air circulation between the Li et al. [92] showed that visual discomfort, solar heat gain,
indoor space and the wall cavity. Driven by buoyancy force, heated lighting energy consumption and HVAC equipment size can be
air enters the room through the top openings and cool air returns reduced by replacing southwest-facing tinted glass windows with
to the Trombe wall through the bottom vents. Research on Trombe semi-transparent a-Si PV panels and applying lighting controls in a
typical office building in Hong Kong. Lu and Law [93] also pointed install than conventional double-glazed windows. It was also in-
out that using semi-transparent c-Si BIPV windows may enhance dicated that the energy payback offsetting the primary energy
building energy performance. They suggested the following opti- used to manufacture and transport the PV modules could be less
mal office orientations for annual electricity savings in order for than two years.
Hong Kong: south-east, south, east, south-west and west. Olivieri
et al. [94] concluded that for intermediate and large openings
covering more than 33% of the façade area, BIPV windows account 4. BIPV/T water system
for 18–59% energy savings compared to glass when applied in a
typical middle-size office building in Spain. 4.1. PV/T water collector
Fig. 11a shows a typical double-pane BIPV window consisting of
a semi-transparent PV panel at the outside and a glass pane at the A typical PV/T water collector is constructed by attaching PV to
inside with an enclosed air cavity in between. Miyazaki et al. [95] the thermal absorber using thermal paste with high conductivity
showed that building primary energy consumption can be reduced [100–102], welding [103], or mechanical force [10,55]. Depending
by installing this type of BIPV window and adopting lighting on the local climate and temperature conditions, an optional
controls. They suggested optimal transmittances of the PV module glazing can be added on top of the PV to form an extra stagnant air
in accordance with different window to wall ratios of the building. layer to increase thermal gains. The thermal performance of a PV/T
A low emissivity coating was further shown to reduce radiative water collector is affected by the following factors:
heat transfer and the U-value of this BIPV window configuration
[28]. Chae et al. [29] showed that up to 30% of the annual HVAC Transmission losses through the upper glazing. The transmis-
energy consumption can be saved by installing double-pane semi- sivity can be increased by applying anti-reflective coatings on
transparent BIPV windows as opposed to double-pane clear glass the two sides of low-iron glass.
windows, in the low and medium latitude US cities. Semi-trans- Absorptivity of solar cells. Solar radiation absorption is opti-
parent PVs of different optical properties were recommended for mised in the wavelength range of 300–1100 nm for silicon solar
maximum utility cost savings for these cities. cells [104]. Ideally, the thermal performance is enhanced using a
Fig. 11b shows a schematic of a typical ventilated double-pane selective coating that ensures maximum solar absorption while
BIPV window with top and bottom vents on the exterior surface maintains low emissivity in the infrared region. Santbergen
allowing heat removal from PV by naturally ventilated air. Ex- et al. [105] showed that anti-reflective coatings on the cover
periments conducted by He et al. [96] indicated that the indoor glass and the top surface of the PV improved both thermal and
heat gain of the ventilated double-pane BIPV window was reduced electrical efficiencies, while low-emissivity coating on the PV
to less than half of that of the single pane BIPV window. The surface increased the thermal output at a cost of reduced
thermal comfort level of the work space was also improved due to electrical performance.
the lower inner surface temperature of the ventilated double-pane Absorptivity of the PV module area not covered by solar cells. A
BIPV window. Chow et al. [97] showed that a PV transmittance of common c-Si PV module is partially covered by photovoltaic
0.45–0.55 in the ventilated BIPV window resulted in the most cells, leaving the rest 10–15% area exposed as a sandwiched
electricity saving when taking into account air-conditioning load, composition of glass/EVA/PVF (polyvinyl fluoride). The white
artificial light consumption and PV electrical generation. Annually PVF backsheet is highly reflective (70–80%) in order to reduce
the BIPV window can cut down the air-conditioning power con- PV's operating temperature. However, this leads to a reduction
sumption by 28% for a typical Hong Kong office, compared to the of available thermal energy in the PV/T system. Improvements
conventional single absorptive glass window [98]. The authors can be achieved by using a solar absorbing or transparent
also stated that high-efficiency thin-film solar cells could facilitate backsheet.
the uptake of PV double-pane windows. From a monetary point of Thermal conductivity between the PV and thermal absorber.
view, Ng and Mithraratne [99] showed that with government Good thermal contact encourages more heat transfer from the
subsidies certain PV modules with high efficiencies are cheaper to solar cells to the working medium. The conductivity can be
Fig. 11. (a) Double-pane semi-transparent photovoltaic window with enclosed air cavity [28]; (b) Ventilated double-pane semi-transparent photovoltaic window with open
air cavity [27].
896 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
improved by using square instead of round ducts [106], by the low-temperature application of direct floor heating. The low
laminating the PV with absorber using a vacuum laminator operating temperature of the PV/T system (below 35 °C) not only
[107], or by replacing TPT (Tedlar/PET/Tedlar) backsheet of the avoided overheating of the room, but also enhanced PV perfor-
PV module by aluminum alloy [108]. Tripanagnostopoulos et al. mance because of better cooling effect. However, PV module
[55] pointed out the importance of promoting better thermal temperatures of above 100 °C were observed for the glazed system
contact using a proper manufacturing procedure at the indus- in summer when there were no heating needs, leading to a strong
trial scale. risk of EVA degradation and yellowing. The solutions included
Withdrawal of electrical energy. Santbergen et al. [105] demon- using amorphous modules which contained no EVA and employ-
strated for the case when a low-e coating is applied on the PV ing non-glazed PV/T collector.
surface, the PV electricity generation mainly accounted for the
annual thermal energy reduction for a PV/T system than a solar 4.2. Investigation of BIPV/T water system
heater.
Fig. 12 shows examples of thermal absorbers used in BIPV/T
The annual performance of a roof-mounted single-glazed PV/T water systems. The sheet-and-tube PV/T configuration (Fig. 12a)
water system was simulated to match the electrical and hot water can achieve satisfactory efficiencies, while being easy to manu-
consumption profiles of a typical UK house [109]. Simulation re- facture by integrating a PV panel with a standard water collector
sults identified that PV packing factor significantly influences with no significant modifications [101,112]. The rectangular
electrical output, and that water flow rate affected hot water channels (Fig. 12b) and flat-box absorber (Fig. 12c) are used to
production to a greater extent. A packing factor of 0.8–1 and a low enhance heat transfer in the BIPV/T system.
flow rate in the range of 20–80 L/h was suggested to increase Bakker et al. [23] developed a manufacturing process where
system performance and reduce CO2 emissions. solar cells and a sheet-and-tube copper absorber are laminated
Bakar et al. [102] designed an unglazed PV/T collector with co- into a single PV/T panel. The performance of a 25 m2 roof-size PV/T
generation of hot water and air. This system can obtain high water installation coupled with ground-source heat pump was analysed
outlet temperatures while reducing penalty in electrical perfor- using TRNSYS. The system was found to meet the total hot water
mance, if low water flow rate and proper air flow rate were and spacing heating demand and nearly all electricity demand for
maintained. With a total thermal efficiency of about 76% under a typical Dutch single-family dwelling. Dupeyrat et al. [107] used a
favourable operating conditions, this system may potentially be vacuum laminator to combine a PV panel and a rollbond alumi-
used for agriculture drying, fresh air pre-heating and domestic hot num absorber into a single PV/T component. In addition, anti-re-
water heating. flective coating was applied on the low-iron glass cover and mono-
Although polymer materials have a lower thermal conductivity crystalline silicon cells with a higher absorptivity were used. The
than copper, stainless steel and aluminum, the light weight of single-glazed PV/T system was shown to achieve thermal effi-
polymer allows a simple mounting at a lower price [110]. Sandnes ciency comparable to that of a thermal collector without selective
and Rekstad [111] constructed a PV/T water collector by pasting coating. Moreover, Dupeyrat et al. [9] demonstrated that a lami-
solar cells onto the polymer absorber plate of a solar collector. nated BIPV/T collector achieved higher electricity and exergy
Experimental results showed that the inlet water temperature outputs plus higher primary energy savings than side-by-side PV
should not exceed 40 °C for unglazed system and 30 °C for single- and thermal collector installations covering the same area. Also to
glazed system so that the solar cell temperature can be maintained improve the thermal contact between PV and the thermal absor-
below 45 °C. Fraisse et al. [10] also examined using PV/T systems in ber, Zakharchenko et al. [115] proposed a PV module design using
Fig. 12. Examples of thermal absorbers of a BIPV/T water system: (a) Sheet-and tube configuration [112]; (b) rectangular water channel [113]; (c) Aluminum-alloy flat-box
configuration [114].
