MC 785 FAC

User instructions
(Panel and wall mounting)

Description: MC 785 FAC with real-time clock (from SW:V2.00) Doc.no.: 031220
Type: USER MANUAL Number of pages: 17 Version: V2.5
File: Do031220 MC785 FAC v25 EN.wpd By: BJB Date: 19-11-2015
Software: MC785FAC Version: V3.08
VDH Products BV - Roden - Holland Initialled: File: Doc'03
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 2 of 17

Table of contents

1 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 On LMS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Switching the MC 785 FAC on and off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Changing the temperature set point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Viewing the temperature sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4 High/low fan speed position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.5 Resetting the alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.6 Readout of the week clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Setting the week clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Programming internal settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


4.1 Parameter table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6 Sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8 Principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8 Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

9 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

The information contained in this document is assumed to be accurate. However, VDH Products BV
accepts no liability for eventual mistakes and errors and reserves the right to change this document without
notice.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 3 of 17

1 Technical specifications
1.1 General

Type : MC 785 FAC


Panel mounting:
Housing : Steel plate wall panel
Material : Steel plate sprayed silver grey
Dimensions : 217 x 155 x 85mm (bhd)
Panel cut-out : 208 x 146mm (bh)
Front : Polycarbonate (IP-44)
Wall mounting:
Housing : Wall mounting panel
Material : Polystyol 454h KG2 natur BASF
Dimensions : 213x 180 x 85mm (bhd)
Front : Polycarbonate (IP-44)
Temperature range : -40/+50°C per 0.°C
Power supply : 230 Vac; 50/60 Hz (-10/+5%), or else see product sticker.
Power consumption : 9 VA
Working temperature : -20/+50°C
Storage temperature : -20/+60°C
Work RH : 10/+90 % RH non-condensing
Accuracy : ± 0.5 % of the range

1.2 Front

Displays : 4-Digit digital display for the outgoing air temperature


4-Digit digital display for temperature set point
4-Digit digital display for measured temperature
4-Digit digital display for valve position, pressure and RH
LEDs : Fan Alarm = Fan failure
Heater Alarm = Heater failure
Frost Alarm = Frost danger
Low Temp. Alarm = Air temperature below minimum
DP = DP alarm
Sens. = Sensor defect alarm
Fan Low = Fan at low speeds
Fan High = Fan at high speeds
Water in = Temperature heat exchanger in
Water out = Temperature heat exchanger out
Cooled Air = Temperature air conditioning cabinet out
Cool = Regulator in cool mode
Heat = Regulator in heating mode
Keys: ON/OFF = On/off keys control
SET = Setpoint pushbutton
+ = UP key
- = DOWN key
PRG = Programming key
HIGH/LOW = Fan high/low key
RESET ALARM = Alarm reset key
SENS = Readout sensors key
DP = Readout pressure sensor
RH = Readout relative humidity of air (RH)
= Readout after-heating percentage
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 4 of 17

1.3 Inputs and outputs


Sensors : Temp.sensor-1: Water-in temperature (10K, 2-wire)
Temp.sensor-2: Water-out temperature (10K, 2-wire)
Temp.sensor-3: Control temperature (AIR-CONTROL) (10K, 2-wire)
Temp.sensor-4: Blowing-out temperature (AIR-OUT) (10K, 2-wire)
RH-sensor (0-100%RH=0-1Vdc, 3-wire)
Pressure sensor PX25 range: 0-500 Pa (4/20mA output, 3-wire)

Outputs: Ry1: Relay Alarm (SPDT 250Vac/8A non-inductive)


I2C-bus (for LMS-units) (2-wire shielded min. 0.75mm 2)
RS485-network (for PC and remote LMS) (2x Twisted-pair shielded min. 0.75mm 2)

1.4 On LMS Modules


Digital inputs : LMS DIGIN MODULE(S) or LMS CONTR.MODULE (944.800347) thru RS485
IN1-1: Fan failure (NC potential free input contact)
(max. 4) IN1-2: Heater failure (NC potential free input contact)
IN1-3: Emergency stop (NC potential free input contact)
IN1-4: Exhaust fan failure (NO potential free input contact)
IN1-5: External on / off (see parameter P36) (NO potential free input contact)
IN1-6: External hi / lo (see parameter P36) or (NO potential free input contact)
External frost protection contact (see parameter P36)
IN2-1: External frost protection contact (see par. P36) (NO potential free input contact)
(max. 4) IN2-2: Spare (NO potential free input contact)
IN2-3: Spare (NO potential free input contact)
IN2-4: Spare (NO potential free input contact)
IN2-5: Spare (NO potential free input contact)
IN2-6: Spare (NO potential free input contact)

