INSTRUCTION MANUAL
GRE130
( Ver. 2.0)
6 F 2 T 0 1 7 6
Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRE130. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
DANGER Indicates an imminently hazardous situation which will result in death or serious
injury if you do not follow the instructions.
WARNING Indicates a potentially hazardous situation which could result in death or serious
injury if you do not follow the instructions.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result in
minor injury or moderate injury.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result in
property damage.
1
6 F 2 T 0 1 7 6
DANGER
• Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage generated is
dangerous.
• Residual voltage
Hazardous voltage can be present in the DC circuit immediately after switching off the power
supply. It takes approximately 30 seconds for the voltage to discharge.
CAUTION
• Earth
CAUTION
• Operating environment
The equipment must only be used within the range of ambient temperature, humidity and dust
detailed in the specification and in an environment free of abnormal vibration.
• Ratings
Before applying AC voltage or the power supply to the equipment, check that they conform to the
equipment ratings.
• Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is on, as this
may cause the equipment to malfunction.
• External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
• Connection cable
If a power supply has not been supplied to the relay for two days or more, then all fault records,
event records and disturbance records and the internal clock may be cleared soon after restoring the
power. This is because the back-up RAM may have discharged and may contain uncertain data.
• Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
• Disposal
This product does not contain expendable supplies nor parts that can be recycled. When disposing of
this equipment, do so in a safe manner according to local regulations as an industrial waste. If any
points are unclear, please contact our sales representatives.
2
6 F 2 T 0 1 7 6
Contents
Safety Precautions 1
1. Introduction 6
2. Application Notes 8
2.1 Overvoltage and Undervoltage Protection 8
2.1.1 Phase Overvoltage Protection 8
2.1.2 Phase Undervoltage Protection 12
2.1.3 Zero Phase Sequence Overvoltage Protection 16
2.1.4 Negative Phase Sequence Overvoltage Protection 19
2.2 Frequency Protection 22
2.2.1 Frequency element 22
2.2.2 Frequency rate-of-change element 22
2.3 Trip and Alarm Signal Output 27
3. Technical Description 29
3.1 Hardware Description 29
3.1.1 Outline of Hardware Modules 29
3.2 Input and Output Signals 31
3.2.1 AC Input Signals 31
3.2.2 Binary Input Signals 31
3.2.3 Binary Output Signals 35
3.2.4 PLC (Programmable Logic Controller) Function 36
3.3 Automatic Supervision 37
3.3.1 Basic Concept of Supervision 37
3.3.2 Relay Monitoring 37
3.3.3 Trip Circuit Supervision 38
3.3.4 Circuit Breaker Monitoring 40
3.3.5 Failure Alarms 40
3.3.6 Trip Blocking 41
3.3.7 Setting 42
3.4 Recording Function 42
3.4.1 Fault Recording 42
3.4.2 Event Recording 43
3.4.3 Disturbance Recording 43
3.5 Metering Function 45
3.6 Control Function 46
4. User Interface 47
4.1 Outline of User Interface 47
4.1.1 Front Panel 47
4.1.2 Communication Ports 49
4.2 Operation of the User Interface 50
3
6 F 2 T 0 1 7 6
4
6 F 2 T 0 1 7 6
The data given in this manual are subject to change without notice. (Ver.2.0)
5
6 F 2 T 0 1 7 6
1. Introduction
GRE130 series relays provide overvoltage and undervoltage protection for distribution substations,
generators, motors and transformers.
GRE130 provides continuous monitoring of internal circuits and of software. External circuits are
also monitored, by trip circuit supervision and CB condition monitoring features.
A user-friendly HMI is provided through a backlit LCD, programmable LEDs, keypad and
menu-based operating system. PC access is also provided, either for local connection via a
front-mounted USB port, or for remote connection via a rear-mounted RS485 port. The
communication system allows the user to read and modify the relay settings, and to access data
gathered by the relay’s metering and recording functions. Further, data communication with
substation control and automation systems is supported according to the MODBUS RTU.
Table 1.1.1 shows the members of the GRE130 series and identifies the functions to be provided by
each member.
6
6 F 2 T 0 1 7 6
GRE130 -
Model Number
410A, 411A, 412A
[APPL] setting 1PP 1PN 2PP 2PZ 3PP 3PN 3PV
O/V IDMT
O/V DT
U/V IDMT
U/V DT
ZPS IDMT *
ZPS DT *
NPS IDMT
NPS DT
FRQ
DFRQ
Trip circuit supervision
Self supervision
CB state monitoring
Trip counter alarm
Multiple settings groups
Metering
Fault records
Event records
Disturbance records
MODBUS RTU
communication
IEC60850-5-103
communication
IEC61850 communication
()* ()* ()* ()* ()* ()* ()*
(option)
[APPL]setting; 1PP: single phase-to-phase voltage
1PN: single phase-to-neutral voltage
2PP: two phase-to-phase voltage
2PZ: two phase-to-phase voltage with zero phase voltage input
3PP: three phase-to-phase voltage
3PN: three phase-to-neutral voltage
3PV: three phase-to-neutral voltage with zero phase voltage input
Ve: zero phase sequence voltage V0
IDMT: inverse definite minimum time DT: definite time
O/V: overvoltage protection U/V: undervoltage protection
ZPS: zero phase sequence overvoltage NPS: negative phase sequence overvoltage
FRQ: Frequency protection DFRQ: Frequency rate-of-change protection
∗: V0 calculated from three phase voltages
()*: Optional communication for 412A model .
CAUTION: Do not change the APPL setting under service condition of the relay.
7
6 F 2 T 0 1 7 6
2. Application Notes
2.1 Overvoltage and Undervoltage Protection
2.1.1 Phase Overvoltage Protection
Pickup
Dropoff
0 V
The overvoltage protection element OV1 and OV2 have the IDMT characteristic defined by
equation (1) following the form described in IEC 60255-127:
+ c
TMS ×
k
t (G ) =
(1)
( )
a
V − 1
Vs
where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = overvoltage setting (V),
TMS = time multiplier setting.
k, a, c = constants defining curve.
The IDMT characteristic is illustrated in Figure 2.1.2. In addition to the IDMT curve in Figure
2.1.2, a user configurable curve is available via scheme switches [OV1EN] and [OV2EN]. If
required, set the scheme switch [OV∗EN] to “C” and set the curve defining constants k, a, c. These
curves are defined in Table 2.1.1.
Curve Description k a c
“IDMT” 1 1 0
“C” (User Configurable) 0.000 – 30.000 0.00 – 5.00 0.000 – 5.000
by 0.001 step by 0.01 step by 0.001 step
8
6 F 2 T 0 1 7 6
100.000
TMS = 5
TMS = 2
1.000
TMS = 1
0.100
1 1.5 2 2.5 3
9
6 F 2 T 0 1 7 6
Figure 2.1.4. The scheme logic of OV2 is the same as that of the OV1.
Figure 2.1.5 and Figure 2.1.5 show the scheme logic of the definite time overvoltage protection
OV3. The OV3 gives alarm signals OV3_ALARM through the delayed pick-up timers TOV3.
The OV1 to OV3 protection can be disabled by the scheme switches [OV1EN] to [OV3EN].
63 TOV1
1(∗) & & t 0 102
OV1-A_TRIP
OV1 2(∗) 64 ≥1
66 TOV2
1(∗) & & t 0 109
OV2-A_TRIP
OV2 2(∗) 67 ≥1
69 TOV3
1(∗) & & t 0 116
OV3-A_ALARM
OV3 2(∗) 70
[OV3EN]
& & t 0 118
+ OV3-C_ ALARM
17
0.00 - 300.00s 115
OV3_BLOCK 1 ≥1 OV3_ ALARM
10
6 F 2 T 0 1 7 6
[APPL] setting
Phase
1PP 1PN 2PP / 2PZ 3PN / 3PV 3PP
1 phase-to-phase phase-to-neutral A - B phase A phase A - B phase
2 - - B - C phase B phase B - C phase
3 - - - C phase C - A phase
Setting
The table shows the setting elements necessary for the overvoltage protection and their setting
ranges.
Element Range Step Default Remarks
OV1 10.0 – 200.0 V 0.1 V 120.0 V OV1 threshold setting
TOV1M 0.05 – 100.00 0.01 1.00 OV1 time multiplier setting. Required if [OV1EN] = IDMT.
TOV1 0.00 – 300.00 s 0.01 s 1.00 s OV1 definite time setting. Required if [OV1EN] = DT.
TOV1R 0.0 – 300.0 s 0.1 s 0.0 s OV1 definite time delayed reset.
OV1DPR 10 – 98 % 1% 95 % OV1 DO/PU ratio setting.
OV2 10.0 – 200.0 V 0.1 V 140.0 V OV2 threshold setting
TOV2M 0.05 – 100.00 0.01 1.00 OV2 time multiplier setting. Required if [OV2EN] = IDMT.
TOV2 0.00 – 300.00 s 0.01 s 1.00 s OV2 definite time setting. Required if [OV2EN] = DT.
TOV2R 0.0 – 300.0 s 0.1 s 0.0 s OV2 definite time delayed reset.
OV2DPR 10 – 98 % 1% 95 % OV2 DO/PU ratio setting.
OV3 10.0 – 200.0 V 0.1 V 140.0 V OV3 threshold setting.
TOV3 0.00 – 300.00 s 0.01 s 1.00 s OV3 definite time setting.
OV3DPR 10 - 98 % 1% 95 % OV3 DO/PU ratio setting.
[OV1EN] Off/DT/IDMT/C Off OV1 Enable
[OV2EN] Off/DT/IDMT/C Off OV2 Enable
[OV3EN] Off / On Off OV3 Enable
11
6 F 2 T 0 1 7 6
GRE130 provides three independent phase undervoltage elements. UV1 and UV2 are
programmable for inverse time (IDMT) or definite time (DT) operation. UV3 has definite time
characteristic only.
Figure 2.1.7 shows the characteristic of the undervoltage elements.
0 V
The undervoltage protection element UV1 has an IDMT characteristic defined by equation (2)
following the form described in IEC 60255-127:
+ c
TMS ×
k
t (G ) = a (2)
1 − V
( )
Vs
where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = undervoltage setting (V),
TMS = time multiplier setting.
k, a, c = constants defining curve.
The IDMT characteristic is illustrated in Figure 2.1.8. In addition to the IDMT curve in Figure
2.1.8, a user configurable curve is available via scheme switches [UV1EN] and [UV2EN]. If
required, set the scheme switch [UV∗EN] to “C” and set the curve defining constants k, a, c. These
curves are defined in Table 2.1.1.
The UV3 element is used for definite time overvoltage protection.
12
6 F 2 T 0 1 7 6
This does not apply following a trip operation, in which case resetting is always instantaneous.
100.000
TMS = 10
10.000
TMS = 5
TMS = 2
TMS = 1
1.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)
Scheme Logic
Figures 2.1.9 to 2.1.11 show the scheme logic of the undervoltage protection UV1 to UV3.
The UV1 protection provides a selective definite time or inverse time characteristic as shown in
Figure 2.1.8. The definite time protection is enabled by setting [UV1EN] to “DT”, and trip signal
UV1_TRIP is given through the delayed pick-up timer TUV1. The inverse time protection is
enabled by setting [UV1EN] to “IDMT”, and trip signal UV1_TRIP is given.
The UV2 protection also provides a selective definite time or inverse time characteristic as shown in
Figure 2.1.10. The scheme logic of UV2 is the same as that of the UV1.
Figure 2.1.11 shows the scheme logic of the definite time undervoltage protection UV3. The UV3
gives alarm signal UV3_ALARM through the delayed pick-up timers TUV3.
The UV1 to UV3 protection can be disabled by the scheme switches [UV1EN] to [UV3EN].
In addition, there is a user programmable voltage threshold VBLK. If all measured phase voltages
drop below this setting, then both UV1 to UV3 are prevented from operating. This function can be
blocked by the scheme switch [VBLKEN]. The [VBLKEN] should be set to “OFF” (not used) when
the UV elements are used as fault detectors, and set to “ON” (used) when used for load shedding.
Note: The VBLK must be set lower than any other UV setting values.
13
6 F 2 T 0 1 7 6
72 TUV1
1(∗) & & t 0 123
UV1-A_TRIP
UV1 2(∗) 73 ≥1
74 & & t 0 124
UV1-B_TRIP
3(∗)
≥1
157
1(∗) & & t 0 125
UV1-C_TRIP
UV1 2(∗) 158 ≥1
INST 0.00 - 300.00s
3(∗) 159
UVBLK 122
97
≥1 UV1_TRIP
&
VBLK 1 NON
& UVBLK
&
[VBLKEN]
+ &
"ON"
[UVTST]
"OFF" "DT"
[UV1EN]
≥1
+
"IDMT"
18
UV1_BLOCK 1
75 TUV2
1(∗) & & t 0 127
UV2-A_TRIP
UV2 2(∗) 76 ≥1
77 & & t 0 128
UV2-B_TRIP
3(∗)
≥1
177
1(∗) & & t 0 129
UV2-C_TRIP
UV2 2(∗) 178 NON ≥1
INST UVBLK 0.00 - 300.00s
179
3(∗) "DT"
[UV2EN]
≥1 ≥1
126
UV2_TRIP
+ &
"IDMT"
19 &
UV2_BLOCK 1
&
78 TUV3
1(∗) & & t 0 131
79 UV3-A_ALARM
UV3 2(∗)
80 & t 0 132
3(∗) & UV3-B_ALARM
[UV3EN]
+ & & t 0 133
UV3-C_ALARM
"ON"
NON BLK 0.00 - 300.00s
130
20 ≥1 UV3_ALARM
UV3_BLOCK 1
14
6 F 2 T 0 1 7 6
[APPL] setting
Phase
1PP 1PN 2PP / 2PZ 3PN / 3PV 3PP
1 phase-to-phase phase-to-neutral A - B phase A phase A - B phase
2 - - B - C phase B phase B - C phase
3 - - - C phase C - A phase
Setting
The table shows the setting elements necessary for the undervoltage protection and their setting
ranges.
Element Range Step Default Remarks
UV1 5.0 – 130.0 V 0.1 V 60.0 V UV1 threshold setting
TUV1M 0.05– 100.00 0.01 1.00 UVI time multiplier setting. Required if [UV1EN] = IDMT.
TUV1 0.00 – 300.00 s 0.01 s 1.00 s UV1 definite time setting. Required if [UV1EN] = DT.
TUV1R 0.0 – 300.0 s 0.1 s 0.0 s UV1 definite time delayed reset.
UV2 5.0 – 130.0 V 0.1 V 40.0 V UV1 threshold setting
TUV2M 0.05– 100.00 0.01 1.00 UVI time multiplier setting. Required if [UV2EN] = IDMT.
TUV2 0.00 – 300.00 s 0.01 s 1.00 s UV1 definite time setting. Required if [UV2EN] = DT.
TUV2R 0.0 – 300.0 s 0.1 s 0.0 s UV1 definite time delayed reset.
UV3 5.0 – 130.0 V 0.1 V 40.0 V UV3 threshold setting.
TUV3 0.00 – 300.00 s 0.01 s 1.00 s UV3 definite time setting.
VBLK 5.0 - 20.0 V 0.1 V 10.0 V Undervoltage block threshold setting.
[UV1EN] Off/ DT/ IDMT/ DT UV1 Enable
C
[VBLKEN] Off / On Off UV block Enable
[UV2EN] Off/ DT/ IDMT/ DT UV2 Enable
C
[UV3EN] Off / On Off UV3 Enable
15
6 F 2 T 0 1 7 6
The zero phase sequence overvoltage protection (ZPS) is applied to earth fault detection on
unearthed, resistance-earthed system or on ac generators.
The low voltage settings which may be applied make the ZPS element susceptible to any 3rd
harmonic component which may be superimposed on the input signal. Therefore, a 3rd harmonic
filter is provided to suppress such superimposed components.
For earth fault detection, the following two methods are in general use.
• Measuring the zero sequence voltage produced by a VT residual connection (broken-delta
connection) as shown in Figure 2.1.13.
• Measuring the residual voltage across an earthing transformer as shown in Figure 2.114.
A B C
GRE130
V0
A B
GRE130
V0
Resistor
Two independent elements ZPS1 and ZPS2 are provided. These elements are programmable for
definite time delayed or inverse time delayed (IDMT) operation.
The inverse time characteristic is defined by equation (3) following the form described in IEC
60255-127:
16
6 F 2 T 0 1 7 6
k + c
t (G ) = TMS × (3)
V0 − 1
α
V S
where:
t = operating time for constant voltage V0 (seconds),
V0 = Zero sequence voltage (V),
Vs = Zero sequence overvoltage setting (V),
TMS = time multiplier setting.
k, a, c = constants defining curve.
The IDMT characteristic is illustrated in Figure 2.1.15. In addition to the IDMT curve in Figure
2.1.15, a user configurable curve is available via scheme switches [ZPS1EN] and [ZPS2EN]. If
required, set the scheme switch [ZPS∗EN] to “C” and set the curve defining constants k, a, c. These
curves are defined in Table 2.1.1.
ZPS Overvoltage
Inverse Time Curves
1000.000
100.000
Operating Time (secs)
10.000
1.000
TMS = 10
TMS = 5
TMS = 2
0.100
TMS = 1
0.010
0 5 10 15 20
17
6 F 2 T 0 1 7 6
Scheme Logic
Figures 2.1.16 and 2.1.17 show the scheme logic of the zero-phase sequence overvoltage protection.
Two zero-phase sequence overvoltage elements ZPS1 and ZPS2 with independent thresholds output
trip signals ZPS1 TRIP and ZPS2 TRIP through delayed pick-up timers TZOV1 and TZPS2.
The tripping can be disabled by the scheme switches [ZPS1EN] and [ZPS2EN].
93 TZPS1
ZPS1 t 0
& & 134
ZPS1 197 ≥1 ZPS1 TRIP
INST 0.00 - 300.00s
"DT"
[ZPS1EN] ≥1
+ &
"IDMT"
21
ZPS1_BLOCK 1
94 TZPS2
ZPS2 t 0
& & 135
ZPS2 198 ≥1 ZPS2_ALARM
INST 0.00 - 300.00s
"DT"
[ZPS2EN] ≥1
+ &
"IDMT"
22
ZPS2_BLOCK 1
Setting
The table below shows the setting elements necessary for the zero sequence overvoltage protection
and their setting ranges.
Element Range Step Default Remarks
ZPS1 1.0 - 130.0 V 0.1V 20.0 V ZPS1 threshold setting (V0) for tripping.
TZPS1M 0.05 – 100.00 0.01 1.00 ZPS1 time multiplier setting. Required if
[ZPS1EN]=IDMT.
TZPS1 0.00 – 300.00 s 0.01 s 1.00 s ZPS1 definite time setting. Required if [ZPS1EN]=DT.
TZPS1R 0.0 – 300.0 s 0.1 s 0.0 s ZPS1 definite time delayed reset.
ZPS2 1.0 - 130.0 V 0.1V 40.0 V ZPS2 threshold setting (V0) for alarming.
TZPS2M 0.05 – 100.00 0.01 1.00 ZPS2 time multiplier setting. Required if
[ZPS2EN]=IDMT.
TZPS2 0.00 – 300.00 s 0.01 s 1.00 s ZPS2 definite time setting. Required if [ZPS2EN]=DT.
TZPS2R 0.0 – 300.0 s 0.1 s 0.0 s ZPS2 definite time delayed reset.
[ZPS1EN] Off /DT/ IDMT/ C DT ZPS1 Enable
[ZPS2EN] Off / On Off ZPS2 Enable
18
6 F 2 T 0 1 7 6
The negative phase sequence overvoltage protection (NPS) is used to detect voltage unbalance
conditions such as reverse-phase rotation, unbalanced voltage supply etc.
The NPS protection is applied to protect three-phase motors from the damage which may be caused
by the voltage unbalance. Unbalanced voltage supply to motors due to a phase loss can lead to
increases in the negative sequence voltage.
The NPS protection is also applied to prevent the starting of the motor in the wrong direction, if the
phase sequence is reversed.
Two independent elements NPS1 and NPS2 are provided. The elements are programmable for
definite time delayed or inverse time delayed (IDMT) operation.
The inverse time characteristic is defined by equation (4) following the form described in IEC
60255-127.
k + c
t (G ) = TMS × (4)
V 2 − 1
α
V S
where:
t = operating time for constant voltage V2 (seconds),
V2 = Negative sequence voltage (V),
Vs = Negative sequence overvoltage setting (V),
TMS = time multiplier setting.
k, a, c = constants defining curve.
The IDMT characteristic is illustrated in Figure 2.1.18. In addition to the IDMT curve in Figure
2.1.18, a user configurable curve is available via scheme switches [NPS1EN] and [NPS2EN]. If
required, set the scheme switch [NPS∗EN] to “C” and set the curve defining constants k, a, c. These
curves are defined in Table 2.1.1.
19
6 F 2 T 0 1 7 6
NPS Overvoltage
Inverse Time Curves
1000.000
100.000
1.000 TMS = 10
TMS = 5
TMS = 2
0.100
TMS = 1
0.010
0 5 10 15 20
Applied Voltage (x Vs)
Scheme Logic
Figures 2.1.19 and 2.1.20 show the scheme logic of the negative sequence overvoltage protection.
Two negative sequence overvoltage elements NPS1 and NPS2 with independent thresholds output
trip signals NPS1 TRIP and NPS2 TRIP through delayed pick-up timers TNPS1 and TNPS2.
The tripping can be disabled using scheme switches [NPS1EN] and [NPS2EN].
95 TNPS1
NPS1 t 0
& & 136
NPS1 199 ≥1 NPS1 TRIP
INST 0.00 - 300.00s
"DT"
[NPS1EN] ≥1
+ &
"IDMT"
23
NPS1_BLOCK 1
20
6 F 2 T 0 1 7 6
96 TNPS2
NPS2 t 0
& & 137
NPS2 200 ≥1 NPS2_ALARM
INST 0.00 - 300.00s
"DT"
[NPS2EN] ≥1
+ &
"IDMT"
24
NPS2_BLOCK 1
Setting
The table below shows the setting elements necessary for the negative sequence overvoltage
protection and their setting ranges.
The delay time setting TNPS1 and TNPS2 is added to the inherent delay of the measuring elements
NPS1 and NPS2. The minimum operating time of the NPS elements is approximately 200ms.
Element Range Step Default Remarks
NPS1 1.0 - 130.0 V 0.1V 20.0 V NPS1 threshold setting for tripping.
TNPS1M 0.05 – 100.00 0.01 1.00 NPS1 time multiplier setting. Required if [NPS1EN]=IDMT.
TNPS1 0.00 – 300.00 s 0.01 s 1.00 s NPS1 definite time setting. Required if [NPS1EN]=DT.
TNPS1R 0.0 – 300.0 s 0.1 s 0.0 s NPS1 definite time delayed reset.
NPS2 1.0 - 130.0 V 0.1V 40.0 V NPS2 threshold setting for alarming.
TNPS2M 0.05 – 100.00 0.01 1.00 NPS2 time multiplier setting. Required if [NPS2EN]=IDMT.
TNPS2 0.00 – 300.00 s 0.01 s 1.00 s NPS2 definite time setting. Required if [NPS2EN]=DT.
TNPS2R 0.0 – 300.0 s 0.1 s 0.0 s NPS2 definite time delayed reset.
[NPS1EN] Off /DT/ IDMT/ C Off NPS1 Enable
[NPS2EN] Off / On Off NPS2 Enable
21
6 F 2 T 0 1 7 6
Underfrequency element UF operates when the power system frequency falls under the setting value.
Overfrequency element OF operates when the power system frequency rises over the setting value.
These elements measure the frequency and check for underfrequency or overfrequency every 5 ms.
They operate when the underfrequency or overfrequency condition is detected 16 consecutive times.
The outputs of both the UF and OF elements is invalidated by undervoltage block element
(FRQBLK) operation during an undervoltage condition.
Figure 2.2.1 shows the characteristics of the UF and OF elements.
The frequency rate-of-change element calculates the gradient of frequency change (df/dt). GRE130
provides two rate-of-change elements, a frequency decay rate element (D) and a frequency rise rate
element (R). These elements measure the change in frequency (Δf) over a time interval (Δt=100ms),
as shown Figure 2.2.2 and calculate the Δf/Δt every 5 ms. They operate when the frequency change
exceeds the setting value 50 consecutive times.
The output of both the D and R elements is invalidated by undervoltage block element (FRQBLK)
operation during undervoltage condition.
