Vous êtes sur la page 1sur 8

L APPA

ICA R
TR
Tech Note No. 29 Application Considerations of PWM Inverters

AT
C
ELE

US
TECH NOTE NO. 29 Reliable Solutions Today! EA SA

SER

N
IO
IC

V
T
E A IA
SSOC

APPLICATION CONSIDERATIONS OF PULSE-WIDTH


MODULATED INVERTERS AND AC INDUCTION
MOTORS TO A TOTAL SYSTEM
By Ausin H. Bonnett, Fellow IEEE
EASA Technology & Education Consultant

ABSTRACT tion and lower cost, the use of higher performance PWM
The pulse-width modulated (PWM) inverter is one of the drives has grown at an exponential rate.
newest and fastest evolving technologies used in electric
power systems to accomplish speed control. Constant and Figure 1 shows how drives have evolved over the past 20
rapid changes require a continuous evaluation of their im- years, from silicon-controlled rectifiers (SCRs) at 300Hz to
pact on the system the current gate turn-off thyristors (GTOs) and the newer in-
sulated gate bipolar transistors (IGBTs) that operate up to
The purpose of this paper is to establish the criteria for the 20 kHz range. IGBTs are now the industry standard. Note
applying PWM low voltage drives and AC induction motors how winding stress changes as switching frequency
as a system to the driven equipment. increases.

Emphasis is placed on the impact the PWM waveform has WINDING DIELECTRIC STRESS VERSUS
on the motor life and performance. Various laboratory and THE DEVELOPMENT OF TRANSISTORS
field tests have been conducted to verify the conclusions.
Recommendations are made on insulation systems that will INVERTER APPLIED STRESS LEVELS
WINDING VOLTAGE STRESS

AT SWITCHING FREQUENCY (REPETITIVE)


provide increased motor life. The impact of standing waves is
SINEWAVE INTERMITTENT CAPABILITY
explored along with shaft currents. A detailed list of applica-
tion considerations and constraints is provided to assist in a
complete system approach to applying the drives, cable runs,
motors, couplings and driven equipment. An important part
of this study is the compilation of an extensive bibliography of
other related studies. SCR's TRANSISTORS GTO's IGBT

300 Hz SWITCHING FREQUENCY 20 kHz


INTRODUCTION 1970 1980 1990 2000
YEAR
This article assumes that the traditional fundamental SIX STEP PWM
sinewave voltage is (except for starting or outside influences) Figure 1
a steady-state condition, with a maximum and a RMS value.

The voltage waveform supplied by a PWM drive, however, WINDING INSULATION SYSTEM
can have significant harmonics and transients that may alter Motor winding insulation systems normally are classified
the motor performance characteristics and life expectancy. according to their thermal capability. Low-voltage systems
The effects of the maximum voltage, rate of rise, switching (600 volts or less) used for drive applications are typically
frequencies, resonance and harmonics will all be considered. Class F (155° C) or Class H (180° C). Qualification testing
subjects the samples (motorette) to a series of cycles of ther-
Much has been written over the years about the various mal stress, mechanical stress, and moisture. Electrical stress,
types of adjustable-speed drives (ASDs) and their associ- however, is limited to 60Hz and 600 volts RMS AC in accor-
ated impact on motor applications. This paper focuses on dance with IEEE Standards [1]. Unfortunately, these standards
the impact of the transient voltage, as defined above, gener- do not specify the maximum repetitive voltage transients (Vm),
ated by the ASD on squirrel-cage induction motors. The scope the switching frequency (kHz) and the rate of rise (dV/dt) that
of product discussed will be PWM and low-voltage random- the winding can safely withstand and still meet the life
wound motors (600 volts or less). expectations.

BACKGROUND As suggested above, various types of output transistors


The pulse-width modulated inverter is one of the newest and modulation schemes have different values of Vm and
and fastest evolving technologies in non-linear devices used dV/dt, which in turn have different effects on the life of motor
in power systems. Originally the motivating force for its de- insulation. Figure 2 shows a typical PWM voltage waveform.
velopment was speed control comparable to mechanical or This is obviously a much more severe condition than nor-
DC drives. With the increased emphasis of energy conserva- mally experienced when operating on sinusoidal voltage.