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912 897
Fig. 13. Schematic illustration and photograph of the roof integrated BIPV/T water system using polyethylene pipes tested in Nottingham, UK [25].
a metallic substrate. A PV/T prototype using this type of PV module effective heat transfer to the tubes from all directions. This system
showed a 10% increase of power generation. can be installed as the roofing panel onto traditional roof framing,
Ghani et al. [116] addressed the uneven flow distribution issue with the bottom structural substrate able to be integrated into the
in sheet-and-tube BIPV/T water collectors and concluded that a building skin and to provide thermal insulation. Yang et al. [120]
manifold to riser pipe ratio of 4:1 and an array aspect ratio greater implemented numerical heat transfer simulation of this BIPV/T
than 0.44 resulted in more uniform flow distributions. The study system using ABAQUS.
recommended a mass flow rate of 0.015 kg/(s m2) for aspect ratios Evola and Marletta [113] proposed a BIPV/T water collector
less than 1.78; while for values greater than 1.78, higher mass flow using rectangular stainless steel ducts to enhance heat transfer
rates was found to increase the net electric generation. Ghani et al. between the thermal absorber and the water passage (Fig. 12b).
[117] further developed an artificial neural network to quickly Thermal modeling demonstrated that there existed an optimum
evaluate the performance of BIPV/T systems according to the water inlet temperature that maximized the overall exergy effi-
specific roofing conditions and energy requirements of the cus- ciency of the BIPV/T collector. The optimal water supply tem-
tomer. It was demonstrated that electrical output was not always perature, which is a function of water mass flow rate, solar ra-
improved by increasing the number of risers, since inferior flow diation and ambient air temperature could be regulated by a
distribution uniformity was resulted. command-control system. Also from the point of exergy gain,
Buker et al. [25] considered using polyethylene pipes as the Chow et al. [121] evaluated the performance of a thermosyphone-
thermal absorber by adhering them to the rear surface of PV type PV/T water system using six parameters: PV packing factor,
modules (Fig. 13). An experimentally validated thermal model cell efficiency, water mass in the tank, solar radiation, ambient air
showed that the overall energy and exergy performances of this temperature and wind velocity. They found that a change of any
BIPV/T system were better compared to the bare PV system. It was parameter affected the electric and thermal exergy efficiencies in
stated that the polyethylene tubes are an economical, easy-to- opposite directions.
maintain and flexible cooling solution for existing PV systems and Fudholi et al. [122] proposed three PV/T thermal absorber de-
do not disturb the original PV system structure. In regard to af- signs, one of which using rectangular stainless steel tubes was
fordable, easily-manufactured and easily-installed BIPV/T designs, later adopted in the development of a BIPV/T water system. The
Timmerman et al. [118] proposed a plug-and-play liquid BIPV/T collector was tested for energy and exergy performances in the hot
panel with the solar cells glued onto a plastic channel absorber. and humid equatorial climate of Malaysia [123]. The combined
The authors suggested the use of labels, multiple connection thermal and electrical efficiency was found to be 55–62%, while
points and different connectors for inlets and outlets to ensure fast the exergy efficiency was found to be between 12% and 14%.
and flexible connection of the BIPV/T panels. Chow et al. [114] proposed a PV/T water collector with alumi-
Yin et al. [119] designed a BIPV/T water system that in- num-alloy flat-box absorber underneath the PV (Fig. 12c). With the
corporated a layer of mixed aluminum and insulating high density natural circulation of water, this system was shown to adapt well
polyethylene with embedded water tubes (Fig. 14). Experimental to ‘hot summer and cold winter’ climate zones of China. The flat-
results showed a small temperature difference between the PV box-type water channel design was later implemented in a façade-
and the outlet water, suggesting that the aluminum enabled integrated BIPV/T system [124]. Operated with a pre-set water
consumption pattern, thermal efficiencies of the BIPV/T system
under natural and forced water circulation modes were similar,
and so were electrical efficiencies. The natural circulation mode
was found more favourable for Hong Kong since the forced cir-
culation mode incurred extra fan power consumption. Annual si-
mulation of the thermosyphonic BIPV/T system showed thermal
and electrical efficiencies of 37.5% and 9.39%, respectively [125].
A BIPV/T water system with PV panels suspended 0.1 m above
an array of black tube-fin absorbers was developed by the Uni-
versity of Colorado Solar Decathlon Team for the 2007 U. S. Solar
Decathlon competition [126]. A numerical model found that the
thermal efficiency was lower than the results from the referenced
literature owing to the ineffectiveness of heat transfer from the PV
Fig. 14. Schematic illustration of the BIPV/T water-type roofing panel [119]. to the absorber by means of convection and radiation as opposed
898 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
to conduction. An electrical efficiency correlation was developed temperatures of BIPV/T systems. The independent heat pipe tubes
as a function of water inlet temperature, ambient air temperature may also avoid the problem of uneven flow distribution across
and solar insolation. Kazanci et al. [11] also presented a BIPV/T roof multiple ducts that may be encountered in BIPV/T water systems.
panel for integration with the Solar Decathlon competition house By selecting proper working fluids, heat pipes can maintain the
of Technical University of Denmark. The BIPV/T installation was operating temperature of photovoltaic modules in a suitable range.
found to fulfill the electrical demand of the building in addition to For example, Moradgholi et al. [133] used methanol and acetone in
contributing to a significant portion of domestic hot water a heat pipe PV/T system for spring and summer working condi-
demand. tions, respectively.
BIPV/T water systems have the potential of enhancing PV Fig. 15 shows the schematic of a typical PV/T heat pipe system
electrical performance in low-temperature applications, such as [134]. The heat pipe evaporator adhered to the back of the PV
pool heating and direct floor heating [10,55,111]. For moderate and module absorbs and transfers heat to the working medium. The
high temperature systems (above 50 °C), it is necessary to com- vaporized medium then travels to the condenser section where it
promise between the thermal requirement and the PV favourable releases the heat and goes through a phase change to a liquid
operating temperature (low temperature). Malvi et al. [127] sug- state. The liquid returns to the evaporator through a wick structure
gested establishing thermal gain targets before PV performance is using capillary force and begins another heat transfer cycle.
optimised by varying system parameters. Pei et al. [134] developed a heat pipe PV/T system with ex-
perimental thermal and electrical efficiencies of 41.9% and 9.4%,
respectively. A dynamic model indicated a maximum temperature
5. Other systems difference of 3 °C between the evaporator and condenser sections
of the heat pipe, showing the level of thermal conductance of the
5.1. BIPV/T systems involving phase change process heat pipes. Further numerical study of the heat pipe PV/T system
suggested that water-copper heat pipes were reliable for the op-
Materials have a large thermal capacity when experiencing the erating conditions in Hong Kong, while ammonia-aluminum heat
phase change process. They possess great potential for cooling PV pipes were suitable for coping with the freezing problem in the
modules. Huang et al. [128] demonstrated that PV module tem- cold winters of Lhasa and Beijing [135]. A variety of parameters
peratures can be maintained below 35 °C on typical June days in including water flow rate, PV packing factor, heat pipe spacing and
Southeast England by incorporating a solid-liquid phase change solar absorption coefficient were discussed in terms of their in-
material (PCM) cavity at the back of the PV. The temperature fluence on the system performance [136]. Pei et al. [137] also
regulation of PV may further be enhanced using internally finned noted that the system performance could be further improved by
PCM cavities [129], two PCMs with different melting temperatures optimizing the refrigerant and enhancing the heat exchange be-
[130], or a metal-embedded matrix [131]. Ho et al. [132] showed tween heat pipe and water tank.
that for a BIPV system cooled by a microencapsulated PCM layer, Wu et al. [138] proposed incorporating radial fins on the con-
the electrical and thermal properties of the system relied on the denser section of the heat pipe to improve heat transfer from the
melting temperature and width-to-height aspect ratio of the PCM heat pipe to the water flow. The system was found to achieve
layer. thermal and electrical efficiencies of 63.65% and 8.45%, respec-
To date, heat pipes and heat pump refrigerant evaporators, tively. PV temperatures were found within a deviation of 2.5 °C,
with a liquid-vapor phase change process, are incorporated in the indicating the isothermal property of heat pipes.
