Description: MC 785 FAC with real-time clock (from SW:V2.00) Doc.no.: 031220
Type: USER MANUAL Number of pages: 17 Version: V2.5
File: Do031220 MC785 FAC v25 EN.wpd By: BJB Date: 19-11-2015
Software: MC785FAC Version: V3.08
VDH Products BV - Roden - Holland Initialled: File: Doc'03
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 2 of 17
Table of contents
1 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 On LMS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Switching the MC 785 FAC on and off. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Changing the temperature set point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Viewing the temperature sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4 High/low fan speed position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.5 Resetting the alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.6 Readout of the week clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.7 Setting the week clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 Sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
The information contained in this document is assumed to be accurate. However, VDH Products BV
accepts no liability for eventual mistakes and errors and reserves the right to change this document without
notice.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 3 of 17
1 Technical specifications
1.1 General
1.2 Front
Analog out: OUT 1-1: 0/+10Vdc (Module-1), function see parameter P60 (Rbmin 10Kohm)
(max. 8) OUT 1-2: 0/+10Vdc (Module-1), function see parameter P61 (Rbmin 10Kohm)
OUT 1-3: 0/+10Vdc (Module-1), function see parameter P62 (Rbmin 10Kohm)
OUT 1-4: 0/+10Vdc (Module-1), function see parameter P63 (Rbmin 10Kohm)
OUT 2-1: 0/+10Vdc (Module-2), function see parameter P64 (Rbmin 10Kohm)
OUT 2-2: 0/+10Vdc (Module-2), function see parameter P65 (Rbmin 10Kohm)
OUT 2-3: 0/+10Vdc (Module-2), function see parameter P66 (Rbmin 10Kohm)
OUT 2-4: 0/+10Vdc (Module-2), function see parameter P67 (Rbmin 10Kohm)
Relay out: Ry 1-1: SPDT contact (Module-1), see param. P70 (Max. 250Vac/8A non-inductive)
(max. 8) Ry 1-2: SPST contact (Module-1), see param. P71 (Max. 250Vac/8A non-inductive)
Ry 1-3: SPST contact (Module-1), see param. P72 (Max. 250Vac/8A non-inductive)
Ry 1-4: SPST contact (Module-1), see param. P73 (Max. 250Vac/8A non-inductive)
Ry 2-1: SPDT contact (Module-2), see param. P74 (Max. 250Vac/8A non-inductive)
Ry 2-2: SPST contact (Module-2), see param. P75 (Max. 250Vac/8A non-inductive)
Ry 2-3: SPST contact (Module-2), see param. P76 (Max. 250Vac/8A non-inductive)
Ry 2-4: SPST contact (Module-2), see param. P77 (Max. 250Vac/8A non-inductive)
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 5 of 17
2 Functional specifications
The MC 785 FAC is an operational system for an airconditioning cabinet.
From software version 2.00 on, it is provided with real-time clock for time ventilation (P100 to P114)
The temperature of the inflowing water determines whether heating or cooling can take place. This is
indicated by means of LED on the regulator.
On the basis of the measured air temperature behind the heat exchanger and the adjusted set point,
the 3-way mixing valve is either opened or shut. The position of the valve is shown in one of the
displays.
The fan can be set at a high or low speed by a key on the front of the controller.
If the measured air pressure, over the airconditioning cabinet, is under the set minimum value or over
the set maximum value, then the heater and fan will be turned off and the control valve will be
opened to the maximum extent. The appropriate alarm LED will light up and the alarm will come on.
A frost protection sensor is fixed to the cold water pipe coming from the heat exchanger. Should this
sensor measure a temperature lower than the set frost protection, then the heater and fan will be
turned off and the control valve will be opened to the maximum extent. It is also possible to connect
an external frost protection contact on the LMS DIGITAL IN module (See parameter P36), this will
also turn off the heater and fan and sets the control valve open to the maximum extent. The
appropriate alarm LED will be lit and the alarm activates.
Should the air temperature by the heat exchanger fall below the set minimum value, the heater and
fan are turned off and the control valve is opened to the maximum. The alarm LED will light up and
the alarm will come on.
Should the air temperature after the heater fall below the set minimum value, the heater and fan are
turned off and the control valve is opened to the maximum. The alarm LED will light up and the alarm
will come on.
Will the input contacts of ‘Heater failure’, ‘Fan-failure’ or ‘Emergency stop’ are opened or ‘Exhaust fan
failure’ is closed, an alarm follows and the LED on the display will light up, the heater and fan are
turned off and the control valve is opened to the maximum.
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 6 of 17
3 Operation
During normal operation the top-left display indicates the measured air temperature by the blowing-
out opening of the fan. The bottom-left display indicates the desired temperature (set point).
In the top-right display the temperature of ingoing or outgoing water temperature is shown, or the
outgoing air temperature by the heat exchanger. One of the sensors can be selected by means of the
sensor key.
The bottom-right display shows the actual position of the valve. By pressing the DP key, the pressure
difference over the LBK is shown. By pressing the RH key the measured relative air humidity can be
shown. By pressing the -key the emitted percentage of the after-heater can be shown.
By holding the PRG key down for longer than 5 seconds it is possible to enter the Internal
Parameters. In the top left display a P followed by a digit will appear. By pressing the UP or DOWN
keys the desired parameter can be found. The bottom left display shows the value of the parameter.
By pressing the SET key and the UP or DOWN key simultaneously the value can be adjusted.
If no key is touched for more than 30 seconds, or if the ON/OFF key is pressed, the display will jump
back to the normal operation mode.
P111 Switch-on time high position Sat. Switch-on 00.00..23.45, OFF - OFF
P112 time low position Sat. 00.00..23.45, OFF - OFF
This is done be replacing the LMS Digital-in module with the LMS Controller module HH-FAC
(VDH-type no. 944.800347). This module converts the RS485-protocol to the I2C-bus so that the
rest of the LMS-units can be connected locally.
6 Sensor calibration
The temperature sensors can be calibrated by the parameters P1 to P4.
Should the temperature sensor indicate 0.2/C too much, for example, then the offset must be
adjusted 0.2/C lower.
7 Alarms
An alarm can be caused by:
The alarm messages are shown in the temperature display (top left).
By pressing the RESET ALARM key the alarm relay can be reset. The error message remains in the
display as long as the error remains. The alarm LED will also continue to blink.
8 Principle diagram
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 12 of 17
8 Front
Front view of MC785-FAC panel mounting model, drawing 980905
9 Connection diagrams
Connection data for MC785-FAC panel mounting model, drawing 001710w2
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 14 of 17
LMS modules via I2C-bus (maximal 5-metres) connection data, drawing 001713w3:
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 16 of 17
LMS modules via RS485-Network (maximal 1 KM) connection data, drawing 021587w3:
User manual Document no. : 031220 Version: V2.5
MC 785 FAC Client: Heinen & Hopman Page: 17 of 17
10 Dimensions
Dimensions of MC 785 panel mounting model, drawing 961271