Académique Documents
Professionnel Documents
Culture Documents
STANDARD SPECIFICATIONS
Refer to GS 01C22T02-00E for Fieldbus
communication type marked with “”.
PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted
parts material code ‘S’ and silicone oil.
Power Supply Effects “”
Reference Accuracy of Calibrated Span
0.005 % per Volt (from 21.6 to 32 V DC, 350 )
(including the effects of zero-based linearity, hyster-
esis, and repeatability, values are in absolute for FUNCTIONAL SPECIFICATIONS
EJA510A)
0.2 % of Span Span & Range Limits
(Values are in absolute for EJA510A)
0.075 % of Span, when/ HAC is specified
(EJA530A: A, B and C capsule) Measurement
Span and MPa psi (/D1) bar (/D3) kgf/cm2(/D4)
Range
0.12 % of Span, when/ HAC is specified
10 to 200 1.45 to 29
(EJA530A: D capsule) Span
kPa
0.1 to 2 0.1 to 2
A
Range 0 to 200 0 to 29 0 to 2 0 to 2
For spans below X, kPa
X Span 0.1 to 2 14.5 to 290 1 to 20 1 to 20
[0.050.15 ] % of Span B
Span Range 0 to 2 0 to 290 0 to 20 0 to 20
X Span 0.5 to 10 72.5 to 1450 5 to 100 5 to 100
[0.0250.05 ] % of span, when/ HAC is C
Span Range 0 to 10 0 to 1450 0 to 100 0 to 100
specified (EJA530A: A, B and C capsule) Span 5 to 50 720 to 7200 50 to 500 50 to 500
D
Range 0 to 50 0 to 7200 0 to 500 0 to 500
X
[0.030.09 ] % of span, when/ HAC is T01E.EPS
Span URL is defined as the Upper Range Limit from the
specified (EJA530A: D capsule) table above.
Where X equals:
Capsule X MPa {psi} Zero Adjustment Limits
A 20 kPa {2.9} Zero can be fully elevated or suppressed, within the
A with/ HAC 40 kPa {5.8} Lower and Upper Range Limits of the capsule.
B 0.2 {29} External Zero Adjustment “”
C 1 {145} External zero is continuously adjustable with 0.01 %
D 8 {1160} incremental resolution of span. Span may be
Ambient Temperature Effects adjusted locally using the digital indicator with range
Total Effects per 28 C (50 F) Change switch.
[0.15% Span 0.15% URL] Mounting Position Effect
Stability Rotation in diaphragm plane has no effect. Tilting up
0.1% of URL per 12 months to 90 will cause zero shift up to 0.27 kPa {1.1 inH2O}
which can be corrected by the zero adjustment.
Vibration Effects
0.1 % of URL Output “”
(5 to 15Hz; 4mm peak-to-peak constant displace- Two wire 4 to 20 mA DC output with digital communi-
ment, 15 to 150Hz; 2g, 150 to 2000Hz; 1g) cations. BRAIN or HART FSK protocol are superim-
posed on the 4 to 20 mA signal.
A 4 MPa abs{580 psia} 4 MPa {580 psig} Figure 1. Working Pressure and Process Temperature
B 4 MPa abs{580 psia} 4 MPa {580 psig} [For model EJA510A]
C 20 MPa abs{2900 psia} 20 MPa {2900 psig}
D 60 MPa abs{8500 psia} 60 MPa {8500 psig}
E-10.5
R=
0.0236 Digital
External Communication
load range
resistance
250
R ()
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E July 01, 2002-00
<<Contents>> <<Index>> 3
Supply Voltage “” PHYSICAL SPECIFICATIONS
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional Wetted Parts Materials:
code /A) Diaphragm and Process connector
10.5 to 30 V DC for intrinsically safe, Type n, Refer to ‘MODEL AND SUFFIX CODE.’
nonincendive, or non-sparking type Non-wetted Parts Materials:
Minimum voltage limited at 16.4 V DC for digital
communications, BRAIN and HART Housing
Low copper cast-aluminum alloy with polyurethane
Load (Output signal code D and E)
paint (Munsell 0.6GY3.1/2.0)
0 to 1335 for operation
250 to 600 for digital communication Degrees of Protection
IP67, NEMA4X, JIS C0920 immersion proof
EMC Conformity Standards: ,
Cover O-rings
EN61326, AS/NZS 2064 Buna-N
European Pressure Equipment Directive 97/23/EC Data plate and tag
SUS304
Category III, Module H, Type of Equipment: Pressure Fill Fluid
Accessory-Vessel, Type of Fluid: Liquid and Gas, Silicone, Fluorinated oil (option)
Group of Fluid: 1 and 2
Weight
Communication Requirements “”
1.6 kg (3.5 lb) without integral indicator, mounting
BRAIN bracket.
Communication Distance Connections
Up to 2 km (1.25 miles) when using CEV polyethyl- Refer to the model code to specify the process and
ene-insulated PVC-sheathed cables. Communication the electrical connection type.
distance varies depending on type of cable used.