BIPV/T system. Other types of heat pipe – the flat plate heat pipe and the loop
heat pipe (LHP) are also used in BIPV/T systems. Quan et al. [139]
5.1.1. BIPV/T heat pipe system addressed that less thermal contact resistance was introduced
Heat pipes have high thermal conductivity; they may enhance with flat plate heat pipes compared to round heat pipes. On a
thermal performance and achieve more uniform PV module typical March day in Beijing, a BIPV/T system using a flat plate pipe
Fig. 15. Schematic of a typical tube heat pipe PV/T system [134].
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912 899
and ten 90 W PV modules was found to raise a 15 m2 room to system was found to generate more electrical power than the
26.3 °C through a floor radiative heating system. Zhao et al. [140] compressor power consumption, with an average COP of 6.01 on a
stated that the LHP based water heating system can eliminate the typical day in January. Xu et al.[147] also used flat extruded alu-
need to transport water for a long distance since the solar re- minum tubes in a low-concentrating PV/T evaporator heat pump
ceiving surface is covered by heat pipes rather than water ducts. water heating system for experimental investigation in Nanjing,
Zhang et al. [141] designed and fabricated a LHP with a vapor-li- China. During the test period the refrigerant-cooled PV cell tem-
quid separation structure to overcome the ‘dry-out’ issue of con- perature varied between 20 °C and 30 °C, whereas the non-re-
ventional gravitational LHPs. Outdoor tests on such a combined frigerant-cooled PV cell temperature increased to 85 °C. PV elec-
PV/LHP and heat pump system showed a maximum daily tem- trical efficiency was found to be 1.36 times higher due to the
perature in the water tank to be around 54 °C in November, cooling effect of refrigerant. Ji et al. [148] further showed a glazed
Shanghai. Experimental results also showed that the PV module PV/T evaporator heat pump system could achieve higher COP than
was cooled by 5.2 °C using a coated aluminum-alloy sheet versus a the air-sourced heat pump. An average PV electrical efficiency of
conventional TPT sheet at the back of the PV module. The PV was over 12% and an average heat pump COP of 5.4 of the PV/T eva-
found to generate more electricity than needed to drive the porator heat pump system was predicted [149].
compressor in this system. By attaching the evaporator coil of a heat pump directly under
the PV modules, the heat pump is ‘directly-assisted’ by a BIPV/T
5.1.2. BIPV/T evaporator system system. Correspondingly, a BIPV/T system can ‘indirectly-assist’ a
Using a roof as the heat source (winter) and heat sink (sum- heat pump by providing heated medium as a heat source. Kar-
mer) of the heat pump was proposed in the 1980 s [142]. This agiorgas et al. [196] showed that the COP of an air-source heat
concept has recently been applied to a BIPV/T evaporator system, pump was increased from 3.33 to 4.94 when the outlet hot air of a
constructed by attaching the direct-expansion evaporation coils of 23.5 m2 façade integrated solar air heater was supplied to the
the heat pump to the rear surface of building-integrated PV evaporator. Hazi and Hazi [197] compared two PV/T indirectly-
modules. The evaporative temperature of the refrigerant allows assisted heat pump systems (a steam ejector heat pump and a
the PV operating temperature to be maintained at a low level mechanical compression heat pump) for hot water production in a
(typically 0–30 °C). In comparison, Tiwari and Sodha [143] pointed paper mill. Numerical simulation results showed that the system
out that the PV cell temperature could reach over 55 °C in a PV/T using a mechanical compression heat pump is more energy effi-
water system. cient. From the exergy point of view, the PV/T assisted steam
Fig. 16 shows a typical BIPV/T evaporator roof configuration, ejector heat pump is more efficient for generating hot water at
which incorporates the functions of roof element, electricity gen- 70 °C.
erator and heat pump evaporator [144]. Numerical simulation re-
sults indicated that an evaporation temperature of 0–10 °C and a 5.2. BIPV/T concentrating system
condensation temperature of 50–70 °C are suitable for running this
system coupled with a heat pump in UK. The system could achieve For a BIPV/T concentrating system, a high density of luminous
55% of thermal efficiency and 19% of electrical efficiency under a flux is cast on a relatively small PV surface with the use of re-
typical Nottingham operating condition. flective/refractive devices, resulting in a significantly high solar
Xu et al. [145] used multi-port flat aluminum extruded eva- cell temperature. A thermal collector may be added to lower cell
porator in a PV/T heat pump system to reduce heat transfer re- temperatures while producing high-temperature fluid that may
sistance between the PV and the evaporator. Simulation results effectively be used for solar heating or cooling. Generally, low
showed that this system can heat 150 L water to 50 °C all year concentration systems are considered promising for building in-
round in Nanjing and Hong Kong, China. On a yearly scale, the tegration due to the static states of concentrating device.
overall performance of the PV/T evaporator heat pump system was Chemisana et al. [150] designed a facade-integrated con-
shown to improve with varying compressor speed in different centrating BIPV/T system using Fresnel reflectors that also acted as
seasons. This conclusion is consistent with the result of a case vertical lattices for illumination control of the building. A solar
study investigating the performance of a glazed PV/T evaporator cooling system consisting of such a concentrating BIPV/T collector
heat pump system in Tibet, China [146]. The refrigerant mass flow covering an aperture area of 540 m2 and a double-effect absorp-
rate was matched to the ever-changing solar radiation and outdoor tion chiller was shown to cover 39% of the cooling demand of a
temperature using a variable-frequency compressor. The examined three-storey building on a typical summer day in Barcelona. Al-
Alili et al. [151] proposed a solar cooling unit consisting of a de-
siccant wheel driven by the thermal output of a concentrating PV/
T system and a conventional vapor compression cycle driven by
the electrical output. TRNSYS simulations results showed that the
proposed system achieved a COP of 0.68, which was higher than
that of either a solar absorption chiller or a standalone vapor
compression cycle. Mittelman et al. [15] addressed that the cost of
a concentrating PV/T cooling system might be comparable to a
conventional cooling system.
Davidsson et al. [16] developed a concentrating BIPV/T window
that incorporated multiple functions including glazing, electricity
generation, hot water generation and shading. Fig. 17 shows that
the reflectors allow passive room heating at a horizontal position
and enabled concentrating apparatus functioning at a vertical
position. Diffuse radiation was found to account for about 40% of
the electrical energy production. Annual simulation showed that
the auxiliary energy need of the building with a BIPV/T window
was 600 kW h less than that without a BIPV/T component [152].
Fig. 16. Schematic drawing of the BIPV/T evaporator roof [144]. Wennerberg et al. [153] pointed out that c-Si PV modules were
900 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
Fig. 19. A BIPV/T water system integrated with the façade of an environmental
chamber [124].
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
and backsheet to enhance
thermal performance.
UTC corrugations are hor-
izontally placed to facilitate
air flow into the plenum.
Australia Sohel et al. [68] Roof Thin-film Numerical Electrical and exergy efficiencies are less sensitive to air flow rate when it exceeds 300 L/s for the system Dynamic performance as-
investigated. sessment under real oper-
Thermal and overall efficiencies decrease while electrical and exergy efficiencies increase with increase of solar ating conditions is
irradiance. performed.
BIPV/T system is installed
on two buildings, one
being a Solar Decathlon
China 2013 house and the
other being the Sustainable
Building Research Centre
building in Australia.
Canada Chen et al. [22]; Roof a-Si Numerical Significant cooling effect of the PV module is achieved with the air flow. The BIPV/T system is in-
Candanedo experimental A typical thermal efficiency of 20% was achieved by the BIPV/T system. stalled in a low-energy so-
et al. [195]; Heat transfer coefficients between air and the PV panel are developed. lar demonstration house in
Yang and The thermal efficiency of the BIPV/T system may be increased by 7% with four multiple inlets. Canada.
Athienitis [70]. Outdoor experiments are
performed.
Indoor experiments on the
BIPV/T system are carried
out in a full-scale solar
simulator.
