Académique Documents
Professionnel Documents
Culture Documents
TECHNICAL SUBMITTAL
PROJECT:
Hariq Training Center Infrastructure
CONTARCTOR:
Anab Group of Contracting company
INDEX
2. GOVERNMENT CERCERTIFICATES. 2
4. PROJECT SPECIFICATIONS 4
5. COMPLIANCE STATEMENT 5
6. TECHNICAL SCHEDULE 6
8. PREVIOUS APPROVALS 8
JOINT GULF BUSINESS CORPORATION
Over the last few years, JGB has been continually evolving to position itself as a
leading supplier of various engineered products in the region.
In the changing landscape, it is anticipated that customer demands will change
rapidly and expectations will also increase exponentially. Our customers are
faced with a multitude of challenges – ensure speedy project execution, deliver
These are indeed exciting times for the company, cost efficiency, actively manage environmental and sustainability concerns, safety
given its rapid progression from providing engineering and risk management, increasing regulatory compliance needs. JGB is innovating
and innova tive solu tions and to solving complex
specific to engineering, to ensure greater engineering predictability, thereby being
in a position to provide substantial reductions in project cost & time.
customer challenges. Technology tools combined with
core engineering exper tise poses a large window of The foundation and the driving force of our growth are our people. From vision
oppor tunity to set in motion disruptive innovations. to excellence, it has been the contribution of individuals and the teamwork that
has made this fast paced growth possible. Be it the international market or be it
challenges or strategies,I am proud to say that in JGB every individual contributes.
We have grown together over many years and the team spirit will ensure that
we will continue to grow.
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
JGB an ISO cer tif ied international company specialized in providing
engineering solutions and services with special focus on oil and gas - petrochemical
- hvac - industrial insulation - electrical - instrumentation - special equipments -
aviation - drilling - marine - offshore. Our key focus is to satisfy customers need
through on time delivery of best quality products from internationally reputed
manufactures at cost effective prices . Head Quar tered in Kingdom Of Bahrain
and branch offices at KSA, Qatar, UAE, Oman, Kuwait , India, Iraq , Korea, USA
and Canada.
WHO WE ARE JGB are better positioned in the Industry as a solution provider and also as an
integrated supply chain management par tner to many end users and contractors
in the market we offer.
JGB and its principles are approved by major entities in the respective countries
• technical assistance and exper tise
• documentation exper tise
• simplified and on time delivery
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
To be internationaly renowned customer focused company offering
VISION comprehensive solutions and quality products
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
OIL & GAS
AVIATION
HVAC -
ELECT-MECH
INDUSTRIAL
WATER & OTHER
PRINCIPLES
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
MAJOR APPROVALS
CENTR AL STORE
DIRECTORY
UAE
KUWAIT
USA
OMAN
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
PRODUCT PORTFOLIO
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
PRODUCT PORTFOLIO
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
JGB
AFFILIATES
JGB MARINE
SPECIAL
EQUIPMENTS
AVIATION DRILLING
DIVISIONS
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
JGB
CLIENTS
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
HOUSTON (USA)
IRAQ
CANADA
JGB
GLOB A L
COV ER AGE
DAMMAM
(SAUDI ARABIA)
RIYADH
(SAUDI ARABIA)
JEDDAH (SAUDI A
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
KUWAIT
BAHRAIN
QATAR
SOUTH KOREA
DUBAI (UAE)
JGB
GLOB A L
COV ER AGE
MUMBAI (INDIA)
OMAN
ARABIA)
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
GLOBAL FOOTPRINT
OIL AND GAS - PETROCHEMICAL - HVAC - INDUSTR IAL INSULATION - ELECTR ICAL - INSTRUMENTATION - SPECIAL EQUIPMENTS - AVIATION - DR ILLING - MAR INE - OFFSHOR E
اﻟﻤﺆﺳﺴﺔ اﻟﺨﻠﻴﺠﻴﺔ اﻟﻤﺸﺘﺮﻛﺔ ﻟﻠﺘﺠﺎرة
Joint Gulf Business (JGB) Corp.
REGISTERED
MANAGEMENT
SYSTEMS
BS EN ISO
9001:2008
sales@jgbksa.com QUAY AUDIT UK LTD
About Us
Joint Gulf Business (JGB) Corp is an ISO Certified Company, specialized in the supply of Engineered
Industrial Products in HVAC, Electro-Mechanical, Oil & Gas, Insulation, Water and other Industrial segments.
Through the Head Office in the Kingdom of Bahrain and branch offices in Saudi Arabia, UAE, Qatar, Oman,
Kuwait, India, USA and Canada, we provide Engineered Industrial solutions from Internationally reputed
manufacturers to the MENA region.
The prime business objective is to provide customers with superior quality products coupled with
excellent Customer service & Technical support, adding value to their business. Our product line includes
Air Handling Units, Fan Coil Units, Air Curtains, Air Ionization Solutions, Kitchen Ecology units, Chemical
Filtration Systems, Odor Control Systems, Humidifiers, Duct Heaters, VAV / CAV, Air outlets, Industrial &
Commercial Ventilation Fans, Jet Fans, Explosion proof HVAC equipment, VCD / Fire & Smoke Dampers, Air
Venturi Valves, Heat Exchangers, Air Separator / Expansion Tanks, Fume Extraction Systems, Smoke Vents /
Skylights, Frequency Converters / UPS, Blast Protection Valves / Dampers, Flexible Ducts, Boilers, Cooling
Towers, Solar Power Solutions, Electrical & Instrumentation, Inertial Filters / Bleed fans, HVAC & Industrial
Valves, Pipe Supports, Seismic Vibration Isolators, Industrial Insulation & Accessories, Aluminum Jacketing,
Water treatment, Analyser shelter, Industrial descalers, etc.
The company has the expertise and ability to supply products for major projects. The engineering and
support staff brings you a broad base of scientific and technical knowledge to draw on with years of
practical experience in the related products.
We are committed to quality products, excellent technical support, fast deliveries and reliable after
sales service.
Corporate
Vision Values
To be internationally Mission Customer satisfaction &
renowned customer loyalty Employee dignity
focused company Serve customers by
procuring and supplying Organizational &
offering comprehensive
quality products individual growth
solutions and quality
products. manufactured by Technical excellence
internationally reputed with professional ethics
manufacturers. Responsibility to society
Industries
MEP / HVAC Construction
Product Range
Oil & Gas
MEP / HVAC Equipment & Accessories
Petrochemical
Oil & Gas Field Products
Chemical
Electrical Products
Pharmaceutical
Power
Instrumentation Products
Water
Water & Industrial Equipment
Food & Beverage
Industrial Insulation & Accessories
Product Range
Product List
KITCHEN ECOLOGY UNIT
Product List
Variable Air Volume (VAV) &
ANEMOSTAT (USA) Air Constant Air Volume (CAV) UNITS
Distribution Products provide
complete range of VAV / CAV, AIR OUTLETS
Diffusers, Registers, Security SECURITY GRILLES
Grilles, Critical Environmental
Products for Operation CRITICAL ENVIRONMENTAL
rooms etc. For those special PRODUCTS (OPERATION ROOMS)
needs, we also provide
products customized to fit all
needs. Products are available
in Steel, Aluminum, Extruded
Aluminum and Stainless
Steel.
Product List
HEATREX (USA) Manufacturer of HVAC Electric Duct
Electric Heat Products Specialists Heaters
in the science and manufacture
of electric heat products, Heatrex Process Duct Heaters
serves an array of national and
international customers. A team
approach and commitment to Total
Quality, combined with encouraged
customer interaction, fosters a
unique and effective environment
for concept development,
prototype design and testing,
and manufacture of top-quality
products.
Product Range • Saudi Aramco Vendor ID: 10039138 • SABIC Vendor ID: 505792 • SEC Vendor ID:2005854
Product List
• Wall Mount Air Conditioners
• Window Units (Through-the-Wall
Custom Controls Company (USA) Air Conditioners)
has been providing Hazardous • Building Pressurization Units
Location and Explosion Proof HVAC • Hazardous Duty and Explosion
equipment for industry since the Proof Exhaust Fans
1960’s having production facility in
Houston, TX. • Purge Blowers
• Packaged Air Conditioners - for
CCC offers a full complement of
Pad or Roof Mounting
customized and Third Party Listed
HVAC solutions for both the U.S. • Explosion Proof Heaters
National Electric Code (NEC) market • Refrigeration Units
and International (IEC standards) • Dehumidifiers
market. Our NEC Division One,
Division Two and IEC Zone 2 HVAC • Split Systems
(ATEX) product lines include: • Explosion Proof Fans
Product List
FuCare is the safety company Blast Valves
specializing in developing safety
Blast Dampers
product solutions with focus on
blast protection systems. With Air tight dampers
its tremendous investment in
technological revolutions through latest
research technologies and continuous
innovations, FuCare has featured its
products offering ranges with high
safety performance, high functional
performance and competitive pricing.
