Vous êtes sur la page 1sur 44

®

Installation
Operation
Maintenance
Packaged Electric/Electric
TSC060 - TSC120
50 Hz

April 2006 T_C-IOM-2A


Introduction

Literature Change History Model Number Description

T_C-IOM-2 (March 2003) All products are identified by a multiple-


Orginal issue TSC060 - TSC120 mod- character model number that precisely
els. identifies a particular type of unit. An ex-
planation of the alphanumeric identifica-
T_C-IOM-2 (March 2004) tion code is provided below. Its use will
Added Phase Monitor enable the owner/operator, installing con-
tractors, and service engineers to define
Overview of Manual the operation, specific components, and
other options for any specific unit.
Note:
One copy of this document ships inside When ordering replacement parts or re-
the control panel of each unit and is questing service, be sure to refer to the
customer property. It must be retained specific model number and serial number
by the unit’s maintenance personnel. printed on the unit nameplate.

This booklet describes proper installa- Unit Nomenclature


tion, operation, and maintenance proce-
dures for air cooled systems. By carefully CAUTION
reviewing the information within this
manual and following the instructions, the Equipment Damage From
risk of improper operation and/or compo-
nent damage will be minimized.
Ultraviolet (UV) Lights!

It is important that periodic maintenance The manufacturer does not recom-


be performed to help assure trouble free mend field installation of ultraviolet
operation. A maintenance schedule is lights in its equipment for the in-
provided at the end of this manual. tended purpose of improving indoor
Should equipment failure occur, contact a air quality. High intensity C-band
qualified service organization with quali- ultraviolet light is known to severely
fied, experienced HVAC technicians to damage polymer (plastic) materials
properly diagnose and repair this equip- and poses a personal safety risk to
ment.
anyone exposed to the light without
proper personal protective equip-
Note:
ment. Polymer materials commonly
Do Not release refrigerant to the
atmosphere! If adding or removing found in HVAC equipment that may be
refrigerant is required, the service susceptible include insulation on
technician must comply with all federal, electrical wiring, fan belts, thermal
state, and local laws. insulation, various fasteners and
bushings. Degradation of these
materials can result in serious
damage to the equipment.

The manufacturer accepts no


responsibility for the performance or
operation of our equipment in which
ultraviolet devices were installed
outside of the manufacturer’s factory
or its approved suppliers.

©American Standard Inc. 2004 T_C-IOM-2A


Contents

Intoduction Field Installed Control Wiring ............ 22 Maintenance


Literature Change History .................. 2 Control Power Transformer .............. 22 Fan Belt Adjustment ......................... 34
Overview of Manual ........................... 2 Controls using 24 VAC ................... 22 Belt Tension Gauge ......................... 35
Model Number Description ................ 2 24V AC Conductors with Reliatel .... 23 Filters ............................................... 36
Unit Nomenclature .............................. 4 Controls using Cooling Season ............................... 36
DC Analog Input/Outputs ................ 23 Heating Season ............................... 36
General Information Customer Low Voltage Routing- ..... 24 Final Process .................................... 37
Typical Field Wiring for Sample Maintenance Log ................ 38
Unit Nameplate .................................. 5
Optional Controls ............................. 25
Compressor Nameplate .................... 5
Space Temperature Averaging ....... 26 Trouble Shooting
Unit Description .................................. 5
Temperature vs Resistance ............. 26
ReliaTel Control ................................. 5 ReliaTel Control ............................... 39
Voltage Imbalance ........................... 27
ReliaTel System Status Checkout Procedure 39
Electrical Phasing .............................. 27
Trane Communication Interface LED 4 (Service) ............................... 39
(Optional) .......................................... 5 System Failure ................................. 39
ReliaTel Pre - Start Cooling Failure ................................. 39
LonTalk Communication Interface Service Test Guide for Service Failure ................................. 40
(Optional) .......................................... 5 Component Operation .................... 29 Simultaneous Heat and Cool Failure . 40
ReliaTel Verifying Proper Air Flow ................. 30 Cool Failure ..................................... 40
Options Module Economizer Start -Up ...................... 31 Cooling and Heating Lockouts .......... 40
(Optional) .......................................... 5 Compressor Start-Up ...................... 31 Zone Temperature Sensor .............. 40
System Scroll Compressors ......................... 31 (ZTS) Service Indicator .................... 40
Input Devices & Functions .............. 6&7 Heating Start-Up .............................. 31 Fan Failure Switch ............................ 40
Zone Temperature Sensor
Pre - Installation Final System Set - Up (ZTS) Test ....................................... 40
Unit Inspection .................................. 8 Final System Setup ......................... 33 Zone Temperature Thermistor
Unit Storage ...................................... 8 (ZTEMP) ......................................... 41
Unit Installation Clearances ................. 9 Test 2 .............................................. 41
Unit Dimensions ............................... 10 Cooling Set Point (CSP) and
Rigging / Center-of-Gravity Data ...... 12 Heating Set Point (HSP) .................. 41

Installation
ReliaTel Refrigeration Module
Foundation ....................................... 13
(RTRM) Default Chart ...................... 41
Unit Supply & Return Air Openings . 14
Ductwork .......................................... 15
Roofcurb .......................................... 15
Rigging ............................................ 16
Factory Installed Economizer ............ 17
Temperature Limit Switch Usage for
Electric Heat Units ............................ 17
Horizontal Discharge Conversion
TSC060 .......................................... 18
TSC072-120 .................................. 19
TCO-A Instructions: ......................... 20
Electric Heat Requirements .............. 21
Condensate Drain Configuration ....... 21
Condensate Trap Installation ............ 21
Filter Installation ................................ 22
Main Unit Power Wiring .................... 22

T_C-IOM-2A 3
Model Number Description

Digit 1 - Product Type Digit 15 - Factory Installed Options Digit 25 - Factory Installed Options
T = Packaged Cooling -Supply Fan -System Monitoring Controls
0 = Standard Drive 0 = Without Monitoring Controls
Digit 2 - Unit Efficiency Level 1 = Oversize Motor 1 = Clogged Filter Switch
S = Standard 2 = Fan Failure Switch
Digit 16 - Factory Installed Options 3 = Discharge Air Sensing Tube
Digit 3 - Airflow Configuration -Hinged Service Access 4 = Clogged Filter Switch and Fan
C = Convertible 0 = Standard Panels Failure Switch
A = Hinged Service Panels 5 = Clogged Filter Switch and
Digit 4, 5, 6 - Cooling Capacity Discharge Air Sensing Tube
060 = 5 Ton ( 17.6 KW ) Digit 17 - Factory Installed Options 6 = Fan Failure Switch and
072 = 6 Ton ( 21.1 KW ) -Condenser Coil Protection Discharge Air Sensing Tube
090 = 7 1/2 Ton ( 26.4 KW ) 0 = Standard 7 = Clogged Filter Switch, Fan Failure
102 = 8 1/2 Ton ( 29.9 KW ) 1= Hail Guard Switch and
120 = 10 Ton ( 35.1 KW ) 2 = Epoxy Coated Condenser Coil Discharge Air Sensing Tube
3 = Epoxy Coated Condenser Coil and
Digit 7 - Major Design Sequence Hail Guard
A 4 = CompleteCoat Condenser Coil
5 = CompleteCoat Condenser Coil and
Digit 8 - Electrical Characteristics Hail Guard

D = 380-415/50/3 Digit 18 - Factory Installed Options


-Through The Base
Digit 9 - Unit Control 0 = Without Through The Base
R = Relia Tel Connection

Digit 10 - Heat Capacity Digit 19 - Factory Installed Options


0 = No Heat -Disconnect Switch/Circuit Breaker
0 = Without Disconnect Switch/Circuit
Digit 11 - Minor Design Sequence Breaker
3 = With Phase Monitor
*
Digit 12, 13 - Service Digit Sequence Digit 20 - Factory Installed Options
** -Convenience Outlet
0 = Without Convenience Outlet
Digit 14 - Factory Installed Options
-Fresh Air Section Digit 21 - Factory Installed Options
0 = No Fresh Air -Communications
A = Manual OA, 0 - 25% 0 = Without Communications Options
B = Motorized OA, 0 - 50% 1 = Trane Communications Interface
C = Economizer Dry Bulb 2 = LonTalk Communications Interface
D = Economizer with
Barometric Relief Digit 22 - Factory Installed Options
E = Economizer, Reference Enthalpy -Refrigeration System
F = Economizer, Reference Enthalpy, 0 = Without Refrigeration System Option
with Barometric Relief
G = Economizer, Comparative Digit 23 - Factory Installed Options
Enthalpy -Refrigeration Controls
H = Economizer, Comparative 0 = Without Refrigeration Controls
Enthalpy, with Barometric Relief
Digit 24 - Factory Installed Options
-Smoke Detector
0 = Without Smoke Detector

©American Standard Inc. 2004 T_C-IOM-2A


General Information

Unit Nameplate Unit Description Economizer Control Actuator


(Optional)
A Mylar unit nameplate is located on the Before shipment, each unit is leak tested, ReliaTel™ Control
unit’s corner support next to the filter ac- dehydrated, charged with refrigerant and The ECA monitors the mixed air tem-
cess panel. It includes the unit model compressor oil, and run tested for proper perature, return air temperature, minimum
number, serial number, electrical charac- control operation. position setpoint (local or remote),
teristics, refrigerant charge, as well as power exhaust setpoint, CO2 setpoint,
other pertinent unit data. The condenser coils are aluminum fin, CO2, and ambient dry bulb/enthalpy
mechanically bonded to copper tubing. sensor or comparative humidity (return air
Compressor Nameplate humidity against ambient humidity) sen-
Direct-drive, vertical discharge condenser sors, if selected, to control dampers to an
The nameplate for the compressors are fans are provided with built-in thermal accuracy of +/- 5% of stroke. The actuator
located on the side of the compressor. overload protection. is spring returned to the closed position
any time that power is lost to the unit. It is
Hazard Identification The ReliaTel™ Control Module is a mi- capable of delivering up to 25 inch
croelectronic control system that is re- pounds (2.82 N-m) of torque and is
ferred to as “Refrigeration Module” powered by 24 VAC.
(RTRM). The acronym RTRM is used
Warnings are provided throughout extensively throughout this document
when referring to the control system net- RTCI -- ReliaTel™ Trane
this manual to indicate to installing
contractors, operators, and service work. Communication Interface
personnel of potentially hazardous (Optional)
situations which, if not avoided, The module through Proportional/Integral This module is used when the application
COULD result in death or serious in- control algorithms perform specific unit calls for an ICSTM building management
jury. functions that governs unit operation in re- type control system. It allows the control
sponse to; zone temperature, supply air and monitoring of the system through an
temperature, and/or humidity conditions ICS panel. The module can be ordered
depending on the application. The from the factory or ordered as a kit to be
stages of capacity control for these units field installed. Follow the installation in-
Cautions are provided throughout are achieved by starting and stopping struction that ships with each kit when field
this manual to indicate to installing the compressors. installation is necessary.
contractors, operators, and service
personnel of potentially hazardous The RTRM is mounted in the control RLCI - ReliaTel™ LonTalk
situations which, if not avoided, MAY panel and is factory wired to the respec-
result in minor or moderate injury. tive internal components. The RTRM re-
Communication Interface
ceives and interprets information from (Optional)
other unit modules, sensors, remote pan- This module is used when the application
els, and customer binary contacts to sat- calls for an ICSTM building management
isfy the applicable request for cooling. type control system that is LonTalk. It al-
lows the control and monitoring of the
system through an ICS panel. The mod-
ule can be ordered from the factory or or-
dered as a kit to be field installed. Follow
the installation instruction that ships with
each kit when field installation is neces-
sary.