UK, Germany Infield et al. Façade c-Si (ST) Numerical Outlet air temperature of the system is around 50 °C in summer and 40 °C in winter. U-values and g-values
[163]; Mei et al. U-value of the façade is fairly constant over the heating season. (SHGCs) are used to char-
[182]. Twelve percent of heating energy can be saved using the ventilations air of the BIPV/T system for the Mataro acterise the thermal per-
Library building in Spain. formance of the semi-
The thermal efficiency of the façade is on average around 13% at the flow velocity of 0.3 m/s in Barcelona, transparent BIPV/T façade
compared to 15% in Stuttgart. and facilitate the energy
modeling of the building.
Heat gains to the ventila-
tion air may offer the po-
tential for solar cooling in
summer.
The BIPV/T system equips
the Mataro Library building
in Spain.
Italy, Spain Bloem [49]; Façade c-Si Experimental Modification to the air inlet may allow air flow to enter the BIPV/T cavity homogeneously without disturbance. The Test Reference En-
Bloem et al. Electrical and thermal performances are studied for BIPV/T systems with different PV module configurations. vironment enables the
[50]. The thermal efficiency varied between around 33% and 42% with cavity air velocity changing from 1.37 m/s and testing of BIPV/T systems
3.43%. using different materials
903
under outdoor conditions.
904
Table 3 (continued )
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
India.
Parallel and serial connec-
tions of the air channels
are evaluated to select an
appropriate system for the
local climate.
Japan Nagano et al. Façade c-Si Experimental Using glass or Teflon as the cover material for the PV module does not affect electrical performance significantly. The BIPV/T system suitable
[54] Thermal efficiencies for glazed and unglazed BIPV/T systems are 20.2–22.3% and 29.2–36.9%. for operation in snowy re-
gions is developed and
tested.
The design facilitate mod-
ular assembly
Greece Zogou and Sta- Façade c-Si Numerical Significant flow entrance effect is observed for the BIPV/T system. The transient performance
pountzis experimental The selection of air flow rate and the heat transfer coefficient between the PV backsheet and the air are critical to of the BIPV/T system is
[66,67] adequately characterise system performance. studied by experiments
under outdoor operating
conditions.
Flow visualization techni-
ques are used to study the
air flow and turbulence
field in the BIPV/T cavity
under indoor steady-state
conditions.
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
energy, insulation, struc-
tural strength and
waterproofing.
Water tube is embedded in
the polyethylene with high
aluminum content. This
allows for heat transfer to
water tubes in all
directions.
China Chow et al. Façade c-Si Numerical Natural over forced water circulation is more suitable for the system in Hong Kong. The BIPV/T water collector
[124,125, 161] experimental The BIPV/T façade reduces thermal loads in summer and winter. is installed on the façade of
Annual thermal and electrical efficiencies are 37.5% and 9.4% in Hong Kong. a test chamber and tested.
Aluminum-alloy flat-box
type of thermal absorber
was used in the BIPV/T
design.
UK Herrando et al. Roof c-Si Numerical The investigated BIPV/T system may cover 52% of the electrical and 36% of the hot water demands annually. The suitability of BIPV/T
[109] High PV packing factor and low water flow rate are recommended. system for the provision of
electricity and hot water
for a typical terraced house
in the UK is assessed.
New Zealand, Anderson et al. Roof c-Si Numerical Low cost materials such as pre-coated color steel may be utilised in the BIPV/T design without significant effi- A BIPV/T water system is
Australia [35] experimental ciency decrease. developed by integrating
Good thermal contact between the PV and the absorber need to be made; this could be achieved using thermally the PV with troughed sheet
conductive adhesives. roof.
USA Corbin and Zhai Roof c-Si Numerical Thermal and overall efficiencies are 19% and 34.9%. Full-scale experimentation
[126] experimental A correlation is developed relating electrical efficiency to inlet water temperature, ambient air temperature and is carried out on a BIPV/T
insolation. water system.
The BIPV/T system is in-
stalled for a Solar Dec-
athlon competition house.
UK Buker et al. [25] Roof c-Si Numerical A thermal efficiency of 20.25% may be achieved with water temperature increase of 16 °C for the BIPV/T system. A BIPV/T system is formed
experimental by laying polyethylene wa-
ter tubes under the PV pa-
nels, offering an in-
expensive and requiring
minimum maintenance
heat extraction solution to
existing PV systems.
905
906
Table 3 (continued )
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
pipe condenser section.
UK, China Zhang et al. Roof c-Si Experimental The experimental mean daily electrical, thermal and exergy efficiencies of the PV/T system are 9.1%, 39.3% and A loop-heat-pipe in-
[141] 15.0%. tegrated PV/T system is
The thermal COP is 5.5. The thermal and electrical combined COP is 8.7. fabricated for use in con-
The aluminum-alloy based PV temperature is 62.4 °C. It is 5.2 °C lower than that of the Tedlar based PV module. nection with the heat
pump.
A coated aluminum-alloy
sheet over the conven-
tional Tedlar material was
used as the backsheet of
the PV module for en-
hanced heat dissipation.
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
Greece Mandalaki et al. Shading device Numerical Lowest energy need for heating, cooling and lighting corresponds to surrounding shading, Brise-Soleil full façade Energy impact on the
[192] and canopy inclined double for both Chania and Athens. building of a large range of
Surrounding shading is the most energy efficient system when PV electricity generation is also considered for window shading device
both cities. designs are studied in the
Mediterranean climate.
USA Dominguez Roof c-Si Experimental Daytime ceiling temperatures under the PV arrays are 2.5 K cooler than under the exposed roof. A building rooftop partially
et al. [189] The PV covered roof may enable a 38% reduction in annual cooling load over exposed roof. covered by a horizontal
The reduced daily variability in rooftop temperature under the PV arrays reduces thermal stresses of the roof. and flush PV array and a
tilted PV arrays is
investigated.
USA, Canada Ban-Weiss et al. Roof a-Si Experimental Summertime daily mean roof upper surface temperature is lowered by 5 °C due to reduced solar absorptance and A BIPV retrofit system is
[24] increased insulation of the BIPV system. installed on an office
Summertime daily heat flux through the roof deck falls to 7 0.1 kW h/m2 from 0.3 to 1.0 kW h/m2. building and investigated.
Switzerland Pola et al. [190] Roof a-Si Experimental Flat roof integrated PVs that are thermally insulated are hotter than PVs mounted on a tilted open rack. A roofing system consisting
Amorphous silicon PV modules are more suitable for thermally insulated applications than c-Si PVs. of PV modules laminated
with polyolefin mem-
branes as a waterproof
system is installed on a
school building.
Note: ST is semi-transparent.
907
908 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
measurements of the interior wall surface behind the BIPV/T wall semi-transparent PV modules. The BIPV/T window has the po-
and the reference wall showed that the BIPV/T façade may reduce tential of reducing cooling load, visual discomfort and artificial
the temperature oscillation amplitude and achieve higher wall lighting consumption in the warm climate than conventional glass
temperatures on a cold cloudy winter day compared to the re- windows. However, the convective heat transfer coefficient of air
ference façade [124]. According to Peng et al. [193], the BIPV wall was relatively low due to its low density and heat capacity, re-
demonstrated a better thermal insulation performance than a sulting in less efficient cooling of PV panels. It is therefore im-
normal wall by reducing 69% of daytime heat gain and 32% of portant to enhance the heat transfer between air and the PV.
nighttime heat loss during the winter (November – April). Increasing the thermal contact between the PV module and the
Compared to a conventional Trombe wall, a BIPV/T Trombe wall water channels has been a research topic for BIPV/T water heating
reduces the cooling load but increases the heating load [85,87]. systems. The conventional round copper tubes may be replaced by
The less efficient heating effect incurred by the PV modules may rectangular stainless steel ducts or aluminum-alloy extruded flat-
be compensated by applying thermal insulation on the massive box absorber so that the contact surface between PV and tubes are
wall [90]. increased, which in turn reduces the thermal resistance. The
The introduction of semi-transparent PV modules in BIPV/T substrate material of the PV may also be considered using a me-
designs complicates the analysis of building energy performance, tallic layer to increase the heat dissipation rate. Although having a
which affects heating load, cooling load, artificial lighting con- much lower thermal conductivity than metal, polymer is also
sumption, and shade control to avoid glare in the workspace. The utilised in BIPV/T water systems because the light weight allows a
optimization of building energy conservation should usually take a simple mounting and lower price reduces initial system cost.