FUCARE’s products have been serving
the global customers including
ExxonMobil, BP, Qatar Petroleum, KOC,
BASF, Petronas, etc.
Product List
Fire & Blast Rated Doors
Fire & Blast Rated Walls
Product List
Cooling Tower
Product List
Thermostatic Mixing Valves
Lawler Manufacturing Company, Inc., Emergency Valves
(USA) established in 1988, manufactures
Shower Valves
one of the deepest and most time-
tested thermostatic mixing valve lines
in North America. The company’s
sole focus is the safe and comfortable
blending of hot and cold water to meet
the needs of the industrial plumbing
industry and its customers.
Valves are available in a variety
of finishes, piping configurations
and cabinet designs to meet your
requirements.
Product List
• Steam Boilers
• Commercial Heating Products
• Thermal Fluid Products
• Ancillary Equipments
• Engineered System
Product List
High-Solids Filtration
Ultra Filtration
Reverse Osmosis & Nanofiltration
Ion Exchange Resins
DOW /FILMTEC™ Water Filtration Membranes
Brackish Water RO Elements provide consistently Electrodeionization
high performance and enhanced element life
when treating difficult industrial water, enabling
lower energy usage and reduced costs.
Compared to other filtration technologies that
rely on a screen or filter to remove particles,
Reverse Osmosis (RO) and Nano filtration (NF)
are pressure-driven separation processes that
employs a semi-permeable membrane and the
principles of cross-flow filtration.
Product List
• Double Block & Bleed
• Double Isolation &
Western Valve, Inc.(USA) takes Bleed Valve
great pride in its ability to • Pipeline Manifolds &
produce the industries highest Terminals
quality valve. We continue
to upgrade and improve our • Commercial Aviation
& Military Fueling
facilities with state of the art
manufacturing equipment. • Propane, Butane, and
This allows us to continue LPG Valves
providing our customers
with the best valves on the
market, while still providing
competitive prices and delivery
times.
Product Range • Saudi Aramco Vendor ID: 10039138 • SABIC Vendor ID: 505792 • SEC Vendor ID:2005854
Product List
Manifold systems
Quick Exhaust Valves
Bifold(UK) are leaders in the design Check Valves & Needle Valves
and manufacture of hydraulic
Solenoid Valves
and pneumatic stainless steel
directional control valves and Chemical Injection Pumps
accessories for hazardous, corrosive
and subsea environments. and accessories for the upstream
Enhanced by a lean and integrated and downstream oil and gas
manufacturing policy, alongside industries, specifically designed
a unique business model, Bifold and developed with the customer
Group has provided peace of in mind, have gained worldwide
mind to contractors, installers approval and credibility for the
and end users for over a century. onerous conditions as found in
Their innovative range of high- hazardous (classified) locations,
tech valve and pump products hostile and subsea environments.
Product List
Concentric Butterfly Valves
ABO valves (Czech Republic) is currently one
High Perf. Butterfly Valves
of the largest European manufactureres of
shut-off and control valves for industrial Check Valves
applications. We produce butterfly valves for Knife Gate Valves
general and industrial applications including Ball Valves
double and triple offset, knife gate and safety
valves for the most demanding conditions. Ball Check Valves
Product List
Pipe Support Hardware
Starline Enterprises is one of the renowned Vibration Control Products
Manufacturers, Exporters and Suppliers
offering a wide range of Split Clamps and
Vibration Control Products. The quality
products offered by us comprises Mild
Steel U Bolt, Riser Clamp, Sprinkler Clamp,
U Strap Clamp, Adjustable Clevis Hanger,
Rubber Support Insert , Anti Vibration Spring
Hangers, Anti Vibration Spring Mounts, Anti
Vibration Rubber Pads, etc. Besides, all the
products are tested for their compliance with
the international standards that ultimately
bring in repeated orders for the company.
AZUD (SPAIN) group is among the world leaders
in filtration, giving solutions to optimization of the
quality of water in industrial, agricultural and urban
applications. Sistema Azud is an international brand
with strategy based on culture of water and present in
more than 70 countries of the five continents.
Areas of Expertise:
• Irrigation & Landscape : Micro-sprinklers, irrigation
filters, heap leach mining systems
• Industrial Filtration : Automatic screen filters, disc
filters, cooling tower filters, recirculation water filters
• Water Treatement : UV water treatement, waste
water treatment
Applications
Refinery descaling application
such as Heat Exchangers, All type
crackers, Converters, Air & Gas
Compressors, Pumps, Piping
SUMMIT (USA) is a recognized industry
Paper mill descaling applications
leader in chemical descaling and
such as Liquid-Ring Vacuum Pumps
synthetic lubricant technology, serving
& Filters, Calendar Rolls, Mill Rolls,
commercial customers around the
Liquor Tanks, Pulverizers
world for more than 25 years. This is a
water-based solvent enhanced with
wetting agents, corrosion inhibitors and
degreasing compounds. It is designed
Product List
to penetrate and remove encrusted DESCALERS
lime scale, rust, dirt and corrosion by- DEGREASERS
products from water-wetted internal
surfaces of commercial and industrial
processing equipment.
Product List
Calcium Silicate
Perlite Insulation
Phenolic Insulation
Polyurethane Insulation
Rockwool Insulation
Ceramic Fiber
Cellular Glass
Rubber Insulation
Insulation Adhesive
Sealants
Aluminum Jacketing with Polysurlyn /
Polykraft moisture barrier
Stainless Steel Jacketing
Aluminum and SS corrugated Jacketing
Stainless Steel insulation accessories
CORPORATE OFFICE SUBSIDIARY OFFICES
JGB International Co. W.L.L. JGB International L.L.C.
PO Box 75903, Dream Bldg 3 PO Box 124804, Ras Al Khor
Manama, Kingdom of Bahrain Dubai, United Arab Emirates
T: +973 171 80681/82 | F: +973 179 10805 T: +971 4 284 3616 | F: +971 4 284 3617
E: bah@jgbinternational.com E: sales@jgbuae.com | www.jgbuae.com
www.jgbinternational.com
Joint Gulf Business Co. (JGB Co.)
PO Box 13200, Salwa Road
JGB SAUDI ARABIA
Doha, Qatar
Joint Gulf Business Corp (JGB Corp.) T: +974 4275193 | F: +974 4275195
PO Box 1602, King Fahad Road E: sales@jgbqatar.com | www.jgbqatar.com
Dammam 31441, Kingdom of Saudi Arabia
T: +966 13 843 7711 | F: +966 13 841 8181 Joint Gulf Business Co. L.L.C (JGB)
E: sales@jgbksa.com | www.jgbksa.com PO Box 140, Postal Code 131
Muscat, Sultanate of Oman
Joint Gulf Business Corp (JGB Corp.) T: +968 2 461 9661 / 2 449 8521
Malaz Sitheen Street F: +968 2 461 9662
Riyadh, Kingdom of Saudi Arabia E: sales@jgboman.com | www.jgboman.com
T: +966 11 476 5157 | F: +966 11 476 2931
E: sales@jgbksa.com | www.jgbksa.com JGP Trading & Contracting Co.
PO Box 757, Dasman 15458, Kuwait
Joint Gulf Business Corp (JGB Corp.) T: +965 23927982 | F: +965 23927985
Kanoo Building # 1, Madinah Road Email: sales@jgbkuwait.com | www.jgbkuwait.com
Jeddah, Kingdom of Saudi Arabia
T: +966 12 263 2889 | F: +966 12 263 2838 JGB International
E: sales@jgbksa.com | www.jgbksa.com BKC Bandara, Mumbai, India
T: +91 22 6162 3472
E: operations@jgbinternational.com
www.jgbinternational.com
CANADA QATAR
JGB International (Canada) inc.