RTOM – ReliaTel™ Options


Module (Optional)
The RTOM monitors the supply fan
proving, clogged filter, supply air tem-
perature, exhaust fan setpoint, supply air
tempering, Frostat™ and smoke detec-
tor. Refer to system input devices and
functions for operation.

T_C-IOM-2A 5
General Information

System Input Devices & Clogged Filter Switch (Optional) Low Pressure Control
Functions The unit mounted clogged filter switch ReliaTel Control
monitors the pressure differential across When the LPC is opened for 1 continu-
The RTRM must have a zone sensor or the return air filters. It is mounted in the fil- ous second, the compressor for that cir-
thermostat input in order to operate the ter section and is connected to the cuit is turned off immediately. The com-
unit. The flexibility of having several RTOM. A diagnostic SERVICE signal is pressor will not be allowed to restart for a
mode capabilities depends upon the sent to the remote panel if the pressure minimum of 3 minutes.
type of zone sensor or thermostat se- differential across the filters is at least 0.5"
lected to interface with the RTRM. w.c.(124.5 Pa). The contacts will auto- If four consecutive open conditions occur
matically open when the pressure differ- during the first three minutes of operation,
The descriptions of the following basic In- ential across the filters decreases to ap- the compressor will be locked out, a di-
put Devices used within the RTRM net- proximately 0.4" w.c.(99.6 Pa). The agnostic communicated to ICSTM if appli-
work are to acquaint the operator with clogged filter output is energized when cable, and a manual reset will be required
their function as they interface with the the supply fan is operating and the to restart the compressor.
various modules. Refer to the unit’s elec- clogged filter switch has been closed for
trical schematic for the specific module at least 2 minutes. The system will con- High Pressure Control
connections. tinue to operate regardless of the status ReliaTel Control
of the filter switch. The high pressure controls are wired in
The following controls are available from series between the compressor outputs
the factory for field installation. Compressor Disable (CPR1/2) on the RTRM and the compressor
This input incorporates the low pressure contactor coils. If the high pressure control
Supply Fan Failure Input (Optional) control (LPC) of each refrigeration circuit switch opens, the RTRM senses a lack
The Fan Failure Switch can be connected and can be activated by opening a field of current while calling for cooling and
to sense indoor fan operation: supplied contact installed on the LTB. locks the compressor out.
FFS (Fan Failure Switch) If air flow
through the unit is not proven by the dif- If this circuit is open before the compres- On dual circuit units, if the high pressure
ferential pressure switch connected to the sor is started, the compressor will not be control opens, the compressor on the af-
RTOM (factory set point 0.07 “ w.c. allowed to operate. Anytime this circuit is fected circuit is locked out. A manual reset
(17.4 Pa)) within 40 seconds nominally, opened for 1 continuous second during for the affected circuit is required.
the RTRM will shut off all mechanical op- compressor operation, the compressor
erations, lock the system out, send a di- for that circuit is immediately turned “Off”. Lead/Lag Control (Dual Circuit Only)
agnostic to ICS, and the SERVICE out- The compressor will not be allowed to ReliaTel Control
put will flash. The system will remain restart for a minimum of 3 minutes should Lead/Lag is a selectable input located on
locked out until a reset is initiated either the contacts close. the RTRM. The RTRM is configured from
manually or through ICS. the factory with the Lead/Lag control
If four consecutive open conditions occur disabled. To activate the Lead/Lag
during the first three minutes of operation, function, simply cut the wire connected to
the compressor for that circuit will be J3-8 at the RTRM. When it is activated,
locked out, a diagnostic communicated to each time the designated lead compres-
the remote panel (if installed), and a sor is shut off due to the load being
manual reset will be required to restart satisfied, the lead compressor or refrigera-
the compressor. tion circuit switches. When the RTRM is
powered up, i.e. after a power failure, the
control will default to the number one circuit
compressor.

6 T_C-IOM-2A
General Information

Zone Sensor Module (ZSM) The Option Menu is used to enable or Remote Zone Sensor
(BAYSENS006B) disable applicable functions, i.e.; Morning (BAYSENS017B)
This electronic sensor features three sys- Warm-up, Economizer minimum position This electronic sensor can be used with
tem switch settings (Heat, Cool, and override during unoccupied status, Fahr- BAYSENS006B, 008B, 010B, 019B
Off) and two fan settings (On and Auto). enheit or Centigrade, Supply air temper- Remote Panels. When this sensor is
It is a manual changeover control with ing, Remote zone temperature sensor, wired to a BAYSENS019B Remote
single setpoint. (Cooling Setpoint Only) 12/24 hour time display, Smart fan, and Panel, wiring must be 18 AWG (.75mm2
Computed recovery. ) Shielded Twisted Pair (Belden 8760 or
Zone Sensor Module (ZSM) equivalent). Refer to the specific Remote
(BAYSENS008B) During an occupied period, an auxiliary Panel for wiring details.
This electronic sensor features four sys- relay rated for 1.25 amps @ 30 volts
tem switch settings (Heat, Cool, Auto, AC with one set of single pole double BAYSTAT036A
and Off) and two fan settings (On and throw contacts is activated. Single Stage - 1 Heat/1 Cool
Auto). It is a manual or auto changeover
control with dual setpoint capability. It can Status Inputs (4 Wires Optional) BAYSTAT037A
be used with a remote zone temperature The ZSM can be wired to receive four (4) Multi Stage - 2 Heat/2 Cool - Can be
sensor BAYSENS017B. operating status signals from the RTRM Used for Economizer Operation
(HEAT, COOL, SYSTEM “ON”, SER-
Zone Sensor (BAYSENS010B) VICE). Four (4) wires from the RTRM BAYSENS025A
This electronic sensor features four sys- should be connected to the appropriate Remote sensor for BAYSTAT036A,
tem switch settings (Heat, Cool, Auto, terminals (7, 8, 9 & 10) on the ZSM. 037A.
and Off) and two fan settings (On and
Auto) with four system status LED’s. It is Remote Zone Sensor Phase Monitor (Optional)
a manual or auto changeover control with (BAYSENS013C) ReliaTel Control Only
dual setpoint capability. It can be used This electronic sensor features remote This sensor monitors voltage between
with a remote zone temperature sensor zone sensing and timed override with the 3 conductors of the 3 phase power
BAYSENS017B. override cancellation. It is used with a supply. Two LED lights are provided.
Trane Integrated ComfortTM building man- The green light indicates that a balanced
Programmable Zone Sensor - agement system. 3 phase supply circuit is properly con-
BAYSENS019B nected. The red light indicates that unit
This 7 day programmable sensor fea- Remote Zone Sensor operation has been prevented. There
tures 2, 3 or 4 periods for Occupied or (BAYSENS014C) are two conditions that will prevent unit
Unoccupied programming per day. If the This electronic sensor features single operation.The power supply circuit is not
power is interrupted, the program is re- setpoint capability and timed override balanced with the proper phase se-
tained in permanent memory. If power is with override cancellation. It is used with a quence of L1,L2,L3 for the 3 conductors
off for an extended period of time, only Trane Integrated ComfortTM building man- of a 3 phase circuit. The line to line volt-
the clock and day may have to be reset. agement system. age is not between 180 volts and 633
volts.
The Zone Sensor allows selection of 2, 3 Remote Zone Sensor
or 4 system modes (Heat, Cool, Auto, (BAYSENS016A)
and Off), two fan modes (On and Auto). This bullet type temperature sensor can
It has dual temperature selection with be used for; outside air (ambient) sens-
programmable start time capability. ing, return air temperature sensing, sup-
ply air temperature sensing, remote tem-
The occupied cooling set point ranges perature sensing (uncovered. Wiring pro-
between 45 F (7.2 C)and 98 F (35.6 C) cedures vary according to the particular
Fahrenheit. The heating set point ranges application and equipment involved. Re-
between 43 F (6.1 C) and 96 F ( 35.6 fer to the unit’s wiring diagrams for proper
C) degrees. connections.
A liquid crystal display (LCD) displays
zone temperature, temperature set
points, day of the week, time, and opera-
tional mode symbols.

T_C-IOM-2A 7
General Information

Unit Inspection Storage Unit Clearances


As soon as the unit arrives at the job site Take precautions to prevent condensate Figure 1 illustrates the minimum operating
from forming inside the unit’s electrical and service clearances for either a single
[ ] Verify that the nameplate data compartments and motors if: or multiple unit installation. These clear-
matches the data on the sales order ances are the minimum distances neces-
and bill of lading (including electrical a. the unit is stored before it is installed; sary to assure adequate serviceability,
data). or, cataloged unit capacity, and peak operat-
ing efficiency.
[ ] Verify that the power supply complies b. the unit is set on the roof curb, and
with the unit nameplate specifications. temporary heat is provided in the Providing less than the recommended
building. Isolate all side panel service clearances may result in condenser coil
[ ] Visually inspect the exterior of the unit, entrances and base pan openings starvation, “short-circuiting” of exhaust
including the roof, for signs of shipping (e.g., conduit holes, S/A and R/A and economizer airflows, or recirculation
damage. openings, and flue openings) from the of hot condenser air.
ambient air until the unit is ready for
If the job site inspection of the unit re- start-up.
veals damage or material shortages, file a
claim with the carrier immediately. Note:
Specify the type and extent of the dam- Do not use the unit’s heater for
age on the “bill of lading” before signing. temporary heat without first completing
the start-up procedure detailed under
[ ] Visually inspect the internal compo- “Heating Start Up”.
nents for shipping damage as soon as
possible after delivery and before it is The manufacturer will not assume any re-
stored. Do not walk on the sheet metal sponsibility for equipment damage re-
base pans. sulting from condensate accumulation on
the unit’s electrical and/or mechanical com-
[ ] If concealed damage is discovered, ponents.
notify the carrier’s terminal of damage
immediately by phone and by mail.
Concealed damage must be reported
within 15 days.