holistic view, considering parameters including installation area, These properties are important for building application because
a-Si PV transparency (c-Si PV packing factor), room depth, venti- less weight reduces the load on the building's physical structure
lation mode, orientation and climate. It is generally demonstrated and a significant amount of investment may be saved for a large
through numerical modeling and experimentation that using installation on a building scale. When taking the advantages of
semi-transparent BIPV windows as opposed to glazed windows both material options into account, it may be interesting to de-
can provide energy saving opportunities in warm climates [78,92– velop a mix of polymer material and metallic particles for BIPV/T
94,97,194]. This is mainly due to the low solar transmittance and water systems. In addition, BIPV/T water systems have been ex-
U-value of semi-transparent BIPV windows reducing heating loads tensively investigated in regard to the number of glazing, glazing
significantly in cooling-dominated locations. Investigation of a material, anti-reflective/low-emissivity coating, as well as operat-
BIPV window system was also conducted for the cold climate such ing mode between natural and forced convection.
as Japan [77,95]. Wong recommended using transparent insulation The constraints of air-based and water-based BIPV/T systems
material to increase heat gain magnitude and duration while are: (1) limited heat transfer rate; (2) reduced heat absorbing
limiting the night-time heat loss. The annual energy saving po- ability with increased fluid temperature which results in sig-
tential of integrating the a-Si PV modules into the window system nificant temperature variations of the PV; (3) conflict between
of a medium-sized office building in 6 typical US climates from dry maintaining favourable low operating temperature of the PV and
tropical to humid continental was evaluated [29]. It was found that obtaining high-grade thermal energy. BIPV/T systems may make
building heating energy demand was found to depend highly on use of the phase change process which has considerable heat ab-
the local climate and thermal-optical properties of the PV. The use sorbing potential at a constant temperature to address the above-
of BIPV window may reduce the heating load in low latitude sites mentioned issues to some extent. So far, BIPV/T systems integrated
including Miami, Phoenix and Los Angeles, yet increase the heat- with PCMs, heat pipes, and the evaporators of heat pumps have
ing load in Duluth at 46°47’N. It was concluded that BIPV windows been developed and studied.
can be a good candidate for reducing annual HVAC energy con- A heat pipe BIPV/T system often works with another fluid cir-
sumption for low and medium latitude locations. cuit that transports the thermal energy away from the condenser
section of the heat pipe. The sealed heat pipes may reduce the risk
of leakage and avoid uneven fluid distribution from manifold to
8. Discussion and conclusions riser pipes encountered in water and heat pump BIPV/T systems.
The working medium and fill ratio of the heat pipe are yet to be
8.1. Summary of BIPV/T systems explored to optimise system performance in different climates and
for different serving purposes. The heat exchanger that removes
The omnipresence and light weight of air makes BIPV/T air thermal energy from the hot end of the heat pipe should be
systems available for integration with multiple building elements carefully designed to allow efficient heat transportation.
including roof, façade, window and skylight. Open-loop active For the BIPV/T system integrated with the evaporator of a heat
systems are often found equipping the opaque building envelope pump, not only can the PV temperature be maintained at favour-
such as the roof and façade, and the active heat recovery system able levels, but also the COP of the heat pump is elevated owing to
may be used to provide fresh preheated air or operated in con- the solar energy input. Selecting the refrigerant, determining the
nection with other energy systems of the building. Open-loop evaporation and condensation temperatures, and regulating the
active BIPV/T air systems may contribute to achieving net-zero compressor speed with different seasons are crucial to enhancing
energy buildings enormously where space heating load dominates system performance.
the annual energy consumption of the building. Existing building The PCM in the BIPV/T cavity may cool down the PV module
materials or energy components such as ribbed metal roofing during the daytime through a phase change process from solid to
sheet, photovoltaic shingles, Trombe wall and unglazed transpired liquid, and release the stored heat at night. Selecting adequate
collector may be exploited for use to develop innovative BIPV/T type and quantity of PCM according to the temperature require-
systems. In addition, the open-joint ventilated façade may help to ments and thermal load is important to ensure sufficient cooling of
achieve energy savings in climates with hot summers and mild the PV.
winters. It is promising to use PV modules as the outmost cladding The additional reflective/refractive devices of concentrating
in this type of façade. On the other hand, the transparent surfaces rather than flat BIPV/T systems make it necessary to develop in-
of the building envelope such as window and skylight provide novative integration designs into the building. Nonetheless, the
integration locations for passive BIPV/T system often utilising concentrated solar energy could produce high-temperature liquids
T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912 909
to assist solar cooling despite the system complexity. The potential integrated building facades. Renew Energy 1996;8:475–9.
of integrating more types of concentrating devices in an innovative [5] Hayter SJ, Martin RL. Photovoltaics for buildings: Cutting-edge PV. Presented
at UPVG Utility PV Experience (UPEx)’98, San Diego, California, September
way into buildings may be further investigated. 28–30;1998.
To further assist the understanding of the BIPV/T technology, [6] Eiffert P. U.S. guidelines for the economic analysis of building-integrated
main international research activities on BIPV/T systems are listed photovoltaic power system Colorado (USA): National Renewable Energy La-
boratory; 2000 NREL/TP-710-25266.
in Table 3. [7] Ponsnansky M, Gnos S, Coonen S. The importance of hybrid PV-building
integration. Paper presented at the IEEE Photovoltaic Specialists Conference,
Hawaii; 1994.
8.2. Research needs and opportunities
[8] Fujisawa T, Tani T. Annual exergy evaluation on photovoltaic-thermal hybrid
collector. Solar Energy Mater Solar Cells 1997;47:135–48.
The following topics are areas of further BIPV/T system research [9] Dupeyrat P, Menezo C, Fortuin S. Study of the thermal and electrical per-
formances of PVT solar hot water system. Energy Build 2014;68:751–5.
as identified by the literature reviewed in this paper:
[10] Fraisse G, Menezo C, Johannes K. Energy performance of water hybrid PV/T
collectors applied to combisystems of Direct Solar Floor type. Solar Energy
(1) Improved design of BIPV/T systems and modules and their 2007;81:1426–38.
performance investigation through experimental and numer- [11] Kazanci OB, Skrupskelis M, Sevela P, Pavlov GK, Olesen BW. Sustainable
heating, cooling and ventilation of a plus-energy house via photovoltaic/
ical approaches remain an important need. Many factors need thermal panels. Energy Build 2014;83:122–9.
to be taken into account, including but not limited to working [12] Guiavarch A, Peuportier B. Photovoltaic collectors efficiency according to
medium, heat transfer enhancement measures, materials, their integration in buildings. Solar Energy 2006;80(1):65–77.
[13] Assoa YB, Menezo C, Fraisse G, Yezou R, Brau J. Study of a new concept of
structure and climate. photovoltaic-thermal hybrid collector. Solar Energy 2007;81:1132–43.
(2) It is necessary to develop compact plug-and-play BIPV/T [14] Vats K, Tomar V, Tiwari GN. Effect of packing factor on the performance of a
modules to allow standard and handy installation of BIPV/T building integrated semitransparent photovoltaic thermal (BISPVT) system
with air duct. Energy Build 2012;53:159–65.
systems. Pre-fabricated BIPV/T modules enable the construc-
[15] Mittelman G, Kribus A, Dayan A. Solar cooling with concentrating photo-
tion at high precision and are vital for cold climate regions voltaic/thermal (CPV/T) systems. Energy Convers Manag 2007;48:2481–90.
where it is nearly impossible to perform outdoor construction [16] Davidsson H, Perers B, Karlsson B. Performance of a multifunctional PV/T
hybrid solar window. Solar Energy 2010;84:365–72.
work in snowy months.