(Update - 7/99)
Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.” TN29-1
Application Considerations of PWM Inverters Tech Note No. 29

HALF CYCLE VOLTAGE WAVEFORM


WINDING DAMAGE OR FAILURE
FOR TYPICAL PWM ASD Four basic stresses act on the stator winding: [2]
Vm ● Thermal ● Mechanical
● Dielectrical ● Environmental
% VOLTAGE

All of these stresses are impacted by ASD voltage wave-


dV/dt forms, in that the longevity of the winding is predicated upon
the integrity of the whole insulation system. During the early
(TEMPERATURE) stages of applying six-step ASDs to AC motors, the major
focus was on the thermal stress generated by the unwanted
drive harmonics passed through to the motor and the associ-
1/T=f TIME (µSEC) ated heating. The other critical factor dealt with the increased
dV/dt = RATE OF RISE OF VOLTAGE heating as a result of reduced cooling capacity at slower
Vm = MAXIMUM WITHSTAND VOLTAGE
f = SWITCHING FREQUENCY speeds. In addition, more attention was given to rotor bar
Figure 2 shapes than to the stator insulation voltage withstand capa-
bility, since the bar shape significantly influences the
Figures 3, 4 and 5 show a typical PWM control circuit and speed-torque characteristics of the motor.
its resulting voltage and current waveforms.
With the present PWM drive technology, which uses much
higher switching rates (sometimes referred to as carrier fre-
TYPICAL PULSE-WIDTH MODULATED CONTROLLER
quencies), and its increased application, the focus must now
turn to the stator winding insulation system. This is not to
D.C. imply that the rotor designs can be ignored. The phase-to-
CONVERTER

LINK
phase and the phase-to-ground insulation is relatively easy
OUTPUT
INPUT

INVERTER

to address. In fact it normally is not the highest stress point


as it was when operating on sinewave power where the
steady-state turn-to-turn stress was relatively low (usually
under 25 volts/turn). The standard magnet wire used by most
CONTROL motor manufacturers is typically a Class H heavy-coated poly-
CIRCUIT ester wire (enameled) with a typical build of .0025” per side.
In accordance with NEMA magnet wire standard, [3] this wire
Figure 3
under ideal conditions (twisted wire pair test) is capable of a
withstand voltage of 5700 volts at a rise time not to exceed
PULSE WIDTH MODULATED VOLTAGE AND 500 volts/second.
CURRENT WAVEFORMS
Windings designed for definite purpose inverter-fed mo-
1500 tors normally use magnet wire with increased build (i.e., triple
and quad build). These polyester based wires demonstrate
1000
higher dielectric breakdown strength when stressed by sine-
500 wave voltage or intermittent transients. When stressed with
VOLTS

high dV/dt’s and fast switching frequencies, however, their


0
withstand capabilities are less effective. The newer inverter
grade magnet wires [4] offer significantly increased life capa-
bility, as shown in Figure 6.

LIFE AT 2kV, 20 kHz, 90°C


0 2 4 6 8
TIME (µSEC) 100000
Figure 4
10000
LIFE (SEC)

4
1000
3
100
2
CURRENT

1 10

1
HEAVY TRIPLE NEW
(HEAVY)
WIRE FILM THICKNESS
Figure 6
0 2 4 6 8
TIME (µSEC)
These values assume that the wire film is applied concen-
Figure 5
trically to the copper, and that no damage or depreciation of