Request an immediate joint inspection


of the damage by the carrier and the
consignee. Do not remove damaged
material from the receiving location.
Take photos of the damage, if pos-
sible. The owner must provide rea-
sonable evidence that the damage
did not occur after delivery.

[ ] Notify the appropriate sales represen-


tative before installing or repairing a
damaged unit.

8 T_C-IOM-2A
Pre - Installation

Figure 1
Tyical Installation Clearances for Single & Multible Unit Applications

T_C-IOM-2A 9
Unit Dimensions

Figure 2
Unit Dimensional Data
TSC060AD

36 1/4"
921 MM
4 1/4"
108 MM

23 9/16"
598 MM

69 7/8" 42 1/4"
1775 MM 1073 MM
5 9/16"
141 MM
5 5/8" 7 5/8"
143 MM 194 MM
9 5/8" 44 1/4"
244 MM 1124 MM

10 T_C-IOM-2A
Unit Dimensions

Figure 2 - Continued
Unit Dimensional Data
T/SC072AD, TSC090AD

Unit Dimensional Data


TSC102AD, TSC120AD

T_C-IOM-2A 11
Unit / Accessory Weights

Table 1
Typical Unit Weights & Point Loading Data
Net Center Net Center
Unit Weight Corner Wt. (lbs) of Gravity (In.) Unit Weight Corner Wt. (kg) of Gravity (m m .)
Model (lbs) A B C D Length Width Model (kg) A B C D Length Width
TSC060AD* 518 165 124 105 124 31 19 TSC060AD* 235 75 56 48 56 790 480
TSC072AD* 718 235 182 128 173 38 22 TSC072AD* 326 107 83 58 78 970 560
TSC090AD* 857 289 222 148 197 38 21 TSC090AD* 389 131 101 67 89 970 530
TSC102AD* 893 294 233 159 207 39 22 TSC102AD* 405 133 106 72 94 990 560
TSC120AD* 982 323 253 178 229 39 22 TSC120AD* 445 146 115 81 104 990 560

Typical Accessory Weights


1
Net Weights lbs Net Weights (kg)1
Accessory 5 Ton 6 - 10 Tons Accessory 5 Ton 6 - 10 Tons
Economizer 26 36 Economizer 12 16
Barometric Relief 7 10 Barometric Relief 3 5
Motorized Outside Air Damper 20 30 Motorized Outside Air Damper 9 14
Manual Outside Air Damper 16 26 Manual Outside Air Damper 7 12
Roof Curb 70 115 Roof Curb 32 52
Oversized Motor 5 8 Oversized Motor 2 4
Coil Guards 12 20 Coil Guards 5 9
Hinged Doors 10 12 Hinged Doors 5 5
NOTES:
(1) Net w eight should be added to unit w eight w hen ordering factory-installed accessories.

Figure 3
Rigging and Center-of-Gravity Data

LIFTING AND MOVING INSTRUCTIONS!

DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS


SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.

EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT


UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.

LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE


SAME LENGTH. ADJUST AS NECESSARY FOR EVEN LEVEL
LIFT.

USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER TO


TABLE 1 FOR UNIT WEIGHT.

12 T_C-IOM-2A
Installation

Foundation
Horizontal Units
If the unit is installed at ground level, elevate it above the snow line. Provide con-
crete footings at each support location with a “full perimeter” support structure or a
slab foundation for support. Refer to Table 1 for the unit’s operating and point
loading weights when constructing a footing foundation.

If anchoring is required, anchor the unit to the slab using hold down bolts or isola-
tors. Isolators should be installed to minimize the transmission of vibrations into
the building.

For rooftop applications, ensure the roof is strong enough to support the com-
bined unit and support structural weight. Refer to Table 1 for the unit operating
weights. If anchoring is required, anchor the unit to the roof with hold-down bolts
or isolators.

Check with a roofing contractor for proper waterproofing procedures.

T_C-IOM-2A 13
Installation

Figure 4 TSC060AD
TSC060AD Downflow Unit Supply & Return Air Opening
Horizontal Unit Supply & Return Air Opening

TSC072AD-120AD
TSC072AD-120AD Downflow Unit Supply & Return Air Openings
Downflow Unit Supply & Return Air Openings

Return

Supply

14 T_C-IOM-2A
Installation

Ductwork Step-by-step curb assembly and instal-


lation instructions ship with each acces-
Figure 4-1 illustrates the supply and re- sory roof curb kit. Follow the instructions
turn air openings as viewed from the rear carefully to assure proper fit-up when the
of the unit. unit is set into place.

Elbows with turning vanes or splitters are Note:


recommended to minimize air noise due To assure proper condensate flow during
to turbulence and to reduce static pres- operation, the unit (and curb) must be
sure. level.

When attaching the ductwork to the unit, If the unit is elevated, a field constructed
provide a water tight flexible connector at catwalk around the unit is strongly recom-
the unit to prevent operating sounds mended to provide easy access for unit
from transmitting through the ductwork. maintenance and service.

All outdoor ductwork between the unit Recommendations for installing the Sup-
and the structure should be weather ply Air and Return Air ductwork joining
proofed after installation is completed. the roof curb are included in the curb in-
struction booklet. Curb ductwork must be
Roof Curb fabricated and installed by the installing
contractor before the unit is set into place.
Downflow
The roof curbs for these units consists of Note:
a “full perimeter” enclosure to support the For sound consideration, cut only the
unit. holes in the roof deck for the ductwork
penetrations. Do not cut out the entire
Before installing any roof curb, verify; roof deck within the curb perimeter.

1. That it is the correct curb for the unit, If a Curb Accessory Kit is not used:

2. That it includes the necessary gaskets a. The ductwork can be attached


and hardware, directly to the factory-provided
flanges around the unit’s supply
3. That the purposed installation location and return air openings. Be sure to
provides the required clearance for use flexible duct connections at
proper operation. the unit.

4. Insure that the curb is level and square. b. For “built-up” curbs supplied by
The top surface of the curb must be others, gaskets must be installed
true to assure an adequate curb-to-unit around the curb perimeter flange
seal. and the supply and return air
opening flanges.

T_C-IOM-2A 15
Installation

Rigging
A Rigging illustration and Center-of- DO NOT USE CABLES (CHAINS OR
Gravity dimensional data table is shown SLINGS) EXCEPT AS SHOWN. OTHER
in Figure 3. Refer to the typical unit oper- LIFTING ARRANGEMENTS MAY CAUSE
ating weights table before proceeding. EQUIPMENT DAMAGE OR SERIOUS
PERSONAL INJURY.
1. The wooden top is secured to the unit
EACH OF THE CABLES (CHAINS OR
by a plastic strap. The plastic strap is SLINGS) USED TO LIFT UNIT MUST BE
secured to the right front corner post of CAPABLE OF SUPPORTING THE EN-
the unit with one screw. Remove this TIRE WEIGHT OF THE UNIT.
screw to release the strap. Remove
the wooden top and plastic strap. Re- LIFTING CHAINS (CABLES OR SLINGS)
place the screw in the right front corner MAY NOT BE THE SAME LENGTH. AD-
post. JUST AS NECESSARY FOR EVEN LEVEL
LIFT.
2. Remove protective covering from
around the unit. 3. Rig the unit as shown in Figure 3. At-
tach adequate strength lifting slings to
all four lifting brackets in the unit base
rail. Do not use cables, chains, or
slings except as shown.

4. Install a lifting bar, as shown in Figure


3, to protect the unit and to facilitate a
uniform lift. The minimum distance be-
tween the lifting hook and the top of
the unit should be 7 feet (21m).

5. Test-lift the unit to ensure it is properly


rigged and balanced, make any nec-
essary rigging adjustments.

6. Lift the unit enough to allow the re-


moval of two Fork Lift brackets and
hardware. Remove the two Fork Lift
brackets, two metal runners and three
wooden boards as shown.

7. Downflow units; align the base rail of


the unit with the curb rail while lowering
the unit onto the curb. Make sure that
the gasket on the curb is not damaged
while positioning the unit.

16 T_C-IOM-2A
Installation

General Unit Requirements Factory Installed Economizer

The checklist listed below is a summary [ ] Ensure the economizer has been
of the steps required to successfully in- pulled out into the operating position.
stall a commercial unit. This checklist is in- Refer to the economizer installers
tended to acquaint the installing person- guide for proper position and setup.
nel with what is required in the installation
process. It does not replace the detailed [ ] Install all access panels.
instructions called out in the applicable
sections of this manual. Temperature Limit Switch Usage for
Electric Heat Units
[ ] Check the unit for shipping damage
and material shortage; file a freight Units are factory shipped in the
claim and notify appropriate sales rep- downflow discharge configuration but can
resentative. be field converted to a horizontal dis-
charge configuration. Some, but not all
[ ] Verify correct model, options and volt- units require a different TC0-A limit
age from nameplate. switch, if horizontal discharge configuration
is used.
[ ] Verify that the installation location of the
unit will provide the required clearance Note:
for proper operation. The following units require a limit switch
change out for horizontal discharge.
[ ] Assemble and install the roof curb (if Refer to the Horizontal Discharge
applicable). Refer to the latest edition Conversion, Step 5 for the following
of the curb installers guide that ships model / heater combination.
with each curb kit.
Unit Electric Heater
[ ] Fabricate and install ductwork; secure Model Number Model Number
ductwork to curb. TSC072AD, 090AD BAYHTRS427A, 436A
TSC120AD BAYHTRT454A
[ ] Rigging the unit.

[ ] Set the unit onto the curb; check for


levelness.

[ ] Ensure unit-to-curb seal is tight and


without buckles or cracks.

[ ] Install and connect a condensate drain


line to the evaporator drain connection.

T_C-IOM-2A 17
Installation

Horizontal Discharge Conversion 4. Slide duct covers into duct openings until endward edge of
TSC060 the duct cover engages with the 2 retaining clips on the duct
flanges. Secure the outward edge of the each duct cover
If a unit is to be converted to Horizontal discharge, the follow- with 2 screws.
ing conversion must be performed:

1. Remove the return and supply duct covers.

2. Apply gasket to the supply duct cover as shown.

3. Position duct covers as shown below. Rotate supply duct


cover 90 degrees to allow it to be slid into supply opening.