Analog out: OUT 1-1: 0/+10Vdc (Module-1), function see parameter P60 (Rbmin 10Kohm)
(max. 8) OUT 1-2: 0/+10Vdc (Module-1), function see parameter P61 (Rbmin 10Kohm)
OUT 1-3: 0/+10Vdc (Module-1), function see parameter P62 (Rbmin 10Kohm)
OUT 1-4: 0/+10Vdc (Module-1), function see parameter P63 (Rbmin 10Kohm)
OUT 2-1: 0/+10Vdc (Module-2), function see parameter P64 (Rbmin 10Kohm)
OUT 2-2: 0/+10Vdc (Module-2), function see parameter P65 (Rbmin 10Kohm)
OUT 2-3: 0/+10Vdc (Module-2), function see parameter P66 (Rbmin 10Kohm)
OUT 2-4: 0/+10Vdc (Module-2), function see parameter P67 (Rbmin 10Kohm)

Relay out: Ry 1-1: SPDT contact (Module-1), see param. P70 (Max. 250Vac/8A non-inductive)
(max. 8) Ry 1-2: SPST contact (Module-1), see param. P71 (Max. 250Vac/8A non-inductive)
Ry 1-3: SPST contact (Module-1), see param. P72 (Max. 250Vac/8A non-inductive)
Ry 1-4: SPST contact (Module-1), see param. P73 (Max. 250Vac/8A non-inductive)
Ry 2-1: SPDT contact (Module-2), see param. P74 (Max. 250Vac/8A non-inductive)
Ry 2-2: SPST contact (Module-2), see param. P75 (Max. 250Vac/8A non-inductive)
Ry 2-3: SPST contact (Module-2), see param. P76 (Max. 250Vac/8A non-inductive)
Ry 2-4: SPST contact (Module-2), see param. P77 (Max. 250Vac/8A non-inductive)
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 5 of 17

2 Functional specifications
The MC 785 FAC is an operational system for an airconditioning cabinet.
From software version 2.00 on, it is provided with real-time clock for time ventilation (P100 to P114)

The temperature of the inflowing water determines whether heating or cooling can take place. This is
indicated by means of LED on the regulator.

On the basis of the measured air temperature behind the heat exchanger and the adjusted set point,
the 3-way mixing valve is either opened or shut. The position of the valve is shown in one of the
displays.

The fan can be set at a high or low speed by a key on the front of the controller.

If the measured air pressure, over the airconditioning cabinet, is under the set minimum value or over
the set maximum value, then the heater and fan will be turned off and the control valve will be
opened to the maximum extent. The appropriate alarm LED will light up and the alarm will come on.

A frost protection sensor is fixed to the cold water pipe coming from the heat exchanger. Should this
sensor measure a temperature lower than the set frost protection, then the heater and fan will be
turned off and the control valve will be opened to the maximum extent. It is also possible to connect
an external frost protection contact on the LMS DIGITAL IN module (See parameter P36), this will
also turn off the heater and fan and sets the control valve open to the maximum extent. The
appropriate alarm LED will be lit and the alarm activates.

Should the air temperature by the heat exchanger fall below the set minimum value, the heater and
fan are turned off and the control valve is opened to the maximum. The alarm LED will light up and
the alarm will come on.

Should the air temperature after the heater fall below the set minimum value, the heater and fan are
turned off and the control valve is opened to the maximum. The alarm LED will light up and the alarm
will come on.

Will the input contacts of ‘Heater failure’, ‘Fan-failure’ or ‘Emergency stop’ are opened or ‘Exhaust fan
failure’ is closed, an alarm follows and the LED on the display will light up, the heater and fan are
turned off and the control valve is opened to the maximum.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 6 of 17

3 Operation
During normal operation the top-left display indicates the measured air temperature by the blowing-
out opening of the fan. The bottom-left display indicates the desired temperature (set point).

In the top-right display the temperature of ingoing or outgoing water temperature is shown, or the
outgoing air temperature by the heat exchanger. One of the sensors can be selected by means of the
sensor key.

The bottom-right display shows the actual position of the valve. By pressing the DP key, the pressure
difference over the LBK is shown. By pressing the RH key the measured relative air humidity can be
shown. By pressing the -key the emitted percentage of the after-heater can be shown.

3.1 Switching the MC 785 FAC on and off.


By pressing the ON/OFF key the controller can be switched on or off.

3.2 Changing the temperature set point.


Press the SET key next to the temperature set point display. The set point will start to blink.
The set point can be changed by means of the Up or Down keys. By pressing the SET key
again the set point will again appear continuously in the display.