(Update - 7/99)
TN29-2 Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.”
Tech Note No. 29 Application Considerations of PWM Inverters

film thickness occurs in the manufacturing process or opera- A number of investigations by motor and insulation manu-
tion of the motor. The standards for these films in some cases facturers are in process to determine more accurately the
allows for a max/min ratio of up to 4:1. By reducing this ratio voltage endurance levels of the present and proposed insu-
for the same thickness, significant improvement can be made lations systems. Preliminary results [5] [13] indicate that the
in the voltage withstand capability. At high operating tempera- transient voltage levels combined with the operating tempera-
tures the turn-to-turn bond strength may decrease significantly. tures can exceed corona starting levels, which may result in
Hence, coil movement and abrasion reduce the thickness of insulation damage if appropriate precautions are not taken
the turn insulation over time, which can cause premature fail- (e.g., line filters or special insulation systems).
ure of the turn insulation. This condition can be minimized by
improving the winding treatment process. Figure 7 illustrates Figure 8 shows the results of a study conducted [6] [7] to
the various modes of winding failure for a typical stator. Note determine the maximum voltage drop across the first turns of
that it is possible to have any combination of these modes. the lead coils. It is important to understand that the theory of
first or last turn failures is predicated upon the assumption
that the other coils are not weaker links but coils of similar
WYE CONNECTED STATOR SHOWING dielectric strength.
POSSIBLE FAILURE MODES

L1 TURN TO TURN VOLTAGE ACROSS THE FIRST TURNS


COIL TO COIL 1

VOLTAGE DROP ACROSS


OPEN CIRCUIT 0.8

FIRST TURNS
L3 0.6

PHASE TO PHASE 0.4

COIL TO GROUND
0.2
STEADY STATE
L2
0
Figure 7 0 1 2
VOLTAGE RISE TIME (µ sec)
Figure 8
Regardless of the origin of the voltage transient, the high-
est stress points usually occur in the first or last turns of any
given phase. [2] On medium- and high-voltage machines us- STANDING WAVES OR THE “RINGING” EFFECT
ing form coils, additional turn insulation may be added to Using the classical line transmission theory [7], it can be
compensate for this condition. This approach, however, is shown that, depending upon the cable length between a PWM
not practical on low-voltage random-wound windings. On drive and the AC motor, it is possible to experience a voltage
these machines that are specifically designed for inverter- reflection at the motor terminals of up to two times the ap-
duty applications, some manufacturers have developed plied voltage (2Pu). The impedance of a typical induction
special insulation systems that address increased bond motor is mostly inductive and at high switching frequencies
strength, lower operating temperature and higher turn-to-turn appears like an open circuit. Hence, the opportunity for a large
insulation, along with modified phase and ground insulation. incident voltage waveform traveling to the motor terminals
The next section summarizes the various options that can be exists and presents the possibility of serious insulation
exercised to improve the insulation system to qualify it for damage.
inverter-duty application.
VOLTAGE WAVEFORM FOR PWM ASD SHOWING
INVERTER GRADE INSULATION SYSTEM RISE TIME AND "RINGING" EFFECT (5)
FOR ASD MOTORS
1600
The inverter grade insulation system usually consists of
the following key features: 1200

● Magnet wire with increased dielectric strength 800


VOLTAGE

● Improved insulation on end turns, in slots and between 400


phases
0
● Heavy-duty lacing or taping of end turns
● Extra cycles of varnish dip or vacuum impregnation
● Maximized copper content in slots
● High temperature insulation with low thermal rise levels -8 -6 -4 -2 0 2 4 6 8
TIME IN (µ sec)
Frequently this system is combined with a premium effi- Figure 9
cient motor design to increase thermal capability and high
torque capabilities. The motor is normally sized to run at less Figure 9 shows the impact of cable length on peak-to-peak
than the full load point without using the service factor. voltage values at the motor terminals. [6] Figure 10 shows
the relationship between cable length and the rise time. [8]

(Update - 7/99)
Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.” TN29-3
Application Considerations of PWM Inverters Tech Note No. 29

The “Ringing Effect” can be corrected or minimized with of the impact of the ringing effect as a function of the cable
the use of various filter devices that are commercially avail- length.
able, by reducing the cable length (usually to less than 50
feet), or by the use of motors with inverter grade insulation VOLTAGE WAVE FORM WITH FILTER
systems. In some extreme cases more than one of these 100 FT. CABLE RUN
options must be used. The other alternative when long cable 1500
runs are necessary is to apply drives less prone to deliver
these high reflected voltages. 1000

HALF CYCLE VOLTAGE WAVEFORM 500

VOLTAGE
FOR TYPICAL PWM ASD
APPROX. CRITICAL CABLE LENGTH (FT.)