22
6 F 2 T 0 1 7 6
Hz
Δf
Δt
sec
Scheme Logic
Figure 2.2.3 shows the scheme logic of the frequency protection for stage 1. The first frequency
element F11, the second F12, the frequency rise rate-of-change element DFR1 and frequency decay
rate-of-change element DFD1 can all output a trip command independently under the condition that
the system voltage is higher than the setting of the undervoltage element FVBLK.
214
DF-D1 234
& & DFD
R
≥1
D
FVBLK BOTH ≥1
[DFT1] OFF
+
42
FRQ1 BLOCK 1
To apply the various types of frequency protection, the GRE130 has the following three scheme
switches for each stage. For stage 1,
[FT1]: This switch selects the frequency protection to apply as well as provide the
measuring elements F11 and F12 with an overfrequency or underfrequency
characteristic.
23
6 F 2 T 0 1 7 6
[DFT1]: This switch selects which frequency rate-of-change protection to apply. The
following protections can be selected by the [DFT1] settings.
[LOGIC1]: This switch is provided in the scheme logic selection circuit in Table 2.2.1 and
determines the trip command combination of frequency element output and
frequency rate-of-change element output. The following table shows the [Logic1]
setting and corresponding combinations.
F1 ≥1
&
E E = F1 + F2 x (DFR + DFD)
F2
L3 DFR
≥1
DFD
24
6 F 2 T 0 1 7 6
The individual scheme logic for stages 2 to 4 are similar to that of stage 1 except that the device
names of the measuring elements, timers, scheme switches and binary input signals change and the
logic described above is applied to stages 2 to 4.
218
DF-D2 239
& & DFD
R
≥1
D
FVBLK BOTH ≥1
[DFT2] OFF
+
43
FRQ2 BLOCK 1
222
DF-D3 244
& & DFD
R
≥1
D
FVBLK BOTH ≥1
[DFT3] OFF
+
44
FRQ3 BLOCK 1
25
6 F 2 T 0 1 7 6
226
DF-D4 249
& & DFD
R
≥1
D
FVBLK BOTH ≥1
[DFT4] OFF
+
45
FRQ4 BLOCK 1
Setting
The setting elements necessary for the frequency protection and their setting ranges are shown in the
table below.
Element Range Step Default Remarks
F1 (*) 45.00 – 55.00 Hz 0.01 Hz 51.00 Hz First frequency element setting
( 54.00 – 66.00 Hz 0.01 Hz 61.00 Hz )
F2 45.00 – 55.00 Hz 0.01 Hz 49.00 Hz Second frequency element setting
( 54.00 – 66.00 Hz 0.01 Hz 59.00 Hz )
DF (**) 0.1 – 9.9 Hz/s 0.1 Hz/s 0.5 Hz/s Frequency rate-of-change (**)
FVBLK(***) 40 –100 V 1V 40 V Undervoltage block
TF1 0.00 – 100.00 s 0.01 s 1.00 s Timer setting of first frequency element
TF2 0.00 – 100.00 s 0.01 s 1.00 s Timer setting of second frequency element
FT Off / O / U / B / OO / UU B Frequency protection selection
DFT Off / R / D / Both Both Frequency rate-of-change protection selection
Logic L1 / L2 / L3 / L4 / L5 L1 Scheme logic selection
(*): Number 1 to 4 enter into for stages 1 to 4 respectively.
(**): DF is a common setting element name for DFR and DFD.
(***): FVBLK is common to stage 1 to 4.
26
6 F 2 T 0 1 7 6
OV1 TRIP
OV2 TRIP
UV1 TRIP 141
GEN_TRIP
UV2 TRIP ≥1
ZPS1 TRIP
NPS1 TRIP
FRQ1 TRIP
FRQ2 TRIP
FRQ3 TRIP
FRQ4 TRIP
OV1-A TRIP
OV2-A TRIP 372
≥1 GEN_TRIP-A
UV1-A TRIP
UV2-A TRIP
OV1-B TRIP
OV2-B TRIP 373
≥1 GEN_TRIP-B
UV1-B TRIP
UV2-B TRIP
OV1-C TRIP
OV2-C TRIP 374
≥1 GEN_TRIP-C
UV1-C TRIP
UV2-C TRIP
375
ZPS1_TRIP GEN. TRIP-N
27
6 F 2 T 0 1 7 6
OV3 ALARM
380
UV3 ALARM ≥1 GEN_ALARM
ZPS2 ALARM
NPS2 ALARM
OV3-B ALARM
≥1 382
GEN_ALARM-B
UV3-B ALARM
OV3-C ALARM
≥1 383
GEN_ALARM-C
UV3-C ALARM
384
ZPS2 ALARM GEN_ALARM-N
Pick-up signals
GRE130 provides various pick-up signal outputs to select the signal No. for pick-up. The pick-up
signal of IDMT elements are output from ***-INST shown as each scheme logic. When the DT
elements operate, the ***-INST element is NOT output.
28
6 F 2 T 0 1 7 6
3. Technical Description
3.1 Hardware Description
3.1.1 Outline of Hardware Modules
LED1 to LED6 are user-configurable. Each is driven via a logic gate which can be programmed for
OR gate or AND gate operation. Further, each LED has a programmable reset characteristic,
settable for instantaneous drop-off, or for latched operation. A configurable LED can be
programmed to indicate the OR combination of a maximum of 4 elements, and the LED color can be
changed to one of three colors- (Red / Green / Yellow) , the individual status of which can be viewed
on the LCD screen as “Virtual LEDs.” For the setting, see Section 4.2.6.10. For the operation, see
Section 4.2.1.
The TRIP LED and an operated LED if latching operation is selected, must be reset by the user,
29
6 F 2 T 0 1 7 6
either by pressing the RESET key, by energising a binary input which has been programmed for
‘Remote Reset’ operation, or by a communications command. Other LEDs operate as long as a
signal is present. The RESET key is ineffective for these LEDs. Further, the TRIP LED is
controlled with the scheme switch [AOLED] whether it is lit or not by the output of an alarm element
such as OV4 ALARM, UV4 ALARM, etc..
The CB CLOSED and CB OPEN LEDs indicate CB condition. The CB CLOSED LED color can
be changed to one of three colors-(Red / Green / Yellow) .
The LOCAL / REMOTE LED indicates the CB control hierarchy. When the LOCAL LED is lit, the
CB can be controlled using the ○ and | keys on the front panel. When the REMOTE LED is lit,
the CB can be controlled using a binary input signal or via relay communications. When neither of
these LEDs are lit , the CB control function is disabled.
The ▼ key starts the Digest screen (Metering, Virtual LED) view on the LCD. The ▼ key will
scroll the screen through “Virtual LED” → “Metering” →”Indication and back-light off” when the
LCD is in the Digest screen mode.
The ENTER key starts the Main menu indication on the LCD.
The END key clears the LCD indication and turns the LCD back-light off when the LCD is in
the “MAIN MENU”.
The operation keys are used to display the records, status and setting data on the LCD, to input
settings or to change settings.
The USB connector is a B-type connector. This connector is used for connection with a local
personal computer.
Liquid crystal
display
Light emitting
diodes (LED)
Light emitting
diodes (LED)
Control keys
Motor status
Operation keys
To a local PC
30
6 F 2 T 0 1 7 6
Table 3.2.1 shows the AC input signals necessary for the GRE130 model and their respective input
terminal numbers. Their terminal numbers depend on their scheme switch [APPL] setting.
Phase-to- Phase-to- A-B phase A-B phase A phase A phase A-B phase
1-2 phase neutral
voltage voltage voltage voltage voltage voltage voltage
The GRE130 provides 2 (Model 410) or 6 (Model 411 / 412) programmable binary input circuits.
Each binary input circuit is programmable, and provided with the function of Logic level inversion,
detection threshold voltage change and function selection.
The binary input circuit of the GRE130 is provided with a logic level inversion function, a pick-up
and drop-off delay timer function and a detection threshold voltage change as shown in Figure 3.2.1.
Each input circuit has a binary switch BISNS which can be used to select either normal or inverted
operation. This allows the inputs to be driven either by normally open or normally closed contacts.
Where the driving contact meets the contact conditions then the BISNS can be set to “Norm”
(normal). If not, then “Inv” (inverted) should be selected. The pick-up and drop-off delay times can
be set 0.0 to 300.00s respectively.
The binary input detection nominal voltage is programmable by the user, and the setting range varies
depending on the rated DC power supply voltage. In the case that a 110V / 220Vdc rated model is
ordered, the input detection nominal voltage can be set to 48V, 110V or 220V for BI1 and BI2, and
to 110V or 220V for BI3-BI6. In the case of a 24 / 48Vdc model, the input detection nominal voltage
can be set to 12V, 24V or 48V for BI1 and BI2, and to 24V or 48V for BI3-BI6.
The binary input detection threshold voltage (i.e. minimum operating voltage) is normally set at 77V
and 154V for supply voltages of 110V and 220V respectively. In the case of 24V and 48V supplies,
the normal thresholds are 16.8V and 33.6V respectively. Binary inputs can be configured for
operation in a Trip Circuit Supervision (TCS) scheme by setting the [TCSPEN] switch to “Enable”.
For the case where TCS using 2 binary inputs is to be applied (refer to Section 3.3.3), then the
binary input detection threshold of BI1 and BI2 should be set to less than half of the rated dc supply
31
6 F 2 T 0 1 7 6
voltage.
The logic level inversion function, pick-up and drop-off delay timer and detection voltage change
settings are as follow:
Element Contents Range Step Default
BI1SNS – BI6SNS Binary switch Norm/ Inv Norm
BITHR1 * BI1-2 nominal voltage 48 / 110 / 220 110
(12 / 24 / 48 ) (24)
(24 / 48 / 110 ) (48)
BITHR2 * BI3-6 nominal voltage 110 / 220 110
(24 / 48) (24)
(48 / 110) (110)
TCSPEN TCS enable Off / On / Opt-On Off
BI1PUD – BI6PUD Delayed pick-up timer 0.00 - 300.00s 0.01s 0.00
BI1DOD – BI6DOD Delayed drop-off timer 0.00 - 300.00s 0.01s 0.00
*At the PC interface software RSM100 (Relay Setting and Monitoring system), BI threshold voltage
settings are indicated by V1, V2 and V3. The V1, V2 and V3 are distinguished with 11th digit of
ordering code for supply voltage, as shown below,:
Supply voltage (11th digt of ordering cord) V1 V2 V3
110 - 220V (-1x-xx) BITH1 48V 110V 220
BITH2 110V 220V -
48 - 110V (-2x-xx) BITH1 24V 48V 110V
BITH2 48V 110V -
12 - 48V (-Ax-xx) BITH1 12V 24V 48V
BITH2 24V 48V -
Four alarm messages (Alarm1 to Alarm4) can be set. The user can define a text message within 16
characters for each alarm. The messages are valid for any of the input signals BI1 to BI2 or BI6 by
setting. Then when inputs associated with that alarm are raised, the defined text is displayed on the
LCD.
The binary input detection threshold of BI1 and BI2 should be set to less than half of the rated dc
supply voltage.
The logic level inversion function, pick-up and drop-off delay timer and detection voltage change
settings are as follow:
32
6 F 2 T 0 1 7 6
GRE130
(+) (−) BI1PUD BI1DOD [BI1SNS]
BI1 t 0 0 t
BI1 command
BI1
"Norm"
1
"Inv"
BI2PUD BI2DOD [BI2SNS]
BI2 t 0 0 t
BI2 command
BI2
"Norm"
[BITHR1]
1
+
"220V" "Inv"
BI3 +
"110V"
+
"48V"
BI6PUD BI6DOD [BI6SNS]
BI6 t 0 0 t
BI6 BI6 command
"Norm"
[BITHR2] 1
+ "Inv"
"220V"
+
"110V"
0V
Function selection
The input signals BI1 COMMAND to BI6 COMMAND are used for the functions listed in Table
3.2.2. Each input signal can be allocated for one or some of those functions by setting. For the
setting, refer to Section 4.2.6.8.
The Table also shows the signal name corresponding to each function used in the scheme logic and
the LCD indication and driving contact condition required for each function.
[OV1BLK]
BI1 COMMAND OV1 BLOCK
"ON"
[OV2BLK]
OV2 BLOCK
"ON"
[OV3BLK]
OV3 BLOCK
"ON"
[Alarm4]
Alarm 4
"ON"
The logic of BI2 COMMAND to BI6 COMMAND are the same as that of BI1 COMMAND as
shown in Figure 3.2.2.
33
6 F 2 T 0 1 7 6
The binary input signals can be programmed to switch between four settings groups.
Element Contents Range Step Default
BI1SGS – BI6SGS Setting group selection OFF / 1 / 2 OFF
Four alarm messages can be set. The user can define a text message using up to 22 characters for
each alarm. The messages are valid for any of the input signals BI1 to BI6 by setting. Then when
inputs associated with that alarm are raised, the defined text is displayed on the LCD.
34
6 F 2 T 0 1 7 6
≥1
4 GATES
&
TBO
0 t
&
[RESET] "Dw" 0.00 – 10.00s
+ "Dl" S
&
F/F
"Lat"
R
Reset button
+
≥
BI1_COMMAND RMTRST
35
6 F 2 T 0 1 7 6
Settings
The setting elements necessary for binary output relays and their setting ranges are as follows:
Element Range Step Default Remarks
[RESET] Ins Dl / Dw /Lat See Appendix A Output relay reset time. Instantaneous,
delayed, dwell or latched.
TBO 0.00 – 10.00s 0.01s See Appendix A
36
6 F 2 T 0 1 7 6
37
6 F 2 T 0 1 7 6
Watchdog Timer
A hardware timer that is cleared periodically by the relay software is provided, to check that the
relay software is running normally.
The circuit breaker tripping control circuit can be monitored by either one or two binary inputs, as
described below.
The circuit breaker tripping control circuit can be monitored using a binary input. Figure 3.3.1
shows a typical scheme. When the trip circuit is intact , a small current flows through the binary
input, the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker
open and closed conditions. Then the logic signal output of the binary input circuit TC FAIL is "1"
under healthy conditions.
If the trip supply is lost or if a connection becomes open circuit, then the binary input resets and TC
FAIL becomes "0". Figure 3.3.2 shows the scheme logic. A trip circuit fail alarm TCSV is output
when the TC FAIL output is "0". If the trip circuit failure is detected, then “ALARM” LED is lit and
“Err: TC” is displayed in LCD message.
Monitoring is enabled by setting the scheme switch [TCSPEN] to "ON" or "OPT-ON" and one BI is
selected for "TCFAIL". When "OPT-ON" is selected, monitoring is enabled only while the CB is
closed.
GRE130 Circuit Breaker
Binary CB Aux.
Input Contacts
38
6 F 2 T 0 1 7 6
t 0 0 t
TC FAIL TCSV
≥1 1 &
(BI command)
0.4s 0.4s
TC FAIL
(BI command)
CB status “closed”
& ≥1
"OPT-ON"
[TCSPEN]
"ON"
+
The circuit breaker tripping control circuit can be monitored using two binary inputs. Figure 3.3.3
shows a typical scheme. When the trip circuit is intact a small current flows in the photo-couplers,
the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker open
and breaker closed conditions.
If the trip circuit supply is lost or if a connection becomes open circuit then the TCS issues a Trip
Circuit Fail alarm.
Monitoring is enabled by setting scheme switch [TCSPEN] to "ON" or "OPT-ON" and the two BIs
selected for " TCFAIL". When "OPT-ON" is selected, monitoring is enabled only while the CB is
closed. TCS using 2BIs should be applied using BI1 and BI2 for the BI inputs. For TCS using 2BIs
the BI nominal operating voltage ([BITHR1]) should be set to a value of approximately half that of
the trip supply voltage. If the trip supply voltage is 110V (or 24V) , [BITHR1] can be set at "48" (or
"12").
GRE130 Circuit Breaker
Resistor
The resistors connected in series with the binary inputs are to prevent unnecessary tripping of the
circuit breaker if any one component suffers a short-circuit condition. The value of resistance should
be chosen to limit the current flowing through the circuit breaker trip coil to 60mA in the event of a
short circuit of BI1 with the circuit breaker closed. A typical value for a 110V dc rated circuit is
3.3kΩ.
39
6 F 2 T 0 1 7 6
CB CONT_CLS
[CBSMEN]
"ON"
+
Figure 3.3.4 CB State Monitoring Scheme Logic
40
6 F 2 T 0 1 7 6
The LCD messages are shown on the "Auto-supervision" screen, which is displayed automatically
when a failure is detected or displayed by pressing ▼ key. The event record messages are shown on
the "Event record" screen by opening the "Record" sub-menu.
The alarms are retained until the failure is recovered.
The alarms can be disabled collectively by setting the scheme switch [AMF] to "OFF". The setting
is used to block unnecessary alarms during commissioning, test or maintenance.
When the Watchdog Timer detects that the software is not running normally, LCD display and event
recording of the failure may not function normally.
Table 3.3.1 Supervision Items and Alarms
The failure alarm and the relationship between the LCD message and the location of the failure is
shown in Table 6.7.1 in Section 6.7.2.
When a failure is detected by the following supervision items, the trip function is blocked for as long
as the failure exists, and is restored when the failure is removed.
• A/D accuracy check
• Memory monitoring
• Watchdog Timer
When a fault is detected by the AC input imbalance monitoring, the scheme switch [SVCNT]
setting can be used to determine if both tripping is blocked and an alarm is output(ALM&BLK), or
if only an alarm is output (ALM).
41
6 F 2 T 0 1 7 6
3.3.7 Setting
The setting element necessary for the automatic supervision and its setting range are shown in the
table below.
The scheme switch [SVCNT] is set in the "Application" sub-menu. Other scheme switches are set
in the "Scheme sw" sub-menu.
Fault recording is initiated by a tripping command from the GRE130 and the following items are
recorded for one fault:
Date and time
Trip mode
Operating phase
Power system quantities
Up to the 4 most-recent faults are stored as fault records. If a new fault occurs when 4 faults have
been stored, the record of the oldest fault is deleted and the record of the latest fault is then stored.
Trip mode
This shows the protection scheme such as OV1, UV1 etc. that output the tripping command.
Faulted phase
This is the phase to which a tripping command is output.
42
6 F 2 T 0 1 7 6
The events shown in Appendix B are recorded with a 1 ms resolution time-tag when the status
changes. For BI1 to BI6 commands, the user can select the items to be recorded and their status
change mode to initiate recording as below.
One of the following four modes is selectable.
Modes Setting
Not to record the event. N
To record the event when the status changes to "operate". O
To record the event when the status changes to "reset". R
To record the event when the status changes both to "operate" and "reset". B
For the setting, see Section 4.2.6.5. The default setting is "B"
Up to 200 records can be stored. If an additional event occurs after 200 records have been stored,
the oldest event record is overwritten. The LCD display only shows 100 records. All event records
(200 records) can be displayed on a PC. For how to download all of the event records onto a PC refer
to the RSM100 instruction manual.
Disturbance recording is initiated when the overvoltage or undervoltage starter element operates or
a tripping command is initiated. Further, disturbance recording is initiated when a start command is
initiated. The user can configure four disturbance record triggers.
The records include a maximum of 8 analogue signals as shown in Table 3.4.1, 32 binary signals
and the dates and times at which recording started. Any binary signal shown in Appendix B can be
assigned using the binary signal setting of a disturbance record.
43
6 F 2 T 0 1 7 6
The LCD display only shows the dates and times of the disturbance records stored. Details can be
displayed on a PC. For how to obtain disturbance records on a PC, see the RSM software
instruction manual.
The pre-fault recording time can be set between 0.1 and 4.9s and the post-fault recording time can be
set between 0.1 and 3.0s. But the combined duration for the pre-fault and post-fault recording times
is 5.0s or less. The number of records stored depends on the post-fault recording time. The
approximate relationship between the post-fault recording time and the number of records stored is
shown in Table 3.4.2. (Recording time = pre-fault recording time + post-fault recording time)
Note: If the recording time setting is changed, the records stored so far are deleted.
Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored
Settings
The elements necessary for initiating a disturbance recording and their setting ranges are shown in
the table below.
Element Range Step Default Remarks
Time1 0.1-4.9 s 0.1 s 0.3 s Pre--fault recording time
Time2 0.1-4.9 s 0.1 s 3.0 s Post--fault recording time
OV 10.0-200.0 V 0.1 V 120.0 V Overvoltage detection
UV 5.0-130.0 V 0.1 V 60.0 V Undervoltage detection
ZPS 1.0-130.0 V 0.1 V 20.0 V Zero sequence overvoltage detection
NPS 1.0-130.0 V 0.1 V 20.0 V Negative sequence overvoltage detection
Starting disturbance recording using a tripping command or the starter element listed above is
enabled or disabled by setting the following scheme switches.
44
6 F 2 T 0 1 7 6
45
6 F 2 T 0 1 7 6
46
6 F 2 T 0 1 7 6
4. User Interface
4.1 Outline of User Interface
The user can access the relay from the front or rear panel.
Local communication with the relay is also possible using RSM (Relay Setting and Monitoring) via
a USB port. Furthermore, remote communication is also possible using MODBUS communication
via an RS485 port.
This section describes the front panel configuration and the basic configuration of the menu tree for
the local human machine communication ports and HMI (Human Machine Interface).
As shown in Figure 3.1.1, the front panel is provided with a liquid crystal display (LCD), light
emitting diodes (LED), operation keys, and USB type B connector.
LCD
The LCD screen, provided with an 8-line, 16-character display and back-light, provides the user
with information such as records, statuses and settings. The LCD screen is normally unlit, but
pressing ▼ key will display the digest screen and pressing ENTER key will display the main-
menu screen.
These screens are turned off by pressing the END key when viewing the LCD display at the top of
the main-menu. If any display is left for approximately 5 minutes without operation, the back-light
will go off.
LED
There are 14 LED displays. The signal labels and LED colors are defined as follows:
47
6 F 2 T 0 1 7 6
Operation keys
The operation keys are used to display records, status, and set values on the LCD, as well as to input
or change set values. The function of each operation key is as follows:
▼, ▲,
▲
▼
END : Used to end the entering operation, return to the upper screen or turn off the
display.
ENTER : Used to store or establish entries.
RESET key
Pressing the RESET key causes the Trip LED to turn off and latched output relays to be released.
Control keys
The control keys are used for CB control. When the LCD display cursor is not at the CB control
position-(CB close/open , Local / Remote), the Control keys will not function.
○ : Used for CB open operation. When the CB is in the open position, the ○ key does
not function.
48
6 F 2 T 0 1 7 6
② | : Used for CB close operation. When the CB is in the closed position, the |
key does not function
③ L/R : Used for CB control hierarchy (local / remote) change.
CAUTION
The CB close control key | is linked to BO1 and the CB open control key ○ is linked to BO2,
when the control function is enabled.
USB connector
The USB connector is a B-type connector for connection with a local personal computer.
USB port
This connector is a standard B-type connector for USB transmission and is mounted on the front
panel. By connecting a personal computer (PC) to this connector, setting operation and display
functions can be performed.
RS485 port
The RS485 port is used for MODBUS communication to connect between relays and to construct a
network communication system.
The RS485 port is provided on the rear of the relay as shown in Figure 4.1.2.
TB2
TB1
RS485 Port
49
6 F 2 T 0 1 7 6
1 2 1 2
3 4 3 4
5 6
5 6 7 8
7 8 9 10
9 10 11 12
11 12
13 14
for Optional
Communication Port
When the GRE130 is operating normally, the green "IN SERVICE" LED is lit and the LCD is off.
Press the ▼ key when the LCD is off to display the digest screens which are the "Indication",
"Metering", "Latest fault", "Auto-supervision" and "Alarm Display" screens in turn. "Latest fault",
"Auto-supervision" and "Alarm Display" screens are displayed only when there is some data. The
following are the digest screens and can be displayed without entering the menu screens.
Indication
I N D 1 [ 0 0 0 0 0 0 0 0 ]
I N D 2 [ 0 0 0 0 0 0 0 0 ]
50
6 F 2 T 0 1 7 6
Metering
V a n * * . * * V
V b n * * . * * V
V c n * * . * * V
V 0 * * . * * V
V 1 * * . * * V
V 2 * * . * * V
f * * . * * H z
f / t * * . * * H z / s
To clear the latched indications (LEDs, LCD screen of Latest fault) of the latest fault indication,
press RESET key for 3 seconds or more.
For any display, the back-light is automatically turned off after five minutes.
Indication
I N D 2 [ 0 0 0 0 0 0 0 0 ]
Status of element,
Elements depend on user setting. 1: Operate, 0: Not operate (Reset)
Displays in tripping
Latest fault
P h a s e A B C : Faulted phases.
O V 1 : Tripping element
If a fault occurs and a tripping command is output when the LCD is off, the red "TRIP" LED is lit
as well as other configurable LEDs if assigned to trigger by tripping.