2859 Galleon Crescent Joint Gulf Business Co.
Mississauga. Ontario. L5M 5V1, Canada. PO Box 13200, Salwa Road
Doha, Qatar
DUBAI (UAE)
JGB International L.L.C.
PO Box 124804, Ras Al Khor
Dubai, United Arab Emirates
DAMMAM
(SAUDI ARABIA) MUMBAI (INDIA)
Joint Gulf Business Corp (JGB Corp.) JGB International
PO Box 1602, King Fahad Road BKC Bandara, Mumbai, India
Dammam 31441, Kingdom of Saudi Arabia
RIYADH
(SAUDI ARABIA)
Joint Gulf Business Corp (JGB Corp.)
Malaz Sitheen Street
Riyadh, Kingdom of Saudi Arabia
OMAN
Joint Gulf Business Co. L.L.C.
PO Box 140, Postal Code 131
JEDDAH (SAUDI ARABIA) Muscat, Sultanate of Oman
Joint Gulf Business Corp (JGB Corp.)
Kanoo Building # 1, Madinah Road
Jeddah, Kingdom of Saudi Arabia
GOVERNMENT CERTIFICATES
١٤٤٠/٠٢/٢٢ ﺍﻟﺘﺎﺭﻳﺦ
٢٠١٨/١٠/٣١ ﺍﻟﻤﻮﺍﻓﻖ
ﺭﻣﺰ ﺍﻟﺸﻬﺎﺩﺓ ٢٧٢٩٠٥٨٧
ﺷﻬﺎﺩﺓ
ﻛﺘﺎﺑﺔ ﺭﻗﻤﺎ
ﺳﺘﺔ ﻣﺸﺘﺮﻛﻴﻦ ٦ ﻋﺪﺩ ﺍﻟﻤﺸﺘﺮﻛﻴﻦ ﺍﻟﺴﻌﻮﺩﻳﻴﻦ
ﺃﺭﺑﻌﻪ ﻭ ﻋﺸﺮﻭﻥ ﻣﺸﺘﺮﻛﺎ ٢٤ ﻋﺪﺩ ﺍﻟﻤﺸﺘﺮﻛﻴﻦ ﻏﻴﺮ ﺍﻟﺴﻌﻮﺩﻳﻴﻦ
ﺛﻼﺛﻮﻥ ﻣﺸﺘﺮﻛﺎ ٣٠ ﺍﻟﻤﺠﻤﻮﻉ
ﺗﺸﻬﺪ ﺍﻟﻤﺆﺳﺴﺔ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺘﺄﻣﻴﻨﺎﺕ ﺍﻹﺟﺘﻤﺎﻋﻴﺔ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺄﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺃﻋﻼﻩ ﻗﺪ ﺃﻭﻓﺖ ﺑﺈﻟﺘﺰﺍﻣﺎﺗﻬﺎ ﺗﺠﺎﻩ ﺍﻟﻤﺆﺳﺴﺔ
ﻭﻓﻖ ﺍﻟﺒﻴﺎﻧﺎﺕ ﺍﻟﻤﻘﺪﻣﺔ ﻣﻨﻬﺎ ﺣﺘﻰ ﺗﺎﺭﻳﺦ ﺇﺻﺪﺍﺭ ﻫﺬﻩ ﺍﻟﺸﻬﺎﺩﺓ ،ﻭﺍﻟﺘﻲ ﺗﻢ ﻣﻨﺤﻬﺎ ﻟﺘﻘﺪﻳﻤﻬﺎ ﻷﻳﺔ ﺟﻬﺔ ﺗﻄﻠﺒﻬﺎ ،ﻭﻫﻲ
ﺻﺎﻟﺤﺔ ﻟﺠﻤﻴﻊ ﺍﻷﻏﺮﺍﺽ ﺍﻟﺘﻲ ﻧﺺ ﻋﻠﻴﻬﺎ ﻧﻈﺎﻡ ﺍﻟﺘﺄﻣﻴﻨﺎﺕ ﺍﻹﺟﺘﻤﺎﻋﻴﺔ ﻓﻲ ﺍﻟﻤﺎﺩﺓ ) (٦/١٩ﻣﻨﻪ.
ﻫﺬﻩ ﺍﻟﺸﻬﺎﺩﺓ ﺳﺎﺭﻳﺔ ﺍﻟﻤﻔﻌﻮﻝ ﺣﺘﻰ ١٤٤٠/٠٣/٢٢ﻫـ.
ﻋﻦ ﻃﺮﻳﻖ ﺍﺳﺘﺨﺪﺍﻡ ﺃﻭ ﻳﻠﺰﻡ ﺍﻟﺘﺤﻘﻖ ﻣﻦ ﺻﺤﺔ ﻭﺻﻼﺣﻴﺔ ﺍﻟﺸﻬﺎﺩﺓ ﻋﺒﺮ ﺯﻳﺎﺭﺓ ﺍﻟﺮﺍﺑﻂ
ﺍﻟﺮﻣﺰ ﺍﻟﻤﻌﺮﻑ ﺍﻟﺘﺎﻟﻲ : ﺃﺩﻧﺎﻩ ﻓﻲ ﺍﻟﻤﻮﻗﻊ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ ﻟﻠﻤﺆﺳﺴﺔ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺘﺄﻣﻴﻨﺎﺕ ﺍﻹﺟﺘﻤﺎﻋﻴﺔ
www.gosi.gov.sa/vc
ﺗﻌﺪ ﻫﺬﻩ ﺍﻟﺸﻬﺎﺩﺓ ﻣﻦ ﺍﻟﻮﺛﺎﺋﻖ ﺍﻻﻟﻜﺘﺮﻭﻧﻴﺔ ﺍﻟﺤﻜﻮﻣﻴﺔ ﺍﻟﺮﺳﻤﻴﺔ ،ﻭﻳﺤﻈﺮ ﻗﻄﻌﻴﺎ ﺗﻘﻠﻴﺪﻫﺎ ﺃﻭ ﺇﺩﺧﺎﻝ ﺃﻱ ﺗﻌﺪﻳﻼﺕ ﻋﻠﻴﻬﺎ ﺳﻮﺍﺀ ﺑﺎﻹﺿﺎﻓﺔ ﺃﻭ ﺍﻟﺤﺬﻑ
ﺃﻭ ﺍﻟﺘﻐﻴﻴﺮ ﻓﻲ ﺑﻴﺎﻧﺎﺗﻬﺎ ﺃﻭ ﻏﻴﺮ ﺫﻟﻚ ﻣﻦ ﺍﻧﻮﺍﻉ ﺍﻟﺘﻌﺪﻳﻞ ،ﻭﺗﻌﺪ ﺍﻟﺸﻬﺎﺩﺓ ﻻﻏﻴﺔ ﺇﺫﺍ ﺷﺎﺑﻬﺎ ﺷﻲﺀ ﻣﻦ ﺫﻟﻚ ،ﻛﻤﺎ ﺗﻌﺮﺽ ﺻﺎﺣﺒﻬﺎ ﻟﻠﻤﻼﺣﻘﺔ ﺍﻟﻨﻈﺎﻣﻴﺔ
ﺃﻣﺎﻡ ﺍﻟﺠﻬﺎﺕ ﺍﻟﻤﺨﺘﺼﺔ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﻣﺎﻳﻔﺮﺿﻪ ﻧﻈﺎﻡ ﺍﻟﺘﺄﻣﻴﻨﺎﺕ ﺍﻻﺟﺘﻤﺎﻋﻴﺔ ﻣﻦ ﻋﻘﻮﺑﺎﺕ ،ﻭﻻﻳﺠﻮﺯ ﺗﺪﺍﻭﻝ ﺍﻟﺸﻬﺎﺩﺓ ﺇﻻ ﻓﻲ ﺍﻷﻏﺮﺍﺽ ﺍﻟﺘﻲ
ﺃﺻﺪﺭﺕ ﻷﺟﻠﻬﺎ ﻭﻓﻘﺎ ﻷﺣﻜﺎﻡ ﻧﻈﺎﻡ ﺍﻟﺘﺄﻣﻴﻨﺎﺕ ﺍﻻﺟﺘﻤﺎﻋﻴﺔ ،ﻭﺍﻟﻤﺆﺳﺴﺔ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺘﺄﻣﻴﻨﺎﺕ ﺍﻻﺟﺘﻤﺎﻋﻴﺔ ﻏﻴﺮ ﻣﺴﺆﻭﻟﻪ ﻋﻦ ﺃﻱ ﺁﺛﺎﺭ ﺃﺧﺮﻯ ﻣﺘﺮﺗﺒﺔ
ﻗﺒﻞ ﺍﻟﻐﻴﺮ ﻋﻦ ﺍﻟﺸﻬﺎﺩﺓ ﻭﻏﻴﺮ ﻣﺴﺆﻭﻟﺔ ﻋﻦ ﺃﻱ ﻋﻤﻠﻴﺔ ﺗﺰﻭﻳﺮ ﺃﻭ ﺗﻌﺪﻳﻞ ﺗﺘﻢ ﻋﻠﻰ ﺍﻟﺒﻴﺎﻧﺎﺕ ﺍﻟﻮﺍﺭﺩﺓ ﻓﻴﻬﺎ .
