Académique Documents
Professionnel Documents
Culture Documents
html
Receptacle NTR-20
GFCI Receptacle NTR-15-GFCI
GFCI Receptacle NTR-20-GFCI
Installation Instructions Isolated Ground Receptacle NTR-15-IG
Please Leave for Occupant Isolated Ground Receptacle NTR-20-IG
Receptacle With the power OFF on this circuit and power ON
for all other circuits, plug test lamp into all
Important Note receptacles. Receptacles where test lamp is out
Connect only No. 12 or 14 gauge copper or are on the same circuit as receptacle to be
copper-clad wire to this device. Do not connect protected. Mark these receptacles.
aluminum wire to this device. See device for strip Check both outlets on each receptacle with test
length. lamp to insure that receptacle is not part of a multi-
wire or split-circuit. Check to determine if
Installation receptacle is controlled by a switch. If receptacle is
1. Turn power OFF. Remove old receptacle and part of a split circuit or only one side of receptacle
disconnect all wires. is switch controlled, the Ground Fault Receptacle
2. Refer to Wiring Diagrams. cannot be used as a replacement at this location.
3. Connect black wire(s) to brass screw terminal(s), 2. Turn Power OFF. Remove old receptacle and
and tighten securely. disconnect all wires.
4. Connect white wire(s) to silver screw terminal(s), 3. Refer to Wiring Diagrams.
and tighten securely. 4. Connect black wire(s) to brass screw terminal(s),
5. Connect green or bare copper wire to green and tighten securely.
grounding screw terminal, and tighten securely. 5. Connect white wire(s) to silver screw terminal(s),
6. Refer to Mounting Instructions. and tighten securely.
6. Connect green or bare copper wire to green
grounding screw terminal, and tighten securely.
GFCI Receptacle 7. Observe labeling when wiring to “LINE” and
“LOAD” terminals. Refer to wiring diagrams for
Important Notes proper wiring.
1. Do not install this receptacle unless you are a 8. Refer to Mounting Instructions.
qualified electrician.
2. GFCI Receptacles will provide protection against Testing GFCI Receptacle
line to ground faults only. Although the ground fault 1. Turn power ON to Ground Fault Receptacle. The
receptacle does not limit the magnitude of fault “RESET” button should be pushed in almost flush
current, and therefore cannot prevent electrical with face of device. Check power by plugging a
shock, it does limit the duration of the shock to a lamp into receptacle and all downstream
period considered safe for normally healthy (protected) receptacles. The lamp should light.
people. They will not protect against overloads or 2. Push “TEST” button. The “RESET” button should
short circuits. This is the function of the fuse or pop out and lamp should be out at the Ground
circuit breaker. Fault and all downstream (protected) receptacles.
3. GFCI Receptacle is rated at 20A in feed-through 3. If “RESET” button does not pop out and lamp
applications. remains lit, DO NOT USE. With Power OFF,
4. Connect only No. 10, 12 or 14 gauge copper or recheck all wiring steps and connections. If all
copper-clad wire to this device. Do not connect connections are correct, repeat 1 and 2 with power
aluminum wire to this device. See device for strip ON. If “RESET” button still does not pop out and
length. lamp remains lit, DO NOT USE, return device for
5. Hospital Applications: GFCI-TYPE replacement.
RECEPTACLES SHOULD NOT BE USED IN 4. If Ground Fault Receptacle will not stay on after
CRITICAL CARE PATIENT AREAS OR FOR LIFE being reset (with no appliance on circuit), then:
SUPPORT EQUIPMENT APPLICATIONS 1) The load side of the neutral of the receptacle
BECAUSE OF THE POSSIBILITY OF POWER may be grounded;
INTERRUPTION. 2) A ground fault exists on load side;
3) The line and load neutral wires on receptacle
Installation are reversed.
1. Locating Circuit To Be Protected: Using a test
lamp, locate circuit breaker (or fuse) that controls
circuit to be protected. Identify this circuit on the
panel box with a number and mark this number on
the panel box label supplied with Ground Fault
Receptacle.