Load Capacitance < Settings When Shipped > “”
0.22 F or less (see note)
Tag Number As specified in order *1
Load Inductance Output Mode ‘Linear’
3.3 mH or less (see note) Display Mode ‘Linear’
Input Impedance of communicating device Operation ‘Normal’ unless otherwise specified in
Mode order
10 k or more at 2.4 kHz.
Damping Time ‘2 sec.’
Constant
Note : For general-use and Flameproof type. Calibration
For Intrinsically safe type, please refer to Range
‘OPTIONAL SPECIFICATIONS.’ Lower Range As specified in order
Value
HART Calibration
Range
As specified in order
Communication Distance Higher Range
Up to 1.5 km (1 mile) when using multiple twisted pair Value
cables. Communication distance varies depending on Selected from mmH2O, mmAq, mmWG,
Calibration mmHg, Torr, Pa, hPa, kPa, MPa, mbar,
type of cable used. Range Units bar, gf/cm2, kgf/cm2, inH2O, inHg, ftH2O,
psi, or atm.(Only one unit can be specified)
Use the following formula to determine cable length T05E.EPS
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E Oct. 01, 2002-00
<<Contents>> <<Index>> 4
MODEL AND SUFFIX CODES
Model EJA510A and EJA530A
The ‘’ marks indicate the most typical selection for each specification. Example: EJA530A-DAS4N-02NN/
*1: Not applicable for Output signal code F
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E Jan. 13, 2004-00
<<Contents>> <<Index>> 5
OPTIONAL SPECIFICATIONS (For Explosion Protected types “”)
For FOUNDATION Fieldbus explosion protected type, see GS 01C22T02-00E.
*1: Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).
*3: Applicable for Output signal code D and E.
For intrinsically safe approval, use the safety barrier certified by the testing laboratories (BARD-400 is not applicable).
*4: Applicable for Electrical connection code 2, 3, 4, 7, 8 and 9 (1/2 NPT, Pg 13.5, and M20 female).
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E Apr. 01, 2003-00
<<Contents>> <<Index>> 6
OPTIONAL SPECIFICATIONS
Item Description Code
High accuracy type *11 High accuracy HAC
Color change Amplifier cover only P
Painting *12
Coating change Epoxy resin-baked coating X1
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically
Lightning protector safe type, 9 to 32 V DC for Fieldbus communication type.) A
Allowable current: Max. 6000 A (140 s), Repeating 1000 A (140 s) 100 times
Degrease cleansing treatment K1
Oil-prohibited use Degrease cleansing treatment and with fluorinated oil filled capsule.
Operating temperature 20 to 80C K2
Stainless steel tag plate SUS304 stainless steel tag plate wired onto transmitter N4
PED 97/23/EC
European Pressure
Category: III, Module: H, Type of Equipment: Pressure Accessory-Vessel, PE3
Equipment Directive
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Mill Certificate Process connector M15
Test Pressure: 200 kPa (2 kgf/cm2) *4 T05
Pressure test/Leak test Test Pressure: 2 MPa (20 kgf/cm2) *5 Nitrogen (N2) Gas or Water *8 T06
Certificate Retention time: 10 minutes
Test Pressure: 10 MPa (100 kgf/cm2) *6 T07
Test Pressure: 50 MPa (500 kgf/cm2) *7 T08
T04E.EPS
*1: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by Optional code
D1, D3 and D4.
*2: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or capsule.
When combining with Optional code F1, output status for down-scale is –2.5%, 3.6 mA DC or less.
*3: Applicable for Electrical connection code 2, 3, 4, and 7. Not applicable for Optional code P and X1.
*4: Applicable for Capsule code A.
*5: Applicable for Capsule code B.
*6: Applicable for Capsule code C.
*7: Applicable for Capsule code D.
*8: Pure nitrogen gas or pure water is used for oil-prohibited use (Optional code K1 and K2)
*9: Applicable for Output signal code D and E. Consult Yokogawa when combining with Optional code for explosion
protected type.
*10: Not applicable for Optional code C1.
*11: Applicable for EJA530A. Refer to GS 01C21F01-02E.
*12: Standard polyurethan painting can be used in acid atmosphere, whereas the epoxy resin-baked coating (Option code
X1) can be used in alkaline atmosphere. Anti-corrosion coating, the combination of polyurethan and epoxy resin-baked
coating, is available by special order as sea water, alkaline, and acid resistant.