ﺗﺎﺭﻳﺦ ﺍﻹﺻﺪﺍﺭ ١٤٤٠/٠٢/٢٣ :
ﺍﺳﻢ ﺍﻟﻤﻨﺸﺄﺓ :ﺍﻟﻤﺆﺳﺴﺔ ﺍﻟﺨﻠﻴﺠﻴﺔ ﺍﻟﻤﺸﺘﺮﻛﺔ ﻟﻠﺘﺠﺎﺭﺓ ﻟﺼﺎﺣﺒﻬﺎ ﺍﺳﺎﻣﺔ ﺣﻤﻴﺪ ﻣﻨﺼﻮﺭ
ﺗﺸﻬﺪ ﻭﺯﺍﺭﺓ ﺍﻟﻌﻤﻞ ﻭﺍﻟﺘﻨﻤﯿﺔ ﺍﻻﺟﺘﻤﺎﻋﯿﺔ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺄﺓ ﺍﻟﻤﺬﮐﻮﺭﺓ ﺃﻋﻼﻩ ﺣﻘﻘﺖ ﻧﺴﺐ ﺍﻟﺘﻮﻃﯿﻦ ﺍﻟﻤﻄﻠﻮﺑﺔ ﻣﻨﻬﺎ..
ﻭﺗﻢ ﻣﻨﺤﻬﺎ ﻫﺬﻩ ﺍﻟﺸﻬﺎﺩﺓ ﺣﺴﺐ ﻃﻠﺒﻬﺎ
ﺗﻨﺒﻴﻬﺎﺕ:
- ٢ﻓﻲ ﺣﺎﻝ ﺍﻛﺘﺸﺎﻑ ﺃﻱ ﻋﻤﻠﻴﺔ ﺗﺰﻭﻳﺮ ﻓﻲ ﺍﻟﺸﻬﺎﺩﺓ ﺍﻟﻤﻘﺪﻣﺔ ﻧﺮﺟﻮ ﺍﻟﺘﺒﻠﻴﻎ ﻋﻦ ﺫﻟﻚ ﺑﺨﻄﺎﺏ ﺭﺳﻤﻲ ﻷﻗﺮﺏ ﻣﻜﺘﺐ ﻋﻤﻞ.
1040443480
رﻗﻢ اﻟﺸﻬﺎدة ١٠٤٠٤٤٣٤٨٠ :
١٤٤٠/٠٢/٣٠ :ﻫـ اﻟﺘﺎرﻳﺦ
اﻟﺮﻗﻢ اﳌﻤﻴﺰ ٣٠٠٤١٦٧٤٦٥ : ﻓﺮع اﻟﺪﻣﺎم
ﺗﺸﻬﺪ اﻟﻬﻴﺌﺔ اﻟﻌﺎﻣﺔ ﻟﻠﺰﻛﺎة واﻟﺪﺧﻞ ﺑﺄن اﳌﻜﻠﻒ /اﳌﺆﺳﺴﺔ اﻟﺨﻠﻴﺠﻴﺔ اﳌﺸﱰﻛﺔ ﻟﻠﺘﺠﺎرة
ﺳﺠﻞ ﻣﺪﻲﻧ رﻗﻢ ٧٠٠١٨٠٢١٠٢وﺳﺠﻞ ﺗﺠﺎري رﻗﻢ ٢٠٥٠٠٦١٠١٧
ﻗﺪم إﻗﺮاره ﻋﻦ اﻟﻔﱰة اﳌﻨﺘﻬﻴﻪ ﰲ ٢٠١٧/١٢/٣١م
وﻗﺪ ﻣﻨﺢ ﻫﺬه اﻟﺸﻬﺎده ﻟﺘﻤﻜﻴﻨﻪ ﻣﻦ إﻧﻬﺎء ﺟﻤﻴﻊ ﻣﻌﺎﻣﻼﺗﻪ ﻤﺑﺎ ﰲ ذﻟﻚ ﴏف ﻣﺴﺘﺤﻘﺎﺗﻪ اﻟﻨﻬﺎﺋﻴﺔ ﻋﻦ اﻟﻌﻘﻮد.
ﻳﴪي ﻣﻔﻌﻮل ﻫﺬه اﻟﺸﻬﺎدة ﺣﺘﻰ ﺗﺎرﻳﺦ ١٤٤٠/٠٨/٢٥ﻩ اﳌﻮاﻓﻖ ٢٠١٩/٠٤/٣٠م.
)اﻟﺨﺎﻣﺲ و اﻟﻌﴩون ﻣﻦ ﺷﻌﺒﺎن أﻟﻒ و أرﺑﻌﺎﻤﺋﺔ و أرﺑﻌﻮن ﻫﺠﺮي(
اﻟﺨﺘﻢ اﻟﺮﺳﻤﻲ
SCOPE OF ACTIVITIES
4669 & 4674 Trading & Supply of HVAC, Electro-Mechanical,
Insulation Materials and Oil & Gas Products (Pipe and Fittings)
!*1&$2&&,$*34"(&4$*,4$*55'+1&4$2/$
Quay Audit UK Ltd$(+$(!&$0+66+7",.$-*,*.&-&,($#(*,4*'48
BS EN ISO 9001:2015
!&$*55'+1&4$-*,*.&-&,($#/#(&-#$*556/$(+$(!&$0+66+7",.$#%+5&8
!"#$%&'(")%*(&$"#$'&#('"%(&4$(+$(!+#&$#%+5&#$+0$23#",&##$*%("1"(/$4&#%'"2&4$
",$(!&$",(&',*("+,*66/$'&%+.,"#&4$P:<?$<+4&#$6"#(&4$2&6+78
!"#$"#$*,$*%%'&4"(&4$%&'(")%*(&$*3(!+'"#&4$0+'$"##3&$2/$:%%'&4"(*("+,$;&'1"%&$0+'$<&'("0/",.$=+4"&#$>?3'+5&@$A"-"(&4$7!+$!*1&$*##&##&4$B3*/$:34"($CD$A"-"(&4$
*.*",#($4&),&4$%'"(&'"*$*,4$",$%+.,"#*,%&$+0$E;9$FGHIF8IHFF$J<+,0+'-"(/$:##&##-&,($K$L&M3"'&-&,(#$0+'$2+4"&#$5'+1"4",.$*34"($*,4$%&'(")%*("+,$+0$-*,*.&-&,($
#/#(&-#NO$ !"#$%&'(")%*(&$"#$+,6/$1*6"4$7!&,$%+,)'-&4$2/$(!&$'&."#(&'$6"#(&4$",$(!&$E,(&',*("+,*6$L&."#(&'$+0$B3*6"(/$:##&##&4$9'.*,"#*("+,#8$www.irqao.com
Grove House 8 St. Julian’s Friars Shrewsbury Shropshire SY1 1XL | (44)1743 351677 | post@quayaudit.co.uk | www.quayaudit.co.uk
JOINT GULF BUSINESS CORPORATION
37 PRINCESS NOURA UNIVERSITY RIYADH ZAMIL COOLCARE INSULATION WORK JGB CORP & RPR USA
38 RABIGH RABIGH HANBO INSULATION MATERIALS INSUWRAPID,ITW,
39 KING ABDUL AZIZ UNIVERSITY JEDDAH AL MASHARIQ EXHAUST FANS PENNBARRY USA
41 DAMMAM UNIVERSITY DAMMAM AL HASHIM AC EXHAUST FANS & VAV PENNBARRY USA, METALAIRE
JUBAIL EXPORT REFINERY
42 JUBAIL BASEELAH MECHANICAL EXHAUST FAN,VAV PENNBARRY USA, METALAIRE
PROJECT
STATE INSULATION, RH
43 QURAYAH IPP QURAYAH ARABIAN BEMCO INSULATION MATERIALS
PROFILE
44 JEBAL AL OMAR MAKKAH NESMA & PARTNERS EXPANSION JOINT METALIC FLEX GERMANY
45 SABIC YANBU SABIC VALVE BIFOLD UK
46 PARK HAYYAT HOTEL JEDDAH PARK HAYYAT HOTEL FULTON BOILER FULTON ( USA)
47 RADISSON BLU HOTEL YANBU RADISSON BLU HOTEL FULTON BOILER FULTON ( USA)
48 YANBU REFINERY YANBU ABV ROCK BLAST VALVE TEMET ( FINLAND)
49 JERP-5A JUBAIL SAUDI ARCHIRODON AIR PURIFICATION SYSTEM PUREAIR(USA)
50 NYLON JUBAIL NESMA & PARTNERS DUCT HEATER TUTCO (USA)
51 KFU AL HASSA FEMCO CONT STRAINER TITAN ( USA)
52 SAP-TASNEE JUBAIL KAMCO SAUDI INERTIAL FILTER FILTRO TECHNICA (ITALY)
53 JERP JUBAIL CCE CONT VALVE FEVISA(SPAIN)& TYNE(UK)
54 SAFANIYAH JUBAIL MTTS HUMIDIFIER&VAV CARNES (USA)
JGB MAJOR PROJECTS HANDLED IN SAUDI ARABIA.