Note:
Certain unit/electric heater combinations require a limit switch
change out for horizontal airflow applications. Refer to the
following instructions to determine if this process is required
for the unit undergoing installation.
Note: If unit is equipped with Discharge Air Sensing
5. After completing installation of the duct covers for horizontal
option refer to the following figure for proper tube
discharge,proceed to TCO-A instructions.
positioning based on unit tonnage.

18 T_C-IOM-2A
Installation

Horizontal Discharge Conversion 4. Slide return duct cover ( insulation side up ) into supply
TSC072-120 openings until endward edge of the duct cover engages with
the 2 retaining clips on the duct flanges. Secure the outward
If a unit is to be converted to Horizontal discharge, the follow- edge of the each duct cover with 2 screws.
ing conversion must be performed:

1. Remove the return and supply duct covers. Note:


Certain unit/electric heater combinations require a limit switch
2. Apply gasket to the return duct cover as shown below. change out for horizontal airflow applications. Refer to the
following instructions to determine if this process is required
for the unit undergoing installation.

5. After completing installation of the duct covers for horizon

5. After completing installation of the duct covers for horizontal


discharge, proceed to TCO-A instructions.

3. Position duct covers as shown below. The supply duct cover


is installed ( insulation side down ) over the downflow return
opening by engaging one side of the panel under a retaining
angle and securing the other side with 3 screws.

T_C-IOM-2A 19
Installation

TCO-A Instructions:
If the unit being installed is listed in the following table and is equipped with the corre-
sponding model number of factory installed electric heater package in the table, the
limit control TCO-A must be replaced with the extra limit control shipped in the heater
compartment. Replace TCO-A following the instructions in steps 1through 4 below.
If the unit being installed does not have a installed electric heater package or is
equipped with a installed electric heater model that does not correspond to any in this
table, skip steps1 through 4 and go on to next step in the installation process.

Unit Electric Heater


Model Number Model Number
TSC072AD, 090AD BAYHTRS427A, 436A
TSC120AD BAYHTRT454A

1. Remove the heater section access panel and open the electric heater dead front
panel.

2. TCO-A is the limit control located in the central part of the heater mounting plate
and that is located on the bottom of the two heater element assemblies. To re-
place this device, first remove the two wires connected to the terminals. Next, re-
move the two screws which secure it to the heater element mounting plate. Once
TCO-A has been removed form the heater element mounting plate, discard this
device.

3. Obtain the replacement TCO-A which is secured by a wire tie near the electric
heater terminal block in the heater compartment . Attach it to the heater element
mounting plate with the two screws that were removed in step 8 above. Connect
the two wires that were un-hooked in step 8 to the terminals on the new TCO-A.
Refer to the heater package wiring diagram to assure that the wiring is connected
properly.

4. Close the electric heater dead front panel and replace heat section access panel.

20 T_C-IOM-2A
Installation

Main Electrical Power Requirements To convert drain condensate out the 8. Replace the front support panel by
front of unit: aligning the panel with tabs in the race-
[ ] Verify that the power supply complies 1. Remove evaporator access panel way. Align the plugged condensate
with the unit nameplate specifications. and supply air access panels. drain pan coupling in the grommeted
hole as the panel is put in place.
[ ] Inspect all control panel components; 2. Remove the support panel that the
tighten any loose connections. condensate drain pan exits through. 9. Replace evaporator access panel
and supply air access panels.
[ ] Connect properly sized and protected 3. Slide the condensate drain pan out of
power supply wiring to a field-sup- the unit and rotate 180°. A condensate trap must be installed at
plied/installed disconnect switch and to the unit due to the drain connection being
the main power terminal block (HTB1) 4. Slide the condensate drain pan back on the “negative pressure” side of the
in the unit control panel. into the unit, align the drain with the fan. Install the P-Trap using the guidelines
grommeted opening in the rear sup- in Figure 5.
[ ] Install proper grounding wires to an port panel and push until the coupling
earth ground. is seated in the grommet. A condensate drain line must be con-
nected to the P-Trap. Pitch the drain lines
Note: 5. Replace the front support panel by at least 1/2 inch (13 mm) for every 10
All field-installed wiring must comply with aligning the panel with tabs in the race- feet (3.0 m) of horizontal run to assure
applicable state and local codes. way. Align the condensate drain pan proper condensate flow. Do not allow
support in the grommeted hole as the the horizontal run to sag causing a pos-
Electric Heat Requirements panel is put in place. sible double-trap condition which could
result in condensate backup due to “air
[ ] Verify that the power supply complies 6. Replace evaporator access panel lock”.
with the electric heater specifications and supply air access panels.
on the unit and heater nameplate. Figure 5
To convert drain condensate through Condensate Trap Installation
[ ] Inspect the heater junction box and the base of unit:
control panel; tighten any loose con- 1. Remove evaporator access panel
nections. and supply air access panels.

[ ] Check electric heat circuits for continu- 2. Remove the support panel that the
ity. condensate drain pan exits through.

Low Voltage Wiring (AC & DC) Re- 3. Slide the condensate drain pan out of
quirements the unit.

[ ] Install the zone thermostat, with or with- 4. Place on a level surface in the position
out switching subbase. it was removed from the unit.

[ ] Connect properly sized control wiring 5. Remove the plug knockout in the bot-
to the proper termination points be- tom of the drainpan to convert it to
tween the zone thermostat and the through the base drainage.
unit control panel.
6. Plug the original condensate drain
Condensate Drain Configuration opening with a field supplied 3/4"
NPT plug.
An evaporator condensate drain connec-
tion is provided on each unit. Refer to 7. Slide the condensate drain pan back
Figure 4 for the appropriate drain loca- into the unit, align the drain support
tion. with the grommeted opening in the
rear support panel and push until the
The condensate drain pan is factory in- support is seated in the grommet.
stalled to drain condensate to the back
side of the unit. See Figure 5. It can be
converted to drain condensate out the
front side of the unit or through the base.

T_C-IOM-2A 21
Installation

Filter Installation Main Unit Power Wiring

TSC060AD unit ships with one inch (25 1. The unit is not equipped with an op-
mm) filters. The quantity of filters is deter- tional factory installed nonfused dis-
HAZARDOUS VOLTAGE
mined by unit size. Access to the filters is connect switch or circuit breaker.A field
obtained by removing the indoor fan ac- supplied disconnect switch must be DISCONNECT ALL ELECTRIC
cess panel. To modify the unit’s filter rack installed at or near the unit in accor- POWER INCLUDING REMOTE
to accept two inch (50 mm) filters, re- dance with State and Local codes. DISCONNECTS BEFORE SERVICING.
move the L-shaped angle attachment
screws and rotate the angles 90 de- 2. Location of the applicable electrical Failure to disconnect power before
grees. service entrance is illustrated in Figure servicing can cause severe personal injury
2. Complete the unit’s power wiring or death.
Reinstall the screws and insert new filters. connections onto either; the main ter-
Refer to the unit Service Facts (shipped minal wire connectors inside the unit The transformer is located in the control
with each unit) for filter requirements. control panel, the field supplied panel. The circuit breaker is located on
nonfused disconnect switch (UCD) or the left side of the transformer and can be
Note: circuit breaker (UCB). Refer to the reset by pressing in on the black reset
Do not operate the unit without filters. customer connection diagram that is button.
shipped with the unit for specific termi-
Field Installed Power Wiring nation points. Controls using 24 VAC
An overall dimensional layout for the field
installed wiring entrance into the unit is il- 3. Provide proper grounding for the unit Before installing any connecting wiring,
lustrated in Figure 2. To insure that the in accordance with local and national refer to Figure 2 for the electrical access
unit’s supply power wiring is properly codes. locations provided on the unit and
sized and installed, follow the guidelines Table 2 for AC conductor sizing guide-
outlined below. Field Installed Control Wiring lines, and;

Note: An overall layout of the various control a. Use copper conductors unless other-
All field installed wiring must conform to options available with the required num- wise specified.
State and Local codes. ber of conductors for each control device
is illustrated in Figure 6. b. Ensure that the AC control wiring be-
Verify that the power supply available is tween the controls and the unit’s termi-
compatible with the unit’s nameplate rat- Note: nation point does not exceed three
ings. The available supply power must All field wiring must conform to State and (3) ohms/conductor for the length of
be within 10% of the rated voltage Local codes. the run.
stamped on the nameplate. Use only
copper conductors to connect the power Control Power Transformer Note:
supply to the unit. Resistance in excess of 3 ohms per
The 24 volt control power transformers conductor may cause component failure
are to be used only with the accessories due to insufficient AC voltage supply.
called out in this manual. Transformers
USE COPPER CONDUCTORS ONLY! rated greater than 50 VA are equipped c. Be sure to check all loads and conduc-
with internal circuit breakers. If a circuit tors for grounds, shorts, and mis-wir-
UNIT TERMINALS ARE NOT DE-
breaker trips, turn “Off” all power to the ing.
SIGNED TO ACCEPT OTHER TYPES
unit before attempting to reset it.
OF CONDUCTORS. d. Do not run the AC low voltage wiring
in the same conduit with the high volt-
Failure to do so may cause damage age power wiring.
to the equipment.
e. Route low voltage wiring per illustra-
tions on page 24.

22 T_C-IOM-2A
Installation

Table 2A - DC Conductors
24V AC Conductors with Reliatel Table 3
Distance from Unit Recommended e Sensor Module wiring
to Control Wire Size Distance from Recommended
000 - 460 feet 18 gauge Unit to Control Wire Size
000 - 140 m .75 mm 2 0 - 150 feet 22 gauge
461 - 732 feet 16 gauge 0 - 45.7 m .33 mm 2
141 - 223 m 1.3 mm 2 151 - 240 feet 20 gauge
733 - 1000 feet 14 gauge 46 - 73.1 m .50 mm 2
224 - 305 m 2.0 mm 2 241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm 2
Controls using DC Analog Input/ 386 - 610 feet 16 gauge
Outputs 117.7 - 185.9 m 1.3 mm 2
(Standard Low Voltage 611 - 970 feet 14 gauge
Multiconductor Wire) 186.2 - 295.7 m 2.0 mm 2
Before installing any connecting wiring
between the unit and components utiliz-
ing a DC analog input\output signal, refer
to Figure 2 for the electrical access loca-
tions provided on the unit.

a. Table 3 lists the conductor sizing


guidelines that must be followed when
interconnecting the DC binary output
devices and the system components
utilizing a DC analog input\output sig-
nal to the unit.