Press the ▼ to scroll the LCD screen to read the rest of the messages.
Press the RESET key for more than 3s to reset the LEDs; the Trip LED and configurable LEDs
(LED1 through LED6) are assigned to a latched signal if triggered by tripping.
To return from the menu screen to the digest "Latest fault" screen, do the following:
• Return to the top screen of the menu by repeatedly pressing the END or CANCEL key.
51
6 F 2 T 0 1 7 6
• Press the END key to turn off the LCD when the LCD is displaying the top menu.
If the automatic supervision function detects a failure when the LCD is off, the "Auto-supervision"
screen is displayed automatically, showing the location of the failure, and the "ALARM" LED
lights.
Press the ▼ to display other digest screens in turn including the "Metering" and "Latest fault"
screens.
Press the RESET key to turn off the LEDs. However, if the failure continues, the "ALARM" LED
remains lit.
After recovery from a failure, the "ALARM" LED and "Auto-supervision" display turn off
automatically.
If a failure is detected when any of the screens is displayed, the current screen remains displayed and
the "ALARM" LED lights.
When any of the menu screens is displayed, the RESET key is available. To return to the digest
"Auto-supervision" screen, do the following:
• Return to the top screen of the menu by repeatedly pressing the END or CANCEL key.
Alarm Display
Alarm Display (ALM1 to ALM4)
* * * * * * * * * * * * * *
* * * * * * * * : A L M 1
The four alarm screens can be provided, and their text messages are defined by the user. (For setting,
see Section 4.2.6.8) These alarms are raised by associated binary inputs.
Press the ▼ to display other digest screens in turn including the "Metering" and "Latest fault"
screens.
To clear the Alarm Display, press RESET key. Clearing is available after displaying up to ALM4.
52
6 F 2 T 0 1 7 6
Record
In the "Record" menu, the fault records, event records, disturbance records and counts such as trip
count can be accessed.
53
6 F 2 T 0 1 7 6
Status
The "Status" menu displays the power system quantities, binary input and output status, relay
measuring element status, signal source for time synchronisation (BI or RSM), adjusts clock and
LCD contrast.
Set. (view)
The "Set. (view)" menu displays the relay version, description, relay address and baud rate for
RSM, the current settings of record, status, protection, binary inputs, configurable binary outputs
and configurable LEDs.
Set. (change)
The "Set. (change)" menu is used to change the settings for password, description, relay address and
baud rate for Modbus communication, record, status, protection, binary inputs, configurable binary
outputs and configurable LEDs.
Since this is an important menu and is used to change settings related to relay tripping, it has
password security protection.
Control
The "Control" menu is used to operate the CB. When the cursor (>) is in the Local / Remote position,
the CB control hierarchy change over key L/R is enabled. When the cursor (>) is in the CB
close/open position, the CB control keys ○ and | are enabled.
Since this is an important menu and is related to relay tripping, it has password security protection.
Test
The "Test" menu is used to set test switches and to forcibly operate binary output relays.
When the LCD is off, press the ENTER key to display the top "MAIN MENU" screen and then
proceed to the relay menus.
M A I N M E N U
> R e c o r d
S t a t u s
S e t . ( v i e w )
S e t . ( c h a n g e )
C o n t r o l
T e s t
To display the "MAIN MENU" screen when the digest screen is displayed, press the ▼ key to turn
off the LCD, then press the ENTER key.
Press the END key when the top screen is displayed to turn off the LCD.
An example of the sub-menu screen is shown below. The top line shows the hierarchical layer. The
8th line under some items is not displayed for all of the screens. " ",or " " or " " displayed on the
far right shows that lower or upper lines exist.
To move the cursor downward or upward for setting or for viewing other lines not displayed on the
window, use the ▼ and ▲ keys.
54
6 F 2 T 0 1 7 6
/ 4 S c h e m e s w
T r i p _
> T r i p 1
O f f / O n
B I 1
O f f / O n
O V 1
O f f / O n
U V 1
O f f / O n
Z P S 1
O f F / O n
N P S 1
O f f / O n
F R Q 1
O f f / O n
To return to the higher screen or move from the right side screen to the left side screen in Appendix
D press the END or CANCEL key.
The CANCEL key can also be used to return to the higher screen but it must be used carefully
because it may cancel entries made so far.
To move between screens of the same hierarchical depth, first return to the higher screen and then
move to the lower screen.
/ 1 R e c o r d
> F a u l t
E v e n t
D i s t u r b a n c e
C o u n t e r
55
6 F 2 T 0 1 7 6
/ 2 F a u l t
> V i e w r e c o r d
C l e a r
• Select "View record" to display the dates and times of the fault records stored in the relay from
the top in new-to-old sequence.
/ 3 F a u l t
> ♯ 1 0 1 / J a n / 2 0 1 0
0 0 : 0 0 : 0 0 . 0 1 0
♯ 2 0 1 / J a n / 2 0 1 0
0 0 : 0 0 : 0 0 . 0 0 0
♯ 3 0 1 / J a n / 2 0 1 0
0 0 : 0 0 : 0 0 . 0 0 0
• Move the cursor to the fault record line to be displayed using the ▲ and ▼ keys and press the
ENTER key to display the details of the fault record.
The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys.
/ 4 F a u l t ♯ 1
P r e f a u l t v a l u e s
V a n * * . * * k V
* * * . * °
V b n * * . * * k V
* * * . * °
V c n * * . * * k V
* * * . * °
V a b * * . * * k V
* * * . * °
V b c * * . * * k V
* * * . * °
V c a * * . * * k V
* * * . * °
V p h * * . * * k V
V 0 * * . * * k V
* * * . * °
V 1 * * . * * k V
* * * . * °
V 2 * * . * * k V
* * * . * °
f * * . * * H z
f / t * * . * * H z / s
56
6 F 2 T 0 1 7 6
Note: Phase angles above are expressed taking that of positive sequence voltage (V1) as a reference phase
angle. When the V1 is not available, phase angles are not displayed.
Frequency above is displayed as "0Hz" when only residual voltage (zero sequence voltage) is input to
the relay
C l e a r r e c o r d s
E N D = Y C A N C E L = N
• Press the END (= Y) key to clear all the fault records stored in non-volatile memory.
If all fault records have been cleared, the "Latest fault" screen of the digest screens is not displayed.
/ 2 E v e n t
> V i e w r e c o r d
C l e a r
• Select "View record" to display the events with date from the top in new-to-old sequence.
/ 3 E v e n t
2 4 / A u g / 2 0 1 0 1 0 0
O V 1 ・ A t r i P O n
2 4 / A u g / 2 0 1 0 0 9 9
O V 1 ・ A t r i p O N
2 4 / A u g / 2 0 1 0 9 8
O V 1 ・ A t r i p O n
2 4 / A u g / 2 0 1 0 0 0 2
O V 1 ・ A t r i p O n
2 4 / A u g / 2 0 1 0 0 0 1
O V 1 ・ A t r i p O n
57
6 F 2 T 0 1 7 6
▼
The time is displayed by pressing the key.
/ 3 E v e n t
1 3 : 2 2 : 4 5 . 2 1 1
O V 1 ・ A t r i p O n
1 3 : 2 2 : 4 5 . 2 0 0
O V 1 ・ A t r i p O N
1 3 : 2 2 : 4 5 . 1 1 1
O V 1 ・ A t r i p O n
1 3 : 2 2 : 4 4 . 1 1 1
O V 1 ・ A t r i p O n
1 3 : 2 2 : 4 4 . 1 0 0
O V 1 ・ A t r i p O n
▲
The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys.
C l e a r r e c o r d s
E N D = Y C A N C E L = N
• Press the END (= Y) key to clear all the event records stored in non-volatile memory.
"Data lost" or "E.record CLR" and "F.record CLR" are displayed at the initial setting.
Details of disturbance records can be displayed on the PC screen only (*); the LCD displays only the
recorded date and time for all disturbances stored in the relay. They are displayed in the following
sequence.
(*) For the display on the PC screen, refer to the RSM100 manual.
• Open the top "MAIN MENU" screen by pressing the ENTER key.
58
6 F 2 T 0 1 7 6
/ 2 D i s t u r b a n c e
> V i e w r e c o r d
C l e a r
• Select "View record" to display the date and time of the disturbance records from the top in
new-to-old sequence.
/ 3 D i s t u r b a n c e
♯ 1 0 1 / J a n / 2 0 0 9
0 0 : 0 0 : 0 0 . 0 0 0
♯ 2 0 1 / J a n / 2 0 0 9
0 0 : 0 0 : 0 0 . 0 0 0
♯ 3 0 1 / J a n / 2 0 0 9
0 0 : 0 0 : 0 0 . 0 0 0
The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys.
C l e a r r e c o r d s
E N D = Y C A N C E L = N
• Press the END (= Y) key to clear all the disturbance records stored in non-volatile memory.
• Open the top "MAIN MENU" screen by pressing the ENTER key.
/ 2 C o u n t e r
> V i e w c o u n t e r
C l e a r T r i p s
C l e a r T r i p s A (*)
C l e a r T r i p s B (*)
C l e a r T r i p s C (*)
(*) Note: These settings are only available when single phase External Trip BI functions
59
6 F 2 T 0 1 7 6
are used. In this case, the main "Clear Trips" option is not available.
/ 3 C o u n t e r
T r i p s * * * * * *
T r i p s A * * * * * * (*)
T r i p s B * * * * * * (*)
T r i p s C * * * * * * (*)
(*) Note: These settings are only available when single phase External Trip BI functions
are used. In this case, the main "Trips" option is not available.
The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys.
C l e a r T r i p s ?
E N D = Y C A N C E L = N
C l e a r T r i p s A ?
E N D = Y C A N C E L = N
C l e a r T r i p s B ?
E N D = Y C A N C E L = N
C l e a r T r i p s C ?
E N D = Y C A N C E L = N
• Press the END (= Y) key to clear the count stored in non-volatile memory.
60
6 F 2 T 0 1 7 6
From the sub-menu "Status", the following status condition can be displayed on the LCD:
Metering data of the protected line, apparatus, etc.
Status of binary inputs and outputs
Status of measuring elements output
Status of time synchronisation source
Status of clock adjustment
Status of LCD contrast
The data is updated every second.
/ 1 S t a t u s
> M e t e r i n g
B i n a r y I / O
R e l a y e l e m e n t
T i m e s y n c .
C l o c k a d j u s t .
L C D c o n t r a s t
/ 4 M e t e r i n g
V a n * * . * * k V APPL = 3PP
* * * . * °
V b n * * . * * k V
* * * . * °
V c n * * . * * k V
* * * . * °
V a b * * . * * k V APPL = 3PN
* * * . * °
V b c * * . * * k V
* * * . * °
V c a * * . * * k V
* * * . * °
V p h * * . * * k V APPL = 1PP
61
6 F 2 T 0 1 7 6
V 0 * * . * * k V
* * * . * °
V 1 * * . * * k V
* * * . * °
V 2 * * . * * k V
* * * . * °
f * * . * * H z
f m a x * * . * * H z
f m i n * * . * * H z
f / t * * . * * H z / s
f / t x * * . * * H z / s
f / t n * * . * * H z / s
Note: Phase angles above are expressed taking that of positive sequence voltage (V1) as a reference phase
angle. When the V1 is not available, phase angles are not displayed.
Frequency above is displayed as "0Hz" when only residual voltage (zero sequence voltage) is input to
the relay
/ 2 B i n a r y I / O
I P [ 0 0 0 0 0 0 ]
O P [ 0 0 0 0 0 ]
O P 2 [ 0 0 0 0 ]
Line 1 shows the binary input status. BI1 to BI6 correspond to each binary input signal. For the
binary input signal, see Appendix B and G. The status is expressed with logical level "1" or "0" at
the photo-coupler output circuit. BI3 to BI6 are not available for model 410.
Line 2 shows the binary output status. All binary outputs BO1 to BO4 and FAIL are configurable.
The status of these outputs is expressed with logical level "1" or "0" at the input circuit of the output
relay driver. That is, the output relay is energised when the status is "1".
FAIL is a normally closed contact for detection of a relay fail condition.
Line 3 shows the binary output status for model 412. BO5-8 (OP2) are available only at model 412
62
6 F 2 T 0 1 7 6
/ 2 R y e l e m e n t
A N O V 1 - 3 [ 0 0 0 ]
B N O V 1 - 3 [ 0 0 0 ]
C N O V 1 - 3 [ 0 0 0 ]
A B O V 1 - 3 [ 0 0 0 ]
B C O V 1 - 3 [ 0 0 0 ]
C A O V 1 - 3 [ 0 0 0 ]
O V 1 - 3 [ 0 0 0 ]
A N U V 1 - 3 [ 0 0 0 ]
B N U V 1 - 3 [ 0 0 0 ]
C N U V 1 - 3 [ 0 0 0 ]
A B U V 1 - 3 [ 0 0 0 ]
B C U V 1 - 3 [ 0 0 0 ]
C A U V 1 - 3 [ 0 0 0 ]
U V 1 - 3 [ 0 0 0 ]
V Z P S 1 - 2 [ 0 0 ]
V N P S 1 - 2 [ 0 0 ]
F R Q 1 - 4 [ 0 0 0 0 ]
The operation status of phase and residual overcurrent elements are shown as below.
[ ]
AN OV1-3 OV1 OV2 OV3 A phase OV elements
BN OV1-3 OV1 OV2 OV3 B phase OV element
CN OV1-3 OV1 OV2 OV3 C phase OV element
AB OV1-3 OV1 OV2 OV3 A to B phase OV elements
BC OV1-3 OV1 OV2 OV3 B to C phase OV element
CA OV1-3 OV1 OV2 OV3 C to A phase OV element
OV1-3 OV1 OV2 OV3 OV elements
AN UV1-3 UV1 UV2 UV3 A phase UV element
BN UV1-3 UV1 UV2 UV3 B phase UV element
CN UV1-3 UV1 UV2 UV3 C phase UV element
AB UV1-3 UV1 UV2 UV3 A to B phase UV element
BC UV1-3 UV1 UV2 UV3 B to C phase UV element
CA UV1-3 UV1 UV2 UV3 C to A phase UV element
ZPS1-2 ZPS1 ZPS2 Zero Phase Sequence element
NPS1-2 NPS1 NPS2 - - Negative Phase Sequence element
FRQ1-4 FRQ1 FRQ2 FRQ3 FRQ4 Frequency element
63
6 F 2 T 0 1 7 6
The status of each element is expressed with logical level "1" or "0". Status "1" means the element is
in operation.
The internal clock of the GRE130 can be synchronised with external clocks such as the binary input
signal clock, Modbus or IEC60870-5-103 or SNTP(IEC61850). To display on the LCD whether
these clocks are active (=Act.) or inactive (=Inact.) and which clock the relay is synchronised with,
do the following:
• Select "Status" on the top "MAIN MENU" screen to display the "Status" screen.
• Select "Time sync." to display the status of time synchronisation sources.
/ 2 T i m e s y n c .
* B I : A C T .
M o d b u s : I n a c t .
I E C I n a c t
S N T P I n a c t
The asterisk on the far left shows that the internal clock is synchronised with the marked source
clock. If the marked source clock is inactive, the internal clock runs locally.
Note: If the Binary input signal has not been detected for one hour or more after the last detection, the
status becomes "inactive".
For details of the setting time synchronisation, see Section 4.2.6.6.
To adjust the clock when the internal clock is running locally, do the following:
• Select "Status" on the "MAIN MENU" screen to display the "Status" screen.
• Select "Clock adjust." to display the setting screen.
/ 2 2 6 / A u g / 2 0 1 0
0 0 : 0 0 : 0 0 [ L ]
> M i n u t e
0 _
H o u r
0 _
D a y
2 6 _
M o n t h
8 _
Y e a r
2 0 1 0 _
64
6 F 2 T 0 1 7 6
Lines 1 and 2 show the current date and time. The time can be adjusted only when the clock is
running locally. When[BI], [M] or [S] is active, the adjustment is invalid.
• Enter a numerical value for each item and press the ENTER key. For details on how to enter a
numerical value, see 4.2.6.1.
• Press the END key to adjust the internal clock to the set hours without fractions and return to
the previous screen.
If a date which does not exist in the calendar is set and END is pressed, "**** Error ****" is
displayed on the top line and the adjustment is discarded. Return to the normal screen by pressing the
CANCEL key and adjust again.
/ 2 L C D C o n t r a s t
■ ■ ■ ■
• Press the
▲
or key to adjust the contrast. The characters on the screen become thinner by
▲
The sub-menu "Set. (view)" is used to view the settings made using the sub-menu "Set. (change)".
The following items are displayed:
Relay version
Description
Relay address and baud rate for Modbus communication or optional communication.
Record setting
Status setting
Protection setting
Binary input setting
Binary output setting
LED setting
Control setting
Frequency setting
Enter an item on the LCD to display each item as described in the previous sections.
65
6 F 2 T 0 1 7 6
/ 1 S e t . ( v i e w )
> V e r s i o n
D e s c r i p t i o n
C o m m s
R e c o r d
S t a t u s
P r o t e c t i o n
B i n a r y I / P
B i n a r y O / P
L E D
C o n t r o l
/ 2 V e r s i o n
> R e l a y t y p e
S o f t w a r e .
• Select "Relay type" to display the relay type form and model number. (ex.;GRE130-411A-10-10)
G R E 1 3 0 - 4 1 1 A - 1 0
- 1 0
•Select "Software" to display the relay software type form and version.
(ex.;GS1EM1-03-A)
■ S o f t w a r e
G S 1 E M 1 - 0 3 - *
■ P L C d a t a
P G R E 1 3 0 A * * *
( * * * * * * * * )
66
6 F 2 T 0 1 7 6
4.2.5.2 Settings
The "Set. (change)" sub-menu is used to make or change settings for the following items:
Password
Description
Relay address and IP address
Baud rate in IEC60870-103 or Modbus
IEC 61850 setting
Recording setting
Status setting
Protection setting
Binary input setting
Binary output setting
LED setting
Control setting
Frequency setting
All of the above settings except the password can be seen using the "Set. (view)" sub-menu.
CAUTION
Modification of settings : Care should be taken when modifying settings for "active group",
"scheme switch" and "protection element" in the "Protection" menu. Dependencies exist between the
settings in the various menus, with settings in one menu becoming active (or inactive) depending on
the selection made in another menu. Therefore, it is recommended that all necessary settings changes
be made while the circuit breaker tripping circuit is disconnected.
Alternatively, if it is necessary to make settings changes with the tripping circuit active, then it is
recommended to enter the new settings into a different settings group, and then change the "active
group" setting, thus ensuring that all new settings become valid simultaneously.
67
6 F 2 T 0 1 7 6
The cursor can be moved to the upper or lower lines within the screen by pressing the ▲ and ▼
keys. If a setting (change) is not required, skip the line with the ▲ and ▼ keys.
/ 1 S e t . ( c h a n g e )
> P a s s w o r d
D e s c r i p t i o n
C o m m s
R e c o r d
S t a t u s
P r o t e c t i o n
B i n a r y I / P
B i n a r y O / P
L E D
C o n t r o l
F r e q u e n c y
/ 2 D e s c r i p t i o n
> P l a n t n a m e
D e s c r i p t i o n
A B C D E F G H I J K L M N O P
Q R S T U V W X Y Z a b c d e f
g h i j K l m n o p q r s t u v
w x y z 0 1 2 3 4 5 6 7 8 9 ( )
[ ] @ _ { } * / + - < = > ! “ ♯
$ % & ‘ : ; , . ^ `
• Set the cursor position in the bracket by selecting "→" or "←" and pressing the ENTER key.
• Press the END key to confirm the entry and return to the upper screen.
68
6 F 2 T 0 1 7 6
/ 4 T i m e / S t a r t e r
T i m e 1 _ s
> T i m e 1 2 . 0 s
T i m e 2 2 . 0 s
O V 1 2 0 . 0 V
U V 6 0 . 0 V
Z P S 2 0 . 0 V
N P S 2 0 . 0 V
or key to set a desired value. The value can be raised or lowered by pressing
▲
the or key. ,
• Press the ENTER key to enter the value.
• After completing the setting on the screen, press the END key to return to the upper screen.
To correct the entered numerical value, do the following.
• If it is before pressing the ENTER key, press the CANCEL key and enter the new numerical
value.
• If it is after pressing the ENTER key, move the cursor to the line that is to be corrected by
pressing the ▲ and ▼ keys and enter the new numerical value.
Note: If the CANCEL key is pressed after any entry is confirmed by pressing the ENTER key, all
the entries made so far on the screen concerned are canceled and screen returns to the upper one.
69
6 F 2 T 0 1 7 6
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• When the screen is displayed, press the ENTER key to commence operation using the new
settings, or press the CANCEL key to correct or cancel entries. In the latter case, the screen
will return to the setting screen to enable re-entries. Press the CANCEL key to cancel entries
that have been made so far and to return to the "Set. (change)" sub-menu.
4.2.6.2 Password
For the sake of security of Setting changes and Testing, password protection can be set as follows:
• Select "Set. (change)" on the "MAIN MENU" screen to display the "Setting change" screen.
• Select "Password" to display the "Password" screen.
• Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
S e t . ( c h a n g e )
I n p u t [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• For confirmation, enter the same 4-digit number in the brackets after "Retype".
S e t . ( c h a n g e )
R e t y p e [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• Press the END key to display the confirmation screen. If the retyped number is different from
that first entered, the following message is displayed on the bottom of the "Password" screen
before returning to the upper screen.
"Unmatch passwd!"
Re-entry is then requested.
Password trap
After the password has been set, the password must be entered in order to enter the setting change
screens.
If "Set. (change)" or "Test" is entered on the top "MAIN MENU" screen, the password trap screen
"Password" is displayed. If the password is not entered correctly, it is not possible to move to the
"Setting (change)" or "Test" sub-menu screens.
70
6 F 2 T 0 1 7 6
S e t . ( c h a n g e )
P a s s w o r d [ _ ]
1 2 3 4 5 6 7 8 9 0 <
To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Set. (change)" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
Press CANCEL and RESET keys together for one second on the top "MAIN MENU" screen.
The screen goes off, and the password protection of the GRE130 is canceled. Set the password
again.
To enter the plant name and other data, do the following. The data will be attached to records.
• Select "Set. (change)" on the "MAIN MENU" screen to display the " Set. (change)" screen.
• Select "Description" to display the "Description" screen.
/ 2 D e s c r i p t i o n
> P l a n t n a m e
D e s c r i p t i o n
• To enter the plant name, select "Plant name" on the "Description" screen.
• To enter special items, select "Description" on the "Description" screen.
• To enter the name for Alarm∗, select "Alarm∗" on the "Description" screen.
A B C D E F G H I J K L M N O P
Q R S T U V W X Y Z a b c d e f
g h i j k l m n o p q r s t u v
w x y z 0 1 2 3 4 5 6 7 8 9 ( )
[ ] @ _ { } * / + - < = > ! “ ♯
$ % & ‘ : ; , . ^ `
71
6 F 2 T 0 1 7 6
4.2.6.4 Communication
If the relay is linked with Modbus or optional communication, the relay address must be set. Do this
as follows:
• Select "Set.(change)" on the main "MAIN MENU" screen to display the "Set.(change)" screen.
• Select "Comms" to display the "Comms" screen.
/ 2 C o m m s
> A d d r . / P a r a m .
S w i t c h
• Select "Addr./Param." on the "Comms" screen to enter the relay address number.
/ 3 A d d r . / P a r a m .
M o d b u s _
This setting is displayed if “RS485P” in
> M o d b u s 1
I P 1 ‐ 1 0
I P 1 ‐ 2 0
I P 1 ‐ 3 0
I P 1 ‐ 4 0
S M 1 ‐ 3 0
S M 1 ‐ 4 0
G W 1 ‐ 1 0
G W 1 ‐ 2 0
G W 1 ‐ 3 0
G W 1 ‐ 4 0
I P 2 ‐ 1 0
I P 2 ‐ 2 0
I P 2 ‐ 3 0
I P 2 ‐ 4 0
This setting is displayed if submodel of
S M 2 ‐ 1 0
S M 2 ‐ 2 0 communication type is B or D.