3.3 Viewing the temperature sensors.


By pressing the SENS key the ingoing water temperature, outgoing water temperature or the air
temperature by the heat exchanger will be indicated in the top-right display.

3.4 High/low fan speed position.


By pressing the HIGH/LOW key the fan can be set in the high or low position. The position of
the fan and heater is shown by LEDs in the display.

3.5 Resetting the alarm.


As soon as an alarm situation occurs and an error code appears in the temperature display, the
alarm can be reset by pressing the RESET ALARM key.
The error code remains visible in the display until the cause of the fault has been corrected.

3.6 Readout of the week clock.


Hold down the PRG and HIGH/LOW keys for longer than 5 seconds in order to read the week
clock. The time is shown in the first display and the day number in the second (1=Mo, 2=Tu,
3=We, 4=Th, 5=Fr, 6=Sa, 7=Su). If a key is not pressed for longer than 20 seconds the readout
will revert to the normal operation mode.

3.7 Setting the week clock.


Go to readout of the week clock (see above). Press the SET key. The hours will start to blink
and can be adjusted using the UP and/or DOWN keys. By pressing the SET key again the
minutes can be adjusted with the UP and/or DOWN keys. By pressing the SET key again the
day number can be adjusted. If no key is pressed for 20 seconds the readout reverts to normal
operation.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 7 of 17

4 Programming internal settings

By holding the PRG key down for longer than 5 seconds it is possible to enter the Internal
Parameters. In the top left display a P followed by a digit will appear. By pressing the UP or DOWN
keys the desired parameter can be found. The bottom left display shows the value of the parameter.
By pressing the SET key and the UP or DOWN key simultaneously the value can be adjusted.
If no key is touched for more than 30 seconds, or if the ON/OFF key is pressed, the display will jump
back to the normal operation mode.

4.1 Parameter table.

Nr. Description Range Unit Default


O
P 01 Offset water-in sensor-1 -30..+30 C/OF 0,0
O
P 02 Offset water-out sensor-2 -30..+30 C/OF 0,0
O
P 03 Offset air-control sensor-3 -30..+30 C/OF 0,0
O
P 04 Offset air-out sensor-4 -30..+30 C/OF 0,0
P 05 Offset humidity sensor -20..+20 % 0
P 06 Offset pressure sensor -50..+50 Pa 0
O
P 10 Minimum temperature water out -40..+150 C/OF 1,0
O
P 11 Minimum temperature control sensor -40..+150 C/OF 2,0
O
P 12 Minimum temperature air out -40..+150 C/OF 18,0
P 13 Minimum pressure difference 0..+500 Pa 50
P 14 Maximum pressure difference 0..+500 Pa 450
O
P 20 Minimum adjustable temperature set point -40..+150 C/OF -40,0
O
P 21 Maximum adjustable temperature set point -40..+150 C/OF +50,0
O
P 22 Set point air by water heat exchanger -40..+150 C/OF +16,0
(AIR CONTROL sensor-3)
P 23 Air curtain control active 0 = no - 0
1 = yes
P 24 Set point RH drying (0 = Not active) 0..100 %RH 0
P25 P-Band humidifying 1..100 %RH 20
P26 Delay humidifying and drying 0..999 minutes 20
P27 Eco mode 0=no - 0
1=yes

P 30 Temperature unit in Celsius or Fahrenheit 0 = °C - 1


1 = °F
P 31 Readout in whole degrees 0 = no -
1 = yes

P 35 Alarm relay function 0 = control - 0


1 = watch
P 36 Remote control (see explanation parameter P36) 0 = no - 0
1 = yes
2 = yes, only on/off
3 = yes, on/off with
hi/lo and frost
protection
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 8 of 17

Nr. Description Range Unit Default


O
P 40 Proportional band cooling 0,1..30 C/OF 1.0
O
P 41 Offset P-band cooling -30..+30 C/OF 0.0
P 42 Interval value cooling (999 indicates only P) 1..999 minutes 999
O
P 43 Proportional band heating 0.1..30 C/OF 1.0
O
P 44 Offset P-band heating -15..+15 C/OF 0.0
P 45 Interval value heating (999 indicates only P) 1..999 minutes 999
O
P 46 Proportional band after-heater (re-heater) 0.1..30 C/OF 1.0
O
P 47 Offset P-band after-heater ( ,, ) -15..+15 C/OF 0.0
P 48 Interval value after-heater (999 indicates only P) 1..999 minutes 999
O
P 49 Differential pro stage 0.1..30 C/OF 1.0