Note:
Resistance in excess of 2.5 ohms per
conductor can cause deviations in the
accuracy of the controls.

b. Ensure that the wiring between con-


trols and the unit’s termination point
does not exceed two and a half (2.5)
ohms/conductor for the length of the
run.

c. Do not run the electrical wires transport-


ing DC signals in or around conduit
housing high voltage wires.

d. Route low voltage wiring per illustra-


tions on page 22.

T_C-IOM-2A 23
Installation

Reliatel Conventional Thermostat Field Wiring Reliatel Refrigeration Module


Diagrams

Reliatel Control
Customer Low Voltage Routing-

24 T_C-IOM-2A
Installation

Figure 6
Typical Field Wiring Diagrams for Optional Controls (ReliaTel™ only)

T_C-IOM-2A 25
Installation

Space Temperature Averaging


ReliaTel™

Space temperature averaging is accomplished by wiring a


number of remote sensors in a series/parallel circuit.

Using the BAYSENS016* or BAYSENS017*, at least four


sensors are required to accomplish space temperature averag-
ing. Example #1 illustrates two series circuits with two sensors in
each circiut wired in parallel. The square of any number of re-
mote sensors required. Example #2 illustrates three sensors
squared in a series/parallel circuit. Using BAYSENS032*, two
sensors are required to accomplish space temperature averag-
ing. Example #3 illustrates the circuit required for this senor.
Table 4 lists the temperature versus resistance coefficient for all
sensing.

26 T_C-IOM-2A
Installation

Table 4 [ ] Verify that the correct size and number of filters are in place.
Temperature vs Resistance
Temperature
[ ] Inspect the interior of the unit for tools and debris and install all
Nominal Resistance
Degrees F° Degrees C°
panels in preparation for starting the unit.
-20° -28.9° 170.1 K - Ohms
-15° -26.1° 143.5 K - Ohms Voltage Imbalance
-10° -23.3° 121.4 K - Ohms
-5° -20.6° 103.0 K - Ohms Three phase electrical power to the unit must meet stringent re-
0° -17.8° 87.56 K - Ohms quirements for the unit to operate properly. Measure each leg
5° -15.0° 74.65 K - Ohms (phase-to-phase) of the power supply. Each reading must fall
10° -12.2° 63.80 K - Ohms within the utilization range stamped on the unit nameplate. If any
15° -9.4° 54.66 K - Ohms
20° -6.7° 46.94 K - Ohms
of the readings do not fall within the proper tolerances, notify the
25° -3.8° 40.40 K - Ohms power company to correct this situation before operating the
30° -1.1° 34.85 K - Ohms unit.
35° 1.7° 30.18 K - Ohms
40° 4.4° 26.22 K - Ohms Excessive three phase voltage imbalance between phases
45° 7.2° 22.85 K - Ohms will cause motors to overheat and eventually fail. The maximum
50° 10.0° 19.96 K - Ohms allowable voltage imbalance is 2%. Measure and record the
55° 12.8° 17.47 K - Ohms voltage between phases 1, 2, and 3 and calculate the amount
60° 15.6° 15.33 K - Ohms of imbalance as follows:
65° 18.3° 13.49 K - Ohms
70° 21.1° 11.89 K - Ohms
75° 23.9° 10.50 K - Ohms % Voltage Imbalance = 100 X AV - VD where;
80° 26.7° 9.297 K - Ohms AV
85° 29.4° 8.247 K - Ohms
90° 32.2° 7.330 K - Ohms AV (Average Voltage) = Volt 1 + Volt 2 + Volt 3
95° 35.0° 6.528 K - Ohms 3
100° 37.8° 5.824 K - Ohms
Use the checklist provided below in conjunction with the “Gen- V1, V2, V3 = Line Voltage Readings
eral Unit Requirements” checklist to ensure that the unit is prop- VD = Line Voltage reading that deviates the farthest from
erly installed and ready for operation. the average voltage.

Example: If the voltage readings of the supply power


measured 403, 402, and 389, the average volts would be:
HAZARDOUS VOLTAGE! 403 + 402 + 389 = 398 Avg.
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE 3
DISCONNECTS BEFORE SERVICING.
VD (reading farthest from average) = 389
Failure to disconnect power before servicing can cause
The percentage of Imbalance equals:
severe personal injury or death.
100 X 398 - 389 = 2.2%
[ ] Check all electrical connections for tightness and “point of ter-
398
mination” accuracy.
The 2.2% imbalance in this example exceeds the maximum al-
lowable imbalance of 2.0%. This much imbalance between
[ ] Verify that the condenser airflow will be unobstructed.
phases can equal as much as a 20% current imbalance with a
resulting increase in motor winding temperatures that will de-
[ ] Verify that the condenser fan and indoor blower turn freely
crease motor life. If the voltage imbalance is over 2%, notify the
without rubbing and are properly tightened on the shafts.
proper agencies to correct the voltage problem before operat-
ing this equipment.
[ ] Check the supply fan belts for proper tension and the fan
bearings for sufficient lubrication. If the belts require adjust-
ment, or if the bearings need lubricating, refer to the mainte-
nance section of this manual for instructions.

[ ] Verify that a condensate trap is installed and the piping is


properly sized and pitched.

T_C-IOM-2A 27
Installation

Electrical Phasing
(Three Phase Motors)

The compressor motor(s) and the supply fan motor are inter-
nally connected for the proper rotation when the incoming
power supply is phased as A, B, C.

Proper electrical supply phasing can be quickly determined and


corrected before starting the unit by using an instrument such as
an Associated Research Model 45 Phase Sequence Indicator
and following the steps below:

[ ] Turn the field supplied disconnect switch that provides power


to the main power terminal block or to the “Line” side of the
optional factory mounted disconnect switch to the “Off” posi-
tion.

[ ] Connect the phase sequence indicator leads to the terminal


block or to the “Line” side of the optional factory mounted
disconnect switch as follows;

Black (phase A) to L1
Red (phase B) to L2
Yellow (phase C) to L3

[ ] Close the field supplied main power disconnect switch or cir-


cuit protector switch that provides the supply power to the
unit.

HAZARDOUS VOLTAGE!
HIGH VOLTAGE IS PRESENT AT THE TERMINAL BLOCK
OR UNIT MOUNTED DISCONNECT SWITCH.

To prevent injury or death from electrocution, it is the responsibil-


ity of the technician to recognize this hazard and use extreme
care when performing service procedures with the electrical
power energized.

[ ] Observe the ABC and CBA phase indicator lights on the


face of the sequencer. The ABC indicator light will glow if the
phase is ABC. If the CBA indicator light glows, open the
disconnect switch or circuit protection switch and reverse any
two power wires.

[ ] Restore the main electrical power and recheck the phasing. If


the phasing is correct, open the disconnect switch or circuit
protection switch and remove the phase sequence indicator.

28 T_C-IOM-2A
Pre - Start

dividually by temporarily shorting across


2. Resistance Test Mode - This method
the “Test” terminals for two to three sec-
can be used for start-up providing a
onds. The Liteport LED located on the
HAZARDOUS VOLTAGE! decade box for variable resistance
RTRM module will blink when the test
HIGH VOLTAGE IS PRESENT AT THE outputs is available. This method ini-
mode has been initiated. The unit can be
TERMINAL BLOCK OR UNIT tiates the different components of
left in any “Test” step for up to one hour
MOUNTED DISCONNECT SWITCH. the unit, one at a time, when a spe-
before it will automatically terminate, or it
cific resistance value is placed across
can be terminated by opening the main
To prevent injury or death from electrocu- the two test terminals. The unit will re-
power disconnect switch. Once the test
tion, it is the responsibility of the technician main in the specific test mode for ap-
mode has been terminated, the Liteport
to recognize this hazard and use extreme proximately one hour even though
LED will glow continuously and the unit
the resistance is left on the test termi-
care when performing service procedures will revert to the “System” control.
nals.
with the electrical power energized.
Test Modes 3. Auto Test Mode - This method is not
ReliaTel Controls recommended for start-up due to the
Upon power initialization, the RTRM per- There are three methods in which the short timing between individual com-
forms self-diagnostic checks to insure that “Test” mode can be cycled at LTB-Test ponent steps. This method initiates
all internal controls are functional. It also 1 and LTB-Test 2. the different components of the unit,
checks the configuration parameters one at a time, when a jumper is in-
against the components connected to the 1. Step Test Mode - This method ini- stalled across the test terminals. The
system. The Liteport LED located on the tiates the different components of the unit will start the first test step and
RTRM module is turned “On” within one unit, one at a time, by temporarily change to the next step every 30
second of power-up if internal operation shorting across the two test terminals seconds. At the end of the test
is okay. for two to three seconds. mode, control of the unit will auto-
matically revert to the applied "Sys-
Use one of the following “Test” proce- For the initial start-up of the unit, this tem" control method.
dure to bypass some time delays and to method allows the technician to cycle a
start the unit at the control panel. Each component “On” and have up to one For unit test steps, test modes, and
step of unit operation can be activated in- hour to complete the check. step resistance values to cycle the vari-
ous components, refer to Table 5.

Table 5
Service Test Guide for Component Operation
TEST MODE Fan Econ Comp Comp Heat Heat Ohms
STEP (Note 2) 1 2 1 2
Minimum
Fan On Position Off Off Off Off
1 Setpoint 2.2K
0%
Minimum
Ventilation On Selectable Off Off Off Off
2 Economizer
Test Open On Open Off Off Off Off 3.3K
3 Cool Minimum (Note 1)
Stage 1 On Position On Off Off Off 4.7K
4 Cool Minimum (Note 1) (Note 1)
(Note 3) Stage 2 On Position On On Off Off 6.8K
5
Reheat On Minimum On On Off Off 33K
(Note 3)
6 Heat
(Note 3) Stage 1 On Minimum Off Off On Off 10K
7 Heat
(Note 3) Stage 2 On Minimum Off Off On On 15K

Notes:
1 - The condenser fans will operate any time a compressor is "On"
providing the outdoor air temperatures are within the operating values.

T_C-IOM-2A 29
Pre - Start

Verifying Proper Air Flow


(Units with Belt Drive Indoor Fan) a. Relieve supply and/or return duct static.