250 0

-500
200

-1000
150
-1500
100 0 10 20 30 40 50 60
TIME (milliseconds)
Figure 12
50

COMPARISON OF PWM VOLTAGE WAVE


0 WITH 6 FT. OF CABLE [6]
0 1 2 3
RISE TIME (µ sec)
Figure 10
Length of cable from drive motor: (6 ft.)

IMPACT OF CABLE LENGTH 1000


The impact of long cable runs can be illustrated by the
VOLTAGE (V)

500
following example of field failures on 8 of 15 standard AC
motors (10HP, 4 pole) on an application powered by typical
0
PWM drives with a switching frequency of 2 kHz. When the
motors failed on initial start up (within 30 days), it was con- -500
cluded that the motors were defective. All 15 motors were
replaced with new motors of another make. The new motors -1000
also started failing within one week of operation. Next, the
user challenged the ASDs as being defective, but no fault
could be found. It was then revealed that the cable run be-
tween the ASDs and motors was 100 feet. -400 -300 -200 -100 0 100 200 300 400
TIME (µ sec)
VOLTAGE WAVE FORM WITHOUT FILTER Figure 13
100 FT. CABLE RUN
COMPARISON OF PWM VOLTAGE WAVE
1500 WITH 100 FT. OF CABLE [6]

1000

500 Length of cable from drive motor: (100 ft.)


VOLTAGE

1000
0
VOLTAGE (V)

500
-500

0
-1000

-500
-1500
0 10 20 30 40 50 60
TIME (milliseconds) -1000
Figure 11

A simulation test conducted with and without a long cable


run demonstrated that there were excessive voltage levels -400 -300 -200 -100 0 100 200 300 400
and high dV/dt’s. Figures 11 and 12 show the impact of in- TIME (µ sec)
stalling line filters between the drive and motor when operating Figure 14
with the 100 foot cable run. Unfortunately, it was not possible
to separate the spikes caused by the ASD from those caused Numerous examples of this particular problem have been
by the cable run. Figures 13 and 14 provide a clear example documented with a wide variety of PWM drives and motors.

(Update - 7/99)
TN29-4 Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.”
Tech Note No. 29 Application Considerations of PWM Inverters

Close inspection of most of the failed units indicated that turn- Note that in many cases the distortion caused by ASDs cre-
to-turn shorts occurred in several places without any ates little or no problems with equipment connected to either
significant signs of generalized heating. The data, however, the “line side” or the “load side” of the circuit.
does not provide adequate information to confirm that the
turn-to-turn faults were in the first or last coil of a given phase. Regardless of the type of drive, cable run or motor em-
Note too that there are many successful installations with long ployed in a system, when the voltage waveform exceeds the
cable runs. limits specified in NEMA MG 1-30 or 1-31 (1993), it may be
necessary to reduce the stress levels by installing line reac-
Overvoltage and ringing can occur at both the beginning tors at the drive to assure adequate winding life. The
and end of each pulse, [9] as indicated in Figure 15. While impedance of these devices usually is in the 1% to 3% range,
most “external” voltage line transients occur infrequently, the depending on the system impedance. Proper installation of
overvoltage associated with ASDs can occur 20 to 100 times line reactors can provide increased protection for the ASD
per cycle. These repetitions, along with the rise time, have and the motor. Line reactors reduce line disturbances, at-
the most potential for insulation damage. As shown in Figure tenuate harmonics and minimize nuisance tripping. The
8, which provides an envelope or range, as much as 85% of reactor acts like a current-limiting device that filters the wave-
the peak overvoltage can be dropped across the first turn of form and reduces the noise associated with the drive output.
the first coil of a phase, depending upon the dV/dt. [6]
MOTOR NOISE LEVELS
MEASURED PHASE TO PHASE MOTOR When induction motors are operated from non-sinusoidal
TERMINAL VOLTAGE [9] waveforms, the noise emitted by the motor may increase due
1000 to the harmonic content of the waveform. Table 1 illustrates
how motor noise levels differ for operation on sinusoidal and
750 non-sinusoidal waveforms. Normal sinewave performance
readings obtained from a 60 Hz line are in the column on the
500 right.
VOLTAGE (V)