S M 2 ‐ 3 0
S M 2 ‐ 4 0
G W 2 ‐ 1 0
G W 2 ‐ 2 0
G W 2 ‐ 3 0
G W 2 ‐ 4 0
72
6 F 2 T 0 1 7 6
I E C B 1 1
I E C B 2 2
I E C B 3 3
I E C B 4 4
I E C G T 1
I E C A T 1
I E C B T 1
I E C E 3 0
I E C E 4 0
I E C E 5 0
I E C E 6 0
I E C E 7 0
I E C E 8 0
I E C I 1 0
I E C I 2 0
I E C I 3 0
I E C I 4 0
I E C I 5 0
I E C I 6 0
I E C I 7 0
I E C I 8 0
I E C 2 B 1 1
I E C 2 B 2 2
I E C 2 B 3 3
I E C 2 B 4 4
I E C 2 G T 1
I E C 2 E 1 0
I E C 2 E 2 0
I E C 2 E 3 0
I E C 2 E 4 0
I E C 2 E 5 0
I E C 2 E 6 0
I E C 2 E 7 0
I E C 2 E 8 0
I E C 2 I 1 0
I E C 2 I 2 0
73
6 F 2 T 0 1 7 6
I E C 2 I 3 0
I E C 2 I 7 0
I E C 2 I 8 0
This setting is displayed if submodel of communication
S M O D E 0 type is A-D.
G O I N T 1 s
This setting is displayed if submodel of communication
D E A D T 1 s type is A-D and “RS485P” in comms switch settimg
is ”off”.
• Enter the relay address number on the "Modbus" line for Modbus or the "IEC" line for
IEC60870-5-103 and press the ENTER key.
• Enter IP address for IP1-1 to IP1-4, Subnet mask for SM1-1 to SM1-4, Default gateway for
GW1-1 to GW1-4, and SNTP server address for SI1-1 to SI2-4. two SNTP servers are
available.
Enter "0" or "1" on "SMODE" column to set the standard time synchronized mode for SNTP
server. Using low accuracy level of time server, synchronized compensation to maintain
synchronization accuracy may not be done automatically. Therefore enter "1", and synchronized
compensation is done forcibly. The default setting is "0".
Enter the IP address of the device for PG1-1 to PG2-4 if Ping response is checked.
IP address: ∗∗∗. ∗∗∗. ∗∗∗. ∗∗∗ (IP1-1. IP1-2. IP1-3. IP1-4) and (IP2-1. IP2-2. IP2-3. IP2-4)
SM1-1 to SM2-4, GW1-1 to GW2-4, SI1-1 to SI2-4: same as above.
• Press the ENTER key.
74
6 F 2 T 0 1 7 6
• Select "Switch" on the "Comms" screen to select the protocol and transmission speed (baud
rate), etc., for Modbus, IEC60870-5-103 and IEC61850.
/ 3 S w i t c h
R S 4 8 5 B R
> R S 4 8 5 B R
9 . 6 / 1 9 . 2
This setting is displayed if “RS485P” in comms
I E C B L K 0
switch settimg is ”IEC103”.
N o r m a l / B l o c k e d
R S 4 8 5 P 0
O f f / M o d / I E C 1 0 3
E t h e r P 0
T S T M O D 0
O f f / O n
G S E C H K 0
O f f / O n
This setting is displayed if submodel of communication
P I N G C H K 0
type is A0-D0.
O f f / O n
I E C G I 1 0
N o / Y e s
This setting is displayed if “RS485P” in
I E C G I 2 0
comms switch settimg is ”IEC103”.
N o / Y e s
I E C G I 3 0
N o / Y e s
I E C G I 4 0
N o / Y e s
I E C G I 5 0
I E C G I 7 0
N o / Y e s
I E C G I 8 0
N o / Y e s
I E C 2 G I 1 0
This setting is displayed if submodel of
N o / Y e s
communication type is 2 and “RS485P” in
I E C 2 G I 2 0
comms switch settimg is ”IEC103”.
N o / Y e s
75
6 F 2 T 0 1 7 6
I E C 2 G I 3 0
N o / Y e s
I E C 2 G I 4 0
N o / Y e s
N o / Y e s
I E C 2 G I 7 0
N o / Y e s
I E C 2 G I 8 0
N o / Y e s
This setting is displayed if “RS485P” in comms
I E C N F I 0
switch settimg is ”IEC103”.
1 . 2 / 2 . 4
<RS485BR>
This line is to select the baud rate when the Modbus or IEC60870-5-103 protocols are applied.
<IECBLK>
Enter 1(=Blocked) to block the monitor direction in the IEC60870-5-103 communication.
<IECNFI >
This line is to select the normalized factor (1.2 or 2.4) of the current measurand.
<IECGI1 - 8 >
These lines are to use the GI (General Interrogation) or not for user customized signals. If GI is to be
used , enter 1(=Yes).
<RS485P>
This line is to select the communication protocol when the MODBUS or IEC60850-5-103 system
applied.
<EtherP>
This line is to select the communication protocol when the IEC61850 system applied.
<61850BLK>
Select 1 (=Blocked) to block transmission from relay to BCU for IEC61850 communication. When
using the IEC61850 communication, select 0 (=Normal).
<TSTMOD>
Select 1 (=On) to set the test mode in IEC61850 communication.
<GSECHK>
This function is to alarm if any one of the GOOSE messages written in a GOOSE subscribe file
cannot be received.
Select 1 (=On) to execute a GOOSE receive check for IEC61850 communication.
<PINGCHK>
This function is to check the health of the network by regularly sending a ‘Ping’ to IP address which
is set on PG∗-∗.
Select 1 (=On) to execute a ‘Ping’ response check.
76
6 F 2 T 0 1 7 6
/ 2 R e c o r d
> E v e n t
D i s t u r b a n c e
C o u n t e r
/ 3 E v e n t
B I 1 c o m m . _
> B I 1 c o m m . 3
N / O / R / B
B I 2 c o m m . 3
N / O / R / B
B I 3 c o m m . 3
N / O / R / B
B I 4 c o m m . 3
N / O / R / B
B I 5 c o m m . 3
N / O / R / B
B I 6 c o m m . 3
N / O / R / B
• Enter 0(=None) or 1(=Operate) or 2(=Reset) or 3(=Both) for BI command trigger setting and
press the ENTER key.
/ 3 D i s t u r b a n c e
> T i m e / S t a r t e r
S c h e m e s w
B i n a r y s i g .
77
6 F 2 T 0 1 7 6
/ 4 T i m e / S t a r t e r
T i m e 1 _ s
> T i m e 1 2 . 0 s
T i m e 2 2 . 0 s
O V 1 2 0 . 0 V
U V 6 0 . 0 V
Z P S 2 0 . 0 V
N P S 2 0 . 0 V
/ 4 S c h e m e s w
T r i p _
> T r i p 1
O f f / O n
B I 1
O f f / O n
O V 1
O f f / O n
U V 1
O f f / O n
Z P S 1
O f f / O n
N P S 1
O f f / O n
F R Q 1
O f f / O n
D F R Q 1
O f f / O n
/ 4 B i n a r y s i g .
S I G 1 _
> S I G 1 5 1
S I G 2 5 1
S I G 3 5 1
S I G 4 5 1
78
6 F 2 T 0 1 7 6
S I G 3 2 5 1
/ 3 C o u n t e r
> S c h e m e s w
A l a r m s e t
/ 4 S c h e m e s w
T C S P E N _
> T C S P E N 1
O f f / O n / O p t - O n
C B S M E N 1
O f f / O n
T C A E N 1
O f f / O n
/ 4 A l a r m s e t
T C A L M _
> T C A L M 1 0 0 0 0
4.2.6.6 Status
/ 2 S t a t u s
> M e t e r i n g
T i m e s y n c .
This setting is displayed if submodel of
T i m e z o n e
communication type is A-D.
79
6 F 2 T 0 1 7 6
/ 3 M e t e r i n g
D i s p l a y _
> D i s p l a y 1
P r i / S e c
/ 3 T i m e s y n c .
T i m e s y n c . _
> T i m e s y n c . 1
O f f / B I / M o d / 1 0 3 /
S N T P
When the calendar clock is synchronized with the SNTP time standard, it is possible to transform
GMT to the local time.
• Select "Time zone" to display the "Time zone" screen.
• Enter the difference between GMT and local time. Enter numerical values to GMT (hours) and
80
6 F 2 T 0 1 7 6
/ 3 T i m e z o n e .
G M T _
> G M T + 0 h r s
G M T m + 0 m i n
4.2.6.7 Protection
The GRE130 can have 2 setting groups for protection in order to accommodate changes in the
operation of the power system, one setting group is assigned active. To set the protection, do the
following:
• Select "Protection" on the "Set. (change)" screen to display the "Protection" screen.
/ 2 P r o t e c t i o n
> C h a n g e a c t . g p .
C h a n g e s e t
C o p y g p .
/ 3 C h a n g e a c t .
g p .
A c t i v e g p . _
> A c t i v e g p . 1
/ 3 A c t g p . = 1
> C o m m o n
G r o u p 1
G r o u p 2
81
6 F 2 T 0 1 7 6
/ 4 C o m m o n
A P P L _
> A P P L 1
1 P P / 1 P N / 2 P P / 2 P Z
3 P N / 3 P V / 3 P P
A O L E D
O f f / O n
<APPL>
• Enter 0(=1PP), 1(=1PN), 3(=2PP), 4(=2PZ), 5(=3PN), 6(=3PV) or 7(=3PP) to set the voltage
input state and press the ENTER key.
<AOLED>
This switch is used to control the “TRIP” LED light when an alarm element is output.
• Enter 1 (=On) to illuminate the “TRIP” LED when an alarm element outputs, and press the
ENTER key. If not, enter 0 (=Off) and press the ENTER key.
/ 4 G r o u p *
> P a r a m e t e r
T r i p
/ 5 P a r a m e t e r
> L i n e n a m e
V T r a t i o
82
6 F 2 T 0 1 7 6
/ 6 V T r a t i o
P V T _
> P V T 1 0 0
R V T 1 0 0
/ 5 T r i p
> S c h e m e s w
P r o t . e l e m e n t
/ 6 S c h e m e s w
> A p p l i c a t i o n
O V p r o t .
U V p r o t .
Z P S p r o t .
N P S p r o t .
F R Q p r o t .
/ 7 A p p l i c a t i o n
S V C N T _
> S V C N T 1
A L M & B L K / A L M
<SVCNT>
Set the alarming and tripping block, or only alarming when a failure is detected by the automatic
supervision and AC input imbalance supervision.
• Enter 0(=ALM&BLK, alarming and tripping block) or 1(=ALM, only alarming) and press the
ENTER key.
83
6 F 2 T 0 1 7 6
/ 7 O V p r o t .
O V 1 E N _
> O V 1 E N 1
O f f / D T / I M D T / C
O V 2 E N 1
O f f / D T / I M D T / C
O V 3 E N 1
O f f / O n
<OV1EN>, <OV2EN>
To set the OV1 and OV2 delay type, do the following.
• Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If
disabling the OV1 or OV2, enter 0 (=Off) and press the ENTER key.
<OV3EN>
• Enter 1 (=On) to enable the OV3, and press the ENTER key. If disabling the OV3, enter 0
(=Off) and press the ENTER key.
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
/ 7 U V p r o t .
U V 1 E N _
> U V 1 E N 1
O f f / D T / I M D T / C
U V 2 E N 1
O f f / D T / I M D T / C
U V 3 E N 1
O f f / O n
V B L K E N 1
O f f / O n
84
6 F 2 T 0 1 7 6
<UV1EN>, <UV2EN>
To set the UV1 and UV2 delay type, do the following.
• Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If
disabling the UV1 or UV2, enter 0 (=Off) and press the ENTER key.
<UV3EN>
• Enter 1 (=On) to enable the UV3, and press the ENTER key. If disabling the UV3, enter 0
(=Off) and press the ENTER key.
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
<VBLKEN>
• Enter 1 (=On) to enable the UV blocking and press the ENTER key. If disabling the UV
blocking, enter 0 (=Off) and press the ENTER key.
/ 7 Z P S p r o t
Z P S 1 E N _
> Z P S 1 E N 1
O f f / D T / I D M T / C
Z P S 2 E N 1
O f f / D T / I D M T / C
<ZPS1EN>, <ZPS2EN>
To set the ZPS1 and ZPS2 time delayed type, do the following.
• Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If
disabling the ZPS1 or ZPS2, enter 0(=Off) and press the ENTER key.
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
85
6 F 2 T 0 1 7 6
/ 7 N P S p r o t
N P S 1 E N _
> N P S 1 E N 1
O f f / D T / I D M T / C
N P S 2 E N 1
O f f / D T / I D M T / C
<NPS1EN>, <NPS2EN>
To set the NPS1 and NPS2 time delayed type, do the following.
• Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If
disabling the NPS1 or NPS2, enter 0(=Off) and press the ENTER key.
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
/ 7 F R Q p r o t
F T 1 _
> F T 1 1
O f f / O / U / B / O O / U U
D F T 1 1
O f f / R / D / B o t h
L o g i c 1
L 1 / L 2 / L 3 / L 4 / L 5
F T 2 0
O f f / O / U / B / O O / U U
D F T 2 0
O f f / R / D / B o t h
L o g i c 2
L 1 / L 2 / L 3 / L 4 / L 5
F T 3 0
86
6 F 2 T 0 1 7 6
O f f / O / U / B / O O / U U
D F T 3 0
O f f / R / D / B o t h
L o g i c 3
L 1 / L 2 / L 3 / L 4 / L 5
F T 4 0
O f f / O / U / B / O O / U U
D F T 4 0
O f f / R / D / B o t h
L o g i c 4
L 1 / L 2 / L 3 / L 4 / L 5
<FT1>,<FT2>,<FT3>,<FT4>
DFT1, DFT2, DFT3 and DFT4 select the frequency rate-of-change protection.
• Enter 0 or 1 or 2 or 3 and press the ENTER key.
Enter 0 (= Off) not to use the frequency rise rate nor frequency decay rate protection.
Enter 1 (= R) to use only the frequency rise rate protection.
Enter 2 (= D) to use only the frequency decay rate protection.
Enter 3 (= Both) to use both the frequency rise rate and frequency decay rate protections.
Logic 1, Logic 2, Logic 3 and Logic 4 select the tripping combination of the frequency protection
and the frequency rate-of-change protection.
• Enter 0 (=L1) or 1 (=L2) or 2 (=L3) or 3 (=L4) or 4 (=L5) and press the ENTER key.
Refer to Table 2.2.1 for setting.
87
6 F 2 T 0 1 7 6
/ 6 P r o t . e l e m e n t
> O V p r o t .
U V p r o t .
Z P S p r o t
N P S p r o t
F R Q p r o t
/ 7 O V p r o t .
O V 1 _ V
O V 1 - C 0 . 0 0 ditto
O V 2 - c 0 . 0 0 ditto
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
88
6 F 2 T 0 1 7 6
/ 7 U V p r o t .
U V 1 _ V
U V 1 - c 0 . 0 0 ditto
U V 2 - c 0 . 0 0 ditto
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
/ 7 Z P S p r o t
Z P S 1 _ V
89
6 F 2 T 0 1 7 6
Z P S 1 - c 0 . 0 0 ditto
Z P S 2 - c 0 . 0 0 ditto
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
/ 7 N P S p r o t
N P S 1 _ V
N P S 1 - c 0 . 0 0 ditto
N P S 2 - c 0 . 0 0 ditto
90
6 F 2 T 0 1 7 6
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
• Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
/ 7 F R Q p r o t
F 1 1 _ H z
• After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
91
6 F 2 T 0 1 7 6
• Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
/ 3 C o p y A t o B
> A _
B _
• Enter the group number to be copied in line A and press the ENTER key.
• Enter the group number to be overwritten by the copy in line B and press the ENTER key.
The logic level of binary input signals can be inverted by setting before entering the scheme logic.
Inversion is used when the input contact cannot meet the requirements described in Table 3.2.2.
• Select "Binary I/P" on the "Set. (change)" sub-menu to display the "Binary I/P" screen.
/ 2 B i n a r y I / P
> B I S t a t u s
B I 1
B I 2
B I 3
B I 4
B I 5
B I 6
A l a r m 1 T e x t
A l a r m 2 T e x t
A l a r m 3 T e x t
A l a r m 4 T e x t
The binary input nominal operating voltage can be selected in GRE130. Control voltages of 24V,
48V, 110V and 220V are supported.
BI1 and BI2 can be set to one of three nominal voltages - 48 / 110 / 220V ( or 12 / 24 / 48V)
BI3 to BI6 can be set to one of two nominal voltages – 110 / 220V (or 24 / 48V)
Note: The nominal voltage 48V (or 12V) of BI1 and BI2 is used for Trip Circuit Supervision using 2
Binary inputs. See section 3.3.3.
The threshold voltage options of 48-220V and 12-48V correspond to the dc auxiliary voltage
supply rating of the relay models.
To set the binary inputs threshold voltage, do the following:
• Select "BI Status" on the "Binary I/P" screen to display the "BI Status" screen.
92
6 F 2 T 0 1 7 6
/ 3 B I S t a t u s
B I T H R 1
> B I T H R 1 1
4 8 / 1 1 0 / 2 2 0
B I T H R 2 0
1 1 0 / 2 2 0
<BITHR1>
To set the threshold voltage for Binary Inputs 1 and 2 , do the following.
• Enter 0(=48V) or 1(=110V) or 2(=220V) and press the ENTER key.
<BITHR2>
To set the threshold voltage for Binary Inputs 3 to 6 , do the following.
• Enter 0(=110V) or 1(=220V) and press the ENTER key.
/ 3 B I 1
> T i m e r s
F u n c t i o n s
A B C D E F G H I J K L M N O P
Q R S T U V W X Y Z a b c d e f
g h i j k l m n o p q r s t u v
w x y z 0 1 2 3 4 5 6 7 8 9 ( )
[ ] @ _ { } * / + - < = > ! “ ♯
$ % & ‘ : ; , . ^ `
• Enter the characters (up to 22 characters) according to the text setting method.
After setting, press the ENTER key to display the "BI∗" screen.
93
6 F 2 T 0 1 7 6
Setting timers
• Select "Timers" on the "BI" screen to display the "Timers" screen.
/ 4 T i m e r s
B I 1 P U D _ s
• After setting, press the END key to return to the "BI∗" screen.
Setting Functions
• Select "Functions" on the "BI" screen to display the "Functions" screen.
/ 4 F u n c t i o n
B I 1 S N S _
> B I 1 S N S 0
N o r m / I n v
B I 1 S G S 0
O f f / 1 / 2
O V 1 B L K 0
O f f / O n
O V 2 B L K 0
O f f / O n
O V 3 B L K 0
O f f / O n
U V 1 B L K 0
O f f / O n
U V 2 B L K 0
O f f / O n
U V 3 B L K 0
O f f / O n
Z P S B L K 0
O f f / O n
N P S B L K 0
O f f / O n
F R Q B L K 0
O f f / O n
• To set the Binary Input Sense, enter 0(=Normal) or 1(=Inverted) and press the ENTER key.
• After setting, press the END key to return to the "BI∗" screen.
94
6 F 2 T 0 1 7 6
<BI1SNS>
<BI1SGS>
<Others>
• Enter 1(=On) to set the function and press the ENTER key. If not setting the function, enter
0(=Off) and press the ENTER key.
• After setting, press the END key to return to the "BI∗" screen.
CAUTION
When having changed the binary output settings, release the latch state on the digest screen by
pressing the RESET key for more than 3 seconds.
To configure the binary output signals, do the following:
2 B i n a r y O / P
> B O 1
B O 2
B O 3
B O 4
Note: The setting is required for all the binary outputs. If any of the binary outputs are not used, enter
0 to logic gates #1 to #4 in assigning signals.
95
6 F 2 T 0 1 7 6
• Select the output relay number (BO number) and press the ENTER key to display the "BO∗"
screen.
/ 3 B O ∗
> L o g i c / R e s e t
F u n c t i o n s
/ 4 L o g i c / R e s e t
L o g i c _
> L o g i c 0
O R / A N D
R e s e t 0
I n s / D I / D w / L a t
• Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key.
Assigning signals
• Select "Functions" on the "BO∗" screen to display the "Functions" screen.
/ 4 F u n c t i o n s
I n ♯ 1 _
> I n ♯ 1 - - -
I n ♯ 2 - - -
I n ♯ 3 - - -
I n ♯ 4 - - -
T B O 0 . 2 0 s
• Assign signals to gates (In #1 to #4 of “---”) by entering the number corresponding to each signal
referring to Appendix A. Do not assign the signal numbers 170 to 176 (signal names: "BO1 OP"
to "BO8 OP"). And set the delay time of timer TBO.
Note: If signals are not assigned to all the gates #1 to #6, enter 0 for the unassigned gate(s).
Repeat this process for the outputs to be configured.
96
6 F 2 T 0 1 7 6
CAUTION
The CB close control key | is linked to BO1 and the CB open control key ○ is linked to BO2,
when the control function is enabled.
4.2.6.10 LEDs
Six of the LEDs provided by the GRE130 are user-configurable. A configurable LED can be
programmed to indicate an OR combination of a maximum of 4 elements, the individual status of
which can be viewed on the LED screen as “Virtual LEDs.” The signals listed in Appendix A can be
assigned to each LED as follows.
CAUTION
When having changed the LED settings, release the latch state on the digest screen by pressing
the RESET key for more than 3 seconds.
Selection of LEDs
• Select "LED" on the "Set. (change)" screen to display the "LED" screen.
/ 2 L E D
> L E D
V i r t u a l L E D
/ 3 L E D
> L E D 1
L E D 2
L E D 3
L E D 4
L E D 5
L E D 6
C B C L O S E D
Note: The setting is required for all the LEDs. If any of the LEDs are not used, enter 0 to logic gates
#1 to #4 in assigning signals.
• Select the LED number and press the ENTER key to display the "LED∗" screen.
/ 4 L E D ∗
> L o g i c / R e s e t
F u n c t i o n s
L E D C o l o r
97
6 F 2 T 0 1 7 6
/ 5 L o g i c / R e s e t
L o g i c _
> L o g i c 0
O R / A N D
R e s e t 0
I n s t / L a t c h
• Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key.
• Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key.
Assigning signals
• Select "Functions" on the "LED∗" screen to display the "Functions" screen.
/ 5 F u n c t i o n s
I n # 1 _
> I n # 1 - - -
I n # 2 - - -
I n # 3 - - -
I n # 4 - - -
• Assign signals to gates (In #1 to #4 of “---”) by entering the number corresponding to each signal
referring to Appendix A.
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).
/ 5 L E D C o l o r
C o l o r _
> C o l o r 0
R / G / Y
98
6 F 2 T 0 1 7 6
/ 3 V i r t u a l L E D
> I N D 1
I N D 2
• Select the IND number and press the ENTER key to display the "IND∗" screen.
/ 4 I N D 1
> R e s e t
F u n c t i o n s
/ 5 R e s e t
R e s e t _
> R e s e t 0
I n s t / L a t c h
• Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key.
• Press the END key to return to the "IND∗" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.
Assigning signals
• Select "Functions" on the "IND∗" screen to display the "Functions" screen.
/ 5 F n c t i o n s
B I T 1 _
> B I T 1 - - -
B I T 2 - - -
B I T 3 - - -
B I T 4 - - -
B I T 5 - - -
B I T 6 - - -
B I T 7 - - -
B I T 8 - - -
99
6 F 2 T 0 1 7 6
• Assign signals to bits (1 to 8) by entering the number corresponding to each signal referring to
Appendix A.
Note: If signals are not assigned to all the bits 1 to 8, enter 0 for the unassigned bit(s).
4.2.6.11 Control
The GRE130 can control the Circuit Breaker(CB) open / close by using the front panel keys.
The interlock function can be used to block the Circuit Breaker(CB) close command with interlock
signals from binary inputs or from a communication command.
To set the control function and interlock function, do the following:
• Select "Control" on the "Set. (change)" screen to display the "Control" screen.
/ 2 C o n t r o l
C o n t r o l _
> C o n t r o l 0
D i s a b l e / E n a b l e
I n t e r l o c k 0
D i s a b l e / E n a b l e
• Enter 0(=Disable) or 1(=Enable) to select the control function to be in use or not in use and press
the ENTER key.
• Enter 0(=Disable) or 1(=Enable) to select the interlock function to be in use or not in use and
press the ENTER key.
Note: When the Control function is disabled, both the "Local" LED and the "Remote" LED are not
lit, and the sub-menu "Control" on the LCD is not displayed.
4.2.6.12 Frequency
Setting of the system frequency for the GRE130 relay for 50Hz or 60Hz.
To change the system frequency, do the following:
• Select "Frequency" on the "Set. (change)" screen to display the "Frequency" screen.
/ 2 F r e q u e n c y
F r e q u e n c y _
> F r e q u e n c y 0
5 0 H z / 6 0 H z
• Enter 0(=50Hz) or 1(=60Hz) to select the system frequency setting 50Hz or 60Hz and press the
ENTER key.
100
6 F 2 T 0 1 7 6
CAUTION
When having changed the system frequency settings, the GRE130 must reboot to enable the
setting change.
When having changed the system frequency, the frequency protection setting value must be
changed for the system frequency.