Much of the systems performance and reliability is closely as- b. Change indoor fan speed and repeat steps 1.a and
sociated with, and dependent upon having the proper airflow 1.b.
supplied both to the space that is being conditioned and across
the evaporator coil. To Increase Fan RPM; Loosen the pulley adjustment set
screw and close the sheave by moving the two halves
The indoor fan speed is changed by opening or closing the ad- closer together.
justable motor sheave.
To Decrease Fan RPM; Loosen the pulley adjustment set
Before starting the SERVICE TEST, set the minimum position screw and open the sheave by moving the two halves far-
setpoint for the economizer to 0 percent using the setpoint po- ther apart..
tentiometer located on the Economizer Control (ECA), if appli-
cable. 4. To stop the SERVICE TEST, turn the main power discon-
nect switch to the “Off” position or proceed to the next com-
ReliaTel Control ponent start-up procedure.
Using the Service Test Guide in Table 6, momentarily jump
across the Test 1 & Test 2 terminals on LTB1 one time to start
the Minimum Ventilation Test.

Once the supply fan has started, check for proper rotation. The
direction of rotation is indicated by an arrow on the fan housing.

Use the following procedure to determine the proper adjust-


ment of the evaporator fan for a specific application.

1. With the fan operating properly, determine the total system


airflow CFM (m3/h) by;

a. Measuring the actual RPM,

b. Measure the amperage at the supply fan contactor and


compare it with the full load amp (FLA) rating stamped
on the motor nameplate.

c. Calculate the theoretical BHP (KW)

Actual Motor Amps X Motor HP (KW)


Motor Nameplate Amps

d. Using the fan performance tables in the unit Service


Facts, plot the actual RPM (step 1) and the theoretical
BHP (KW) (step 2c) to obtain the operating Air Flow.

2. If the required Air Flow is too low, (external static pressure is


high causing motor HP (KW) output to be below table
value), perform one or both of the following.

a. Relieve supply and/or return duct static.

b. Change indoor fan speed and repeat steps 1.a and


1.b.

3. If the required CFM is too high, (external static pressure is


low causing motor HP output to be above table value), per-
form one or both of the following:

30 T_C-IOM-2A
Start Up

Economizer Start-Up b. If the electrical phasing is correct, be- Heating Start-Up


ReliaTel Control fore condemning a compressor, inter-
Using the Service Test Guide in Table 5, change any two leads (at the com- 1. Clamp an amp meter around one of
momentarily jump across the Test 1 & pressor Terminal block) to check the 1st stage heater power wires at the
Test 2 terminals on LTB1 one time to internal phasing. Refer to the illustra- heater contactor.
start the Minimum Ventilation Test. tion in Figure 5-1 for the compressor
terminal/phase identification. If the 2. ReliaTel Control
compressor runs backward for an ex- Using the Service Test Guide in Table 5,
tended period (15 to 30 minutes), the continue the SERVICE TEST start-up
ROTATING PARTS! motor winding can overheat and cause procedure for each compressor circuit.
UNIT STARTS AUTOMATICALLY the motor winding thermostat to open. Momentarily jump across the Test 1 &
Test 2 terminals on LTB one additional
Verify that the dampers stroked to the c. Check the compressor oil levels. The time if continuing from previous compo-
minimum position. oil level in each compressor sight nent start-up or until the desired start-up
glass should be 1/2 to 3/4 full when component Test is started.
ReliaTel Control they are “Off”.
Momentarily jump across the Test 1 & 3. Verify that the heater stage is operating
Test 2 terminals on LTB one addi- properly.
tional time if continuing from previous Note:
component start-up or until the de- The scroll compressor uses Trane OIL- 4. Clamp an amp meter around one of
sired start-up component Test is 42 without substitution. The appropriate 2nd stage heater power wires at the
started. oil charge for a 9 and 10 Ton scroll heater contactor (if applicable).
compressor is 8 pints. For a 14 and 15
Verify that the dampers stroked to the Ton scroll compressor, use 14 pints ( 6.6 5. ReliaTel Control
full open position. liters). Using the Service Test Guide in Table
5, continue the SERVICE TEST start-
To stop the SERVICE TEST, turn the 2. After the compressor and condenser up procedure for each compressor cir-
main power disconnect switch to the fan have started and operated for ap- cuit. Momentarily jump across the Test
“Off” position or proceed to the next proximately 30 minutes, observe the 1 & Test 2 terminals on LTB one addi-
component start-up procedure. Re- operating pressures. Compare the tional time if continuing from previous
move electro mechanical test mode operating pressures to the operating component start-up or until the de-
connections (if applicable). pressure curve in the Service Facts. sired start-up component Test is
started.
Compressor Start-Up 3. Check system superheat. Follow the
instruction listed on the superheat 6. Verify that the heater stage is operat-
1. Attach a set of service gauges onto charging curve in the Service Facts. ing properly
the suction and discharge gauge ports
for each circuit. Refer to the refrigerant Superheat should be within ±5 F (-15C) 7. To stop the SERVICE TEST, turn the
circuit illustration in the Service Facts. of the superheat chart value. main power disconnect switch to the
“Off” position or proceed to the next
ReliaTel Control 4. Repeat steps 1 through 4 for each re- component start-up procedure. Re-
Using the Service Test Guide in Table 5, frigerant circuit. move electro mechanical test mode
continue the SERVICE TEST start-up connections (if applicable).
procedure for each compressor circuit. 5. To stop the SERVICE TEST, turn the
main power disconnect switch to the
Momentarily jump across the Test 1 & “Off” position or proceed to the next
Test 2 terminals on LTB1 one additional component start-up procedure. Re-
time if continuing from previous compo- move electro mechanical test mode
nent start-up or until the desired start-up connections (if applicable).
component Test is started.

Scroll Compressors
a. Once each compressor has started,
verify that the rotation is correct. If a
scroll compressor is rotating back-
wards, it will not pump and a loud rat-
tling sound can be observed.

T_C-IOM-2A 31
Final System Set Up

Final System Setup


After completing all of the pre-start and
start-up procedures outlined in the previ-
ous sections (i.e., operating the unit in
each of its Modes through all available
stages of cooling & heating), perform
these final checks before leaving the unit:

[ ] Program the Night Setback (NSB)


panel (if applicable) for proper unoc-
cupied operation. Refer to the pro-
gramming instructions for the specific
panel.

[ ] Verify that the Remote panel “Sys-


tem” selection switch, “Fan” selection
switch, and “Zone Temperature” set-
tings for automatic operation are cor-
rect.

[ ] Inspect the unit for misplaced tools,


hardware, and debris.

[ ] Verify that all exterior panels including


the control panel doors and condenser
grilles are secured in place.

[ ] Close the main disconnect switch or cir-


cuit protector switch that provides the
supply power to the unit’s terminal
block or the unit mounted disconnect
switch.

32 T_C-IOM-2A
Maintenance

4. Place the large end of the gauge at the


center of the belt span; then depress
ROTATING PARTS!
the gauge plunger until the large O-
UNIT STARTS AUTOMATICALLY
ring is even with the top of the next
belt or even with a straightedge
Make sure all personnel are standing clear placed across the fan and motor
of the unit before proceeding. The sheaves. Refer to Figure 9.
system components will start when the
power is applied. 5. Remove the belt tension gauge. The
small O-ring now indicates a number
Fan Belt Adjustment other than zero on the plunger’s force
scale. This number represents the
The fan belts must be inspected periodi- force in pounds or newtons required
cally to assure proper unit operation. to give the needed deflection.

Replacement is necessary if the belts 6. Compare the “force” scale reading


appear frayed or worn. Units with dual (Step 5) with the appropriate “force”
belts require a matched set of belts to value listed in Table 7. If the “force”
ensure equal belt length. reading is outside the range, readjust
the belt tension.
When removing or installing the new
belts, do not stretch them over the
sheaves. Loosen the belts using the belt Note:
tension adjustment bolts on the motor Actual belt deflection “force” must not
mounting base. exceed the maximum “force” value
shown in Table 7.
Once the new belts are installed, using a
Browning or Gates tension gauge (or 7. Recheck the belt tension at least twice
equivalent) illustrated in Figure 7; adjust during the first 2 to 3 days of opera-
the belt tension as follows; tion. Belt tension may decrease until
the new belts are “run in”.
1. To determine the appropriate belt de-
flection;

a. Measure the center-to-center shaft


distance in inches or millimeters
between the fan and motor
sheaves.

b. Divide the distance measured in


Step 1a by 64 inches or 152
millimeters; the resulting value
represents the amount of belt
deflection that corresponds to the
proper belt tension.

2. Set the large O-ring on the belt ten-


sion gauge at the deflection value de-
termined in Step 1b.

3. Set the small O-ring at zero on the


force scale of the gauge plunger.

T_C-IOM-2A 33
Maintenance

Figure 7 Table 6
Belt Tension Gauge Belt Tension Measurement and Deflection Ranges

Deflection Force (Lbs.)


Belts Super Steel Cable
Cross Small P.D Gripbelts Gripnotch Gripbelts
Section Range (in) (in) (in)
(in) Min. Max. Min. Max. Min. Max
3.0 - 3.6 3 4 1/2 3 7/8 5 1/2 3 1/4 4
A 3.8 - 4.8 3 1/2 5 4 1/2 6 1/4 3 3/4 4 3/4
5.0 - 7.0 4 5 1/2 5 6 7/8 4 1/4 5 1/4
3.4 - 4.2 4 5 1/2 5 3/4 8 4 1/2 5 1/2
B 4.4 - 5.6 5 1/8 7 1/8 6 1/2 9 1/8 5 3/4 7 1/4
5.8 - 8.8 6 3/8 8 3/4 7 3/8 10 1/8 7 8 3/4

Deflection Force (N.)