250 It is important to realize that the ASD switching frequency


is the source of the motor sound power level (LW) increased
0 at the various frequency levels. Manufacturers of some ASDs
can program their drives to minimize this increase. In some
-250
cases, filters must be inserted in the output circuit leading to
-500 the motor to prevent excessive noise. Consult the ASD sup-
plier if motor noise is unacceptable at frequencies equal to or
-750 below 60 Hz sinewave values.
0.01 0.02 0.03 0.04 0.05 0.06
TIME (msec) Increased noise levels at 90 Hz and 120 Hz are usually
Figure 15 due to the external cooling fan attached to the motor shaft.
Since the motor speed increases in proportion to the increase
ELECTRICAL HARMONIC IMPACT in frequency, the fan speed will also increase. The increased
Distortion of the fundamental voltage and current wave- air volume created by the higher fan speed can produce an
forms in electrical power systems such as ASDs is becoming objectionable noise level.
more of a concern. The basic problems created by these un- Newer style ASDs can usually help minimize the motor
wanted harmonics include: noise created at 60 Hz and lower frequencies by using higher
● Heat-related failures of capacitors, fuses, cables and switching frequencies. Unfortunately, higher switching fre-
motors. quencies can create additional dielectric stress on the
● Nuisance tripping of overcurrent protective devices. insulation system, as previously described.
● Reduced capacity of neutral grounding.
SHAFT CURRENTS
● Excessive noise levels. During the past few years, a significant increase in prob-
● Interference of electrical communications equipment or lems associated with shaft voltages and currents has been
other sensitive electronic controls. observed. In many cases, these currents have caused bear-
● Circuit resonance.
● Pulsating shaft torques. TABLE 1. SOUND POWER-LW A-WEIGHTED (dBA)
PREDOMINANT NOISE OCTAVE BANDS
LINE REACTORS (CHOKES)
These harmonics and their impact can be sig- Noise for Blower Running Blower
4-Pole
nificantly reduced by adding system filters, which with Motor Powered by Inverter on 60 Hz
usually consist of capacitors and reactors. A com- Speed 6 Hz 15 Hz 30 Hz 60 Hz Sinewave
bination of filters can be used to attenuate various Carrier Carrier Carrier Carrier Carrier
Frame dBA Freq. dBA Freq. dBA Freq. dBA Freq. dBA Freq.
harmonics.
145 75.3 .5 - 1k 73.3 1k 74.6 1k 69.2 .5 - 2k
The application of ASDs can cause distortion 184 69.2 .5k 63.8 4k 67.8 4k 67.1 .5 - 1k
on both the “line side” and “load side” of the drive; 215 69.7 4k 73.1 4k 70.0 4k 71.2 4k 68.6 .5k
only the “load side” is addressed in this article. 256 68.9 4k 73.4 4k 74.3 4k 72.0 4k 67.6 1k - 2k