4.2.7 Control
The sub-menu "Control" enables the Circuit Breaker(CB) control function from the front panel keys
- ○ , | and L/R .
Note: When the Control function is disabled, both the "Local" LED and the "Remote" LED are not
lit, and the sub-menu "Control" on the LCD is not displayed.
/ 1 C o n t r o l
> P a s s w o r d ( C t r l )
L o c a l / R e m o t e
C B c l o s e / o p e n
/ 1 C o n t r o l
P a s s w o r d ( C t r l )
> L o c a l / R e m o t e
C B c l o s e / o p e n
/ 1 C o n t r o l
P a s s w o r d ( C t r l )
L o c a l / R e m o t e
> C B c l o s e / o p e n
101
6 F 2 T 0 1 7 6
4.2.7.3 Password
For the sake of security of control password protection can be set as follows:
• Select "Control" on the "MAIN MENU" screen to display the "Control" screen.
• Select "Password" to display the "Password" screen.
• Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
C o n t r o l
I n p u t [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• For confirmation, enter the same 4-digit number in the brackets after "Retype".
C o n t r o l
R e t y p e [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• Press the END key to display the confirmation screen. If the retyped number is different from
that first entered, the following message is displayed on the bottom of the "Password" screen
before returning to the upper screen.
"Unmatch passwd!"
Re-entry is then requested.
Password trap
After the password has been set, the password must be entered in order to enter the control screens.
If "Control" is entered on the "MAIN MENU" screen, the password trap screen "Password" is
displayed. If the password is not entered correctly, it is not possible to move to the "Control"
sub-menu screens.
C o n t r o l
P a s s w o r d [ _ ]
1 2 3 4 5 6 7 8 9 0 <
To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Test" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
102
6 F 2 T 0 1 7 6
Press the CANCEL and RESET keys together for one second on the "MAIN MENU" screen.
The password protection for the GRE130 is canceled. Set the password again.
4.2.8 Testing
The sub-menu "Test" provides such functions as disabling the automatic monitoring function and
forced operation of binary outputs.
Note: When operating the "Test" menu, the "IN SERVICE" LED is flickering. But if an alarm occurs
during the test, the flickering stops. The "IN SERVICE" LED flickers only in a testing state.
The automatic monitor function (A.M.F.) can be disabled by setting the switch [A.M.F] to "OFF".
Disabling the A.M.F. inhibits trip blocking even in the event of a failure of the items that are being
monitored by this function. It also prevents failures from being displayed on the "ALARM" LED
and LCD described in Section 4.2.1. No events related to A.M.F. are recorded, either.
Disabling A.M.F. is useful for blocking the output of unnecessary alarms during testing.
• Select "Test" on the top "MAIN MENU" screen to display the "Test" screen.
/ 1 T e s t
> P a s s w o r d ( T e s t )
S w i t c h
B i n a r y O / P
/ 2 S w i t h
A . M . F _
> A . M . F 1
O f f / O n
U V T S T 0
O f f / O n
• Enter 0(=Off) to disable the A.M.F. and press the ENTER key.
• Enter 1(=On) for UVTST to disable the UV block when testing UV elements and press the
ENTER key.
It is possible to forcibly operate all binary output relays for checking connections to external
103
6 F 2 T 0 1 7 6
devices. Forced operation can be performed on one or more binary outputs at a time.
• Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. Then the LCD
displays the name of the output relay.
/ 2 B i n a r y O / P
B O 1 _
> B O 1 0
D i s a b l e / E n a b l e
B O 2 0
D i s a b l e / E n a b l e
B O 3 0
D i s a b l e / E n a b l e
B O 4 0
D i s a b l e / E n a b l e
F A I L 0
D i s a b l e / E n a b l e
• Enter 1(=Enable) and press the ENTER key to forcibly operate the output relays.
• After completing the entries, press the END key. Then the LCD displays the screen shown
below.
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the assigned output relays.
4.2.8.3 Password
For the sake of security during testing, password protection can be set as follows:
• Select "Test" on the "MAIN MENU" screen to display the "Test" screen.
• Select "Password" to display the "Password" screen.
• Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
T e s t
I n p u t [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• For confirmation, enter the same 4-digit number in the brackets after "Retype".
104
6 F 2 T 0 1 7 6
T e s t
R e t y p e [ _ ]
1 2 3 4 5 6 7 8 9 0 <
• Press the END key to display the confirmation screen. If the retyped number is different from
that first entered, the following message is displayed on the bottom of the "Password" screen
before returning to the upper screen.
"Unmatch passwd!"
Re-entry is then requested.
Password trap
After the password has been set, the password must be entered in order to enter the setting change
screens.
If "Test" is entered on the "MAIN MENU" screen, the password trap screen "Password" is
displayed. If the password is not entered correctly, it is not possible to move to the "Test" sub-menu
screens.
T e s t
P a s s w o r d [ _ ]
1 2 3 4 5 6 7 8 9 0 <
To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Test" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
Press the CANCEL and RESET keys together for one second on the "MAIN MENU" screen.
The screen will go off, and the password protection of the GRE130 is cancelled. Set the password
again.
105
6 F 2 T 0 1 7 6
106
6 F 2 T 0 1 7 6
Figure 4.6.1 shows an example of a substation automation system using Ethernet-based IEC 61850
communication.
or TX
107
6 F 2 T 0 1 7 6
When the LCD is not evident or not displayed clearly, it may be that the contrast adjustment for the
LCD may not be appropriate. To adjust the contrast of the LCD screen on any of the screens, do the
following:
• Press ▼ and ▲ ,at same time for 3 seconds or more to shift to the LCD contrast adjustment
mode.
L C D C o n t r a s t
■ ■ ■ ■
• Press the
▲
key all LEDs are lit and white dots will appear on the whole LCD screen.
The colors of the configurable LEDs (LED1-6) can be chosen in the user setting color.
CB CLOSED CB OPEN LOCAL REMOTE
IN SERVICE
TRIP
User configurable
LEDs (LED1-6)
ALARM
RELAY FAIL
• Release
▲
108
6 F 2 T 0 1 7 6
5. Installation
5.1 Receipt of Relays
When relays are received, carry out an acceptance inspection immediately. In particular, check for
damage during transportation, and if any is found, contact the vendor.
Always store the relays in a clean, dry environment.
127
5
14
117 13 5
The attachment kits can be mounted on a panel thickness of 1 – 2.5mm when the M4x8 screws
included with the kit are used. When mounted on a panel thickness of 2.5-4.5mm, M4x10 screws
together with some spacing washers should be used.
109
6 F 2 T 0 1 7 6
+0.2
217 -0.2
+0.2
-0.2
160
110
6 F 2 T 0 1 7 6
Fig. 5.2.3 Side view of GRE130 showing the positions of the mounting attachment kit
Fig. 5.2.4 Rear view of GRE130 showing the screw location for the mounting attachment kits
5.2.2 Dimensions
111
6 F 2 T 0 1 7 6
The voltage input and power supply terminals (TB1 or TB2) can be connected from both sides.
The binary input , binary output and RS485 communication terminal is a single side connected
terminal block.
The relay terminal block size and the clearance between the terminals are shown at Fig 5.2.4.
112
6 F 2 T 0 1 7 6
17 24 17 24 42
6.35
8.7
8.7
6.35
6.35
7.62
10.0
10.0
7.62
7.62
CAUTION
• Do not pass the relay unit to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
• Place the relay unit on an anti-static surface, or on a conducting surface which is at the same
potential as yourself.
• Do not place the relay unit in polystyrene trays.
It is strongly recommended that detailed investigations on electronic circuitry should be carried out
in a Special Handling Area.
113
6 F 2 T 0 1 7 6
114
6 F 2 T 0 1 7 6
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by monitoring which circuits
function when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests
These tests are performed for the following functions that are fully software-based.
Measuring elements
Metering and recording
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other external
equipment.
6.2 Cautions
6.2.1 Safety Precautions
CAUTION
• When connecting the cable to the rear of the relay, firmly fix it to the terminal block and attach
the cover provided for the terminal block .
• Before checking the interior of the relay, be sure to turn off the power.
Failure to observe any of the precautions above may cause electric shock or malfunction.
115
6 F 2 T 0 1 7 6
CAUTION
• When the power is on, do not draw out/insert the relay unit.
• Before turning the power on, check the following:
- Make sure the polarity and voltage of the power supply are correct.
- Make sure the VT circuit is not short-circuited.
• Be careful to ensure that the relay is not damaged due to an overcurrent or overvoltage.
• If settings are changed for testing, remember to reset them to the original settings.
Failure to observe any of the precautions above may cause damage or malfunction of the relay.
6.3 Preparations
Test equipment
Relay settings
Before starting the tests, it must be specified whether the tests will use the user’s settings or the
default settings.
For the default settings, see the Appendix G Relay Setting Sheet.
Visual inspection
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the relay conform to the user’s
specification. The items are: relay type and model, AC voltage and frequency ratings, and auxiliary
supply voltage rating.
Local PC
When using a local PC, connect it to the relay via the USB port on the front of the relay. RSM100
software is required to run the PC.
For full details, see separate volume "PC INTERFACE RSM100".
116
6 F 2 T 0 1 7 6
This test ensures that the LCD, LEDs and keys function correctly.
• Apply the rated supply voltage and check that the LCD is off and the "IN SERVICE" LED is lit
green.
Note: If there is a failure, the LCD will display the "ERR: " screen when the supply voltage is applied.
• Press
▲
key for 3 seconds or longer and check that white dots appear on the whole screen and
that all LEDs are lit.
Operation keys
• Press the ENTER key when the LCD is off and check that the LCD displays the "MAIN
MENU" screen. Press the END key to turn off the LCD.
• Press the ENTER key when the LCD is off and check that the LCD displays the "MAIN
MENU" screen. Press any keys to check that they operate.
GRE130
TB2 -13
BI1
-14 BI2
BI3
BI4
- 19 BI5
BI6
- 20
+ TB1 - 13
power
supply − - 14
-12
117
6 F 2 T 0 1 7 6
/ 2 B i n a r y I / O
I P [ 0 0 0 0 0 0 ]
O P [ 0 0 0 0 0 ]
• Apply the rated supply voltage to terminals 13-14, 15-16, 17,18,19,20-21 of terminal block
TB2.
Check that the status display corresponding to the input signal (IP) changes from 0 to 1. (For
details of the binary input status display, see Section 4.2.4.2.)
The user will be able to perform this test from one terminal to another or for all the terminals at once.
This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers and
output relays. Operation of the output contacts is monitored at the output terminal. The output
contact and corresponding terminal number are shown in Appendix G.
• Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. The LCD displays
the name of the output relay.
/ 2 B i n a r y O / P
B O 1 _
> B O 1 0
D i s a b l e / E n a b l e
B O 2 0
D i s a b l e / E n a b l e
B O 3 0
D i s a b l e / E n a b l e
B O 4 0
D i s a b l e / E n a b l e
F A I L 0
D i s a b l e / E n a b l e
• After completing the entries, press the END key. The LCD will display the screen shown
below. If 1 is entered for all the output relays, the following forcible operation can be performed
collectively.
118
6 F 2 T 0 1 7 6
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the output relays forcibly.
This test can be performed by applying check currents to the AC input circuits and verifying that the
values applied coincide with the values displayed on the LCD screen.
The testing circuit is shown in Figure 6.4.2.
GRE130
V
TB1
-1 VA
Three-phase -2
voltage -3 VB
source
-4
-5 VC
-6
V
Single-phase -7
voltage
source -8
+ TB1 -13
power
supply
− -14
12
119
6 F 2 T 0 1 7 6
• Select "LED" on the "Set. (change)" screen to display the "2/ LED" screen.
/ 2 L E D
> L E D
V i r t u a l L E D
• Select "LED" on the "/2 LED" screen to display the "/3 LED" screen.
/ 3 L E D
> L E D 1
L E D 2
L E D 3
L E D 4
L E D 5
L E D 6
C B C L O S E D
Note: The setting is required for all of the LEDs. If any of the LEDs are not used, enter 0 to logic gates
#1 to #4 in assigning signals.
120
6 F 2 T 0 1 7 6
• Select the LED number and press the ENTER key to display the "LED∗" screen.
/ 4 L E D ∗
> L o g i c / R e s e t
F u n c t i o n s
L E D C o l o r
/ 5 L o g i c / R e s e t
L o g i c _
> L o g i c 0
O R / A N D
R e s e t 0
I n s t / L a t c h
/ 5 F u n c t i o n s
I n ♯ 1 _
> I n ♯ 1 _ _ _
I n ♯ 2 _ _ _
I n ♯ 3 _ _ _
I n ♯ 4 _ _ _
• Assign the gate In #1 the number corresponding to the testing element referring to Appendix B,
and assign other gates to “0”.
/ 2 B i n a r y O / P
> B O 1
B O 2
B O 3
B O 4
121
6 F 2 T 0 1 7 6
Note: The setting is required for all of the binary outputs. If any of the binary outputs are not used,
enter 0 to logic gates In #1 to #4 in assigning signals.
• Select the output relay number (BO number) and press the ENTER key to display the "BO∗"
screen.
/ 3 B O ∗
> L o g i c / R e s e t
F u n c t i o n s
/ 4 L o g i c / R e s e t
L o g i c _
> L o g i c 0
O R / A N D
R e s e t 0
I n s / D l / D w / L a t
/ 4 F u n c t i o n s
I n ♯ 1 _
> I n ♯ 1
_ _ _
I n ♯ 2
_ _ _
I n ♯ 3
_ _ _
I n ♯ 4
_ _ _
T B O 0 . 2 0 s
• Assign the gate In #1 the number corresponding to the testing element referring to Appendix A
and assign other gates to “0”.
122
6 F 2 T 0 1 7 6
+ TB1 -13
power
supply − -14
-12
(∗ ) :Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1.
Overvoltage and undervoltage elements and their output signal numbers are listed below.
Element Signal No. Element Signal No.
OV1 101 UV1 122
OV2 108 UV2 126
OV3 115 UV3 130
ZPS1 134 ZPS2 135
• Enter the signal number to observe the operation at the LED as shown in Section 6.5.1 and
press the ENTER key.
• Apply a test voltage and change the magnitude of the voltage applied and measure the value
at which the element operates.
Check that the measured value is within 5% of the setting value.
123
6 F 2 T 0 1 7 6
Three-phase Vb
Voltage -3
source
Vc
-5
VN
-6
+ TB1 -13
power
supply
− -14
-12
124
6 F 2 T 0 1 7 6
+ TB1 -13
power
supply
− -14
-12
Frequency elements and their output signal numbers are listed below.
Element Signal No.
FRQ1 251
FRQ2 252
FRQ3 253
FRQ4 254
FVBLK 255
125
6 F 2 T 0 1 7 6
The metering function can be checked while testing the AC input circuit. See Section 6.4.4.
Fault recording can be checked while testing the protection schemes. Open the "Fault record" screen
and check that the descriptions are correct for the fault concerned.
Recording events are listed in Appendix B. There are internal events and external events from
binary input commands. Event recording from an external event can be checked by changing the
status of binary input command signals. Change the status in the same way as the binary input
circuit test (see Section 6.4.2) and check that the description displayed on the "Event record" screen
is correct. Some of the internal events can be checked in the protection scheme tests.
Disturbance recording can be checked while testing the protection schemes. The LCD display only
shows the date and time when a disturbance is recorded. Open the "Disturbance record" screen and
check that the descriptions are correct.
Details can be displayed on a PC. Check that the descriptions on the PC are correct. For details on
how to obtain disturbance records on the PC, see the RSM100 Manual.
6.6 Conjunctive Tests
6.6.1 On Load Test
To check the polarity of the current and voltage transformers, check the load current, system voltage
and their respective phase angles using the metering displays on the LCD screen.
• Open the "Auto-supervision" screen and check that no message appears.
• Open the following "Metering" screen from the "Status" sub-menu to check the above.
/ 2 M e t e r i n g
V a * * . * * k V
V b * * . * * k V
V c * * . * * k V
V e s * * . * * k V
V a b * * . * * k V
V b c * * . * * k V
V c a * * . * * k V
V 1 * * * . * k V
V 2 * * * . * k V
V 0 * * . * * k V
f * * . * * H z
Note: The magnitude of current can be set in values for either the primary side or the secondary
side by a setting. (The default setting is the secondary side.)
The tripping circuit, including the circuit breaker, is checked by forcibly operating the output relay
and monitoring the circuit breaker to confirm that it has tripped. Forcible operation of the output
relay is performed on the "Binary O/P " screen of the "Test" sub-menu as described in Section 6.4.3.
126
6 F 2 T 0 1 7 6
Tripping circuit
• Set the breaker to be closed.
• Select "Binary O/P" on the "Test" sub-menu screen to display the "Binary O/P" screen.
/ 2 B i n a r y O / P
B O 1 _
> B O 1 0
D i s a b l e / E n a b l e
B O 2 0
D i s a b l e / E n a b l e
B O 3 0
D i s a b l e / E n a b l e
B O 4 0
D i s a b l e / E n a b l e
F A I L 0
D i s a b l e / E n a b l e
BO1 to BO4 are output relays with one normally open contact.
• Press the END key. Then the LCD will display the screen shown below.
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the output relay BO2 and check that the A-phase
breaker is tripped.
• Stop pressing the ENTER key to reset the operation.
127
6 F 2 T 0 1 7 6
6.7 Maintenance
6.7.1 Regular Testing
The relay is almost completely self-supervised. The circuits that can not be supervised are binary
input and output circuits and human interfaces.
Therefore, regular testing is minimised to checking the unsupervised circuits. The test procedures
are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3.
6.7.2 Failure Tracing and Repair
Failures will be detected by automatic supervision or regular testing.
When a failure is detected by supervision, a remote alarm is issued from the binary output FAIL
relay and the failure is indicated on the front panel by the LED indicators or LCD display. It is also
recorded in the event record.
Failures detected by supervision are traced by checking the "Err: " screen on the LCD. Table 6.7.1
shows LCD messages and failure locations.
The locations marked with (1) have a higher probability than locations marked with (2).
128
6 F 2 T 0 1 7 6
If there is no message is shown on the LCD it means that the failure location is either in the power
supply circuit or in the microprocessors. If the "ALARM" LED is off, the failure is in the power
supply circuit. If the LED is lit, the failure is in the microprocessors. Replace the relay unit in both
cases after checking if the correct voltage is applied to the relay.
If a failure is detected by the automatic supervision function or regular testing, replace the failed
relay unit.
Note: When a failure or an abnormality is detected during a regular test, confirm the following
first:
- Test circuit connections are correct.
- Correct power voltage is applied.
- Correct AC inputs are applied.
- Test procedures comply with those stated in the manual.
6.7.3 Replacing Failed Relay Unit
If the failure is identified to be in the relay and the user has a spare relay, the user can recover the
protection by replacing the relay.
Repairs at site should be limited to relay replacement. Maintenance at component level is not
recommended.
Check that the replacement relay unit has an identical Model Number and relay version (software
type form) as the relay to be replaced.
The Model Number is indicated on the front of the relay. For the relay version, see Section 4.2.5.1.
6.7.5 Storage
The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the
storage temperature should be −25°C to +70°C, but the temperature of 0°C to +40°C is
recommended for long-term storage.
129
6 F 2 T 0 1 7 6
130
6 F 2 T 0 1 7 6
Appendix A
Signal List
131
6 F 2 T 0 1 7 6
132
6 F 2 T 0 1 7 6
133
6 F 2 T 0 1 7 6
134
6 F 2 T 0 1 7 6
135
6 F 2 T 0 1 7 6
136
6 F 2 T 0 1 7 6
137
6 F 2 T 0 1 7 6
138
6 F 2 T 0 1 7 6
139
6 F 2 T 0 1 7 6
Appendix B
Event Record Items
140
6 F 2 T 0 1 7 6
141
6 F 2 T 0 1 7 6
142
6 F 2 T 0 1 7 6
143
6 F 2 T 0 1 7 6
144
6 F 2 T 0 1 7 6
145
6 F 2 T 0 1 7 6
Appendix C
Binary Output Default Setting List
146
6 F 2 T 0 1 7 6
TB2:
GRE130 BO1 1-2 NON Off (Link to CB Close SW) 0 0 1
-411 BO2 3–4 GENERAL TRIP Relay trip (General) 141 0 1
(Link to CB Open SW)
BO3 5-6 GENERAL ALARM Relay alarm (General) 150 0 1
BO4 7-8 NON Off 0 0 1
R.F. 9 - 10 Relay fail
TB3:
GRE130 BO1 1-2 NON Off (Link to CB Close SW) 0 0 1
-412 BO2 3–4 GENERAL TRIP Relay trip (General) 141 0 1
(Link to CB Open SW)
BO3 5-6 GENERAL ALARM Relay alarm (General) 150 0 1
BO4 7-8 NON Off 0 0 1
R.F. 9 – 10 Relay fail
TB1
BO5 1-2 NON Off 0 0 1
BO6 3-4 NON Off 0 0 1
BO7 5-6 NON Off 0 0 1
BO8 7-8 NON Off 0 0 1
147
6 F 2 T 0 1 7 6
Appendix D
Details of Relay Menu and
LCD & Button Operation
148
6 F 2 T 0 1 7 6
a-1 b-1
MAIN MENU
Record
Status
Set. (view)
Set. (change)
Control
Test
/1 Record
Fault
Event
Disturbance
Counter
/2 Event /3 Event
View record
Clear 16/Jul/2010
Ext. trip A On
Refer to Section
4.2.3.2.
Clear records?
END=Y CANCEL=N
/2 Disturbance /3 Disturbance
View record
Clear #1 16/Jul/2010
Refer to Section
18:13:57.401
4.2.3.3.
Clear records?
END=Y CANCEL=N
a-1
a-1 b-1
149
6 F 2 T 0 1 7 6
/2 Counter /3 Counter
View counter Trips *****
Clear Trips TripsA *****
Clear Trips A TripsB *****
Clear Trips B TripsC *****
Clear Trips C
Clear Trips?
END=Y CANCEL=N
Clear Trips A?
END=Y CANCEL=N
Clear Trips B?
END=Y CANCEL=N
Clear Trips C?
END=Y CANCEL=N
150
6 F 2 T 0 1 7 6
a-1
/1 Status /2 Metering
Metering Va **.** kV
Binary I/O
Relay element /2 Binary I/O
Time sync. IP [0000 00 ]
Clock adjust.
LCD contrast /2 Ry element
AN OV1-4[0000 ]
Refer to Section 4.2.4.
/2 Time sync.
*BI: Act.
/2 16/Jul/2010
22:56:19 [L]
/2 LCD contrast
/1 Set. (view)
Version
Description
Comms
Record
Status
Protection
Binary I/P
Binary O/P
LED
Control
Frequency
Refer to Section 4.2.5
/2 Version
GRE130-411A-10
Relay type
-10
Software
■Software
/2 Description
GS1EM1-03-*
Plant name
■PLC data
Description
/3 Addr.
/2 Comms
Addr. *
Addr.
Switch /3 Switch
a-1, b-1
151
6 F 2 T 0 1 7 6
a-1 b-1
/2 Record /3 Event
Event BI1 comm. 3
Disturbance N/O/R/B
Counter :
/3 Disturbance /4 Time/starter
Time/Starter Time1 2.0s
Scheme sw
Binary sig. /4 Scheme sw
/4 Binary sig.
SIG1 51
/3 Counter /4 Scheme sw
Scheme sw
Alarm set
/4 Alarm set
/3 Metering TCALM 10000
/2 Status
Metering
Time sync.
Time zone /3 Time sync.
/2 Act. gp. =*
/3 Time zone.
Common
Group1
Group2
/3 Common
APPL
/3 Group1
Parameter
Trip
/4 Parameter ∗∗∗∗∗∗∗∗∗∗∗∗∗∗
Line name ∗∗∗∗∗∗
VT ratio
/5 VT ratio
VTS 100
a-1 b-1 c-1 d-1
152
6 F 2 T 0 1 7 6
a-1 b-1 c-1 d-1
/6 ZPS prot.
/6 NPS prot.
/6 FRQ prot.
/5 Prot.element /6 OV prot.
OV prot. OV1 10.0V
UV prot.
/6 UV prot.
ZPS prot.
UV1 10.0V
NPS prot.
/3 Group2 FRQ prot. /6 ZPS prot.
Parameter ZPS1 10.0V
/6 NPS prot.
/2 Binary I/P /3 BI STATUS NPS1 10.0V
BI STATUS
BI1 /6 FRQ prot.