P 50 Minimum valve position 0..100 % 3


O
P 51 Maximum water-in temperature for cooling -40..+150 C/OF 7.0
O
P 52 Minimum water-in temperature for heating -40..+150 C/OF 28.0

P 53 Ventilator low percentage 0..100 % 25


P 54 Ventilator high percentage 0..100 % 75
P 55 Number of after-heaters (re-heaters) 0..2 - 0
P 56 Number of pre-heaters 0..4 - 0
P 57 Pre-heater-mode 0..3 - 0
0 = Solid-state
1 = Relay high/low
2 = Multi-stage (depends on P56) relay
3 = Analog out PI
P 58 Pre-heater delay 0..600 seconds 0
P 59 Switch-on delay next stage as P57=2 0..120 minutes 5
(0 min. = only on temperature)

P 60 Function analog out 1-1 (LMS module-1, out-1) 0..12 - 0


0 = None
1 = After-heater 1 (re-heater)
2 = After-heater 2 (re-heater)
3 = Fan
4 = Valve
5 = Pre-heater 1
6 = Pre-heater 2
7 = Pre-heater 3
8 = Pre-heater 4
9 = Exhaust fan
10 = Humidifier
11 = Preheater PI (P56 > 0)
12 = Afterheater PI (P55 > 0)
P 61 Function analog out 1-2 (module-1) (see P60) 0..12 - 0
P 62 Function analog out 1-3 (module-1) (see P60) 0..12 - 0
P 63 Function analog out 1-4 (module-1) (see P60) 0..12 - 0
P 64 Function analog out 2-1 (module-2) (see P60) 0..12 - 0
P 65 Function analog out 2-2 (module-2) (see P60) 0..12 - 0
P 66 Function analog out 2-3 (module-2) (see P60) 0..12 - 0
P 67 Function analog out 2-4 (module-2) (see P60) 0..12 - 0
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 9 of 17

Nr. Description Range Unit Default

P 70 Function relay out 1-1 (LMS module-1, relay-1) 0..11 - 0


0 = None
1 = Alarm relay
2 = Fan on/off
3 = Fan low/high
4 = LMS fail safe
5 = Exhaust fan on/off
6 = Pre-heater 1
7 = Pre-heater 2
8 = Pre-heater 3
9 = Pre-heater 4
10 = Fire valve
11 = Humidifier enable
P 71 Function relay out 1-2 (module-1) (see P70) 0..11 - 0
P 72 Function relay out 1-3 (module-1) (see P70) 0..11 - 0
P 73 Function relay out 1-4 (module-1) (see P70) 0..11 - 0
P 74 Function relay out 2-1 (module-2) (see P70) 0..11 - 0
P 75 Function relay out 2-2 (module-2) (see P70) 0..11 - 0
P 76 Function relay out 2-3 (module-2) (see P70) 0..11 - 0
P 77 Function relay out 2-4 (module-2) (see P70) 0..11 - 0

P 90 Network number 1..250 - 1


P 91 Log interval 0..120 minutes 5
P 92 Network number LMS Controller ** 0..8 - 0
0 = not used; LMS via I2C-bus

P 95 Software version no. - - -


P 96 Series number - - -
P 97 Production date - year/wk -

P100 Timed-ventilation active 0 = no - 0


1 = yes

P101 Switch-on time high position Monday 00.00..23.45, OFF - OFF


P102 Switch-on time low position Monday 00.00..23.45, OFF - OFF

P103 Switch-on time high position Tues. 00.00..23.45, OFF - OFF


P104 Switch-on time low position Tues. 00.00..23.45, OFF - OFF

P105 Switch-on time high position Wed. 00.00..23.45, OFF - OFF


P106 Switch-on time low position Wed. 00.00..23.45, OFF - OFF

P107 Switch-on time high position Thurs. 00.00..23.45, OFF - OFF


P108 Switch-on time low position Thurs. 00.00..23.45, OFF - OFF

P109 Switch-on time high position Friday 00.00..23.45, OFF - OFF


P110 Switch-on time low position Friday 00.00..23.45, OFF - OFF

P111 Switch-on time high position Sat. Switch-on 00.00..23.45, OFF - OFF
P112 time low position Sat. 00.00..23.45, OFF - OFF

P113 Switch-on time high position Sunday 00.00..23.45, OFF - OFF


P114 Switch-on time low position Sunday 00.00..23.45, OFF - OFF
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 10 of 17

Explanation of Parameter P24:


P24 = 0:
The Hygrostat function drying is not active.
P24 > 0:
Than the Hygrostat function drying is active.
Using the temperature set point and the desired relative humidity, the dew point is calculated.
Is this dew point lower than Parameter P22 (Set point air by water heat exchanger), then it
controls to the dew point. By after heating the desired relative humidity will be reached.
This function is only possible if parameter P23 = 0 (Air curtain control not active).
If the drying function is active the LED RH is flashing.