(Update - 7/99)
Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.” TN29-5
Application Considerations of PWM Inverters Tech Note No. 29

ing failures which are identified as fluting or pitting failures. for the given frame size, reduced motor efficiencies, in-
There are at least three known causes for the phenomena. creased horsepower requirements, or intermittent motor
[10] [11] overloads can all cause excessive temperatures.
1. Electromagnetic dissymmetry, which is usually inherent ● Insufficient motor starting torque due to reduced volts/
in the design and manufacture of the motor. hertz levels, deficiencies in the momentary current ca-
2. Electrostatic charges (associated with friction) accumu- pacity of the drive or incorrect application details.
lated on the rotor assembly. Also, shaft couplings and air ● Motor noise levels exceeding acceptable limits due to
passage are known causes. increased fan noise, excitation of mechanical resonant
3. Electrostatic coupling caused by external power supplies points, or magnetic noise caused by ASD waveforms.
such as PWM inverters. ● Mechanical failure of the motor or associated coupling
Other abnormalities in sinewave power supply associated components due to torque pulsations, mechanical criti-
with grounding, unbalances, or harmonic [17] content may cal frequencies, RPM levels in excess of design
also result in induced shaft voltages. Additional studies are maximums, reduced bearing lubrication at the extreme
underway to further identify and quantify this phenomena. ends of the speed range.
● Winding damage or premature failure due to repetitive
In the case of motors used with ASDs, it is theorized that
high-transient voltages, fast rate of voltage rise, or ex-
the terminal motor voltage supplied by the drive is not bal-
cessive switching rates. Voltage “ringing” is caused by
anced or symmetrical in some aspect. Additional testing and
impedance mismatch, usually related to cable length.
investigation will also be required to confirm these conditions.
● Damage to the motor and drive due to improper installa-
Another possible source of this problem is electrostatic tion or application of power factor correction capacitors.
coupling, which induces a voltage into the shaft large enough ● Loss of third-party listing, such as UL or CSA, for haz-
to cause currents that damage the bearings. The high dV/ ardous location operation due to usage or non-sinusoidal
dt’s associated with the GTO and IGBT transistors are the waveforms.
major sources of this problem. The amount of load, rotor
● Induced shaft voltages, which can cause circulating cur-
speed, method of coupling and type of bearing lubricant can
rents harmful to the bearings.
each aggravate the situation. [16] In some cases, insulated
bearings may not solve this type of problem IEEE Standard 519-1992 (Recommended Practices and
Requirements for Harmonic Control in Electric Power Sys-
Regardless of the cause of the induced shaft voltage, if its
tems) also addresses the effects of the voltage waveform
value exceeds .3 to .5 VRMS sinewave, it may produce cur-
reflected back to the line and passed on to the motor from
rents large enough to permanently damage the bearings. This
the drive. This standard limits line distortion to 5%. Regard-
problem has heretofore been limited to larger motors, usu-
ing the effects of harmonics, the standard states: “Even in
ally 500 frame and up (where the stator outside lamination
the case of the least susceptible equipment, harmonics can
diameters exceed 20”). In most cases, the current passes
be harmful . . . they can cause dielectric, thermal or voltage
through both bearings. This condition can be corrected by
stress, which causes premature aging of electrical insulation.”
insulating the outboard bearing on horizontal motors or the
top bearing on vertical motors. NEMA MG 1-30 (1993), “Application Considerations for
Constant Speed Motors Used on a Sinusoidal Bus with Har-
This approach is usually not practical on smaller motors. monic Content and General Purpose Motors Used with
Some bearing manufacturers [18] [19], however, are now of- Variable-Voltage or Variable-Frequency Controls or Both,” es-
fering anti-friction bearings, in a wide variety and sizes, with tablishes limitations for general purpose NEMA Design A and
insulated outer races. B induction motors. These can be summarized as follows:
Shaft grounding is emerging as an acceptable technology ● Derating curve based upon harmonic content of line
to “bleed-off” shaft currents. This method usually employs a voltage.
carbon brush in contact with the shaft and ground [20] and ● Maximum safe operating speed.
has not always been successful, particularly in hostile envi-
● Reduced torque capability curves for operating speeds
ronments. Experimental work is being done on various bearing
due to reduced cooling.
lubricants to alter the impedance to ground and thereby re-
duce the ground current. ● Reduced torque capability curves for operating speeds
above 60 Hz.
INDUSTRY STANDARDS ● Maximum voltage stress levels:
The new revision of ANSI/IEEE Standard 841 [12] con- ◗ Motors rated 600 volts or less:
tains a list of items to consider when applying ASDs to AC V peak ≤ 1 kV; rise time ≥ 2 µ sec
motors, as shown below. Note that most of them in some ◗ Motors rated greater than 600 volts:
way deal with the effects of the non-linear voltage waveform. V peak ≤ 2.5 pu; rise time ≥ 1 µ sec
MOTOR/DRIVE APPLICATION CONSIDERATIONS NEMA MG 1-31 (1993) now has a new section that speci-
● Motor current exceeding the continuous non-sinusoidal fies limitations for “Definite Purpose Inverter-Fed Motors.”
nameplate data due to excessive voltage harmonics, im- These can be summarized as follows:
proper volts/hertz levels, or increased loading.
● Defininition of rating basis, including speed/torque
● Motor temperatures too high for the rated class of insu- ranges, as well as recommended horsepower and speed
lation at any operating speed or load dictated by the rating.
application. Insufficient cooling, excessive torque levels
● Temperature rise limits.