94 ATHLETIC SPORTS CITY JEDDAH EL SEIF CONTRACTING ODOUR CONTROL SYSTEM IPEC
95 KING ABDULLA SPORTS CITY JEDDAH EL SEIF CONTRACTING AIR CURTAINS POWERDAIRE USA
96 SADARA CHEMICALS III JUBAIL AL ALWAN CONTRACTING BLAST DAMPER TEMET ( FINLAND)
97 KAAU JEDDAH JEDDAH AL MABANI CONTRACTING INERTIAL FILTER & BF FILTROTECHNICA ( ITALY)
INSTITUTE OF DIPLOMATIC
98 RIYADH AL MABANI CONTRACTING BOILERS FULTON (USA)
STUDIES
99 ROYAL COMMISSION JUBAIL SAUDI AIRTEMP VARIABLE AIR VOLUME METALAIRE (USA)
100 RAZ AL KHAIR POWER PLANT JUBAIL ZAMIL COOL CARE EXHAUST FANS PENNBARRY (USA)
JGB MAJOR PROJECTS HANDLED IN SAUDI ARABIA.
PROJECT SPECIFICATIONS
SECTION 15860
PART 1 - GENERAL
A. The Work shall consist of furnishing and installation of ventilation and exhaust
system as shown on the drawings and specified herein.
1.2 REFERENCES
1.3 SUBMITTALS
A. Product Data: Submit manufacturer's technical data for air distribution equipment,
including capacity ratings, fan performance curves with operating point clearly
indicated, gages and finishes of materials, dimensions, weights, furnished
accessories, and installation and instructions.
E. Spare Parts List: Submit the manufacturer's spare parts list for ventilation equipment
for a period of 2 years for the Engineer's review and approval.
A. Motors and electrical accessories shall comply with the applicable NEMA Standards.
PART 2 - PRODUCTS
2.1 GENERAL:
A. The design, manufacture and installation of the ventilating fans shall meet the
requirements of AMCA 300, ASHRAE 51/210 or EUROVENT and shall be listed
and labeled by UL. Fans shall be licensed to bear AMCA Seal for sound and air
performance. Fans shall be provided with speed controller (where required) to
perform the duty as mentioned on schedules. The fans shall be selected such that
the sound levels within the area will not exceed the specified levels. Each fan shall
be equipped with disconnect switch, backdraft damper (except for kitchen exhaust
fans) and bird screen. Fans shall be of sizes, types and capacities as shown on the
drawings.
1. Spun aluminum exhaust fans shall be belt drive/direct drive type as shown on
drawings. The fan wheel shall be centrifugal backward inclined, constructed of
aluminum and shall include a wheel cone carefully matched to the inlet cone
for precise running tolerances. Wheels shall be statically and dynamically
balanced. The fan housing shall be constructed of heavy duty gauge
aluminum with a rigid internal support structure and a birdscreen.
2. Motors shall be heavy duty ball bearing type, carefully matched to the fan
load, and furnished at the specified voltage, phase and enclosure. Drive frame
assembly shall be constructed of heavy duty gauge steel. Motors and drives
shall be mounted on vibration isolators, out of the airstream. Fresh air for
motor cooling shall be drawn into the motor compartment through a large
space between the fan shroud and the motor cover. Motors and drives shall
be readily accessible for maintenance.
1. Spun aluminum exhaust fans shall be centrifugal direct/belt driven type. The
fan wheel shall be centrifugal backward inclined, constructed of aluminum and
shall include a wheel cone carefully matched to the inlet cone for precise
running tolerances. Wheels shall be statically and dynamically balanced. The
fan housing shall be constructed of heavy gauge aluminum with a rigid
internal support structure. A leakproof fan housing shall be constructed with a
one piece windband with an integral rolled bead for added strength and shall
be joined to the curbcap with a continuously welded seam.
2. Motors shall be heavy duty ball bearing type, carefully matched to the fan
load, and furnished at the specified voltage, phase and enclosure. Drive frame
assembly shall be constructed of heavy gauge steel. Motors and drives shall
be mounted on vibration isolators, out of the airstream. Fresh air for motor
cooling shall be drawn into the motor compartment through a tube free of
discharge contaminants. Motors and drives shall be readily accessible for
maintenance.
5. All fans shall bear the AMCA Certified Ratings Seal for sound and air
performance. Each fan shall bear a permanently affixed manufacturer’s
engraved metal nameplate containing the model number and individual serial
number for future identification. Rating, type and size of exhaust fans shall be
as indicated on Drawings.
1. Fans shall be belt driven, axial type hooded propeller roof fans.
Fan hood and base construction shall be galvanized steel. Hood panels shall
be arched with interlocking ribs. Fan bases shall be low style except where tall
bases are specified. (Where access doors are required for inspection and
service of damper and actuator, tall bases should be specified). Hood support
angles shall be heavy gauge galvanized steel. Birdscreens of ½” galvanized
mesh shall be horizontally mounted in the discharge/intake perimeter of the
hood.
Motors shall be permanently lubricated, heavy duty type, matched to the fan
load and furnished at the specified voltage, phase and enclosure.
Drive frame and panel assemblies shall be galvanized steel. Drive frames
shall be formed channels and fan panels shall have a deep formed inlet
venturi.
The axial exhaust, supply and filtered supply fans shall bear the AMCA
Certified Ratings Seals for both sound and air performance. Fans shall be of
type and capacity as shown on the drawings.
1. Direct drive, axial type sidewall fans shall be as specified herein. Propellers
shall be constructed with fabricated steel blades and hubs. A standard square
key and set screw or tapered bushing shall lock the propeller to the motor
shaft. All propellers shall be statically and dynamically balanced.
3. The axial exhaust fans shall bear the AMCA Certified Ratings Seals for both
sound and air performance. Fans type and capacity as indicated on drawings.
1. Belt driven, axial type sidewall fans shall be provided as specified herein.
Propellers shall be constructed with fabricated steel blades and hubs.
Propellers shall be securely attached to fan shafts. All propellers shall be
statically and dynamically balanced.
Drive frame and panel assemblies shall be galvanized steel or painted steel.
Drive frames shall be formed channels and fan panels shall have prepunched
mounting holes, formed flanges, and a deep formed inlet venturi. Drive frames
and panels shall be bolted construction or welded construction. The axial
exhaust fans shall bear the AMCA Certified Ratings Seals for both sound and
air performance. Fans type and capacity as indicated on drawings.
1. Roof-mounted, filtered makeup air units shall have belt driven double
width/double inlet, forward curved centrifugal blower type supply fans. Motors
shall be permanently lubricated, heavy duty, ball bearing type, carefully
matched to the fan load and furnished at the specified voltage, phase and
enclosure. The fan shaft shall be ground and polished steel mounted in heavy
duty, sealed ball bearings. Bearings shall be selected for a minimum (L50) life
in excess of 200,000 hours at maximum cataloged operating speeds. Pulleys
shall be of the fully machined cast iron type, keyed and securely attached to
the wheel and motor shafts. Motor sheaves shall be adjustable for final system
balancing. Drives shall be sized for a minimum of 150% of driven horsepower.