BI2 /3 BI1 FRQ1 10.0Hz
BI3 Timers
BI4 /4 Timers
Functions
BI5 BI1PUD 0.00s
BI6
Alarm1 Text /4 Functions
Alarm2 Text /3 BI6
Alarm3 Text Timers
Alarm4 Text Functions
∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗
Alarm∗ Text
a-1 b-1
153
6 F 2 T 0 1 7 6
a-1 b-1
/2 Binary O/P
BO1 AND, DL
0, 0, 0, 0
BO4 OR , Lat
141, 1, 2, 3
/2 LED
LED /3 LED
Virtual LED
/2 Control
/3 Virtual LED /4 IND1
IND1 BIT1 I,O
/2 Frequency IND2
/4 IND2
/1 Set.(change) BIT1 I,O
Password
Description : Password trap
Comms Set.(change)
Record Password [_ ]
Status 1234567890←
Protection
Binary I/P : Confirmation trap
1234567890← 1234567890←
/2 Description _
Plant name ABCDEFG
Description
_
Refer to Section
4.2.6.3. ABCDEFG
/2 Comms /3 Addr.
Addr. Addr
Switch
Refer to Section
/3 Switch
4.2.6.4. RS485
a-1 b-2
154
6 F 2 T 0 1 7 6
a-1 b-2
/2 Record /3 Event
Event BI1 comm.
Disturbance BI1 comm. 3 _
Counter N/O/R/B
:
/4 Time/starter
Refer to Section :
4.2.6.5.
/3 Disturbance /4 Scheme sw
Time/starter
Scheme sw
Binary sig. /4 Binary sig.
/3 Counter /4 Scheme sw
Scheme sw
Alarm set
/4 Alarm set
/2 Status /3 Metering
Metering Display
Time sync.
Time zone /3 Time sync.
Refer to Section Time sync.
4.2.6.6.
/3 Time zone
/2 Protection GMT _
Change act. gp.
Change set.
Refer to Section
Copy gp. 4.2.6.7.
/3 Change act.
gp.
/3 Act gp.=1
Common
Group1
Group2
/4 Common
APPL
a-1 b-2 c-2 d-2
155
6 F 2 T 0 1 7 6
a-1 b-2 c-2 d-2
/4 Group1
Parameter
Trip
/5 Parameter _
Line name ABCDEFG
VT ratio
/6 VT ratio
VTS
/7 ZPS prot.
/7 NPS prot.
/7 FRQ prot.
/6 Prot.element /7 OV prot.
OV prot.
UV prot.
/7 UV prot.
ZPS prot.
NPS prot.
FRQ prot. /7 ZPS prot.
/7 NPS prot.
/4 Group2
Parameter
/7 FRQ prot.
156
6 F 2 T 0 1 7 6
a-1 b-2 c-2
/3 Copy A to B
A _
B _
/3 BI Status
/2 Binary I/P BITHR1
BI Status
BI1 /3 BI1 /4 Timers
BI2 Timers
BI3 Functions
BI4 /4 Functions
BI5 /3 BI6
BI6 Timers
Alarm1 Text Functions
Alarm2 Text
Alarm3 Text ∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗
Alarm4 Text ABCDEFG
Refer to Section Alarm∗ Text
4.2.6.8.
/2 Binary O/P /3 BO1 /4 Logic/Reset
BO1 Logic/Reset
BO2 Functions
BO3 /4 Functions
BO4 /3 BO4
Refer to Section Logic/Reset
4.2.6.9. Functions
/2 LED
LED
Virtual LED Refer to Section
4.2.6.10.
157
6 F 2 T 0 1 7 6
Control
Password [_ ]
1234567890←
Test
/2 Switch
Password [_ ]
A.M.F. 1 _ 1234567890←
Off/On
UVTST 0
Off/S0/S3
BO4 0
Disable/Enable
158
6 F 2 T 0 1 7 6
Appendix E
Case Outline
159
6 F 2 T 0 1 7 6
Case Outline
160
6 F 2 T 0 1 7 6
161
6 F 2 T 0 1 7 6
Appendix F
Typical External Connection
162
6 F 2 T 0 1 7 6
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-410A TB2
APPL ; 1PP CB CLOSE CB CLOSE BO1
TB1
SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Vph SW
3
3 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail BO5
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
Available for 33.6/77/154V
FG TCS 13
(CB CLOSED) 14
AUXILIARY Threshold BI2
Available for 33.6/77/154V
FRONT PANEL TCS 15
(CB OPEN) 16 N
USB Type B 17
N.C. 18
19
20
Rear PANEL 22 A+
B-
RS485 COM
COM 21 COM
RJ45 N.C. A+ 23 A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
163
6 F 2 T 0 1 7 6
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-411A TB2
APPL ; 1PN CB CLOSE CB CLOSE BO1
TB1
SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Vph SW
3
3 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail BO5
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
33.6/77/154V
FG Available for 13
TCS 14
AUXILIARY Threshold BI2
33.6/77/154V
FRONT PANEL Available for 15
TCS
Threshold
16
77/154V
USB Type B
(CB CLOSED) AUXILIARY 17
(CB OPEN) AUXILIARY 18
AUXILIARY 19
AUXILIARY 20
Rear PANEL 22 N
A+
B-
RS485 COM
COM 21 COM
RJ45 N.C. A+ 23 A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
164
6 F 2 T 0 1 7 6
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-410A TB2
APPL ; 2PP CB CLOSE CB CLOSE BO1
TB1 2PZ SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Vab SW
3
3 Vbc 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail BO5
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
Available for 33.6/77/154V
FG TCS 13
(CB CLOSED) 14
AUXILIARY Threshold BI2
Available for 33.6/77/154V
FRONT PANEL TCS 15
(CB OPEN) 16 N
USB Type B 17
N.C.
18
19
20
Rear PANEL 22 A+
B-
RS485 COM
COM 21 COM
RJ45 N.C. A+ 23 A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
Typical External Connections for the GRE130 - 410A 2PP ( 2PZ ) setting
165
6 F 2 T 0 1 7 6
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-411A TB2
APPL ; 3PN CB CLOSE CB CLOSE BO1
TB1 3PV
SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Va SW
3
3 Vb 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 Vc 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail BO5
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
33.6/77/154V
FG Available for 13
TCS 14
AUXILIARY Threshold BI2
33.6/77/154V
FRONT PANEL Available for 15
TCS
Threshold
16
77/154V
USB Type B
(CB CLOSED) AUXILIARY 17
(CB OPEN) AUXILIARY 18
AUXILIARY 19
AUXILIARY 20
Rear PANEL 22 N
A+
B-
RS485 COM
COM 21
RJ45 N.C. A+ 23 COM
A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
Typical External Connections for the GRE130 - 410A 3PN ( 3PV ) setting
166
6 F 2 T 0 1 7 6
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-410A TB2
APPL ; 3PP CB CLOSE CB CLOSE BO1
TB1
SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Vab SW
3
3 Vbc 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 Vca 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail BO5
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
Available for 33.6/77/154V
FG TCS 13
(CB CLOSED) 14
AUXILIARY Threshold BI2
Available for 33.6/77/154V
FRONT PANEL TCS 15
(CB OPEN) 16 N
USB Type B 17
N.C.
18
19
20
Rear PANEL 22 A+
B-
RS485 COM
COM 21
RJ45 N.C. A+ 23 COM
A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
167
6 F 2 T 0 1 7 6
A
B
C Control
Power
P
Controled
CB
GRE130-412A TB3
APPL ; 3PP CB CLOSE CB CLOSE BO1
TB2
SW
1
2
1 CB OPEN CB OPEN/TRIP BO2
2 Vab SW
3
3 Vbc 4
4 AUXILIARY BO3
TRIP
COIL
CLOSE
5 Vca 5 N
COIL
6 *
6
7 Ve AUXILIARY BO4
8 7
*
9 8
P
10 N.C. Relay fail R.F.
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
BI1
33.6/77/154V
FG Available for 13
TCS 14
AUXILIARY Threshold BI2
33.6/77/154V
FRONT PANEL Available for 15
TCS 16
Threshold
77/154V
USB Type B
(CB CLOSED) AUXILIARY 17
(CB OPEN) AUXILIARY 18
AUXILIARY 19
Rear PANEL AUXILIARY 20
22 N
A+
B-
RS485 COM
RJ45
COM 21
A+ 23 COM
A+
N.C. B- 24 B-
Control
TB1 Power
AUXILIARY BO5
1
2
AUXILIARY BO6
OUTPUT CONACTS
SIGNAL LIST (DEFAULT) Optional Communication 3
BO1 OFF(CB CLOSE)
Port *** 4
AUXILIARY BO7
BO2 GENERAL TRIP
BO3 GENERAL ALARM *
5
BO4 OFF
100BASE-TX 6
1port / 2port AUXILIARY BO8
BO5 OFF
BO6 OFF 7 *
BO7 OFF 8
BO8 OFF 9
N.C. 10
100BASE-FX
1port / 2port 11
12
168
6 F 2 T 0 1 7 6
Appendix G
Relay Setting Sheet
1. Relay Identification
2. Line parameter
3. Contacts setting
4. Relay setting sheet
169
6 F 2 T 0 1 7 6
2. Line parameter
VT ratio PVT: RVT:
3. Contacts setting
TB2 (For model type 412, the terminal block number is TB3 )
BO1 Terminal 1-2
BO2 Terminal 3-4
BO3 Terminal 5-6
BO4 Terminal 7-8
170
6 F 2 T 0 1 7 6
171
6 F 2 T 0 1 7 6
172
6 F 2 T 0 1 7 6
173
6 F 2 T 0 1 7 6
174
6 F 2 T 0 1 7 6
175
6 F 2 T 0 1 7 6
176
6 F 2 T 0 1 7 6
177
6 F 2 T 0 1 7 6
178
6 F 2 T 0 1 7 6
Appendix H
Commissioning Test Sheet (sample)
1. Relay identification
2. Preliminary check
3. Hardware check
3.1 User interface check
3.2 Binary input/binary output circuit check
3.3 AC input circuit check
4. Function test
4.1 Overvoltage and undervoltage elements test
4.2 Negative sequence overvoltage elements test
5. Protection scheme test
6. Metering and recording check
179
6 F 2 T 0 1 7 6
1. Relay identification
2. Preliminary check
Ratings
Power supply
Wiring
Calendar and clock
3. Hardware check
180
6 F 2 T 0 1 7 6
4. Function test
181
6 F 2 T 0 1 7 6
7. Conjunctive test
Scheme Results
On load check
Tripping circuit
182
6 F 2 T 0 1 7 6
Appendix I
Return Repair Form
183
6 F 2 T 0 1 7 6
TOSHIBA CORPORATION Fuchu Operations – Industrial and Power Systems & Services
1, Toshiba-cho, Fuchu-shi, Tokyo, Japan
For: Power Systems Protection & Control Department
Quality Assurance Section
Product No.:
Serial No.:
Date:
2. Fault records, event records or disturbance records stored in the relay and relay settings are
very helpful information to investigate the incident.
Please provide relevant information regarding the incident on USB stick or CD rom, or fill
in the attached fault record sheet and relay setting sheet.
184
6 F 2 T 0 1 7 6
Fault Record
Date/Month/Year Time / /
/ : : .
(Example: 04/ Jul./ 2012 15:09:58.442)
Faulty phase:
Prefault values
Van: V
Vbn: V
Vcn: V
Vab: V
Vbc: V
Vca : V
Vph: V
V0: V
V1: V
V2: V
f: Hz
Fault values
Van: V
Vbn: V
Vcn: V
Vab: V
Vbc: V
Vca : V
Vph: V
V0: V
V1: V
V2: V
f: Hz
185
6 F 2 T 0 1 7 6
3. What was the message on the LCD display at the time of the incident?
6. Give any comments about the GRE130, including any relevant documents:
186
6 F 2 T 0 1 7 6
Customer
Name:
Company Name:
Address:
Telephone No.:
Facsimile No.:
Signature:
187
6 F 2 T 0 1 7 6
Appendix J
Technical Data
188
6 F 2 T 0 1 7 6
TECHNICAL DATA
Ratings
AC voltage Vn: 63.5V / 110V
Frequency: 50/60Hz
Power supply: 110-250Vdc or 100-220Vac
(Operative range: 88–300Vdc / 88–264Vac)
48-110Vdc (Operative range: 38.4 – 132Vdc)
24-48Vdc (Operative range: 19.2 – 60.0Vdc)
Superimposed AC ripple on DC supply: maximum 12%
Power supply interruption: maximum 50ms at 110V
Binary input circuit DC voltage: For alarm indication
110-250Vdc (Operative range: 88 - 300Vdc)
48-110Vdc (Operative range: 38.4 - 132Vdc)
24-48Vdc (Operative range: 19.2 – 60.0Vdc)
For trip circuit supervision
Operative range: ≥38.4V (for 110Vdc rating)
≥88V (for 220/250Vdc rating)
≥19.2V (for 48Vdc rating)
≥9.6V (for 24Vdc rating)
Overload Ratings
AC voltage inputs: 2 times rated voltage continuous
Burden
AC phase voltage inputs: ≤ 0.1 VA (at rated voltage)
Power supply: ≤ 10W (quiescent), ≤ 15W (maximum)
Binary input circuit: ≤ 0.5W per input at 220Vdc
Overvoltage Protection (59)
1st, 2nd, 3rd Overvoltage thresholds: OFF, 10.0 – 200.0V in 0.1V steps
Delay type: DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
DO/PU ratio 10 - 98% in 1% steps
Reset Delay: Instantaneous, 0.1 – 300.0s in 0.1s steps
Undervoltage Protection (27)
1st, 2nd, 3rd Undervoltage thresholds: OFF, 5.0 – 130.0V in 0.1V steps
Delay type: DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay: Instantaneous, 0.1 – 300.0s in 0.1s steps
Zero Sequence Overvoltage (ZPS) Protection (59N)
st nd
1 , 2 ZPS Overvoltage thresholds: OFF, 1.0 – 130.0V in 0.1V steps
st
Delay type (1 threshold only): DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (1st threshold only): Instantaneous, 0.1 – 300.0s in 0.1s steps
189
6 F 2 T 0 1 7 6
190
6 F 2 T 0 1 7 6
191
6 F 2 T 0 1 7 6
ENVIRONMENTAL PERFORMANCE
Test Standards Details
Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range: -20°C to +60°C.
IEC 60068-2-30 Storage / Transit: -25°C to +70°C.
Humidity IEC 60068-2-78 56 days at 40°C and 93% relative humidity.
Enclosure Protection IEC 60529 IP52 (front), IP20 (rear), IP40 (top)
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-5 2kVrms for 1 minute between all terminals and earth.
IEEE C37.90.0 2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage Impulse IEC 60255-5 Three positive and three negative impulses of
5kV(peak) for CT, Power Supply Unit (PSU), BI and BO
circuits; between terminals and earth, and between
independent circuits
3kV (peak) for RS485 circuit; between terminals and earth
3kV (peak) for BO circuit; across normally open contacts
1.2/50µs, 0.5J between all terminals and between all terminals
and earth.
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1MHz 2.5kV to 3kV (peak) applied to all ports in common mode.
Disturbance / Damped IEC 61000-4-12 1MHz 1.0kV applied to all ports in differential mode.
Oscillatory Wave IEEE C37.90.1
Electrostatic IEC 60255-22-2 Class 3, 6kV contact discharge, 8kV air discharge.
Discharge IEC 61000-4-2
Radiated RF IEC 60255-22-3 Class 3, Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
Electromagnetic IEC 61000-4-3 and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
Disturbance 900 and 1890MHz.
Fast Transient IEC 60255-22-4 Class A, 4kV, 2.5kHz, 5/50ns applied to all inputs.
Disturbance IEC 61000-4-4,
IEEE C37.90.1
Surge Immunity IEC 60255-22-5, 1.2/50µs surge in common/differential modes:
IEC 61000-4-5 HV, PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF IEC 60255-22-6 Class 3, 10Vrms applied over frequency range 150kHz to 100MHz.
Electromagnetic IEC 61000-4-6 Additional spot tests at 27 and 68MHz.
Disturbance
Power Frequency IEC 60255-22-7 Class A, 300V 50Hz for 10s applied to ports in common mode.
Disturbance IEC 61000-4-16 150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
192
6 F 2 T 0 1 7 6
193
6 F 2 T 0 1 7 6
Appendix K
Symbols Used in Scheme Logic
194
6 F 2 T 0 1 7 6
The symbols used in the scheme logic and their respective meanings are as follows:
Signal names
Marked with : Measuring element output signal
Marked with : Binary signal input from or output to external equipment
Marked with [ ] : Scheme switch
Marked with " " : Scheme switch position
Unmarked : Internal scheme logic signal
AND gates
A B C Output
A
1 1 1 1
B & Output Other cases 0
C
A
A B C Output
B & Output 1 1 0 1
C Other cases 0
A
A B C Output
B & Output 1 0 0 1
C Other cases 0
OR gates
A A B C Output
B ≥1 Output 0 0 0 0
C Other cases 1
A
A B C Output
B ≥1 Output 0 0 1 0
C Other cases 1
A
A B C Output
B ≥1 Output 0 1 1 0
C Other cases 1
195
6 F 2 T 0 1 7 6
Signal inversion
A Output
A 1 Output 0 1
1 0
Timer
t 0
Delayed pick-up timer with fixed setting
XXX: Set time
XXX
One-shot timer
A
A Output
Output
XXX - YYY
Scheme switch
A Switch Output
A Output
1 ON 1
ON
Other cases 0
Switch Output
+ Output ON 1
ON OFF 0
196
6 F 2 T 0 1 7 6
Appendix L
Modbus: Interoperability
197
6 F 2 T 0 1 7 6
Modbus: Interoperability
1. Physical and Data Link Layer
- RS485(EIA/TIA-485) 2-wire interface
- RTU mode only
- Coding System:
8–bit binary (1 start bit, 8 data bits, 1 parity bit, 1 stop bit)
Even parity
- Address setting range: 1-247
- Baud rate setting range: 9600 or 19200
2. Application Layer
198
6 F 2 T 0 1 7 6
17 Report Slave ID
Response Data
Byte Count (1byte) 18bytes
Slave ID (17bytes) Relay type and model ID
GRE130-411A-10-10 ASCII
Run Indicator Status (1byte) 0x00=out of service, 0xFF=in service
199
6 F 2 T 0 1 7 6
200
6 F 2 T 0 1 7 6
201
6 F 2 T 0 1 7 6
202
6 F 2 T 0 1 7 6
203
6 F 2 T 0 1 7 6
204
6 F 2 T 0 1 7 6
205
6 F 2 T 0 1 7 6
206
6 F 2 T 0 1 7 6
207
6 F 2 T 0 1 7 6
208
6 F 2 T 0 1 7 6
209
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6023 SIG25 Disturbance trigger
6024 SIG26 Disturbance trigger
6025 SIG27 Disturbance trigger
Disturbance 6026 SIG28 Disturbance trigger
Record 6027 SIG29 Disturbance trigger
6028 SIG30 Disturbance trigger
6029 SIG31 Disturbance trigger
602A SIG32 Disturbance trigger
602B TCSPEN Trip Circuit Supervision Enable
602C CBSMEN Circuit Breaker State Monitoring Alarm Enable
Counter
602D TCAEN Trip Count Alarm Enable
6030 TCALM Trip Count Alarm Threshold setting
6400 Display Metering
6401 Time sync. Time synchronization method
Status
6402 GMT Time zone (Hours)
640A GMTm Time zone (minutes)
6C00 BITHR1 BI threshold for BI1 & BI2
6C01 BITHR2 BI threshold for BI3-6
6C02 BI1 BI1PUD Binary Input 1 Pick-up delay
6C03 BI1 BI1DOD Binary Input 1 Drop-off delay
6C04 BI1 BI1SNS Binary Input 1 Sense
6C05 BI1 BI1SGS Binary Input 1 Settings Group Select
6C06 BI1 OV1BLK OV1 Block
6C07 BI1 OV2BLK OV2 Block
6C08 BI1 OV3BLK OV3 Block
6C09 BI1 UV1BLK UV1 Block
6C0A BI1 UV2BLK UV2 Block
6C0B BI1 UV3BLK UV3 Block
Binary Input 6C0C BI1 ZP1BLK ZPS1 Block
6C0D BI1 ZP2BLK ZPS2 Block
6C0E BI1 NP1BLK NPS1 Block
6C0F BI1 NP2BLK NPS2 Block
6C10 BI1 TCFALM Trip Circuit Fail Alarm
6C11 BI1 CBOPN Circuit Breaker Open
6C12 BI1 CBCLS Circuit Breaker Close
6C13 BI1 EXT3PH External Trip - 3 phase
6C14 BI1 EXTAPH External Trip - A phase
6C15 BI1 EXTBPH External Trip - B phase
6C16 BI1 EXTCPH External Trip - C phase
6C17 BI1 RMTRST Remote Reset
6C18 BI1 SYNCLK Synchronize clock
6C19 BI1 STORCD Store Disturbance Record
6C1A BI1 Alarm1 Alarm screen 1.
6C1B BI1 Alarm2 Alarm screen 2.
210
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6C1C BI1 Alarm3 Alarm screen 3.
6C1D BI1 Alarm4 Alarm screen 4.
6C1E BI1 RMTOPN Remote CB Open Control
6C1F BI1 RMTCLS Remote CB Close Control
6C20 BI1 CNTLCK Interlock Input
6C21 BI1 FRQ1BLK FRQ1 Block
6C22 BI1 FRQ2BLK FRQ2 Block
6C23 BI1 FRQ3BLK FRQ3 Block
6C24 BI1 FRQ4BLK FRQ4 Block
6C25 BI2 BI2PUD Binary Input 2 Pick-up delay
6C26 BI2 BI2DOD Binary Input 2 Drop-off delay
6C27 BI2 BI2SNS Binary Input 2 Sense
6C28 BI2 BI2SGS Binary Input 2 Settings Group Select
6C29 BI2 OV1BLK OV1 Block
6C2A BI2 OV2BLK OV2 Block
6C2B BI2 OV3BLK OV3 Block
6C2C BI2 UV1BLK UV1 Block
6C2D BI2 UV2BLK UV2 Block
Binary Input
6C2E BI2 UV3BLK UV3 Block
6C2F BI2 ZP1BLK ZPS1 Block
6C30 BI2 ZP2BLK ZPS2 Block
6C31 BI2 NP1BLK NPS1 Block
6C32 BI2 NP2BLK NPS2 Block
6C33 BI2 TCFALM Trip Circuit Fail Alarm
6C34 BI2 CBOPN Circuit Breaker Open
6C35 BI2 CBCLS Circuit Breaker Close
6C36 BI2 EXT3PH External Trip - 3 phase
6C37 BI2 EXTAPH External Trip - A phase
6C38 BI2 EXTBPH External Trip - B phase
6C39 BI2 EXTCPH External Trip - C phase
6C3A BI2 RMTRST Remote Reset
6C3B BI2 SYNCLK Synchronize clock
6C3C BI2 STORCD Store Disturbance Record
6C3D BI2 Alarm1 Alarm screen 1.
6C3E BI2 Alarm2 Alarm screen 2.
6C3F BI2 Alarm3 Alarm screen 3.
6C40 BI2 Alarm4 Alarm screen 4.
6C41 BI2 RMTOPN Remote CB Open Control
6C42 BI2 RMTCLS Remote CB Close Control
6C43 BI2 CNTLCK Interlock Input
6C44 BI2 FRQ1BLK FRQ1 Block
6C45 BI2 FRQ2BLK FRQ2 Block
6C46 BI2 FRQ3BLK FRQ3 Block
6C47 BI2 FRQ4BLK FRQ4 Block
211
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6C48 BI3 BI3PUD Binary Input 3 Pick-up delay
6C49 BI3 BI3DOD Binary Input 3 Drop-off delay
6C4A BI3 BI3SNS Binary Input 3 Sense
6C4B BI3 BI3SGS Binary Input 3 Settings Group Select
6C4C BI3 OV1BLK OV1 Block
6C4D BI3 OV2BLK OV2 Block
6C4E BI3 OV3BLK OV3 Block
6C4F BI3 UV1BLK UV1 Block
6C50 BI3 UV2BLK UV2 Block
6C51 BI3 UV3BLK UV3 Block
6C52 BI3 ZP1BLK ZPS1 Block
6C53 BI3 ZP2BLK ZPS2 Block
6C54 BI3 NP1BLK NPS1 Block
6C55 BI3 NP2BLK NPS2 Block
6C56 BI3 TCFALM Trip Circuit Fail Alarm
6C57 BI3 CBOPN Circuit Breaker Open
6C58 BI3 CBCLS Circuit Breaker Close
6C59 BI3 EXT3PH External Trip - 3 phase
6C5A BI3 EXTAPH External Trip - A phase
Binary Input 6C5B BI3 EXTBPH External Trip - B phase
6C5C BI3 EXTCPH External Trip - C phase
6C5D BI3 RMTRST Remote Reset
6C5E BI3 SYNCLK Synchronize clock
6C5F BI3 STORCD Store Disturbance Record
6C60 BI3 Alarm1 Alarm screen 1.