(Update - 7/99)
TN29-6 Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.”
Tech Note No. 29 Application Considerations of PWM Inverters

● Starting, operating and breakdown torque consideration. 6. Mecker, Steven L. “Considerations In Derating Induc-
● Leakage currents and shaft voltages. tion Motors For Applications On Variable-Frequency
● Voltage spikes and pulsed voltage rise time requirements Drives”; CH3142-7/92.
for motors rated 600 volts or less to be compatible with 7. Persson, Erik. “Transient Effects In Application Of PWM
PWM inverter drives. Inverters To Induction Motors”; CH297-6/91.
● Maximum voltage stress levels: 8. Nailen, Richard L. “Taking A New Look At Inverter-Duty
◗ Motors rated 600 volts or less: Motors.” Electrical Apparatus, 8/93.
V peak ≤ 1.6 kV; rise time ≥ .1 µ sec 9. Melhorn, C.J. “Effects Of PWM ASDs On Standard Squir-
◗ Motors rated over 600 volts: rel-Cage Induction Motors”; proposed Electroteck
V peak ≤ 2.5 pu; rise time ≥ .1 µ sec Concepts, Inc. paper.
where: 1 pu = √ 2 VLL/√ 3 10. Daugherty, R.H. and Wennerstrom, C.H. “Need For In-
dustry Standards For AC Induction Motors Intended For
CONCLUSIONS Use With Adjustable-Frequency Controllers”; IEEE PCIC-
Much of the existing confusion about successful applica- 90-5 (1990) 41-53.
tion of ASDs is due to the fact that the impact of ASDs on 11. Erdman, J., Kerkman, R., Schlegel, D. and Skibinski, G.
motors has been evaluated amid a rapidly changing technol- “Effect Of PWM Inverters On AC Motor Bearing Currents
ogy. For instance, early studies of the effect of drives on And Shaft Voltages”; APEC ’95 Proceedings, Tenth An-
bearing currents were conducted in an environment of low nual Applied Power Electronics Conference and
dv/dt’s and low carrier frequencies. The same can be said of Exhibition, 3/95.
studies that focused on the impact of long cable runs and 12. IEEE Standard 841-1994 For Petroleum And Chemical
noise/vibration levels. Industry Up To And Including 500 Hp.
Another major variable is the wide variety of power tran- 13. Divljakovic, V. and Kline, J. (U.S. Electrical Motors), and
sistors and circuitry employed in generating the motor voltage Barta, D. and Floryan, D. (Phelps Dodge Magnet Wire
waveform. Motor insulation systems also vary widely, as do Company). “Aging Of Magnetic Wire In The Presence
the ways in which they respond to the various waveforms Of Variable Frequency, High Rise Time And High Volt-
that can be applied. age Pulses”; CEIDP 1994 #94CH3456-1.
14. Bonnett, A. H. “Analysis Of The Impact Of Pulse-Width
Hence, future studies of the impact of ASDs and motors Modulated Inverter Voltage Waveforms On AC Induc-
on a system should be done on equipment that uses state- tion Motors”; 1994 IEEE Pulp and Paper Industry
of-the-art technology. Some technical publications on the Technical Conference.
subject do not even make clear which hardware was em-
15. Hansen, L. and Petersen, F. “Experiences With PWM
ployed in the evaluation.
Inverters And Motors”; Danfoss Drives and Controls,
