Kariba south Power Station

Station Automation Project I/O Listing

Digital Inputs
Wire No Remarks
No Description cable Type S800
1 ACB Closed 1 Ind 553
2 ACB Open 1 Ind 554
3 isolator g4 closed 1 Ind 555
4 isolator g4 open 1 Ind 556
5 E /Switch G1A closed 1 Ind 557
6 E /Switch G1A open 1 Ind 558
7 E /Switch G1B closed 1 Ind 559
8 E /Switch G1B open 1 Ind 560
9 ACB Low Air pressure 1 Alarm 561
10 ACB trip supply fail 1 Alarm 562
11 Main Protection Operated 2 Alarm 563
12 Backup Protection Operated 2 Alarm 564
13 Unit Tx bucholz 2 Alarm 565
14 VT fail/ Trip to Manual 2 Alarm 566
15 overvolatge 2 Alarm 567
16 Over current 2 Alarm 568
17 Merz price 2 Alarm 570
18 Earth fault 2 Alarm 571
19 Excitation Build up failure 3 Alarm 572
20 Rotor earth fault 3 Alarm 573
21 Rotor high temp 3 Alarm 574
22 Electronic power pack failure 3 Alarm 575
23 Convertor line fuse failed 3 Alarm 576
24 Convertor surge circuit failure 3 Alarm 577
25 Excitation tx high temp 3 Alarm 578
26 (Air flow failure) Thyristor cooling failure 3 Alarm 579
27 Electronic power supply failure 3 Alarm 580
28 Thyristor fault 3 Alarm 581
29 AC standby power sup.failure 3 Alarm 582
30 DC auxiliary power sup.failure 3 Alarm 583
31 Under excitation limit 3 Alarm 584
32 Over excitation limit 3 Alarm 585
33 Thyristor high temp. trip 3 Alarm 587
34 Thyristor high temp.alarm 3 Alarm 588
35 Excitation in Auto 3 Ind 589
36 Stator current limit 3 Alarm 590
37 Field contactor closed 3 Ind 591
38 Power system Stabiliser failed 3 alarm 592
39 Standby control-maula control 3 Ind 593
40 sequencer failure 4 Alarm 594
41 incoplete sequence 4 Alarm 595
42 Auto synch on 4 Ind 596
43 ready to synch 4 Ind 597
44 unit in operation 4 Ind 598
45 Unit at rest avilable for Start 4 Ind 599
46 Unit start in progress( this includes a speed bargragh) 4 Ind 600
47 Unit Isolated 4 Ind 601
48 Unit start up Auxiliaries(this includes a speed bar grah 4 Ind 602
49 Unit Start up to speed-no load 4 Ind 604
50 Commissioning in progress -Do not Operate 4 Ind 605
51 Unit at speed no load 4 Ind 606
52 Unit Synchronising sequence 4 Ind 607
53 Turbine to governor power setting-generator ready to 4 Ind 608
54 Unit Stop in progress( Includes speed bar gragh) 4 Ind 609
55 Turbine at rest 4 Ind 610

Page 1 of 6
56 Speed signal fault 4 Ind 611
57 Caution Test mode Enabled 4 Ind 612
58 Battery Faulty 4 Ind 613
59 Self test 4 Ind 614
60 High bearing temp 5 Alarm 615
61 Gov Low oil Pressue 5 Alarm 616
62 Gv fail to close 5 Alarm 617
63 brake air pressure low 5 Alarm 618
64 cooling water failure 5 Alarm 619
65 S/By G.O.P running 5 Alarm 621
66 Gv fail to open 5 Alarm 622
67 shear-pin failure 5 Alarm 623
68 Stator air temp 5 Alarm 624
69 Gov oil level low 5 Alarm 625
70 Brakes fail to operate 5 Alarm 626
71 co2 released 5 Alarm 627
72 fail to start 5 Alarm 628
73 overspeed 5 Alarm 629
74 Exciter trip to Stand by manual 3 Alarm 630
75 gen guide bearing oil level 5 Alarm 631
76 TGB and GTB oil level 5 Alarm 632
77 filters clogged/gov problem 5 Alarm 633
78 TURBINE TO COVER HWLl trip 5 Alarm 634
79 Brake interlock failure 5 Alarm 635
80 Urgent Excitation trouble 5 Alarm 636
81 Tcw/Stn Drain sump hwl * Tcw (2,4,6) Stn-(1,3,5) 5 Alarm 638
82 governor failure 5 Alarm 639
83 governor fault 5 Alarm 640
84 C/S supply avail 5 Ind 641
85 Unit Tx supply avail 5 Ind 642
86 C/S supply on 5 Ind 643
87 Unit Tx supply on 5 Ind 644
88 Auto/manual 5 Ind 645
89 remote/local 5 Ind 646
90 Intake gate closed 5 Ind 647
91 Intake gate Open 5 Ind 648
92 Topcover hwl alarm 5 Alarm 649
93 Alarm supply fail 6 Alarm 650
94 unit tx Co2 released 6 Alarm 651
95 Unit Tx 380v earth fault 6 Alarm 652
96 shutdown relay operated 6 Alarm 653
97 Unit Txco2 isolated
98 EDP running (Unit 6 only) 6 Alarm
99 To be allaocated
100 To be allaocated
101 To be allaocated
102 To be allaocated
103 To be allaocated
104 To be allaocated
105 To be allaocated
106 To be allaocated
107 To be allaocated
108 To be allaocated
109 To be allaocated
110 To be allaocated
111 To be allaocated
112 To be allaocated

Digital out puts


No Description cable
1 Unit Start 4 655 656

Page 2 of 6
2 Unit Stop 4 657 658
3 Unit Sycnronise 4 659 660
4 Reset Auto Synch 4 661 662
5 Not In use 4 663 664
6 Open ACB 4 665 666
7 intake gate trip 4 667 668

Page 3 of 6
Analogue Inputs

1 Stator air temp1 505 506


2 Stator air temp2 507 508
3 TGB temp 509 510
4 GTB temp 511 512
5 GGB temp 513 514
6 Stator temp 515 516
7 Rotor temp 517 518
8 Rotor Current 519 520
9 Spiral casing press 521 522
10 Gov oil press 523 524
11 Gov.air vess press 525 526
12 Stator current 527 528
13 Kvolts 529 530
14 waterflow 531 532
15 Lake Level Connected to Unit 1 533 534
16 Tail water Level Connected to Unit 1 535 536

Page 4 of 6
Digital inputs

No Description cable
1 Unit Start 4
2 Unit Stop 4
3 Unit Sycnronise 4
4 Open ACB 4
5 volts raise 4
6 volts lower 4
7 intake gate trip 4
Analogue Inputs

1 Stator air temp1


2 Stator air temp2
3 TGB temp
4 GTB temp
5 GGB temp
6 Stator temp
7 Rotor temp
8 Rotor Current
9 waterflow
10 Spiral casing press
11 Gov oil press
12 Kvolts
13 Gov.air vess press
14 Stator current