POWER DB (DB‐P) FOR SUBSTATION NATC

8‐WAY SINGLE BUS BAR DB 40A TP MCCB
3PH, 415V, 50Hz 40A ‐4P‐30mA R.C.C.B
CKT  TRIP  NO. OF  WIRE  GND  CONDUIT 
LOAD SERVED POINT NO. LOCATION CONTROLLED BY WATT
TOTAL KW
NO. AMPS POLES MM2 MM2 MM R Y B
1R  16 1 4 2.5 25 POWER SOCKETS P1‐P4 BATTERY ROOM 13A SW SOCK. TWIN 4 X 200 0.800
1Y 16 1 4 2.5 25 POWER SOCKETS P5‐P8 UPS ROOM 13A SW SOCK. TWIN 4 X 200 0.800
1B 16 1 4 2.5 25 POWER SOCKETS P20‐P22 GENERATOR ROOM 13A SW SOCK. TWIN 3 X 200 0.600
2R  16 1 4 2.5 25 POWER SOCKETS P12‐P14 TRANSFORMER ROOM 13A SW SOCK. TWIN 3 X 200 0.600
2Y 16 1 4 2.5 25 POWER SOCKETS P19 FM‐200 ROOM 13A SW SOCK. TWIN 1 X 200 0.200
2B 16 1 4 2.5 25 POWER SOCKETS P15‐P18 L.V. ROOM 13A SW SOCK. TWIN 4 X 200 0.800
3R  16 1 4 2.5 25 POWER SOCKETS P9‐P11 M.V. ROOM 13A SW SOCK. TWIN 3 X 200 0.600
3Y 16 1 2.5 1.5 25 BATTERY EXHAUST FAN BEF BATTERY ROOM ROOF 20A SPN ISO + DP + IP CONTACTOR 1 X 180 0.180
3B 16 1 4 2.5 25 15A INDUSTRIAL SOCKET ROOF 1 X 1000 1.000
4R  16 1 SPARE
4Y 16 1 4 2.5 25 15A INDUSTRIAL SOCKET ROOF 1 X 1000 1.000
4B 16 1 SPARE
5R  20A TPN ISO +  1.000
5Y 20 3 4 2.5 25 GENE. EXHAUST FAN GEF‐01A GENERATOR ROOF CONTACTOR+ DP +  3000 1.000
5B THERMOSTAT 1.000
6R  20A TPN ISO +  1.000
6Y 20 3 4 2.5 25 GENE. EXHAUST FAN GEF‐01B GENERATOR ROOF CONTACTOR+ DP +  3000 1.000
6B THERMOSTAT 1.000
7R  16 1 SPARE
7Y 16 1 SPARE
7B 16 1 SPARE
8R  16 1 SPARE
8Y 16 1 SPARE
8B 16 1 SPARE
TOTAL KILOWATTS / PHASE 4.000 4.180 4.400
TOTAL CONNECTED LOAD (KW) 12.580