This product may be covered by one or more of the following U.S. patents: 4,737,609;
4,745,351; 4,803,380; DES 311,372; DES 335,867; and corresponding foreign patents.
U.S. and foreign patents pending. Lutron and Nova T* are a registered trademarks of Lutron
Electronics Co., Inc.
© 1997 Lutron Electronics Co., Inc.
Isolated Ground Receptacle Mounting Instructions
Important Notes 1. Push wire(s) into wallbox. Do not pinch wires.
1. Do not install this receptacle unless you are a 2. Mount Receptacle to wallbox using screws
qualified electrician. provided.
2. The grounding contact on the isolated ground 3. Separate faceplate from adapter plate. Pull
receptacle is isolated from the mounting means to faceplate off from the top.
reduce electromagnetic interference. 4. Mount adapter plate with mounting screws
3. Caution: Care must be given to the specification provided.
of a system with isolated ground receptacles since 5. Snap on faceplate.
the grounding impedance is controlled only by the Receptacle Adapter
grounding wires and does not benefit functionally Mounting Screws Mounting
from any parallel grounding paths. Screws
4. Connect only No. 12 or 14 gauge copper or
copper-clad wire to this device. Do not connect
aluminum wire to this device. See device for strip
length.
Installation
1. Turn power OFF. Remove old receptacle and
disconnect all wires.
2. Refer to Wiring Diagrams.
3. Connect black wire(s) to brass screw terminal(s), Receptacle
0 0 1 1+1 4 4+1
Number 1 1 3 5 6
of Large 2 4 6 7
Controls 3 6 8
4 9
Note: When ganging an even number of small Table B: Wallbox Requirement Chart for Side
controls with side sections intact, use gangable Sections Removed
3” x 2” wallboxes. Space an additional wallbox 3/4”
All Inside Side Number ofSmall Controls
apart from the other wallboxes. A 3/4” chase nipple is
Sections Removed 0 1 2 3 4 5 6
recommended as a spacer between wallboxes.
0 0 1 2 3 4 5 6
Example: Wallbox arrangement required for ganging 4 Number 1 1 3 4 5 6 7 8
small controls with side sections intact: of Large 2 3 5 6 7 8 9 10
Controls 3 5 7 8 9 10 11 12
4 7 9 10 11 12 13 14
3/4" Space Required Note: Do not remove outer side sections of controls
(Use chase nipple) on ends of gang.
Wiring Diagrams
NTR-15 and NTR-20 Receptacle Wiring
Hot
(Black) Brass
Screws
Ground
120V (Green or Bare)
60Hz
Nickel-
Plated
Neutral Screws
(White)
Hot
(Black)
Brass
Hot Screws
Wiring Notes: (Black) Brass Terminals
1. Wire terminals accept Ground
120V Switch Break Off
No. 12 or 14 gauge (Green or Bare)
Connecting
60Hz 120V
wire. Solid copper only. 60Hz Link With
Screwdriver
2. See device for proper Nickel-
strip length of wires. Plated
Neutral Screws
(White)
NTR-15-GFCI and NTR-20-GFCI Receptacle Wiring
Ground
(Green or Bare)
Ground
(Green or Bare)
Neutral
Neutral White White
(White) NP P P
Line Load
To Panel
Box Black Black Hot
Hot P-Protected
(Black) NP-Not Protected
Wiring Notes:
1. Wire terminals accept Ground
(Green or Bare)
No. 12 or 14 gauge wire.
Solid copper only. Neutral
Neutral White
2. See device for proper (White) P P P
strip length of wires. Line Load
To Panel
Box Black Hot
Hot P-Protected
(Black) NP-Not Protected
Hot
(Black) Brass
Screws Building Ground
(To Metal Box)
Green
120V Screw
60Hz
Hot
(Black)
Brass
Hot Screws Building Ground
(Black) (To Metal Box)
Wiring Notes: Green
120V Switch Screw
1. Wire terminals accept 60Hz 120V Brass Terminals
No. 12 or 14 gauge wire. 60Hz
Nickel- Break Off
Solid copper only. Plated Isolated Ground Connecting
2. See device for proper Neutral Screws Link With
(White) Screwdriver
strip length of wires.