[17] Chemisana D, Rosell JI. Design and optical performance of a nonimaging
(3) The enhancement of heat transfer from the PV panel to the Fresnel transmissive concentrator for building integration applications. En-
working medium is important for lowering PV panel tem- ergy Convers Manag 2011;52(10):3241–8.
perature and increasing thermal efficiency of the BIPV/T sys- [18] Chow TT. A review on photovoltaic/thermal hybrid solar technology. Appl
Energy 2010;87:365–79.
tem. Current commercial PV panels use low thermal con- [19] Kumar R, Rosen MA. A critical review of photovoltaic-thermal solar collectors
ductivity materials such as Tedlar as the backsheet, which do for air heating. Appl Energy 2011;88:3603–14.
not provide good thermal contact between PV panels and the [20] Tyagi VV, Kaushik SC, Tyagi SK. Advancement in solar photovoltaic/thermal
(PV/T) hybrid collector technology. Renew Sustain Energy Rev
working medium. 2012;16:1383–98.
(4) Means for avoiding overheating need to be studied since [21] Jelle BP, Breivik C, Rokenes HD. Building integrated photovoltaic products: a
temperatures of PV over 70 °C cause module deterioration. state-of-the-art review and future research opportunities. Solar Energy
Mater Solar Cells 2012;100:69–96.
(5) Methods for effective building integration need to be studied.
[22] Chen Y, Athienitis AK, Galal K. Modeling, design and thermal performance of
They enable BIPV/T systems to be an attractive building design a BIPV/T system thermally coupled with a ventilated concrete slab in a low
option and aiding BIPV/T becoming a standard building energy solar house: Part 1, BIPV/T system and house energy concept. Solar
Energy 2010;84:1892–907.
component.
[23] Bakker M, Zondag HA, Elswijk MJ, Strootman KJ, Jong MJM. Performance and
(6) Integration of the BIPV/T system with other energy systems costs of a roof-sized PV/thermal array combined with a ground coupled heat
such as heat pump, heat storage, heat recovery ventilator and pump. Solar Energy 2005;78:331–9.
solar cooling system needs to be studied, so that the produced [24] Ban-Weiss G, Wray C, Delp W, Ly P, Akbari H, Levinson R. Electricity pro-
duction and cooling energy savings from installation of a building-integrated
thermal energy may be used more efficiently. photovoltaic roof on an office building. Energy Build 2013;56:210–20.
(7) It is necessary to explore the use of a-Si PV modules in BIPV/T [25] Buker MS, Mempouo B, Riffat SB. Performance evaluation and techno-eco-
systems with high-temperature applications such as solar nomic analysis of a novel building integrated PV/T roof collector: An ex-
perimental validation. Energy Build 2014;76:164–75.
cooling. The a-Si PV modules have lower temperature coeffi- [26] Athienitis AK, Bambara J, O’Neill B, Faille J. A prototype photovoltaic/thermal
cient and also experience the annealing process that reverses system integrated with transpired collector. Solar Energy 2011;85:139–53.
the module degradation under hot conditions. In addition, the [27] Peng J, Lu L, Yang H. An experimental study of the thermal performance of a
novel photovoltaic double-skin façade in Hong Kong. Solar Energy
yellowing of EVA in c-Si PV modules may be avoided because
2013;97:293–304.
EVA is not used in a-Si PV modules. [28] Han J, Lu L, Yang H. Numerical evaluation of the mixed convective heat
transfer in a double-pane window integrated with see-through a-Si PV cells
with low-e coatings. Appl Energy 2010;87:3431–7.
[29] Chae YT, Kim J, Park H, Shin B. Building energy performance evaluation of
Acknowledgement building integrated photovoltaic (BIPV) window with semi-transparent solar
cells. Appl Energy 2014;129:217–27.
[30] Solar.co.uk. o 〈http://www.solarpv.co.uk/solar-pv-facades.html〉 4
This work is supported by the NSERC Smart Net-Zero Energy
[accessed 29.10.14].
Buildings Strategic Research Network. The authors would also like [31] T. Reijenga Photovoltaic building integration concepts – what do architects
to thank Gerald Parnis for his contribution. need? IEA PVPS Task 7 workshop 2000.
[32] OnyxSolar, Projects and References. [〈http://www.onyxsolardownloads.com/
docs/ALL-YOU-NEED/Professional-Experience-Book-EN.pdf〉]. [accessed
12.11.14].
References [33] SwissInso. [〈http://www.swissinso.com/〉]. [accessed 12.11.14].
[34] CSEM. White solar modules: a revolution for building integration. [〈http://
www.csem.ch/docs/Show.aspx/28546/docname/CP14-white-pv-EN.pdf〉].
[1] Roaf S, Brotas L, Nicol F. Counting the costs of comfort. Build Res Inf [accessed 11.11.14].
2015;43:269–73. [35] Anderson TN, Duke M, Morrison GL, Carson JK. Performance of a building
[2] Wolf M. Performance analysis of combined heating and photovoltaic power integrated photovoltaic/thermal (BIPVT) solar collector. Solar Energy
systems for residences. Energy Convers 1976;16:79–90. 2009;83:445–55.
[3] Florschuetz LW. Extension of the Hottel-Whiller model to the analysis of [36] Eiffert P, Kiss JG. Building-integrated photovoltaic designs for commercial
combined photovoltaic/thermal flat plate collectors. Solar Energy and institutional structures: a sourcebook for architects Oak Ridge (USA): U.
1979;22:361–6. S. Department of Energy's (DOE's); 2000 NREL/BK-520-25272.
[4] Clarke JA, Hand JW, Johnstone CM, Kelly N, Strachan PA. Photovoltaic- [37] Xuan XD, Zheng XY. Façade design in building integrated photovoltaics. In:
910 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
Solar Energy 2003;74:253–69. [131] Maiti S, Banerjee S, Vyas K, Patel P, Ghosh PK. Self regulation of photovoltaic
[102] Bakar MNA, Othman M, Din MH, Manaf NA, Jarimi H. Design concept and module temperature in V-trough using a metal-wax composite phase change
mathematical model of a bi-fluid photovoltaic/thermal (PV/T) solar collector. matrix. Solar Energy 2011;85:1805–16.
Renew Energy 2014;67:153–64. [132] Ho CJ, Tanuwijava AO, Lai CM. Thermal and electrical performance of a BIPV
[103] Kalogirou SA, Tripanagnostopoulos Y. Hybrid PV/T solar systems for domestic integrated with a microencapsulated phase change material layer. Energy
hot water and electricity production. Energy Convers Manag 2006;47:3368– Build 2012;50:331–8.
82. [133] Moradgholi M, Nowee SM, Abrishamchi I. Application of heat pipe in an
[104] Zeng LB, Li MH, Chen YF, Shen H. A simplified method to modulate colors on experimental investigation on a novel photovoltaic/thermal (PV/T) system.
industrial multicrystalline silicon solar cells with reduced current losses. Solar Energy 2014;107:82–8.
Solar Energy 2014;103:343–9. [134] Pei G, Fu HD, Zhang T, Ji J. A numerical and experimental study on a heat pipe
[105] Santbergen R, Rindt CCM, Zondag HA, van Zolingen RJC. Detailed analysis of PV/T system. Solar Energy 2011;85:911–21.
the energy yield of systems with covered sheet-and-tube PVT collectors. [135] Pei G, Fu HD, Ji J, Chow TT, Zhang T. Annual analysis of heat pipe PV/T sys-
Solar Energy 2010;84:86–878. tems for domestic hot water and electricity production. Energy Convers
[106] Sobhnamayan F, Sarhaddi F, Alavi MA, Farahat S, Yazdanpanahi J. Optimiza- Manag 2012;56:8–21.
tion of a solar photovoltaic thermal (PV/T) water collector based on exergy [136] Pei G, Fu HD, Zhu HJ, Ji J. Performance study and parametric analysis of a
concept. Renew Energy 2014;68:356–65. novel heat pipe PV/T system. Energy 2012;37:384–95.
[107] Dupeyrat P, Menezo C, Rommel M, Henning HM. Efficient single glazed flat [137] G Pei, T Zhang, Z Yu, HD Fu, JY Wang, J. Ji Comparative study of a heat pipe
plate photovoltaic-thermal hybrid collector for domestic hot water system. PV/T and a water-thermosiphon PV/T. Power and Energy Engineering Con-
Solar Energy 2011;85:1457–68. ference, Asia-Pacific. Chengdu, 28–31 March 2010.
[108] Shan F, Cao L, Fang G. Dynamic performances modeling of a photovoltaic- [138] Wu SY, Zhang QL, Xiao L, Guo FH. A heat pipe photovoltaic/thermal (PV/T)
thermal collector with water heating in buildings. Energy Build hybrid system and its performance evaluation. Energy Build 2011;43:3558–
2013;66:485–94. 67.