Belts Super Steel Cable
Cross Small P.D Gripbelts Gripnotch Gripbelts
Section Range (mm) (mm) (mm)
(mm) Min. Max. Min. Max. Min. Max
13.3 - 16.0 13.3 20.0 17.2 24.5 14.5 17.8
A 16.9 - 21.4 15.6 22.2 20.0 27.8 16.7 21.1
22.0 - 31.1 17.8 24.5 22.2 30.6 18.9 23.4
15.1 - 18.7 17.8 24.5 25.6 35.6 20.0 24.5
B 19.6 - 24.9 22.8 31.7 28.9 40.6 25.6 32.3
25.8 - 39.1 28.4 38.9 32.8 45.0 31.1 38.9

34 T_C-IOM-2A
Maintenance

Monthly Maintenance [ ] Verify that all wire terminal connections Coil Cleaning
are tight.
Before completing the following checks, Regular coil maintenance, including annual
turn the unit OFF and lock the main power [ ] Remove any corrosion present on the cleaning, enhances the unit’s operating
disconnect switch open. exterior surfaces of the unit and repaint efficiency by minimizing: compressor
these areas. head pressure and amperage draw;
evaporator water carryover; fan brake
[ ] Generally inspect the unit for unusual horsepower, due to increase static pres-
HAZARDOUS VOLTAGE!
conditions (e.g., loose access panels, sure losses; airflow reduction.
DISCONNECT ALL ELECTRIC leaking piping connections, etc.)
POWER INCLUDING REMOTE At least once each year, or more often if
DISCONNECTS BEFORE SERVICING. [ ] Make sure that all retaining screws are the unit is located in a “dirty” environment,
reinstalled in the unit access panels clean the evaporator and condenser coils
Failure to disconnect power before once these checks are complete. using the instructions outlined below. Be
servicing can cause severe personal injury sure to follow these instructions as
or death. [ ] With the unit running, check and record closely as possible to avoid damaging
the: ambient temperature; compres- the coils.
Filters sor suction and discharge pressures
(each circuit); superheat (each circuit); To clean refrigerant coils, use a soft brush
[ ] Inspect the return air filters. Clean or re- and a sprayer (either a garden pump-up
place them if necessary. Refer to the Record this data on an “operator’s main- type or a high-pressure sprayer). A high-
unit Service Facts for filter information. tenance log” like the one shown in Table quality detergent is also required; sug-
7. If the operating pressures indicate a gested brands include “SPREX A.C.”,
Cooling Season refrigerant shortage, measure the system “OAKITE 161”, “OAKITE 166” and
superheat. For guidelines, refer to the “COILOX”. If the detergent selected is
[ ] Check the unit’s drain pans and con- “Compressor Start-Up” section. strongly alkaline (ph value exceeds 8.5),
densate piping to ensure that there add an inhibitor.
are no blockages.
Note: 1. Remove enough panels from the unit
[ ] Inspect the evaporator and condenser Do Not release refrigerant to the to gain access to the coil.
coils for dirt, bent fins, etc. If the coils atmosphere! If adding or removing
appear dirty, clean them according to refrigerant is required, the service 2. Protect all electrical devices such as
the instructions described in “Coil technician must comply with all federal, motors and controllers from any over
Cleaning” later in this section. state and local laws. spray.

[ ] Manually rotate the condenser fan(s) to Heating Season 3. Straighten any bent coil fins with a fin
ensure free movement and check mo- comb.
tor bearings for wear. Verify that all of [ ] Inspect the unit’s air filters. If neces-
the fan mounting hardware is tight. sary, clean or replace them. 4. Mix the detergent with water according
to the manufacturer’s instructions. If de-
[ ] Inspect the F/A-R/A damper hinges [ ] Check supply fan motor bearings; re- sired, heat the solution to 150o F
and pins to ensure that all moving pair or replace the motor as neces- (65.6o C) maximum to improve its
parts are securely mounted. Keep the sary. cleansing capability.
blades clean as necessary.
[ ] Inspect both the main unit control panel
[ ] Verify that all damper linkages move and heat section control box for loose
freely; lubricate with white grease, if electrical components and terminal
necessary. connections, as well as damaged wire
insulation. Make any necessary re-
[ ] Check supply fan motor bearings; re- pairs.
pair or replace the motor as neces-
sary. [ ] Verify that the electric heat system op-
erates properly.
[ ] Check the fan shaft bearings for wear.
Replace the bearings as necessary.
[ ] Check the supply fan belt. If the belt is
frayed or worn, replace it. Refer to the
“Fan Belt Adjustment” section for belt
replacement and adjustments.
T_C-IOM-2A 35
Maintenance

Final Process

For future reference, you may find it help-


CONTAINS REFRIGERANT! SYSTEM ful to record the unit data requested be-
CONTAINS OIL AND REFRIGERANT low in the blanks provided.
(1) Complete Unit Model Number:
Do not heat the detergent-and-water
solution above 150o F (65.6o C). Hot
liquids sprayed on the exterior of the coil
will raise the coil’s internal pressure and (2) Unit Serial Number:
may cause it to burst. Failure to follow
proper procedures can result in personal
illness or injury or severe equipment
damage.
(3) Wiring Diagram Numbers (from unit control pane
5. Pour the cleaning solution into the
sprayer. If a high-pressure sprayer is — schematic(s)
used:

a. do not allow sprayer pressure to


exceed 600 psi (41.4 bar).

b. the minimum nozzle spray angle


is 15 degrees.
— connection(s)
c. maintain a minimum clearance of 6"
(152.4 mm) between the sprayer
nozzle and the coil.

d. spray the solution perpendicular


(at 90 degrees) to the coil face.

6. Spray the leaving-airflow side of the


coil first; then spray the opposite side
of the coil. Allow the cleaning solution
to stand on the coil for five minutes.

7. Rinse both sides of the coil with cool,


clean water.

8. Inspect both sides of the coil; if it still


appears to be dirty, repeat Steps 6
and 7.

9. Reinstall all of the components and


panels removed in Step 1 and any
protective covers installed in step 2.

10. Restore the unit to it’s operational


status and check system operation.

36 T_C-IOM-2A
Maintenance

Table 7
Sample Maintenance Log
Refrigerant Circuit #1 Refrigerant Circuit #2
Current
Ambient Compr. Suct. Disch. Liquid Super- Sub- Compr. Suct. Disch. Liquid Super- Sub-
Temp. Oil Press. Press. Press. heat cool. Oil Press. Press. Press. heat cool.
Date F/C Level Psig/kPa Psig/kPa Psig/kPa F/C F/C Level Psig/kPa Psig/kPa Psig/kPa F/C F/C

- ok - ok
- low - low

- ok - ok
- low - low

- ok - ok
- low - low

- ok - ok
- low - low
Note: Check and record the data requested above each month during the cooling season with the unit running.

T_C-IOM-2A 37
Trouble Shooting

ReliaTel Control 5. If no failures are indicated, use one of LED 3 (Cool)


The RTRM has the ability to provide the the TEST mode procedures de- “On” when the cooling cycle is operating.
service personnel with some unit diag- scribed in the “Unit Start-Up” section “Off” when the cooling cycle terminates or
nostics and system status information. to start the unit. This procedure will al- the LED fails.
Before turning the main power discon- low you to check all of the RTRM out- “Flashing” indicates a cooling failure.
nect switch “Off”, follow the steps below puts, and all of the external controls LED 4 (Service)
to check the ReliaTel Refrigeration Mod- (relays, contactors, etc.) that the “On” indicates a clogged filter.
ule (RTRM). All diagnostics & system RTRM outputs energize, for each re- “Off” during normal operation.
status information stored in the RTRM will spective mode. Proceed to Step 6. “Flashing” indicates an evaporator fan fail-
be lost when the main power is turned 6. Step the system through all of the ure
“Off”. available modes, and verify operation
of all outputs, controls, and modes. If a Below is the complete listing of failure in-
problem in operation is noted in any dication causes.
mode, you may leave the system in
that mode for up to one hour while System Failure
HAZARDOUS VOLTAGE!
troubleshooting. Refer to the se- Check the voltage between terminals 6
HIGH VOLTAGE IS PRESENT AT THE
quence of operations for each mode, and 9 on J6, it should read approxi-
TERMINAL BLOCK OR UNIT to assist in verifying proper operation. mately 32 VDC. If no voltage is present,
MOUNTED DISCONNECT SWITCH. Make the necessary repairs and pro- a System failure has occurred. Refer to
ceed to Steps 7 and 8. Step 4 in the previous section for the
To prevent injury or death from electrocu- recommended troubleshooting proce-
tion, it is the responsibility of the technician 7. If no abnormal operating conditions dure.
to recognize this hazard and use extreme appear in the test mode, exit the test
care when performing service procedures mode by turning the power “Off” at Cooling Failure
with the electrical power energized. the main power disconnect switch. 1. Cooling and heating set point (slide
pot) on the zone sensor has failed.
1. Verify that the Liteport LED on the 8. Refer to the individual component test Refer to the “Zone Sensor Test Pro-
RTRM is burning continuously. If the procedures if other microelectronic cedure” section.
LED is lit, go to Step 3. components are suspect.
2. Zone temperature thermistor ZTEMP
2. If the LED is not lit, verify that 24 VAC System Status Checkout Procedure on ZTS failed. Refer to the “Zone
is presence between J1-1 and J1-2. Sensor Test Procedure” section.
If 24 VAC is present, proceed to “System Status” is checked by using
Step 3. If 24 VAC is not present, one of the following two methods: 3. CC1 or CC2 24 VAC control circuit
check the unit main power supply, has opened, check CC1 & CC2 coils,
check transformer (TNS1). Proceed to Method 1 and any of the controls below that ap-
Step 3 if necessary. ply to the unit (HPC1, HPC2).
If the Zone Sensor Module (ZSM) is
3. Utilizing “Method 1” or “Method 2” in equipped with a remote panel with LED 4. LPC1 has opened during the 3 minute
the “System Status Diagnostic” sec- status indication, you can check the unit minimum “on time” during 4 consecu-
tion, check the following: within the space. If the ZSM does not tive compressor starts, check LPC1 or
System status have LED’s, use Method 2. LPC2 by testing voltage between
Heating status BAYSENS010B, BAYSENS011B, the J1-8 & J3-2 terminals on the
Cooling status BAYSENS019A, BAYSENS020A, RTRM and ground. If 24 VAC is
If a System failure is indicated, pro- BAYSENS021A & BAYSENS023A all present, the LPC’s has not tripped. If
ceed to Step 4. If no failures are indi- have the remote panel indication feature. no voltage is present, LPC’s has
cated, proceed to Step 5. The LED descriptions are listed below. tripped.

4. If a System failure is indicated, recheck LED 1 (System) Service Failure


Steps 1 and 2. If the LED is not lit in “On” during normal operation. 1. If the supply fan proving switch has
Step 1, and 24 VAC is present in “Off” if a system failure occurs or the LED closed, the unit will not operate (when
Step 2, the RTRM has failed. Re- fails. connected to RTOM), check the fan
place the RTRM. “Flashing” indicates test mode. motor, belts, and proving switch.