Explanation of Parameter P36:


P36 = 0:
If Parameter P36 = 0, the spare input from the LMS digin module can be used for an external
frost protection contact input.
P36 = 1:
If Parameter P36 = 1, the spare inputs from the LMS digin module can be used for an external
on/off and hi/lo switch.
Input 5 can be use for the external on/off switch
Input 6 can be use for the external hi/lo switch
These inputs have the same functions as the switches on the front panel.
P36 = 2:
If Parameter P36 = 2, the spare inputs from the LMS digin module can be used for an external
on/off and an external frost protection thermostat contact.
Input 5 can be use for the external on/off switch
Input 5 has the same function as the switch on the front panel.
Input 6 can be use for the external Frost protection thermostat contact
Input 6 open = “no frost risk” and closed = “frost risk”.
P36 = 3:
Remote on/off on digital-in module 1, input 5 (closed = on, open = off)
Remote hi/lo on digital-in module 1, input 6 (closed = high, open = low)
External frost message on digital-in module 2, input 1 (closed = failure after 250 seconds
delay)

Explanation of Parameter P92: (from software version 2.00)


If the LMS-units must be connected over a distance greater than 5 metres then the connection
must be made via the RS485 Network instead of via the I2C-bus.

This is done be replacing the LMS Digital-in module with the LMS Controller module HH-FAC
(VDH-type no. 944.800347). This module converts the RS485-protocol to the I2C-bus so that the
rest of the LMS-units can be connected locally.

See the connection diagram 021587 in section 9.

On the 1 RS485-Network a maximum of 8 combinations of MC785-FAC with LMS Controller


module HH-FAC can be connected, each with its own address setting. This takes place by means
of jumpers on the controller. The real address of the LMS controller modules then runs from 101 to
108; these network numbers may not be used for the MC785-FAC’s and other connected
controllers on the RS485-Network.

Explanation of Parameters P101 to 114:


The time settings for these parameters are adjustable per 15 minutes.
When time-ventilation is active (P100 = 1), the HIGH/LOW key can be used as a manual high/low
key; in this case the manual position is exited at the next switching point.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 11 of 17

6 Sensor calibration
The temperature sensors can be calibrated by the parameters P1 to P4.
Should the temperature sensor indicate 0.2/C too much, for example, then the offset must be
adjusted 0.2/C lower.

7 Alarms
An alarm can be caused by:

SORT DISPLAY DESCRIPTION ACTION:


Control alarm: F1 = Control temperature too low Heater/Fan off and Control
valve open to maximum
Frost alarm: F2 = Outgoing water temperature too low and/or ,,
External frost protection contact is active
Air off alarm: F3 = Blowing out temperature too low ,,
Min. pressure F4 = Minimum pressure alarm ,,
alarm:
Max. pressure F5 = Maximum pressure alarm ,,
alarm:
Emergency stop E1 = Emergency stop ,,
Fan alarm: E2 = Fan failure ,,
Heater alarm: E3 = Heater failure ,,
Exhaust alarm: E4 = Exhaust fan failure ,,
LMS modules: E5 = No communication with LMS modules ,,
Sensor failure: U1 = Control temperature sensor ,,
U2 = Water-in sensor defect ,,
U3 = Water-out sensor defect ,,
U4 = Air temperature sensor defect ,,

The alarm messages are shown in the temperature display (top left).

By pressing the RESET ALARM key the alarm relay can be reset. The error message remains in the
display as long as the error remains. The alarm LED will also continue to blink.

8 Principle diagram
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 12 of 17

8 Front
Front view of MC785-FAC panel mounting model, drawing 980905

Front view of MC 785-FAC wall mounting model, drawing 040644


User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 13 of 17

9 Connection diagrams
Connection data for MC785-FAC panel mounting model, drawing 001710w2
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 14 of 17

Connection data for MC785-FAC wall mounting model, drawing 040643w1


User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 15 of 17

LMS modules via I2C-bus (maximal 5-metres) connection data, drawing 001713w3:
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 16 of 17

LMS modules via RS485-Network (maximal 1 KM) connection data, drawing 021587w3:
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 17 of 17

10 Dimensions
Dimensions of MC 785 panel mounting model, drawing 961271
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 18 of 17

Dimensions of MC 785-FAC wall mounting model drawing 940024

-.-.-.-.-.-.-.-.-.- @