The entire fan and motor assembly shall be mounted on a formed, reinforced
support structure with vibration isolators to prevent noise transmission.
Fan wheels shall be of the forward curved type, constructed of heavy gauge
steel and statically and dynamically balanced to ensure smooth, vibration free
operation. Hood construction shall be of heavy gauge extruded aluminum
louvers with mitered and welded corners. Hood shall include an insulated
aluminum cover hinged for access. Filters shall be permanent washable one
inch aluminum. Fans type, size and capacities shall be as shown on drawings.
1. Duct mounted supply, exhaust or return fans shall be of the centrifugal belt
driven in-line type. The fan housing shall be of the square design constructed
of heavy galvanized steel and shall include square duct mounting collars. Fan
construction shall include two removable access panels located perpendicualr
to the motor mounting panel. The access panels must of sufficient size to
1. Duct mounted supply, exhaust or return fans shall be of the centrifugal direct
driven in-line type. The fan housing shall be of the square design constructed
of heavy galvanized steel and shall include square duct mounting collars. Fan
construction shall include two removable access panels located perpendicular
to the motor mounting panel. The access panels must of sufficient size to
permit easy access to all interior components. The fan wheel shall be
centrifugal backward inclined, constructed of aluminum and shall include a
wheel cone carefully matched to the inlet cone for precise running tolerances.
Wheels shall be statically and dynamically balanced. Motors shall be
permanently lubricated and carefully matched to the fan loads. Direct drive
motors shall be mounted in the air stream. Motors shall be readily accessible
for maintenance.
1. Duct mounted supply, exhaust or return fans shall be of the centrifugal, belt
driven in-line type. The fan housing shall be of the rectangular design
constructed of heavy gauge galvanized steel and shall include rectangular
duct mounting collars. A hinged or removable panel shall be provided in the
Motors shall be of the heavy duty type with permanently sealed ball bearings.
The wheel shaft shall be ground and polished steel mounted in permanently
sealed pillow block bearings. Drives shall be sized for a minimum of 150% of
driven horsepower. Pulleys shall be of the machined cast iron type, keyed and
securely attached to the wheel and motor shafts. The motor pulleys shall be
adjustable for final system balancing. All fans shall bear the AMCA Certified
Ratings Seal for air performance.
1. Belt or direct driven as shown on drawings, axial type sidewall fans shall be
provided as specified herein. Propellers shall be constructed with fabricated
steel blades and hubs. Propellers shall be securely attached to fan shafts. All
propellers shall be statically and dynamically balanced.
3. Drive frame and panel assemblies shall be galvanized steel or painted steel.
Drive frames shall be formed channels and fan panels shall have prepunched
mounting holes, formed flanges, and a deep formed inlet venturi. Drive frames
and panels shall be bolted construction or welded construction. The axial
exhaust fans shall bear the AMCA Certified Ratings Seals for both sound and
air performance. Fans shall have fabricated blades and hubs, type and
capacity as indicated on drawings.
1. Vane axial fans shall be direct driven with the motor located downstream from
the fan rotor for cooling. Fan blades and rotor shall be heat treated cast
aluminum alloy A356-T6 with all blade bases and sockets precision machined.
Fan rotor and hub shall be positively secured to the motor shaft with a steel
taper lock bushing keyed to the motor shaft. Fan rotor shall be statically and
dynamically balanced to within 0.3 mils vibration dis-placement peak to peak
as measured on the fan housing. Fan housing shall be fabricated from heavy
gauge steel plate with prepunched flanges at both ends. A minimum of eight
heavy gauge straightening vanes shall be welded to fan housing, downstream
from the rotor. A steel motor support shall be continuously welded inside the
fan housing. Provide quantities and sizes as shown on the drawings.
Accessories shall include belt guards, companion flanges and hinged access
doors.
1. Spun aluminum exhaust fans shall be centrifugal direct/belt driven type. The
fan wheel shall be centrifugal backward inclined, constructed of aluminum and
shall include a wheel cone carefully matched to the inlet cone for precise
running tolerances. Wheels shall be statically and dynamically balanced. The
fan housing shall be constructed of heavy gauge aluminum with a rigid
internal support structure. A leakproof fan housing shall be constructed with a
one piece windband with an integral rolled bead for added strength. Fan shall
be provided with a mounting plate, which is attached and sealed to the wall
prior to locating the entire unit.
2. Motors shall be heavy duty ball bearing type, carefully matched to the fan
load, and furnished at the specified voltage, phase and enclosure. Drive frame
assembly shall be constructed of heavy gauge steel. Motors and drives shall
be mounted on vibration isolators, out of the airstream. Fresh air for motor
cooling shall be drawn into the motor compartment through a ten square inch
tube free of discharge contaminants. Motors and drives shall be readily
accessible for maintenance.
5. All fans shall bear the AMCA Certified Ratings Seal for sound and air
performance. Each fan shall bear a permanently affixed manufacturer’s
engraved metal nameplate containing the model number and individual serial
number for future identification. Rating, type and size of exhaust fans shall be
as indicated on Drawings.
1. Supply, exhaust, or return air fans shall be of the tubular centrifugal type
with backward incline or airfoil wheels. The housing shall be constructed of
continuously welded gauge steel to assure air leakage. The housing and
bearing support shall be constructed of structural steel members to prevent
vibration and rigidly support the shaft and bearings. The wheel shall be of
the non-overloading backward incline or airfoil centrifugal type. Wheels
shall be statically and dynamically balanced. The wheel cone and fan inlet
cone shall be carefully matched and shall have precise running tolerances
for maximum performance and operating efficiency. Welded steel vanes
shall straighten the flow of air from the fan discharge and support bearings
and drives. Turned, precision ground and polished steel shafts shall be
sized so the first critical speed is at least 25% over the maximum operating
2. Close tolerances shall be maintained where the shaft makes contact with
the bearing. Bearings shall be heavy duty, grease lubricated, self aligning
ball bearing or roller pillow block type. Extended lubrication lines shall be
provided with external grease fittings. Bearings shall be selected for a
minimum average of 200,000 hours life at maximum operating speed for
each pressure class. Fan performance shall be based on tests conducted in
accordance with AMCA Standard 210 test code for air moving devices, and
fans shall be licensed to bear the AMCA Certified Ratings Seal. After
assembly each fan shall be given a final balance test at specified operating
RPM to insure smooth vibration free operation. Accessories shall include
inlet vanes, safety screen for inlet vanes, companion flanges and vibration
isolation. Type and capacity as shown on the drawings.
1. Fans shall be of the centrifugal type with backward inclined single width. The
housings shall be of continuously welded heavy gauge steel construction with
the scroll panel material formed and embedded into the side panels. The
housing and bearing support shall be constructed of welded structural steel
members to prevent vibration and rigidly support the shaft and bearings. Fans
shall have manufacturer's standard powder coating over phosphatized
surfaces.
Bearings shall be heavy duty grease lubricated, self aligning or roller pillow
block type. Bearings shall be selected for a basic rating fatigue life (L-10) per
AFBMA Standards in excess of 80,000 hours at maximum operating speed for
each pressure class. Contractor shall provide access doors in either inlet or
outlet ductwork. Accessories shall include disconnect motor cover, belt cover
and vibration pads. Type, size and capacities shall be as shown on the
drawings.
P. Air Curtains:
1. Air curtain shall be manufacturers’ standard full length unit complete with
cabinet, blower assembly, louvers, grilles and other required accessories.
Cabinet shall be all-metal, corrosion resistant, galvanized steel housing with
elctrostatically applied epoxy powder coated finish. The maximum effective
width per motor blower assembly shall not be more than 48 inches and all
cabinets shall have structural sidewall supports a maximum 48 inches apart.
Unit shall have full length discharge and flush louvers and directional vanes for
2. Motors shall be heavy duty, totally enclosed, single speed, permanent split
capacitor with double extended shafts, resilient mounted and furnished with
permanently lubricated rubber-sealed ball bearings.
4. Units shall be UL or ETL listed or approved equal, type, size and capacity as
shown on drawings.