In conclusion, this paper is not intended to discourage the Graasten, Denmark.
use of PWM drives. Instead, the goal is to assure proper ap- 16. Roeber, J. and Gieras, J. “Experimental Investigation Of
plication of the drive and motor to achieve the desired Shaft Voltage Induced In An Inverter-Fed Cage Induc-
performance and life expectations. With proper application, tion Motor”; Dept. of Electrical and Electronic
the rewards and benefits of using ASDs and motors for speed Engineering, University of Cape Town.
control and energy conservation far exceed the risks. As with 17. Leung, Dr. S.W. “The Influence Of Invertors On Bearing
all new technologies, however, knowledge is the key to suc- Currents In Induction Motors”; “Measurements Of Shaft
cess. Because ASD technology is changing rapidly, it is Voltages And Bearing Impedances”; ERA Report No. 82-
important to recognize that the old “rules of thumb” or appli- 82, Project No. 44:01:1251. Leung, Dr. S.W. and Kalsi,
cation standards may no longer apply. R. “A Review Of The Influence Of Invertors On Bearing
Currents In Induction Motors”; ERA Report No. 82-59,
BIBLIOGRAPHY & REFERENCES Project No. 44:02:1251 ERA Technology, Surrey, En-
gland.
1. IEEE STD. 117-1974/ANSI C50.32-1976. “IEEE Stan- 18. S.K.F. Bearing Catalog No. 725-624; February 19, 1987.
dard Test Procedure For Evaluation Of Systems Of
19. Lawson, J.A. “Motor Bearing Fluting”; 1993 Pulp and
Insulating Materials For Random-Wound AC Electric
Paper Industry Technical Conference.
Machinery.”
20. H. Boyanton. “Electrically Induced Bearing Damage: The
2. Bonnett, A.H. and Soukup, G.C. “Cause And Analysis
Need For Shaft Grounding”; Shaft Grounding Systems,
Of Stator And Rotor Failures In Three-Phase Squirrel-
Inc., Nashville CSI Conference, October 10, 1994.
Cage Induction Motors”; 0093-994 1992 IEEE.
21. Bonnett, A.H., “Cause And Analysis Of Anti-Friction Bear-
3. NEMA Magnet Wire Standard, MW1000-3.7.1.1.3.
ing Failures In AC Induction Motors”; 1993 Pulp and
4. Yin, W., Bultemeier, K., Barta, D. and Floryan, D. “Di- Paper Industry Technical Conference.
electric Integrity Of Magnet Wire Insulations Under
Multi-Stresses”; Phelps Dodge Magnet Wire Co.
5. Emerson Technology Center Voltage Endurance Test-
ing At High PWM Switching Frequencies And Noise
Testing.

(Update - 7/99)
Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “Future Tech Notes.” TN29-7
Application Considerations of PWM Inverters Tech Note No. 29

Place this Tech Note in Section 3 of your EASA


Technical Manual for future reference. Note its loca-
tion in Section 15, “Future Tech Notes.”

L APPA
ICA R
TR
Electrical Apparatus Service Association, Inc.
AT
C
ELE

US

EA SA 1331 Baur Boulevard • St. Louis, MO 63132 U.S.A. • (314) 993-2220 • Fax (314) 993-1269 • www.easa.com
SER

N
IO

IC
V

T
E A
SSOC
IA Reliable Solutions Today! Copyright © 1999
(Update - 7/99)
TN29-8 Place in Section 3 of your EASA Technical Manual; note its location in Section 15, “FutureVersion
Tech799DP5M-799
Notes.”

Vous aimerez peut-être aussi