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E Jan. 13, 2004-00
<<Contents>> <<Index>> 7
DIMENSIONS
Model EJA510A and EJA530A
With Process Connection code 7
Unit: mm(Approx. inch)
Conduit connection 12 45
Ground
(0.47) (1.77) terminal
(3.07)
78
127(5.0)
111(4.37)
170(6.69)
LOCK ZERO LOCK
Zero adjustment
Adapter
124(4.88)
Pipe(Open to atmosphere)*1
44(1.73)
(1.85)
47
176(6.92)
6(0.23)
5(0.19)
F03E.EPS
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E July 01, 2002-00
<<Contents>> <<Index>> 8
SELECTION GUIDE
Measurement Span Maximum Working Pressure
Application Type Model Capsule
kPa inH2O MPa psi
L 0.5 to 10 2 to 40 16*4 2250*4
Differential M 1 to 100 4 to 400 16 2250
Pressure Traditional-Mounting*1 EJA110A
H 5 to 500 20 to 2000 16 2250
V 0.14 to 14MPa 20 to 2000 psi 16 2250
L 1 to 10 4 to 40 3.5 500
Flow Integral Orifice EJA115 M 2 to 100 8 to 400 14 2000
H 20 to 210 80 to 830 14 2000
Differential Pressure Extended EJA118N M 2.5 to 100 10 to 400
& Liquid Level Flush EJA118W 25 to 500 Based on Flange Rating
H 100 to 2000
with Remote Seals Combination EJA118Y
Draft Range Traditional-Mounting*1 EJA120A E 0.1 to 1 0.4 to 4 50 kPa 7.25
Differential Pressure Traditional-Mounting*1 M 1 to 100 4 to 400 32 4500
& Liquid Level EJA130A
H 5 to 500 20 to 2000 32 4500
Liquid Level, Closed Flush EJA210A M 1 to 100 4 to 400
20 to 2000 Based on Flange Rating
or Open Tank Extended EJA220A H 5 to 500
L 0.67 to 10*2 2.67 to 40*2 10 kPa*2 40 in H2O*2
Absolute (vacuum) 130 kPa*2
Pressure Traditional-Mounting*1 EJA310A M 1.3 to 130*2 0.38 to 38 inHg*2 18.65*2
A 0.03 to 3 MPa*2 4.3 to 430 psi*2 3000 kPa*2 430*2
A 0.03 to 3 MPa 4.3 to 430 psi 3 430
Gauge Pressure Traditional-Mounting*1 EJA430A 0.14 to 14 MPa 20 to 2000 psi 14
B 2000
Gauge Pressure Extended EJA438N A 0.06 to 3 MPa 8.6 to 430 psi Based on Flange Rating
with Remote Seal B 0.46 to 7 MPa 66 to 1000 psi
Gauge Pressure A 0.06 to 3 MPa 8.6 to 430 psi
Flush EJA438W 66 to 2000 psi Based on Flange Rating
with Remote Seal B 0.46 to 14 MPa
C 5 to 32 MPa 720 to 4500 psi 32 4500
High Gauge Traditional-Mounting*1 EJA440A 5 to 50 MPa 720 to 7200 psi
D 50 7200
A 10 to 200 1.45 to 29 psi 200 kPa 29
Absolute & Gauge EJA510A B 0.1 to 2 MPa 14.5 to 290 psi 2 290
Direct-Mounting
Pressure*3 EJA530A C 0.5 to 10 MPa 72.5 to 1450 psi 10 1450
D 5 to 50 MPa 720 to 7200 psi 50 7200
T06E.EPS
*1: Traditional-mounting is 1/4 - 18 NPTF process connections ( 1/2 - 14 NPTF with process adapters ) on 2-1/8" centers.
*2: Measurement values in absolute.
*3: Measurement values in absolute for EJA510A.
*4: When combined with Wetted parts material code H, M, T, A, D, and B, the value is 3.5 MPa (500 psi).
< Ordering Information > “” < Related Instruments > “”
Specify the following when ordering Power Distributor: Refer to GS 01B04T01-02E or
1. Model, suffix codes, and optional codes GS 01B04T02-00E
2. Calibration range and units: BRAIN TERMINAL: Refer to GS 01C00A11-00E
1) Calibration range can be specified with range
value specifications up to 5 digits < Reference >
(excluding any decimal point) for low or high range 1. Teflon; Trademark of E.I. DuPont de Nemours & Co.
limits within the range of -32000 to 32000. 2. Hastelloy; Trademark of Haynes International Inc.
2) Specify only one unit from the table, ‘Settings 3. HART; Trademark of the HART Communication
when shipped.’ Foundation.
3. Select linear or square root for output mode and 4. FOUNDATION ; Trademark of Fieldbus Foundation.
display mode.
Note: If not specified, the instrument is shipped set for Material Cross Reference Table
linear mode. SUS316L AISI 316L
4. Select normal or reverse for operation mode SUS316 AISI 316
Note: If not specified, the instrument is shipped in SUS304 AISI 304
normal operation mode.
S25C AISI 1025
5. Display scale and units (for transmitters equipped
with integral indicator only) SCM435 AISI 4137
Specify either 0 to 100 % or engineering unit scale SUS630 ASTM630
and ‘Range and Unit’ for engineering units scale: SCS14A ASTM CF-8M
Scale range can be specified with range limit T07E.EPS
All Rights Reserved. Copyright © 1999, Yokogawa Electric Corporation GS 01C21F01-00E Jan. 13, 2004-00