[109] Herrando M, Markides CN, Hellgardt K. A UK-based assessment of hybrid PV [139] Quan ZH, NJ Li, YH. Zhao Experimental study of solar photovoltaic/thermal
and solar-thermal systems for domestic heating and power: system perfor- (PV/T) system based on flat plate heat pipe. Power and Energy Engineering
mance. Appl Energy 2014;122:288–309. Conference, Asia-Pacific. Wuhan, 25–28 March 2011.
[110] Arcuri N, Reda F, De Simone M. Energy and thermo-fluid-dynamics evalua- [140] Zhao XD, Wang ZY, Tang Q. Theoretical investigation of the performance of a
tions of photovoltaic panels cooled by water and air. Solar Energy novel loop heat pipe solar water heating system for use in Beijing, China.
2014;105:147–56. Appl Therm Eng 2010;30:2526–36.
[111] Sandnes B, Rekstad J. A photovoltaic/thermal (PV/T) collector with a polymer [141] Zhang XX, Zhao XD, Shen JC, Hu X, Liu XZ, Xu JH. Design, fabrication and
absorber plate. Experimental study and analytical model. Solar Energy experimental study of a solar photovoltaic/loop-heat-pipe based heat pump
2002;72:63–73. system. Solar Energy 2013;97:551–68.
[112] Zondag HA, De Vries DW, Van Helden WGJ, Van Zolingen RJC, Van Steen- [142] Lazzarin RM, Schibuola L. Energy roof as heat pump source/sink. Int J Refrig
hoven AA. The thermal and electrical yield of a PV-thermal collector. Solar 1986;9:108–12.
Energy 2002;72:113–28. [143] Tiwari A, Sodha MS. Performance evaluation of hybrid PV/thermal water/air
[113] Evola G, Marletta L. Exergy and thermoeconomic optimization of a water- heating system: a parametric study. Renew Energy 2006;31:2460–74.
cooled glazed hybrid photovoltaic/thermal (PVT) collector. Solar Energy [144] Zhao XD, Zhang XX, Riffat SB, Su YX. Theoretical study of the performance of
2014;107:12–25. a novel PV/e roof module for heat pump operation. Energy Convers Manag
[114] Chow TT, He W, Ji J. Hybrid photovoltaic-thermosyphon water heating sys- 2011;52:603–14.
tem for residential application. Solar Energy 2006;80:298–306. [145] Xu GY, Deng SM, Zhang XS, Yang L, Zhang YH. Simulation of a photovoltaic/
[115] Zakharchenko R, Jimenez L, Perez-Garcia SA, Vorobiev P, Dehesa-Carrasco U, thermal heat pump system having a modified collector/evaporator. Solar
et al. Photovoltaic solar panel for a hybrid PV/Thermal system. Solar Energy Energy 2009;83:1967–76.
Mater Solar Cells 2004;82:253–61. [146] Liu KL, Ji J, Chow TT, Pei G, He HF, Jiang AG, Yang JC. Performance study of a
[116] Ghani F, Duke M, Carson JK. Effect of flow distribution on the photovoltaic photovoltaic solar assisted heat pump with variable-frequency compressor –
performance of a building integrated photovoltaic/thermal (BIPV/T) collector. a case study in Tibet. Renew Energy 2009;34:2680–7.
Solar Energy 2012;86:1518–30. [147] Xu GY, Zhang XS, Deng SM. Experimental study on the operating character-
[117] Ghani F, Duke M, Carson JK. Estimation of photovoltaic conversion efficiency istics of a novel low-concentrating solar photovoltaic/thermal integrated heat
of a building integrated photovoltaic/thermal (BIPV/T) collector array using pump water heating system. Appl Therm Eng 2011;31:3689–95.
an artificial neural network. Solar Energy 2012;86:3378–87. [148] Ji J, Pei G, Chow TT, Liu KL, He HF, et al. Experimental study of photovoltaic
[118] Timmerman M, Bakker M, Reinders A, van der Meer T. Plug-and-play liquid solar assisted heat pump system. Solar Energy 2008;82:43–52.
PV thermal panels – integrated design for easy manufacturing and installa- [149] Ji J, He HF, Chow TT, Pei G, He W, Liu KL. Distributed dynamic modeling and
tion. In: Proceedings of the 34th IEEE Photovoltaic Specialists Conference experimental study of PV evaporator in a PV/T solar-assisted heat pump. Int J
(PVSC). Philadelphia, PA, 7–12 June 2009. Heat Mass Transf 2009;52:1365–73.
[119] Yin HM, Yang DJ, Kelly G, Garant J. Design and performance of a novel [150] Chemisana D, Lopez-Villada J, Coronas A, Rosell JI, Lodi C. Building integration
building integrated PV/Thermal system for energy efficiency of buildings. of concentrating systems for solar cooling applications. Appl Therm Eng
Solar Energy 2013;87:184–95. 2013;50:1472–9.
[120] Yang DJ, Yuan ZF, Lee PH, Yin HM. Simulation and experimental validation of [151] Al-Alili A, Hwang Y, Radermacher R, Kubo I. A high efficiency solar air con-
heat transfer in a novel hybrid solar panel. Int J Heat Mass Transf ditioner using concentrating photovoltaic/thermal collectors. Appl Energy
2012;55:1076–82. 2011;93:138–47.
[121] Chow TT, Pei G, Fong KF, Lin Z, Chan ALS, Ji J. Energy and exergy analysis of [152] Davidsson H, Perers B, Karlsson B. System analysis of a multifunctional PV/T
photovoltaic-thermal collector with and without glass cover. Appl Energy hybrid solar window. Solar Energy 2012;86:903–10.
2009;86(3):310–6. [153] Wennerberg J, Kessler J, Hedstrom J, Stolt L, Karlsson B, Ronnelid M. Thin film
[122] Fudholi A, Sopian K, Yazdi MH, Ruslan MH, Ibrahim A, Kazem HA. Perfor- PV modules for low-concentrating systems. Solar Energy 2000;69:243–55.
mance analysis of photovoltaic thermal (PVT) water collectors. Energy Con- [154] Brogren M, Wennerberg J, Kapper R, Karlsson B. Design of concentrating
vers Manag 2014;78:641–51. elements with CIS thin-film solar cells for façade integration. Solar Energy
[123] Ibrahim A, Fudholi A, Sopian K, Othman MY, Ruslan MH. Efficiencies and Mater Solar Cells 2003;75:567–75.
improvement potential of building integrated photovoltaic thermal (BIPVT) [155] Gajbert H, Hall M, Karlsson B. Optimisation of reflector and module geo-
system. Energy Convers Manag 2014;77:527–34. metries for stationary, low-concentrating, façade-integrated photovoltaic
[124] Chow TT, He W, Ji J. An experimental study of façade-integrated photo- systems. Solar Energy Mater Solar Cells 2007;91:1788–99.
voltaic/water-heating system. Appl Therm Eng 2007;27:37–45. [156] Bernardo LR, Perers B, Hakansson H, Karlsson B. Performance evaluation of
[125] Chow TT, Chan ALS, Fong KF, Lin Z, He W, Ji J. Annual performance of low concentrating photovoltaic/thermal systems: a case study from Sweden.
building-integrated photovoltaic/water-heating system for warm climate Solar Energy 2011;85:1499–510.
application. Appl Energy 2009;86:689–96. [157] Coventry JS. Performance of a concentrating photovoltaic/thermal solar col-
[126] Corbin CD, Zhai ZJ. Experimental and numerical investigation on thermal and lector. Solar Energy 2005;78:211–22.
electrical performance of a building integrated photovoltaic-thermal col- [158] Li M, Ji X, Li GL, Wei SX, Li YF, Shi F. Performance study of solar cell arrays
lector system. Energy Build 2010;42:76–82. based on a trough concentrating photovoltaic/thermal system. Appl Energy
[127] Malvi CS, Dixon-Hardy DW, Crook R. Energy balance model of combined 2011;88:3218–27.
photovoltaic solar-thermal system incorporating phase change material. [159] Rosell JI, Vallverdu X, Lechon MA, Ibanez M. Design and simulation of a low
Solar Energy 2011;85:1440–6. concentrating photovoltaic/thermal system. Energy Convers Manag
[128] Huang MJ, Eames PC, Norton B. Thermal regulation of building-integrated 2005;46:3034–46.
photovoltaics using phase change materials. Int J Heat Mass Transf [160] Wang Y, Tian W, Ren J, Zhu L, Wang Q. Influence of a building's integrated-
2004;47:2715–33. photovoltaics on heating and cooling loads. Appl Energy 2006;83:989–1003.