6C61 BI3 Alarm2 Alarm screen 2.
6C62 BI3 Alarm3 Alarm screen 3.
6C63 BI3 Alarm4 Alarm screen 4.
6C64 BI3 RMTOPN Remote CB Open Control
6C65 BI3 RMTCLS Remote CB Close Control
6C66 BI3 CNTLCK Interlock Input
6C67 BI3 FRQ1BLK FRQ1 Block
6C68 BI3 FRQ2BLK FRQ2 Block
6C69 BI3 FRQ3BLK FRQ3 Block
6C6A BI3 FRQ4BLK FRQ4 Block
6C6B BI4 BI4PUD Binary Input 4 Pick-up delay
6C6C BI4 BI4DOD Binary Input 4 Drop-off delay
6C6D BI4 BI4SNS Binary Input 4 Sense
6C6E BI4 BI4SGS Binary Input 4 Settings Group Select
6C6F BI4 OV1BLK OV1 Block
6C70 BI4 OV2BLK OV2 Block
6C71 BI4 OV3BLK OV3 Block
6C72 BI4 UV1BLK UV1 Block
6C73 BI4 UV2BLK UV2 Block
212
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6C74 BI4 UV3BLK UV3 Block
6C75 BI4 ZP1BLK ZPS1 Block
6C76 BI4 ZP2BLK ZPS2 Block
6C77 BI4 NP1BLK NPS1 Block
6C78 BI4 NP2BLK NPS2 Block
6C79 BI4 TCFALM Trip Circuit Fail Alarm
6C7A BI4 CBOPN Circuit Breaker Open
6C7B BI4 CBCLS Circuit Breaker Close
6C7C BI4 EXT3PH External Trip - 3 phase
6C7D BI4 EXTAPH External Trip - A phase
6C7E BI4 EXTBPH External Trip - B phase
6C7F BI4 EXTCPH External Trip - C phase
6C80 BI4 RMTRST Remote Reset
6C81 BI4 SYNCLK Synchronize clock
6C82 BI4 STORCD Store Disturbance Record
6C83 BI4 Alarm1 Alarm screen 1.
6C84 BI4 Alarm2 Alarm screen 2.
6C85 BI4 Alarm3 Alarm screen 3.
6C86 BI4 Alarm4 Alarm screen 4.
6C87 BI4 RMTOPN Remote CB Open Control
6C88 BI4 RMTCLS Remote CB Close Control
Binary Input 6C89 BI4 CNTLCK Interlock Input
6C8A BI4 FRQ1BLK FRQ1 Block
6C8B BI4 FRQ2BLK FRQ2 Block
6C8C BI4 FRQ3BLK FRQ3 Block
6C8D BI4 FRQ4BLK FRQ4 Block
6C8E BI5 BI5PUD Binary Input 5 Pick-up delay
6C8F BI5 BI5DOD Binary Input 5 Drop-off delay
6C90 BI5 BI5SNS Binary Input 5 Sense
6C91 BI5 BI5SGS Binary Input 5 Settings Group Select
6C92 BI5 OV1BLK OV1 Block
6C93 BI5 OV2BLK OV2 Block
6C94 BI5 OV3BLK OV3 Block
6C95 BI5 UV1BLK UV1 Block
6C96 BI5 UV2BLK UV2 Block
6C97 BI5 UV3BLK UV3 Block
6C98 BI5 ZP1BLK ZPS1 Block
6C99 BI5 ZP2BLK ZPS2 Block
6C9A BI5 NP1BLK NPS1 Block
6C9B BI5 NP2BLK NPS2 Block
6C9C BI5 TCFALM Trip Circuit Fail Alarm
6C9D BI5 CBOPN Circuit Breaker Open
6C9E BI5 CBCLS Circuit Breaker Close
6C9F BI5 EXT3PH External Trip - 3 phase
213
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6CA0 BI5 EXTAPH External Trip - A phase
6CA1 BI5 EXTBPH External Trip - B phase
6CA2 BI5 EXTCPH External Trip - C phase
6CA3 BI5 RMTRST Remote Reset
6CA4 BI5 SYNCLK Synchronize clock
6CA5 BI5 STORCD Store Disturbance Record
6CA6 BI5 Alarm1 Alarm screen 1.
6CA7 BI5 Alarm2 Alarm screen 2.
6CA8 BI5 Alarm3 Alarm screen 3.
6CA9 BI5 Alarm4 Alarm screen 4.
6CAA BI5 RMTOPN Remote CB Open Control
6CAB BI5 RMTCLS Remote CB Close Control
6CAC BI5 CNTLCK Interlock Input
6CAD BI5 FRQ1BLK FRQ1 Block
6CAE BI5 FRQ2BLK FRQ2 Block
6CAF BI5 FRQ3BLK FRQ3 Block
6CB0 BI5 FRQ4BLK FRQ4 Block
6CB1 BI6 BI6PUD Binary Input 6 Pick-up delay
6CB2 BI6 BI6DOD Binary Input 6 Drop-off delay
6CB3 BI6 BI6SNS Binary Input 6 Sense
6CB4 BI6 BI6SGS Binary Input 6 Settings Group Select
6CB5 BI6 OV1BLK OV1 Block
6CB6 BI6 OV2BLK OV2 Block
Binary Input 6CB7 BI6 OV3BLK OV3 Block
6CB8 BI6 UV1BLK UV1 Block
6CB9 BI6 UV2BLK UV2 Block
6CBA BI6 UV3BLK UV3 Block
6CBB BI6 ZP1BLK ZPS1 Block
6CBC BI6 ZP2BLK ZPS2 Block
6CBD BI6 NP1BLK NPS1 Block
6CBE BI6 NP2BLK NPS2 Block
6CBF BI6 TCFALM Trip Circuit Fail Alarm
6CC0 BI6 CBOPN Circuit Breaker Open
6CC1 BI6 CBCLS Circuit Breaker Close
6CC2 BI6 EXT3PH External Trip - 3 phase
6CC3 BI6 EXTAPH External Trip - A phase
6CC4 BI6 EXTBPH External Trip - B phase
6CC5 BI6 EXTCPH External Trip - C phase
6CC6 BI6 RMTRST Remote Reset
6CC7 BI6 SYNCLK Synchronize clock
6CC8 BI6 STORCD Store Disturbance Record
6CC9 BI6 Alarm1 Alarm screen 1.
6CCA BI6 Alarm2 Alarm screen 2.
6CCB BI6 Alarm3 Alarm screen 3.
214
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
6CCC BI6 Alarm4 Alarm screen 4.
6CCD BI6 RMTOPN Remote CB Open Control
6CCE BI6 RMTCLS Remote CB Close Control
Binary Input 6CCF BI6 CNTLCK Interlock Input
6CD0 BI6 FRQ1BLK FRQ1 Block
6CD1 BI6 FRQ2BLK FRQ2 Block
6CD2 BI6 FRQ3BLK FRQ3 Block
6CD3 BI6 FRQ4BLK FRQ4 Block
7428 BO1 Logic Logic Gate Type
7429 BO1 Reset Reset operation
7400 BO1 In #1 Functions
7401 BO1 In #2 Functions
7402 BO1 In #3 Functions
7403 BO1 In #4 Functions
7450 BO1 TBO Delay/Pulse Width
742A BO2 Logic Logic Gate Type
742B BO2 Reset Reset operation
7404 BO2 In #1 Functions
7405 BO2 In #2 Functions
7406 BO2 In #3 Functions
7407 BO2 In #4 Functions
7451 BO2 TBO Delay/Pulse Width
742C BO3 Logic Logic Gate Type
742D BO3 Reset Reset operation
7408 BO3 In #1 Functions
7409 BO3 In #2 Functions
740A BO3 In #3 Functions
Binary Output
740B BO3 In #4 Functions
7452 BO3 TBO Delay/Pulse Width
742E BO4 Logic Logic Gate Type
742F BO4 Reset Reset operation
740C BO4 In #1 Functions
740D BO4 In #2 Functions
740E BO4 In #3 Functions
740F BO4 In #4 Functions
7453 BO4 TBO Delay/Pulse Width
7430 BO5 Logic Logic Gate Type
7431 BO5 Reset Reset operation
7410 BO5 In #1 Functions
7411 BO5 In #2 Functions
7412 BO5 In #3 Functions
7413 BO5 In #4 Functions
7454 BO5 TBO Delay/Pulse Width
7432 BO6 Logic Logic Gate Type
215
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
7433 BO6 Reset Reset operation
7414 BO6 In #1 Functions
7415 BO6 In #2 Functions
7416 BO6 In #3 Functions
7417 BO6 In #4 Functions
7455 BO6 TBO Delay/Pulse Width
7434 BO7 Logic Logic Gate Type
7435 BO7 Reset Reset operation
Binary Output 7418 BO7 In #1 Functions
7419 BO7 In #2 Functions
741A BO7 In #3 Functions
741B BO7 In #4 Functions
7456 BO7 TBO Delay/Pulse Width
7436 BO8 Logic Logic Gate Type
7437 BO8 Reset Reset operation
741C BO8 In #1 Functions
741D BO8 In #2 Functions
741E BO8 In #3 Functions
741F BO8 In #4 Functions
7457 BO8 TBO Delay/Pulse Width
7020 LED1 Logic LED1 Logic Gate Type
7021 LED1 Reset LED1 Reset operation
7022 LED2 Logic LED2 Logic Gate Type
7023 LED2 Reset LED2 Reset operation
7024 LED3 Logic LED3 Logic Gate Type
7025 LED3 Reset LED3 Reset operation
7026 LED4 Logic LED4 Logic Gate Type
7027 LED4 Reset LED4 Reset operation
7028 LED5 Logic LED5 Logic Gate Type
7029 LED5 Reset LED5 Reset operation
702A LED6 Logic LED6 Logic Gate Type
Configurable LED 702B LED7 Reset LED6 Reset operation
7000 LED1 In #1 LED Functions
7001 LED1 In #2 LED Functions
7002 LED1 In #3 LED Functions
7003 LED1 In #4 LED Functions
7004 LED2 In #1 LED Functions
7005 LED2 In #2 LED Functions
7006 LED2 In #3 LED Functions
7007 LED2 In #4 LED Functions
7008 LED3 In #1 LED Functions
7009 LED3 In #2 LED Functions
700A LED3 In #3 LED Functions
700B LED3 In #4 LED Functions
216
6 F 2 T 0 1 7 6
Setting Group
Address Name Contents
(Menu)
700C LED4 In #1 LED Functions
700D LED4 In #2 LED Functions
700E LED4 In #3 LED Functions
700F LED4 In #4 LED Functions
7010 LED5 In #1 LED Functions
7011 LED5 In #2 LED Functions
7012 LED5 In #3 LED Functions
7013 LED5 In #4 LED Functions
7014 LED6 In #1 LED Functions
7015 LED6 In #2 LED Functions
7016 LED6 In #3 LED Functions
7017 LED6 In #4 LED Functions
7060 LED1 Color LED Color
Configurable LED
7061 LED2 Color LED Color
7062 LED3 Color LED Color
7063 LED4 Color LED Color
7064 LED5 Color LED Color
7065 LED6 Color LED Color
7066 CB CLOSED Color LED Color
7050 IND1 Reset IND1 Reset operation
7051 IND2 Reset IND1 Reset operation
7030 IND1 BIT1 Virtual LED
7031 IND1 BIT2 Virtual LED
7032 IND1 BIT3 Virtual LED
7033 IND1 BIT4 Virtual LED
7034 IND1 BIT5 Virtual LED
7035 IND1 BIT6 Virtual LED
7036 IND1 BIT7 Virtual LED
7037 IND1 BIT8 Virtual LED
7038 IND2 BIT1 Virtual LED
7039 IND2 BIT2 Virtual LED
703A IND2 BIT3 Virtual LED
703B IND2 BIT4 Virtual LED
Configurable LED
703C IND2 BIT5 Virtual LED
703D IND2 BIT6 Virtual LED
703E IND2 BIT7 Virtual LED
703F IND2 BIT8 Virtual LED
6800 Active gp. Active setting group
6803 AOLED ALARM LED light control for alarm output
Active group/ 6804 Control Control enable
Common 6805 Interlock Interlock enable
6806 Control Kind Control Hierarchy (if Control = Enable)
6807 Frequency Frequency
217
6 F 2 T 0 1 7 6
Setting Address
Group Name Contents
(Menu) Gr.1 Gr.2
4C00 5C00 PVT VT ratio
4C01 5C01 RVT Residual VT ratio
4017 5017 SVCNT AC input imbalance
4000 5000 OV OV1EN OV1 Enable
4001 5001 OV OV2EN OV2 Enable
4002 5002 OV OV3EN OV3 Enable
4003 5003 UV UV1EN UV1 Enable
4004 5004 UV UV2EN UV2 Enable
4005 5005 UV UV3EN UV3 Enable
4006 5006 UV VBLK UVBLOCK Enable
4007 5007 ZPS ZPS1EN ZPS1 Enable
4008 5008 ZPS ZPS2EN ZPS2 Enable
4009 5009 NPS NPS1EN NPS1 Enable
400A 500A NPS NPS2EN NPS2 Enable
400B 500B FRQ1 FT1 FRQ1 Enable / Type
400C 500C FRQ1 DFT1 DFRQ1 Enable / Type
400D 500D FRQ1 Logic1 FRQ1 Logic
400E 500E FRQ2 FT2 FRQ2 Enable / Type
400F 500F FRQ2 DFT2 DFRQ2 Enable / Type
4010 5010 FRQ2 Logic2 FRQ2 Logic
4011 5011 FRQ3 FT3 FRQ3 Enable / Type
Protection 4012 5012 FRQ3 DFT3 DFRQ3 Enable / Type
4013 5013 FRQ3 Logic3 FRQ3 Logic
4014 5014 FRQ4 FT4 FRQ4 Enable / Type
4015 5015 FRQ4 DFT4 DFRQ4 Enable / Type
4016 5016 FRQ4 Logic4 FRQ4 Logic
4800 5800 OV OV1 OV1 Threshold setting
4803 5803 OV TOV1 OV1 Time multiplier setting
4400 5400 OV TOV1 OV1 Definite time setting
4804 5804 OV TOV1R OV1 Definite time reset delay
4805 5805 OV OV1DPR OV1 DO/PU ratio
4801 5801 OV OV2 OV2 Threshold setting
4816 5816 OV TOV2 OV2 Time multiplier setting
4401 5401 OV TOV2 OV2 Definite time setting
4817 5817 OV TOV2R OV2 Definite time reset delay
4806 5806 OV OV2DPR OV2 DO/PU ratio
4802 5802 OV OV3 OV3 Threshold setting
4402 5402 OV TOV3 OV3 Definite time setting
4807 5807 OV OV3DPR OV3 DO/PU ratio
4818 5818 OV OV1-k Configurable IDMT Curve setting of OV1
4819 5819 OV OV1-α Configurable IDMT Curve setting of OV1
481A 581A OV OV1-C Configurable IDMT Curve setting of OV1
481B 581B OV OV2-k Configurable IDMT Curve setting of OV2
218
6 F 2 T 0 1 7 6
Setting Address
Group Name Contents
(Menu) Gr.1 Gr.2
481C 581C OV OV2-α Configurable IDMT Curve setting of OV2
481D 581D OV OV2-C Configurable IDMT Curve setting of OV2
4808 5808 UV UV1 UV1 Threshold setting
480B 580B UV TUV1 UV1 Time multiplier setting
4403 5403 UV TUV1 UV1 Definite time setting
480C 580C UV TUV1R UV1 Definite time reset delay
4809 5809 UV UV2 UV2 Threshold setting
481E 581E UV TUV2 UV2 Time multiplier setting
4404 5404 UV TUV2 UV2 Definite time setting
481F 581F UV TUV2R UV2 Definite time reset delay
480A 580A UV UV3 UV2 Threshold setting
4405 5405 UV TUV3 UV3 Definite time setting
480D 580D UV VBLK UV Block Threshold setting
4820 5820 UV UV1-k Configurable IDMT Curve setting of UV1
4821 5821 UV UV1-α Configurable IDMT Curve setting of UV1
4822 5822 UV UV1-C Configurable IDMT Curve setting of UV1
4823 5823 UV UV2-k Configurable IDMT Curve setting of UV2
4824 5824 UV UV2-α Configurable IDMT Curve setting of UV2
4825 5825 UV UV2-C Configurable IDMT Curve setting of UV2
Protection
480E 580E ZPS ZPS1 ZPS1 Threshold setting
4810 5810 ZPS TZPS1 ZPS1 Time multiplier setting
4406 5406 ZPS TZPS1 ZPS1 Definite time setting
4811 5811 ZPS TZPS1R ZPS1 Definite time reset delay
480F 580F ZPS ZPS2 ZPS2 Threshold setting
4826 5826 ZPS TZPS2 ZPS2 Time multiplier setting
4407 5407 ZPS TZPS2 ZPS2 Definite time setting
4827 5827 ZPS TZPS2R ZPS2 Definite time reset delay
4828 5828 ZPS ZPS 1-k Configurable IDMT Curve setting of ZPS1
4829 5829 ZPS ZPS 1-α Configurable IDMT Curve setting of ZPS1
482A 582A ZPS ZPS 1-C Configurable IDMT Curve setting of ZPS1
482B 582B ZPS ZPS 2-k Configurable IDMT Curve setting of ZPS2
482C 582C ZPS ZPS 2-α Configurable IDMT Curve setting of ZPS2
482D 582D ZPS ZPS 2-C Configurable IDMT Curve setting of ZPS2
4812 5812 NPS NPS1 NPS1 Threshold setting
4814 5814 NPS TNPS1 NPS1 Time multiplier setting
4408 5408 NPS TNPS1 NPS1 Definite time setting
4815 5815 NPS TNPS1R NPS1 Definite time reset delay
4813 5813 NPS NPS2 NPS2 Threshold setting
482E 582E NPS TNPS2 NPS2 Time multiplier setting
4409 5409 NPS TNPS2 NPS2 Definite time setting
482F 582F NPS TNPS2R NPS2 Definite time reset delay
4830 5830 NPS NPS 1-k Configurable IDMT Curve setting of NPS1
4831 5831 NPS NPS 1-α Configurable IDMT Curve setting of NPS1
219
6 F 2 T 0 1 7 6
Setting Address
Group Name Contents
(Menu) Gr.1 Gr.2
4832 5832 NPS NPS 1-C Configurable IDMT Curve setting of NPS1
4833 5833 NPS NPS 2-k Configurable IDMT Curve setting of NPS2
4834 5834 NPS NPS 2-α Configurable IDMT Curve setting of NPS2
4835 5835 NPS NPS 2-C Configurable IDMT Curve setting of NPS2
4836 5836 FRQ F11 F11 Threshold setting
440A 540A FRQ TF11 F11 Time delay setting
4837 5837 FRQ F12 F12 Threshold setting
440B 540B FRQ TF12 F12 Time delay setting
4838 5838 FRQ DF1 DFRQ1 Threshold setting
4839 5839 FRQ F21 F21 Threshold setting
440C 540C FRQ TF21 F21 Time delay setting
Protection
483A 583A FRQ F22 F22 Threshold setting
440D 540D FRQ TF22 F22 Time delay setting
483B 583B FRQ DF2 DFRQ2 Threshold setting
483C 583C FRQ F31 F31 Threshold setting
440E 540E FRQ TF31 F31 Time delay setting
483D 583D FRQ F32 F32 Threshold setting
440F 540F FRQ TF32 F32 Time delay setting
483E 583E FRQ DF3 DFRQ3 Threshold setting
483F 583F FRQ F41 F41 Threshold setting
4410 5410 FRQ TF41 F41 Time delay setting
4840 5840 FRQ F42 F42 Threshold setting
4411 5411 FRQ TF42 F42 Time delay setting
4841 5841 FRQ DF4 DFRQ4 Threshold setting
4842 5842 FRQ FVBLK FRQ Block threshold setting
3. CB remote control
To control the CB at remote site with the Modbus communication, do the following.
・Operation item
- Remote control (CB on / off)
- Change of interlock position
- LED reset
・Operating procedure
To control the CB at remote site with Modbus communication is require the following three steps.
- Pass word authentication
- Enable flag setting for remote control
- Remote control
CAUTION
To control the CB at remote site, set the control hierarchy setting of relay to “Remote”.
220
6 F 2 T 0 1 7 6
Message example
to relay 02050200FF00
from relay 02050200FF00
C. Remote control
To control the CB at remote site, turn on or off the address of “0400: Remote control
command”, ”0401: Remote interlock command” or “0402: Remote reset command”.
The “On” operation command is “FF00”. The “Off” operation command is “0000”.
The operation reply is checked by the “BO” or “LED” signals according to the relay settings.
221
6 F 2 T 0 1 7 6
Appendix M
IEC60870-5-103: Interoperability
222
6 F 2 T 0 1 7 6
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of devices, 32 for one protection equipment
1.2 Transmission speed
User setting: 9600 or 19200 bit/s
2. Application Layer
COMMON ADDRESS of ASDU (Application Service Data Unit)
One COMMON ADDRESS OF ASDU (identical with station address)
3. IEC60870-5-103 Interface
3.1 Spontaneous events
The events created by the relay will be sent using the Function type (FUN) / Information
numbers (INF) to the IEC60870-5-103 master station. 8 wide-use events are provided.
3.2 General interrogation
The GI request can be used to read the status of the relay, the Function types and Information
numbers that will be returned during the GI cycle are shown in the table below.
3.3 Cyclic measurements
The relay will produce measured values using Type ID=3 and 9 on a cyclical basis, this can be
read from the relay using a Class 2 poll. The rate at which the relay produces new measured
values is 2 seconds.
It should be noted that the measurands transmitted by the relay are sent as a proportion of either
1.2 or 2.4 times the rated value of the analog value. Either 1.2 or 2.4 can be selected by the
“IECNFV” and “IECNFf” settings.
3.4 Commands
A list of the supported commands is contained in the table below. The relay will respond to
other commands with an ASDU 1, with a cause of transmission (COT) of negative
acknowledgement of a command.
3.5 Test mode
In test mode, both spontaneous messages and polled measured values, intended for processing in
the control system, are designated by means of the CAUSE OF TRANSMISSION ‘test mode’.
This means that CAUSE OF TRANSMISSION = 7 ‘test mode’ is used for messages normally
transmitted with COT=1 (spontaneous) or COT=2 (cyclic).
For details, refer to the standard IEC60870-5-103.
3.6 Blocking of monitor direction
If the blocking of the monitor direction is activated in the protection equipment, all indications
and measurands are no longer transmitted.
For details, refer to the standard IEC60870-5-103.
223
6 F 2 T 0 1 7 6
4. List of Information
List of Information
Typ
INF Description Contents GI COT FUN
e ID
Standard Information numbers in monitor direction
System Function
0 End of General Interrogation Transmission completion of GI items. -- 8 10 255
0 Time Synchronization Time Synchronization ACK. -- 6 8 255
2 Reset FCB Reset FCB(toggle bit) ACK -- 5 3 215
3 Reset CU Reset CU ACK -- 5 4 215
4 Start/Restart Relay start/restart -- 5 5 215
5 Power On Relay power on. Not supported
Status Indications
If it is possible to use auto-recloser, this item is set active, if
16 Auto-recloser active Not supported
impossible, inactive.
If protection using telecommunication is available, this item is set
17 Teleprotection active Not supported
to active. If not, set to inactive.