Q. Roof Mounted Centrifugal Upblast Exhaust Fan for Smoke Control System
1. Spun aluminum exhaust fans shall be centrifugal belt driven type. The fan
wheel shall be centrifugal backward inclined, constructed of steel and shall
include a wheel cone carefully matched to the inlet cone for precise running
tolerances. Wheels shall be statically and dynamically balanced. The fan
housing shall be constructed of heavy gauge aluminum with a rolled bead
and a rigid internal support structure. A leak-proof fan housing shall be
constructed with a one piece windband with an integral rolled bead for
added strength and shall be joined to the curb cap with a continuously
welded seam.
2. Motors shall be heavy duty ball bearing type, carefully matched to the fan
load, and furnished at the specified voltage, phase and enclosure. Drive
frame assembly shall be constructed of heavy gauge steel. Motors and
drives shall be mounted on safety flange vibration isolators, out of the
airstream. Fresh air for positive motor cooling shall be drawn into the motor
compartment through a ten square inch tube free of discharge
contaminants. Motors and drives shall be readily accessible for
maintenance.
1. Supply exhaust, or return air fans shall be of the inline mixed flow type.
4. The wheel shall be of the mixed flow type. Wheels shall have a wheel cone,
spherical back plate and single thickness cambered blades. Wheels shall
be statistically and dynamically balanced to balance grade G6.3 per ANSI
S2.19. the wheel cone and fan inlet cone shall be carefully matched and
shall have precise running tolerances for maximum performance and
operating efficiency.
5. Each assembled fan shall be test run at the factory at specified fan RPM.
The maximum allowable fan vibration shall be 0.15 in/sec. peak velocity,
filter-in for belt drive units with signatures taken on each bearing in three
planes; horizontal, vertical and axial. Maximum vibration of 0.08 un/sec.
peak velocity, filter-in, for direct drive units in a single plane on the fan
housing. This report shall be provided at no charge to the customer upon
request.
6. Inlet and outlet sound power levels shall be provided for each of the eight
octave bands at the point of operation. Fans shall be licensed to bear the
AMCA Seal for sound and air performance.
8. Belt driven fans were required shall have the following requirements:
1. Sand trap louvers shall separate sand from intake air. Louvers shall be
vertical fixed blade type with blades arranged to provide tortuous air flow
path and thus trap sand.
2. Louver shall have self emptying drain holes. Louvers shall be constructed of
aluminum to ASTM B209 and ANSI.1. Blades shall be 1.6 mm thick with 2.0
mm thick casing. Maximum louver face velocity shall be 1.2 M/s and
maximum pressure drop 50 Pa.
5. Louvers shall have efficiency of 80% with coarse test dust (20 to 200
microns) and 50% efficiency with fine test dust (1 to 70 microns).
PART 3 - EXECUTION
3.1 INSTALLATION
B. Access: Provide access and service space around and over fans as indicated, but in
no case less than that recommended by manufacturer.
C. Support: Unless otherwise indicated, provide 100 mm high concrete pad under
floor-mounted centrifugal fans.
A. Upon completion of installation of fans and after motors has been energized with
normal power source, test the equipment to demonstrate compliance with the
specified requirements.
A. Start-up, test and adjust fans in the presence of the manufacturer's authorized
representative and the Engineer.
END OF SECTION
COMPLIANCE STATEMENT
ZACT.E27827 - Ventilators, Power http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/sho...
ZACT.E27827
Ventilators, Power
Page Bottom
Ventilators, Power
Ceiling mounted ducts, direct drive, "VCDK Series", Model(s) VCDK0040+, VCDK0050+, VCDK0070+, VCDK0090+, VCDK130+, VCDK170+
In-line centrifugal duct fans, belt drive, "VBMBL Series", Model(s) VBMBL12+, VBMBL15+, VBMBL16+, VBMBL18+, VBMBL20+, VBMBL23+,
VBMBL27+, VBMBL30+, VBMBL33+, VBMBL36+, VBMBL40+
In-line centrifugal duct fans, belt drive, "VIBK Series", Model(s) VIBK06+, VIBK08+, VIBK10+, VIBK12+, VIBK15+, VIBK18+, VIBK21+,
VIBK24+, VIBK30+, VIBK36+, VIBK42+
In-line centrifugal duct fans, direct drive, "VIDK Series", Model(s) VIDK06+, VIDK08+, VIDK10+, VIDK12+, VIDK15+, VIDK18+
Power roof ventilators, Model(s) LIBA24, LIBA30, LIBA36, LIBA42, LIBA48, LTBA24, LTBA30, LTBA36, LTBA42, LTBA48, LTBA54, LTBA60,
LUKA24HT, LUKA30HT, LUKA36HT, LUKA42HT, LUKA48HT, LUKA54HT, LUKA60HT
Power ventilators, roof mounted, belt drive, "LUBK Series", Model(s) LUBK24+, LUBK30+, LUBK36+, LUBK42+, LUBK48+
Power ventilators, roof mounted, belt drive, "VEBK Series", Model(s) VEBK06+, VEBK08+, VEBK10+, VEBK12+, VEBK15+, VEBK18+,
VEBK21+, VEBK24+, VEBK30+, VEBK36+, VEBK42+, VEBK48+, VEBK54+
Power ventilators, roof mounted, belt drive, "VEBL Series", Model(s) VEBL06+, VEBL08+, VEBL10+, VEBL12+, VEBL15+, VEBL18+,
VEBL21+, VEBL24+
Power ventilators, roof mounted, belt drive, "VHBB Series", Model(s) VHBB08+, VHBB10+, VHBB12+, VHBB15+, VHBB18+, VHBB20+
Power ventilators, roof mounted, belt drive, "VLBK Series", Model(s) VLBK06+, VLBK08+, VLBK10+, VLBK12+, VLBK15+, VLBK18+,
VLBK21+, VLBK24+, VLBK30+, VLBK36+, VLBK42+, VLBK48+, VLBK54+
Power ventilators, roof mounted, belt drive, "VNBL Series", Model(s) VNBL10, VNBL12, VNBL15, VNBL18, VNBL20
Power ventilators, roof mounted, belt drive, "VSBB Series", Model(s) VSBB08+, VSBB10+, VSBB12+, VSBB15+, VSBB18+, VSBB20+
Power ventilators, roof mounted, belt drive, "VTBK Series", Model(s) VTBK06, VTBK08, VTBK10, VTBK12, VTBK15, VTBK18, VTBK21,
VTBK24, VTBK30, VTBK36, VTBK42, VTBK48
Power ventilators, roof mounted, belt drive, "VUBK Series", Model(s) VUBK06+, VUBK08+, VUBK10+, VUBK12+, VUBK15+, VUBK18+,
VUBK21+, VUBK24+, VUBK30+, VUBK36+, VUBK42+, VUBK48+
Power ventilators, roof mounted, belt drive, "VUBL Series", Model(s) VUBL06+, VUBL08+, VUBL10+, VUBL12+, VUBL15+, VUBL18+,
VUBL21+, VUBL24+
Power ventilators, roof mounted, direct drive, "VEDK Series", Model(s) VEDK06+, VEDK08+, VEDK10+, VEDK12+, VEDK15+, VEDK18+
Power ventilators, roof mounted, direct drive, "VELK Series", Model(s) VELK06+, VELK08+
Power ventilators, roof mounted, direct drive, "VLDK Series", Model(s) VLDK06+, VLDK08+, VLDK10+, VLDK12+, VLDK15+, VLDK18+
Power ventilators, roof mounted, direct drive, "VTDK Series", Model(s) VTDK06, VTDK08, VTDK10, VTDK12, VTDK15, VTDK18
Power ventilators, roof mounted, direct drive, "VUDK Series", Model(s) VUDK06+, VUDK08+, VUDK10+, VUDK12+, VUDK15+, VUDK18+
Power ventilators, roof or wall mounted, direct drive, "VULK Series", Model(s) VULK06+, VULK08+
Power ventilators, wall mounted, belt drive, "LABK Series", Model(s) LABK24+, LABK30+, LABK36+, LABK42+, LABK48+
Power ventilators, wall mounted, belt drive, "LCBK Series", Model(s) LCBK24+, LCBK30+, LCBK36+, LCBK42+, LCBK48+
Power ventilators, wall mounted, belt drive, "LMBK Series", Model(s) LMBK20+, LMBK24+, LMBK36+, LMBK42+, LMBK48+
1 of 2 13-Dec-17, 3:36 PM
ZACT.E27827 - Ventilators, Power http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/sho...