[129] Huang MJ, Eames PC, Norton B, Hewitt NJ. Natural convection in an internally [161] Chow TT, He W, Chan ALS, Fong KF, Lin Z, Ji J. Computer modeling and ex-
finned phase change material heat sink for the thermal management of perimental validation of a building-integrated photovoltaic and water heat-
photovoltaics. Solar Energy Mater Solar Cells 2011;95:1598–603. ing system. Appl Therm Eng 2008;28:1356–64.
[130] Huang MJ. The effect of using two PCMs on the thermal regulation perfor- [162] Dehra H. A two dimensional thermal network model for a photovoltaic solar
mance of BIPV systems. Solar Energy Mater Solar Cells 2011;95:957–63. wall. Solar Energy 2009;83:1933–42.
912 T. Yang, A.K. Athienitis / Renewable and Sustainable Energy Reviews 66 (2016) 886–912
[163] Infield D, Eicker U, Fux V, Mei L, Schumacher J. A simplified approach to thermal characteristics of a building integrated photovoltaic tiled roof. Solar
thermal performance calculation for building integrated mechanically ven- Energy 2009;83:1893–901.
tilated PV facades. Build Environ 2006;41:893–901. [183] Chen FZ, Wittkopf SK, Ng PK, Du H. Solar heat gain coefficient measurement
[164] Sarhaddi F, Farahat S, Ajam H, Behzadmehr A, Adeli MM. An improved of semi-transparent photovoltaic modules with indoor calorimetric hot box
thermal and electrical model for a solar photovoltaic thermal (PV/T) air and solar simulator. Energy Build 2012;53:74–84.
collector. Appl Energy 2010;87:2328–39. [184] Solanki SC, Dubey S, Tiwari A. Indoor simulation and testing of photovoltaic
[165] De Soto W, Klein SA, Beckman WA. Improvement and validation of a model thermal (PV/T) air collectors. Appl Energy 2009;86:2421–8.
for photovoltaic array performance. Solar Energy 2006;80:78–88. [185] Krauter S, Araujo RG, Schroer S, Hanitsch R, Salhi MJ, et al. Combined pho-
[166] Dubey S, Sandhu GS, Tiwari GN. Analytical expression for electrical efficiency tovoltaic and solar thermal systems for façade integration and building in-
of PV/T hybrid air collector. Appl Energy 2009;86:697–705. sulation. Solar Energy 1999;67:239–48.
[167] Shahsavar A, Ameri M. Experimental investigation and modeling of a direct- [186] Friling N, Jimenez MJ, Bloem H, Madsen H. Modelling the heat dynamics of
coupled PV/T air collector. Solar Energy 2010;84:1938–58. building integrated and ventilated photovoltaic modules. Energy Build
[168] Kumar R, Rosen MA. Performance evaluation of a double pass PV/T solar air 2009;41:1051–7.
heater with and without fins. Appl Therm Eng 2011;31:1402–10. [187] Lodi C, J Cipriano, P Bacher, H. Madsen Modelling the heat dynamics of a
[169] Bergene T, Lovvik OM. Model calculations on a flat-plate solar heat collector monitored test reference environment for BIPV systems through determi-
with integrated solar cells. Solar Energy 1995;55:453–62. nistic and stochastic approaches. In: Proceedings of the International
[170] Vokas G, Christandonis N, Skittides F. Hybrid photovoltaic-thermal systems Workshop on ‘whole building testing, evaluation and modelling for energy
for domestic heating and cooling – a theoretical approach. Solar Energy assessment’, Technical University of Denmark, Denmark; 2011.
2006;80:607–15. [188] Bigot D, Miranville F, Fakra AH, Boyer H. A nodal thermal model for photo-
[171] Kamel RS, Fung AS. Modeling, simulation and feasibility analysis of re- voltaic systems: impact on building temperature fields and elements of va-
sidential BIPV/T þ ASHP system in cold climate – Canada. Energy Build lidation for tropical and humid climatic conditions. Energy Build
2014;82:758–70. 2009;41:1117–26.
[172] DeBlois J, Bilec M, Schaefer L. Simulating home cooling load reductions for a [189] Dominguez A, Kleissl J, Luvall JC. Effects of solar photovoltaic panels on roof
novel opaque roof solar chimney configuration. Appl Energy 2013;112:142– heat transfer. Solar Energy 2011;l85:2244–55.
51. [190] Pola I, Chianese D, Bernasconi A. Flat roof integration of a-Si triple junction
[173] King DL, Boyson WE, Kratochvil JA. Photovoltaic array performance model modules laminated together with flexible polyolefin membranes. Solar En-
Sandia National Laboratories Report, SAND2004-3535. ergy 2007;81:1144–58.
[174] Radhi H. Energy analysis of façade-integrated photovoltaic systems applied to [191] Chow TT, Hand JW, Strachan PA. Building-integrated photovoltaic and ther-
UAE commercial buildings. Solar Energy 2010;84:2009–21. mal applications in a subtropical hotel building. Appl Therm Eng
[175] Li S, Karava P, Currie S, Lin WE, Savory E. Energy modeling of photovoltaic 2003;23:2035–49.
thermal systems with corrugated unglazed transpired solar collectors – Part [192] Mandalaki M, Zervas K, Taoutsos T, Vazakas A. Assessment of fixed shading
1: model development and validation. Solar Energy 2014;102:282–96. devices with integrated PV for efficient energy use. Solar Energy
[176] Li S, Karava P. Energy modeling of photovoltaic thermal systems with cor- 2012;86:2561–75.
rugated unglazed transpired solar collectors – Part 2: performance analysis. [193] Peng J, Lu L, Yang HX, Han J. Investigation on the annual thermal perfor-
Solar Energy 2014;102:297–307. mance of a photovoltaic wall mounted on a multi-layer façade. Appl Energy
[177] Gan GH. Numerical determination of adequate air gaps for building-in- 2013;112:646–56.
tegrated photovoltaics. Solar Energy 2009;83:1253–73. [194] Han J, Lu L, Peng JQ, Yang HX. Performance of ventilated double-sided PV
[178] Wilson MJ, Paul MC. Effect of mounting geometry on conversion occurring façade compared with conventional clear glass façade. Energy Build
under a photovoltaic panel and the corresponding efficiency using CFD. Solar 2013;56:204–9.
Energy 2011;85:2540–50. [195] Candanedo LM, Athienitis A, Park KW. Convective heat transfer coefficients in
[179] Mittelman G, Alshare A, Davidson JH. A model and heat transfer correlation a building-integrated photovoltaic/thermal system. J Solar Energy Eng
for rooftop integrated photovoltaics with a passive air cooling channel. Solar 2011;133(2):021002.
Energy 2009;83:1150–60. [196] Karagiorgas M, Galatis K, Tsagouri M, Tsoutsos T, Botzios-Valaskakis A. Solar
[180] Kumar NS, Matty K, Rita E, Simon W, Ortrun A, Alex C, et al. Experimental assisted heat pump on air collectors: a simulation study. Solar Energy
validation of a heat transfer model for concentrating photovoltaic system. 2010;84:66–78.
Appl Therm Eng 2012;33–34:175–82. [197] Hazi A, Hazi G. Comparative study of indirect photovoltaic thermal solar-
[181] Cipriano J, Houzeaux G, Chemisana D, Lodi C, Marti-Herrero J. Numerical assisted heat pump systems for industrial applications. Appl Therm Eng
analysis of the most appropriate heat transfer correlations for free ventilated 2014;70:90–9.
double skin photovoltaic facades. Appl Therm Eng 2013;57:57–68. [198] Pagliaro M, Ciriminna R, Palmisano G. BIPV: merging the photovoltaic with
[182] Mei L, Infield DG, Gottschalg R, Loveday DL, Davies D, Berry M. Equilibrium the construction industry. Progress Photovolt: Res Appl 2010;18:61–72.