If the protection is available, this item is set to active. If not, set to 1, 7, 9, 12,
18 Protection active GI 1 215
inactive. 20
27 Auxiliary input1 User specified signal 1 (Signal specified by IECB1: ON) (*1) GI 1 1, 7, 9 215
28 Auxiliary input2 User specified signal 2 (Signal specified by IECB2: ON) (*1) GI 1 1, 7, 9 215
29 Auxiliary input3 User specified signal 3 (Signal specified by IECB3: ON) (*1) GI 1 1, 7, 9 215
30 Auxiliary input4 User specified signal 4 (Signal specified by IECB4: ON) (*1) GI 1 1, 7, 9 215
Supervision Indications
32 Measurand supervision I Zero sequence current supervision Not supported
33 Measurand supervision V Zero sequence voltage supervision GI 1 1, 7, 9 215
35 Phase sequence supervision Negative sequence voltage supevision GI 1 1, 7, 9 215
36 Trip circuit supervision Output circuit supervision GI 1 7, 9 215
37 I>>backup operation Not supported
38 VT fuse failure VT failure Not supported
39 Teleprotection disturbed CF(Communication system Fail) supervision Not supported
46 Group warning Only alarming GI 1 1, 7, 9 215
47 Group alarm Trip blocking and alarming GI 1 1, 7, 9 215
224
6 F 2 T 0 1 7 6
Typ
INF Description Contents GI COT FUN
e ID
Fault Indications
64 Start/pick-up L1 A phase, A-B phase or C-A phase element pick-up GI 2 1, 7, 9 215
65 Start/pick-up L2 B phase, A-B phase or B-C phase element pick-up GI 2 1, 7, 9 215
66 Start/pick-up L3 C phase, B-C phase or C-A phase element pick-up GI 2 1, 7, 9 215
67 Start/pick-up N Earth fault element pick-up GI 2 1, 7, 9 215
68 General trip BO status specified by IECGT: ON (*1) -- 2 1, 7 215
69 Trip L1 BO status specified by IECAT: ON (*1) -- 2 1, 7 215
70 Trip L2 BO status specified by IECBT: ON (*1) -- 2 1, 7 215
71 Trip L3 BO status specified by IECCT: ON (*1) -- 2 1, 7 215
72 Trip I>>(back-up) Back up trip Not supported
Fault location (prim. [ohm] / second. [ohm] / km selectable by
73 Fault location X In ohms Not supported
IECFL)
74 Fault forward/line Forward fault Not supported
75 Fault reverse/Busbar Reverse fault Not supported
Teleprotection Signal
76 Carrier signal sending Not supported
transmitted
92 Trip IN> Inverse time earth fault OC trip (OR logic of EF1 and SEF1 trip) Not supported
Definite time earth fault OC trip (OR logic of EF1 to EF3 and
93 Trip IN>> Not supported
SEF1 to SEF3 trip)
Autoreclose indications
128 CB 'ON' by Autoreclose CB close command output Not supported
CB 'ON' by long-time
129 Not supported
Autoreclose
130 Autoreclose Blocked Autoreclose block Not supported
225
6 F 2 T 0 1 7 6
Typ
INF Description Contents GI COT FUN
e ID
IECG1
IECI1 User specified 1 Signal specified by IECE1: ON (*1) 2 1, 7 215
(yes/no)
IECG2
IECI2 User specified 2 Signal specified by IECE2: ON (*1) 2 1, 7 215
(yes/no)
IECG3
IECI3 User specified 3 Signal specified by IECE3: ON (*1) 2 1, 7 215
(yes/no)
IECG4
IECI4 User specified 4 Signal specified by IECE4: ON (*1) 2 1, 7 215
(yes/no)
IECG5
IECI5 User specified 5 Signal specified by IECE5: ON (*1) 2 1, 7 215
(yes/no)
IECG6
IECI6 User specified 6 Signal specified by IECE6: ON (*1) 2 1, 7 215
(yes/no)
IECG7
IECI7 User specified 7 Signal specified by IECE7: ON (*1) 2 1, 7 215
(yes/no)
IECG8
IECI8 User specified 8 Signal specified by IECE8: ON (*1) 2 1, 7 215
(yes/no)
Measurands(*3)
144 Measurand I <meaurand I> Not supported
145 Measurand I,V Vb measurand <meaurand I> -- 3.2 2, 7 215
146 Measurand I,V,P,Q Vb measurand <meaurand I> -- 3.3 2, 7 215
147 Measurand IN,VEN Ve measurand <meaurand I> -- 3.4 2, 7 215
Measurand IL1,2,3, VL1,2,3,
148 Va, Vb, Vc measurand <meaurand II> -- 3 2, 7 215
P,Q,f
Generic Function
240 Read Headings Not supported
Read attributes of all entries of
241 Not supported
a group
243 Read directory of entry Not supported
244 Real attribute of entry Not supported
245 End of GGI Not supported
249 Write entry with confirm Not supported
250 Write entry with execute Not supported
251 Write entry aborted Not supported
Type ID=9
Model (INF=148)
IL1 IL2 IL3 VL1 VL2 VL3 3-phase P 3-phase Q f
Model 410 0 0 0 Va Vb Vc 0 0 f
226
6 F 2 T 0 1 7 6
Typ
INF Description Contents COM COT FUN
e ID
Selection of standard information numbers in control direction
System functions
Initiation of general
0 -- 7 9 215
interrogation
0 Time synchronization -- 6 8 215
General commands
16 Auto-recloser on/off Not supported
17 Teleprotection on/off Not supported
18 Protection on/off (*4) ON/OFF 20 20 215
19 LED reset Reset indication of latched LEDs. ON 20 20 215
23 Activate characteristic 1 Setting Group 1 ON 20 20 215
24 Activate characteristic 2 Setting Group 2 ON 20 20 215
25 Activate characteristic 3 Setting Group 3 Not supported
26 Activate characteristic 4 Setting Group 4 Not supported
Generic functions
Read headings of all defined
240 Not supported
groups
Read values or attributes of all
241 Not supported
entries of one group
Note (∗4): When the relay is receiving the "Protection off" command, the " IN SERVICE LED" is off.
GRE130
Description Contents Comment
supported
Basic application functions
Test mode Yes
Blocking of monitor direction Yes
Disturbance data No
Generic services No
Private data No
Miscellaneous
Max. MVAL = rated
Measurand
value times
Current L1 Ia No
Current L2 Ib No
Current L3 Ic No
Voltage L1-E Va 1,2 or 2,4 IECNFV setting
Voltage L2-E Vb 1,2 or 2,4 IECNFV setting
Voltage L3-E Vc 1,2 or 2,4 IECNFV setting
Active power P P No
Reactive power Q Q No
Frequency f f 1,2 or 2,4 IECNFf setting
Voltage L1 - L2 Vab 1,2 or 2,4 IECNFV setting
227
6 F 2 T 0 1 7 6
[Legend]
GI: General Interrogation
Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1)
1 : time-tagged message
2 : time-tagged message with relative time
3 : measurands I
4 : time-tagged measurands with relative time
5 : identification
6 : time synchronization
8 : general interrogation termination
9 : measurands II
10: generic data
11: generic identification
20: general command
23: list of recorded disturbances
26: ready for transmission for disturbance data
27: ready for transmission of a channel
28: ready for transmission of tags
29: transmission of tags
30: transmission of disturbance values
31: end of transmission
COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3)
1: spontaneous
2: cyclic
3: reset frame count bit (FCB)
4: reset communication unit (CU)
5: start / restart
6: power on
7: test mode
8: time synchronization
9: general interrogation
10: termination of general interrogation
11: local operation
12: remote operation
20: positive acknowledgement of command
21: negative acknowledgement of command
31: transmission of disturbance data
40: positive acknowledgement of generic write command
41: negative acknowledgement of generic write command
42: valid data response to generic read command
43: invalid data response to generic read command
44: generic write confirmation
228
6 F 2 T 0 1 7 6
Appendix P
IEC61850: Interoperability
229
6 F 2 T 0 1 7 6
1. IEC61850 Documentation
IEC61850 Model Implementation Conformance Statement (MICS) for GRE130
The GRE130 relay supports IEC 61850 logical nodes and common data classes as indicated in the
following tables.
Logical nodes in IEC 61850-7-4
230
6 F 2 T 0 1 7 6
231
6 F 2 T 0 1 7 6
232
6 F 2 T 0 1 7 6
LPHD class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
PhyName DPL Physical device name plate M Y
PhyHealth INS Physical device health M Y
OutOv SPS Output communications buffer overflow O N
Proxy SPS Indicates if this LN is a proxy M Y
InOv SPS Input communications buffer overflow O N
NumPwrUp INS Number of Power ups O N
WrmStr INS Number of Warm Starts O N
WacTrg INS Number of watchdog device resets detected O N
PwrUp SPS Power Up detected O N
PwrDn SPS Power Down detected O N
PwrSupAlm SPS External power supply alarm O N
RsStat SPC Reset device statistics T O N
LLNO class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
Loc SPS Local operation for complete logical device O Y
OpTmh INS Operation time O N
Controls
Diag SPC Run Diagnostics O Y
LEDRs SPC LED reset T O Y
233
6 F 2 T 0 1 7 6
PFRC class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
BlkV SPS Blocked because of voltage O Y
Settings
StrVal ASG Start Value df/dt O Y
BlkVal ASG Voltage Block Value O Y
OpDlTmms ING Operate Delay Time O N
RsDlTmms ING Reset Delay Time O N
PTOF class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
BlkV SPS Blocked because of voltage O Y
Settings
StrVal ASG Start Value (frequency) O Y
BlkVal ASG Voltage Block Value O Y
OpDITmms ING Operate Delay Time O Y
RsDITmms ING Reset Delay Time O N
PTOV class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T O Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N
234
6 F 2 T 0 1 7 6
PTRC class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Tr ACT Trip C Y
Op ACT Operate (combination of subscribed Op from protection C N
functions)
Str ACD Sum of all starts of all connected Logical Nodes O N
Settings
TrMod ING Trip Mode O N
TrPlsTmms ING Trip Pulse Time O N
Condition C: At least one of the two status information (Tr, Op) shall be used.
PTUV class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N
PTUF class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
BlkV SPS Blocked because of voltage O Y
Settings
StrVal ASG Start Value (frequency) O Y
BlkVal ASG Voltage Block Value O Y
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N
235
6 F 2 T 0 1 7 6
CILO class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
Status Information
EnaOpn SPS Enable Open M Y
EnaCls SPS Enable Close M Y
CSWI class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Controls
Pos DPC Switch, general M Y
PosA DPC Switch L1 O N
PosB DPC Switch L2 O N
PosC DPC Switch L3 O N
OpOpn ACT Operation “Open Switch” T O N
OpCls ACT Operation “Close Switch” T O N
GGIO class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind01 SPS General indication (binary input) O Y
Ind02 SPS General indication (binary input) O Y
Ind03 SPS General indication (binary input) O Y
Ind04 SPS General indication (binary input) O Y
Ind05 SPS General indication (binary input) O Y
Ind06 SPS General indication (binary input) O Y
Ind07 SPS General indication (binary input) O Y
Ind08 SPS General indication (binary input) O Y
Ind09 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
:::
236
6 F 2 T 0 1 7 6
MMXU class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
EEHealth INS External equipment health (external sensor) O N
Measured values
TotW MV Total Active Power (Total P) O N
TotVAr MV Total Reactive Power (Total Q) O N
TotVA MV Total Apparent Power (Total S) O N
TotPF MV Average Power factor (Total PF) O N
Hz MV Frequency O Y
PPV DEL Phase to phase voltages (VL1VL2, …) O Y
PhV WYE Phase to ground voltages (VL1ER, …) O Y
A WYE Phase currents (IL1, IL2, IL3) O N
W WYE Phase active power (P) O N
VAr WYE Phase reactive power (Q) O N
VA WYE Phase apparent power (S) O N
PF WYE Phase power factor O N
Z WYE Phase Impedance O N
237
6 F 2 T 0 1 7 6
MSQI class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Measured values
SeqA SEQ Positive, Negative and Zero Sequence Current C N
SeqV SEQ Positive, Negative and Zero Sequence Voltage C Y
DQ0Seq SEQ DQ0 Sequence O N
ImbA WYE Imbalance current O N
ImbNgA MV Imbalance negative sequence current O N
ImbNgV MV Imbalance negative sequence voltage O N
ImbPPV DEL Imbalance phase-phase voltage O N
ImbV WYE Imbalance voltage O N
ImbZroA MV Imbalance zero sequence current O N
ImbZroV MV Imbalance zero sequence voltage O N
MaxImbA MV Maximum imbalance current O N
MaxImbPPV MV Maximum imbalance phase-phase voltage O N
MaxImbV MV Maximum imbalance voltage O N
Condition C: At least one of either data shall be used.
XCBR class
Attribute Name Attr. Type Explanation T M/O GRE130
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node M Y
Class
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
OpCnt INS Operation counter M Y
Controls
Pos DPC Switch position M Y
BlkOpn SPC Block opening M Y
BlkCls SPC Block closing M Y
ChaMotEna SPC Charger motor enabled O N
Metered Values
SumSwARs BCR Sum of Switched Amperes, resetable O N
Status Information
CBOpCap INS Circuit breaker operating capability M Y
POWCap INS Point On Wave switching capability O N
MaxOpCap INS Circuit breaker operating capability when fully charged O N
238
6 F 2 T 0 1 7 6
SPS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal BOOLEAN ST dchg TRUE | FALSE M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV TRUE | FALSE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13 (see IEC 61850-7-3)
INS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal INT32 ST dchg M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13 (see IEC 61850-7-3)
239
6 F 2 T 0 1 7 6
ACT class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
phsA BOOLEAN ST dchg O Y
phsB BOOLEAN ST dchg O Y
phsC BOOLEAN ST dchg O Y
neut BOOLEAN ST dchg O Y
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
operTm TimeStamp CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13 (see IEC 61850-7-3)
ACD class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
dirGeneral ENUMERATED ST dchg unknown | forward |M Y
backward | both
phsA BOOLEAN ST dchg GC_2 (1) Y
dirPhsA ENUMERATED ST dchg unknown | forward |GC_2 (1) Y
backward
phsB BOOLEAN ST dchg GC_2 (2) Y
dirPhsB ENUMERATED ST dchg unknown | forward |GC_2 (2) Y
backward
phsC BOOLEAN ST dchg GC_2 (3) Y
dirPhsC ENUMERATED ST dchg unknown | forward |GC_2 (3) Y
backward
neut BOOLEAN ST dchg GC_2 (4) Y
dirNeut ENUMERATED ST dchg unknown | forward |GC_2 (4) Y
backward
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13 (see IEC 61850-7-3)
240
6 F 2 T 0 1 7 6
MV class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instMag AnalogueValue MX O N
mag AnalogueValue MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high |O N
low-low |…
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal AnalogueValue SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 … 100 000 O N
zeroDb INT32U CF 0 … 100 000 O N
sVC ScaledValueConfig CF AC_SCAV Y
rangeC RangeConfig CF GC_CON N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21 (see IEC 61850-7-3)
241
6 F 2 T 0 1 7 6
CMV class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instCVal Vector MX O N
cVal Vector MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high |O N
low-low |…
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal Vector SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 … 100 000 O N
zeroDb INT32U CF 0 … 100 000 O N
rangeC RangeConfig CF GC_CON N
magSVC ScaledValueConfig CF AC_SCAV Y
angSVC ScaledValueConfig CF AC_SCAV N
angRef ENUMERATED CF V | A | other … O N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21 (see IEC 61850-7-3)
WYE class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsA CMV GC_1 Y
phsB CMV GC_1 Y
phsC CMV GC_1 Y
neut CMV GC_1 Y
net CMV GC_1 N
res CMV GC_1 N
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | VabO N
| Vbc | Vca | Vother | Aother
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21 (see IEC 61850-7-3)
242
6 F 2 T 0 1 7 6
DEL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsAB CMV GC_1 Y
phsBC CMV GC_1 Y
phsCA CMV GC_1 Y
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | VabO N
| Vbc | Vca | Vother | Aother
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21 (see IEC 61850-7-3)
SEQ class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
c1 CMV M Y
c2 CMV M Y
c3 CMV M Y
DataAttribute
measured attributes
seqT ENUMERATED MX pos-neg-zero | dir-quad-zero M Y
configuration, description and extension
phsRef ENUMERATED CF A|B|C|… O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21 (see IEC 61850-7-3)
243
6 F 2 T 0 1 7 6
SPC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator_RO CO, ST AC_CO_O N
ctlNum INT8U_RO CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_ N
M
SBOw SBOW CO AC_CO_SBOW_E N
_M
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_ N
M and
AC_CO_SBOW_E
_M and
AC_CO_TA_E_M
stVal BOOLEAN ST dchg FALSE | TRUE AC_ST Y
q Quality ST qchg AC_ST Y
t TimeStamp ST AC_ST Y
stSeld BOOLEAN ST dchg AC_CO_O N
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31 (see IEC 61850-7-3) and Table E.2 (see IEC 61850-8-1)
244
6 F 2 T 0 1 7 6
DPC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O N
ctlNum INT8U CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_ Y
M
SBOw SBOW CO AC_CO_SBOW_E N
_M
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_ Y
M and
AC_CO_SBOW_E
_M and
AC_CO_TA_E_M
stVal CODED ENUM ST dchg intermediate-state | off | on |M Y
bad-state
q Quality ST qchg M Y
t TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal CODED ENUM SV intermediate-state | off | on |PICS_SUBST N
bad-state
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
ctlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O Y
sboClass SboClasses CF AC_CO_O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31 (see IEC 61850-7-3) and Table E.3 (see IEC 61850-8-1)
245
6 F 2 T 0 1 7 6
INC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal INT32 CO AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O N
ctlNum INT8U CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_ N
M
SBOw SBOW CO AC_CO_SBOW_E N
_M
Oper Oper CO AC_CO _M N
Cancel Cancel CO AC_CO_SBO_N_ N
M and
AC_CO_SBOW_E
_M and
AC_CO_TA_E_M
stVal INT32 ST dchg M Y
Q Quality ST qchg M Y
t TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31 (see IEC 61850-7-3) and Table E.4 (see IEC 61850-8-1)
246
6 F 2 T 0 1 7 6
ING class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setVal INT32 SP AC_NSG_M Y
setVal INT32 SG, SE AC_SG_M N
configuration, description and extension
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 39 (see IEC 61850-7-3)
ASG class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setMag AnalogueValue SP AC_NSG_M Y
setMag AnalogueValue SG, SE AC_SG_M N
configuration, description and extension
units Unit CF see Annex A O Y
sVC ScaledValueConfig CF AC_SCAV Y
minVal AnalogueValue CF O N
maxVal AnalogueValue CF O N
stepSize AnalogueValue CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 42 (see IEC 61850-7-3)
DPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
hwRev VISIBLE STRING255 DC O N
swRev VISIBLE STRING255 DC O N
serNum VISIBLE STRING255 DC O N
model VISIBLE STRING255 DC O N
location VISIBLE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45 (see IEC 61850-7-3)
247
6 F 2 T 0 1 7 6
LPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRE130
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
swRev VISIBLE STRING255 DC M Y
d VISIBLE STRING255 DC M Y
dU UNICODE STRING255 DC O N
configRev VISIBLE STRING255 DC AC_LN0_M Y
ldNs VISIBLE STRING255 EX shall be included in LLN0 AC_LN0_EX Y
only;
for example "IEC
61850-7-4:2003"
lnNs VISIBLE STRING255 EX AC_DLD_M N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45 (see IEC 61850-7-3)
248
6 F 2 T 0 1 7 6
・NTRODUCTION
This document specifies the Protocol Implementation Conformance Statement (PICS) of the IEC
61850 interface in GRE series IED with communication firmware MVM850-01 series.
Together with the MICS, the PICS forms the basis for a conformance test according to IEC
61850-10.
249
6 F 2 T 0 1 7 6
250
6 F 2 T 0 1 7 6
Application association
S2 Associate M M Y
S3 Abort M M Y
S4 Release M M Y
Logical device
S5 GetLogicalDeviceDirectory M M Y
Logical node
S6 GetLogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O N
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O N
S14 CreateDataSet O O N
S15 DeleteDataSet O O N
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O N
S20 SetSGValues O O N
S21 ConfirmEditSGValues O O N
S22 GetSGValues O O N
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report c6 c6 Y
S24-1 data-change (dchg) Y
S24-2 quality-change (qchg) Y
S24-3 data-update (dupd) N
S25 GetBRCBValues c6 c6 Y
S26 SetBRCBValues c6 c6 Y
Unbuffered report control block (URCB)
S27 Report c6 c6 Y
S27-1 data-change (dchg) Y
S27-2 quality-change (qchg) Y
S27-3 data-update (dupd) N
S28 GetURCBValues c6 c6 Y
S29 SetURCBValues c6 c6 Y
Logging
Log control block
S30 GetLCBValues M M N
S31 SetLCBValues O M N
Log
S32 QueryLogByTime c7 M N
S33 QueryLogAfter c7 M N
S34 GetLogStatusValues M M N
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage c8 c8 Y
S36 GetGoReference O c9 N
S37 GetGOOSEElementNumber O c9 N
S38 GetGoCBValues O O Y
S39 SetGoCBValues O O Y
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage c8 c8 N
S41 GetGsReference O c9 N
S42 GetGSSEDataOffset O c9 N
S43 GetGsCBValues O O N
S44 SetGsCBValues O O N
251
6 F 2 T 0 1 7 6
252
6 F 2 T 0 1 7 6
253
6 F 2 T 0 1 7 6
Protcol Implementation eXtra Information for Testing (PIXIT) for IEC61850 interface in GRE series IED
・Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in GRE series IED with communication firmware MVM850-01 series version
upper than A (MVM850-01-A).
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to
IEC 61850-10.
Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC
61850-10.
254
6 F 2 T 0 1 7 6
255
6 F 2 T 0 1 7 6
256
6 F 2 T 0 1 7 6
257
6 F 2 T 0 1 7 6
258
6 F 2 T 0 1 7 6
259
6 F 2 T 0 1 7 6
Note:
Subscribed payload data structure is checked to
determine if IED accepts/discards the data;
however the TAL timeout is reset even when such
data is discarded.
Go21 What is the behavior when the The device starts sending GOOSE from
device starts up? stNum=1 and sqNum=1.
Go22 Is it supported to set the “ndsCom” N
as TRUE?
260
6 F 2 T 0 1 7 6
Ct10 How to force a “test-not-ok” respond Set orCat with unsupported value.
with SelectWithValue request?
261
6 F 2 T 0 1 7 6
262
6 F 2 T 0 1 7 6
263
6 F 2 T 0 1 7 6
IEC61850 Tissues conformance statement (TICS) of the IEC61850 communication interface GRE series IED
・Introduction
According to the UCA IUG QAP the tissue conformance statement is required to perform a
conformance test and is referenced on the certificate.
This document is applicable for GRE series IED with communication firmware MVM850-01 series
version upper than A (MVM850-01-A).
During the October 2006 meeting IEC TC57 working group 10 decided that:
• green Tissues with the category “IntOp” are mandatory for IEC 61850 edition 1
• Tissues with the category “Ed.2” Tissues should not be implemented.
Below table gives an overview of the implemented IntOp Tissues.
264
6 F 2 T 0 1 7 6
NOTE: Tissue 49, 190, 191, 275 and 278 are part of the optional tissue #453, all other technical tissues in the table are
mandatory if applicable.
265
6 F 2 T 0 1 7 6
After the approval of the server conformance test procedures version 2.2 the following IntOp
tissues were added or changed. It is optional to implement these tissues.
266
6 F 2 T 0 1 7 6
2. CB remote control
To control the CB at remote site with the IEC 61850 communication, do the following.
・Operation item
- Remote control by the Select Before Operate or Direct Operate (CB Open / CB Close)
- Change of interlock position (BlkOpn or BlkCls)
- Trip LED reset
・Operating procedure
To control the CB at remote site with ICE 61850 communication is require the following three steps.
- get Logical nodes by using IEC 61850 data setting tools (such as TAMARACK tool).
- change the control logical node (XCBR, CILO or CSWI).
When CB is remote controlled from PC, showing below the control reaction depending on the CB Status.
CB Status Response
267
6 F 2 T 0 1 7 6
Appendix O
Ordering
268
6 F 2 T 0 1 7 6
Ordering
Under/Overvoltage Relay GRE130 A 0
Type:
Voltage Relay GRE130
Model:
- Model 410: Four pole
2 x BIs, 4 x Bos, 1 x Relay fail 410
6 x BIs, 4 x BOs, 1 x Relay fail 411
6 x BIs, 8 x BOs, 1 x Relay fail 412
Rating:
VT: 110V, f: 50/60Hz, 110-250Vdc or 100-220Vac 1
VT: 110V, f: 50/60Hz, 48-110Vdc 2
VT: 110V, f: 50/60Hz, 24-48Vdc A
Standard and language:
IEC (English) 0
ANSI (English) 1
Chinese 2
Communication:
RS485 1port (Modbus/IEC60870-5-103) 10
RS485 1port (Modbus/DNP3.0) 11
Following options can be equipped
with Model 402 and 422 only 20
RS485 2ports (Modbus/IEC60870-5-103) 21
RS485 2ports (Modbus/DNP3.0) A0
100BASE-TX 1port (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) A1
100BASE-TX 1port (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) B0
100BASE-TX 2ports (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) B1
100BASE-TX 2ports (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) C0
100BASE-FX 1port (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) C1
100BASE-FX 1port (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) D0
100BASE-FX 2ports (Modbus/ IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) D1
100BASE-FX 2ports (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0)
269
6 F 2 T 0 1 7 6
Version-up Records
270