LED 2 (Heat) 2. Clogged filter switch has closed, check


“On” when the heat cycle is operating. the filters.
“Off” when the heat cycle terminates or
the LED fails.
“Flashing” indicates a heating failure.
38 T_C-IOM-2A
Trouble Shooting

Simultaneous Heat and Cool Failure Note: The RTRM will ignore the closing of this
1. Emergency Stop is activated If the system is equipped with a Normally Open switch for 2 (±1) min-
programmable zone sensor, utes. This helps prevent nuisance SER-
Method 2 (BAYSENS019A, BAYSENS020A or VICE LED indications. The exception is
BAYSENS023A), the LED indicators will the LED will flash 40 seconds after the
The second method for determining sys- not function while the BAYSENS010A is fan is turned “On” if the Fan Proving
tem status is done by checking voltage connected. Switch is not made.
readings at the RTRM (J6). The system
indication descriptions and the approxi- Resetting Cooling and Heating Clogged Filter Switch
mate voltages are listed below. Lockouts This LED will remain lit the entire time that
the Normally Open switch is closed. The
System Failure Cooling Failures and Heating Lockouts LED will be turned off immediately after
Measure the voltage between terminals are reset in an identical manner. Method resetting the switch (to the Normally
J6-9 & J6-6. 1 explains resetting the system from the Open position), or any time that the IDM
Normal Operation = approximately 32 space; Method 2 explains resetting the is turned “Off”.
VDC system at the unit.
System Failure = less than 1 VDC, ap- If the switch remains closed, and the IDM
proximately 0.75 VDC is turned “On”, the SERVICE LED will
Note: be turned “On” again after the 2 (±1)
Test Mode = voltage alternates be- Before resetting Cooling Failures and
tween 32 VDC & 0.75 VDC minute ignore delay.
Heating Lockouts check the Failure
Status Diagnostics by the methods This LED being turned “On”, will have no
Heat Failure previously explained. Diagnostics will be
Measure the voltage between terminals other affect on unit operation. It is an indi-
lost when the power to the unit is cator only.
J6-7 & J6-6. disconnected.
Heat Operating = approximately 32
VDC Fan Failure Switch
Method 1 When the “Fan Failure” switch is wired to
Heat Off = less than 1 VDC, approxi-
mately 0.75 VDC the RTOM, the LED will remain flashing
To reset the system from the space, turn the entire time the fan proving switch is
Heating Failure = voltage alternates be- the “Mode” selection switch at the zone
tween 32 VDC & 0.75 VDC closed, indicating a fan failure, and it will
sensor to the “Off” position. After ap- shut the unit operations down.
proximately 30 seconds, turn the
Cool Failure “Mode” selection switch to the desired
Measure the voltage between terminals Zone Temperature Sensor (ZTS) Test
mode, i.e. Heat, Cool or Auto.
J6-8 & J6-6.
Cool Operating = approximately 32 Note:
Method 2
VDC These procedures are not for
Cool Off = less than 1 VDC, approxi- programmable or digital models and are
To reset the system at the unit, cycle the
mately 0.75 VDC conducted with the Zone Sensor Module
unit power by turning the disconnect
Cooling Failure = voltage alternates be- electrically removed from the system.
switch “Off” and then “On”.
tween 32 VDC & 0.75 VDC
Lockouts can be cleared through the Test 1
Service Failure building management system. Refer to Zone Temperature Thermistor
Measure the voltage between terminals the building management system instruc- (ZTEMP)
J6-10 & J6-6. tions for more information.
Clogged Filter = Approximately 32 This component is tested by measuring
VDC. Zone Temperature Sensor (ZTS) the resistance between terminals 1 and 2
Normal = Less than 1 VDC, approxi- Service Indicator on the Zone Temperature Sensor. Be-
mately 0.75 VDC Fan Failure = voltage low are some typical indoor tempera-
alternates between 32 VDC & 0.75 The ZSM SERVICE LED is a generic in- tures, and corresponding resistive val-
VDC. dicator, that will signal the closing of a ues.
Normally Open switch at any time, pro-
To use LED’s for quick status information viding the Indoor Motor (IDM) is operat-
at the unit, purchase a BAYSENS010B ing. This indicator is usually used to indi-
ZSM and connect wires with alligator cate a clogged filter, or an air side fan fail-
clamps to terminals 6 through 10. Con- ure.
nected each respective terminal wire (6
through 10) from the Zone Sensor to the
unit J6 terminals 6 through 10.

T_C-IOM-2A 39
Maintenance

Test 2 Method 2 5. After verifying proper unit operation,


Cooling Set Point (CSP) and Heating exit the test mode. Turn the fan on
Set Point (HSP) Testing the LED with an analog Ohmme- continuously at the ZSM, by pressing
Zone Nominal ZTEMP ter. Connect Ohmmeter across LED in the button with the fan symbol. If the
Temperature Resistance one direction, then reverse the leads for fan comes on and runs continuously,
the opposite direction. The LED should the ZSM is good. If you are not able
50 F° 10.0 C° 19.9 K-Ohms have at least 100 times more resistance to turn the fan on, the ZSM is defec-
55 F° 12.8 C° 17.47 K-Ohms in reverse direction, as compared with tive.
60 F° 15.6 C° 15.3 K-Ohms the forward direction. If high resistance in
65 F° 18.3 C° 13.49 K-Ohms both directions, LED is open. If low in ReliaTel Refrigeration Module
70 F° 21.1 C° 11.9 K-Ohms both directions, LED is shorted. (RTRM) Default Chart
75 F° 23.9 C° 10.50 K-Ohms
80 F° 26.7 C° 9.3 K-Ohms Method 3 If the RTCI loses input from the building
85 F° 29.4 C° 8.25 K-Ohms management system, the RTRM will
7.3 K-Ohms To test LED’s with ZSM connected to control in the default mode after approxi-
90 F° 32.2 C° unit, test voltages at LED terminals on mately 15 minutes. If the RTRM loses
ZSM. A measurement of 32 VDC, the Heating and Cooling setpoint input,
The resistance of these potentiometers
across an unlit LED, means the LED has the RTRM will control in the default mode
are measured between the following
failed. instantaneously. The temperature sens-
ZSM terminals. Refer to the chart above
ing thermistor in the Zone Sensor Mod-
for approximate resistances at the given
Note: ule is the only component required for
setpoints.
Measurements should be made from the “Default Mode” to operate.
Cool SP = Terminals 2 and 3 LED common (ZSM terminal 6 to
respective LED terminal). Refer to the Unit Operation without a Zone Sensor
Range = 100 to 900 Ohms approximate
Zone Sensor Module (ZSM) Terminal
Identification table at the beginning of this This procedure is for temporary opera-
Heat SP = Terminals 2 and 5
section. tion only. The economizer and condenser
Range = 100 to 900 Ohms approximate
fan cycling functions are disabled.
Test 3 Programmable & Digital Zone Sensor
Test 1. Open and Lock the unit disconnect
System Mode and Fan Selection
switch.
The combined resistance of the Mode Testing serial communication voltage
1. Verify 24 VAC is present between 2. Remove the Outside Air Sensor
selection switch and the Fan selection
terminals J6-14 & J6-11. (OAS) from the condenser section of
switch can be measured between termi-
unit.
nals 2 and 4 on the Zone Sensor. The
possible switch combinations are listed 2. Disconnect wires from J6-11 and J6-
12. Measure the voltage between J6- 3. Use two (2) wire nuts, to individually
below with their corresponding resistance
11 and J6-12, should be about 32 cap the wires.
values.
VDC.
4. Locate the RTRM (J6). Connect two
Test 4
3. Reconnect wires to terminals J6-11 (2) wires to terminals J6-1 and 2.
LED Indicator Test, (SYS ON, HEAT,
COOL & SERVICE) and J6-12. Measure voltage again
between J6-11 and J6-12, voltage 5. Connect the sensor (OAS) using two
should flash high and low every 0.5 wire nuts to the two (2) field supplied
Method 1
seconds. The voltage on the low end wires that were connected to terminals
will measure about 19 VDC, while the 1 and 2 on J6.
Testing the LED using a meter with diode
test function. Test both forward and re- voltage on the high end will measure
verse bias. Forward bias should mea- from approximately 24 to 38 VDC.
sure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias 4. Verify all modes of operation, by run-
will show an Over Load, or open circuit ning the unit through all of the steps in
indication if LED is functional. the “Test Modes” section discussed in
“Unit Start-Up”.

40 T_C-IOM-2A
Trouble Shooting

Unit Economizer Control (ECA) Cooling Failure


Troubleshooting 1. Cooling and heating set point (slide
ReliaTel Control pot) on the thermostat has failed.

Verify Economizer Status by Econo- 2. CC1 or CC2 24 VAC control circuit


mizer Actuator (ECA) LED indicator: has opened, check CC1 & CC2 coils,
and any of the controls below that ap-
OFF: No Power or Failure ply to the unit (HPC1, HPC2, LPC1,
ON: Normal, OK to LPC2, Frostat™).
Economize
Slow Flash: Normal, Not OK to Resetting Cooling and Heating
Economize Lockouts
Fast Flash: Communications Cooling Failures and Heating Lockouts
Failure are reset in an identical manner. Method
Pulse Flash: Error Code: 1 explains resetting the system from the
1 Flash: Actuator Fault space; Method 2 explains resetting the
2 Flashes: CO2 Sensor system at the unit.
3 Flashes: RA Humidity Sensor
4 Flashes RA Temp Sensor Method 1
5 Flashes: OA Quality Sensor
6 Flashes: OA Humidity Sensor To reset the system from the space, turn
7 Flashes: OA Temp Sensor the “Mode” selection switch at the ther-
8 Flashes: MA Temp Sensor mostat to the “Off” position. After ap-
9 Flashes: RAM Fault proximately 30 seconds, turn the
10 Flashes: ROM Fault “Mode” selection switch to the desired
11 Flashes: EEPROM Fault mode, i.e. Heat, Cool or Auto.

Method 2

HAZARDOUS VOLTAGE! To reset the system at the unit, cycle the


HIGH VOLTAGE IS PRESENT AT THE unit power by turning the disconnect
TERMINAL BLOCK OR UNIT switch “Off” and then “On”.
MOUNTED DISCONNECT SWITCH.

To prevent injury or death from electrocu-


tion, it is the responsibility of the techni-
cian to recognize this hazard and use ex-
treme care when performing service pro-
cedures with the electrical power ener-
gized.

T_C-IOM-2A 41
42 T_C-IOM-2A
T_C-IOM-2A 43
®

Literature Order Number T_C-IOM-2A


File Number SV-UN-RT-T_C-IOM-2A
Supersedes T_C-IOM-2
The Trane Company
Worldwide Applied Systems Group Stocking Location Webb Mason
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design
An American Standard Company and specifications without notice.

Vous aimerez peut-être aussi