Power ventilators, wall mounted, belt drive, "LNBK Series", Model(s) LNBK24+, LNBK30+, LNBK36+, LNBK42+, LNBK48+, LNBK54+,
LNBK60+
Power ventilators, wall mounted, belt drive, "LRBK Series", Model(s) LRBK24+, LRBK30+, LRBK36+, LRBK42+, LRBK48+, LRBK54+,
LRBK60+
Power ventilators, wall mounted, belt drive, "LWBK Series", Model(s) LWBK20+, LWBK24+, LWBK30+, LWBK36+, LWBK42+, LWBK48+
Power ventilators, wall mounted, belt drive, "VWBK Series", Model(s) VWBK06+, VWBK08+, VWBK10+, VWBK12+, VWBK15+, VWBK18+,
VWBK21+, VWBK24+
Power ventilators, wall mounted, belt drive, "VWBL Series", Model(s) VWBL06+, VWBL08+, VWBL10+, VWBL12+, VWBL15+, VWBL18+,
VWBL21+, VWBL24+
Power ventilators, wall mounted, direct drive, "LJDL Series", Model(s) LJDL10+, LJDL12+, LJDL16+, LJDL18+, LJDL20+, LJDL24+, LJDL30+,
LJDL36+, LJDL42+, LJDL48+, LJDL54+
Power ventilators, wall mounted, direct drive, "LKDL Series", Model(s) LKDL10+, LKDL12+, LKDL16+, LKDL18+, LKDL20+, LKDL24+,
LKDL30+, LKDL36+, LKDL42+, LKDL48+, LKDL54+
Power ventilators, wall mounted, direct drive, "LYDK Series", Model(s) LYDK09+, LYDK10+, LYDK11+, LYDK12+, LYDK13+, LYDK14+,
LYDK15+, LYDK16+, LYDK17+, LYDK18+, LYDK19+, LYDK20+, LYDK21+
Power ventilators, wall mounted, direct drive, "LZDK Series", Model(s) LZDK09+, LZDK10+, LZDK11+, LZDK12+, LZDK13+, LZDK14+,
LZDK15+, LZDK16+, LZDK17+, LZDK18+, LZDK19+, LZDK20+, LZDK21+
Power ventilators, wall mounted, direct drive, "VWDK Series", Model(s) VWDK06+, VWDK08+, VWDK10+, VWDK12+, VWDK15+, VWDK18+
+ - Followed by suffixes.
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction o f the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
"© 2017 UL LLC".
2 of 2 13-Dec-17, 3:36 PM
JOINT GULF BUSINESS CORPORATION
TECHNICAL SCHEDULE
JOINT GULF BUSINESS CORP (JGB CORP)
(Specialized in HVAC, Electromechanical, Insulation, Oil & Gas Products)
Vendor ID #Saudi Aramco: 10039138, Sabic: 505792, SECO: 2005854
PROPOSED SCHEDULE
Page 1 Malaz Sitheen Street, Riyadh Tel: +966 11 4765157, Fax: +966 11 4762931.
Email:sales@jgbksa.com Web: www.jgbksa.com CR No. 2050061017
EF-T.1 TO EF-T.3
HARIQ PROJECT
Model: VEBK30X1G1CA20SEC1 Spun Aluminum
Downblast Centrifugal Belt Drive Powered Ventilator Qty: 3
Options
cULus Listed
2.00 "wg bHP 5.00 100% SE Aluminum
Mill finish
4.00 80 Standard construction
Aluminum insect screen
3.00 60
Standard curb cap
Standard disconnect
1.50
2.00 40
P
R
1.00 20
E
S 1.00 0.00 0
S
U SP/Flow
System
R
Power
E Static Eff.
0.50
CFM
0.00
0 2,800 5,600 8,400 11,200 14,000
VOLUME
EF-R.1 TO EF-R.2
HARIQ PROJECT
Model: VEBK15M1D1CA20SEC1 Spun Aluminum
Downblast Centrifugal Belt Drive Powered Ventilator Qty: 2
Options
cULus Listed
0.75 "wg bHP 0.50 100% SE Aluminum
Mill finish
0.40 80 Standard construction
Aluminum insect screen
0.30 60
Standard curb cap
Standard disconnect
0.20 40
P 0.50
R
0.10 20
E
S 0.00 0
S
U SP/Flow
System
R
0.25 Power
E Static Eff.
CFM
0.00
0 500 1,000 1,500 2,000 2,500
VOLUME
EF-PR.1
HARIQ PROJECT
Model: VEBK12P1D1CA20SEC1 Spun Aluminum
Downblast Centrifugal Belt Drive Powered Ventilator Qty: 1
Options
cULus Listed
1.50 "wg bHP 0.50 100% SE Aluminum
Mill finish
0.40 80 Standard construction
Aluminum insect screen
0.30 60
Standard curb cap
Standard disconnect
0.20 40
P 1.00
R
0.10 20
E
S 0.00 0
S
U SP/Flow
System
R
0.50 Power
E Static Eff.
CFM
0.00
0 400 800 1,200 1,600 2,000
VOLUME
SF-PR.2
HARIQ PROJECT
Model: VNBL18T4D1CG20B_H1 Filtered Supply
Centrifugal Belt Drive Powered Ventilator Qty: 1
Standard Features
Sound Data
Blower and motor assembly is mounted on rubber
Octave Band LwA Sones shear vibration isolators.
Blowers are DWDI-FC constructed of heavy gauge
1 2 3 4 5 6 7 8 steel, statically and dynamically balanced for vibration
79 19.4 free operation.
92 91 80 73 71 67 63 58
Fan shaft is ground and polished and mounted in
(dB re 10-12 watts) dB 70.45 heavy duty, permanently lubricated and sealed ball
bearings with minimum average life L50 = 200,000
hours at operating speed.
Belts are non-static conducting, oil resistant V-belts.
Motors and drives are factory mounted. All units are
factory run-tested and adjusted to proper RPM.
2.00 "wg bHP 5.00 100% SE
Options
4.00 80 cULus Listed
Galvanized
3.00 60 Mill finish
1.50 Finish applied internally and externally
2.00 40 1" filter
P Mounted disconnect
R
1.00 20
E
S 1.00 0.00 0
S
U SP/Flow
System
R
Power
E Static Eff.
0.50
CFM
0.00
0 1,600 3,200 4,800 6,400 8,000
VOLUME
EF-GR.1
HARIQ PROJECT
Model: VEDK06F3K1CA20SEC1 Spun Aluminum
Downblast Centrifugal Direct Drive Powered Ventilator Qty: 1
0.40 0.15 60
0.10 40
P
R
0.30 0.05 20
E
S 0.00 0
S
U 0.20 SP/Flow
System
R
Power
E Static Eff.
0.10
CFM
0.00
0 50 100 150 200 250
VOLUME
JOINT GULF BUSINESS CORPORATION
PROPOSED PRODUCTS
CATALOGUE
CENTRIFUGAL ROOF EXHAUSTERS | Model VEBK and VEDK
The Carnes Company has designed the VE series Testing has been conducted to ensure durability and
downblast fan to meet the rigorous performance and dependability of operation.
SECTION 2
TYPICAL SPECIFICATIONS
Roof exhaust ventilators shall be of the centrifugal belt or direct driven type. The wheel and spun venturi
shall be a centrifugal design of spark resistant construction. For maximum performance and quiet, efficient
operation, the wheel shall overlap the inlet venturi and have backward inclined blades. The wheels shall be
dynamically balanced to assure smooth and vibration-free rotation under maximum loading. The complete
drive assembly, including the motor and the wheel, shall be mounted on vibration isolators. Motor and drives
shall be factory mounted. All fans shall be test run prior to shipment.
VEBK Belt Drive Series VEDK Direct Drive Series
The motor shall be factory wired to the disconnect junction box and a disconnect switch shall be supplied. A conduit
chase shall be provided for running electrical wiring through the curb cap into the motor compartment. Field wiring of
motor, disconnect and conduit are to be in accordance with electrical specifications and local codes. Heavy-gauge
welded galvanized birdscreen shall be furnished.
Horsepower and noise levels shall not exceed the published values and oversized motors will not be acceptable.
Performance ratings shall be AMCA licensed for Air and Sound.
Centrifugal power roof ventilators shall be Carnes Company Model VEBK, belt drive, sizes 06 through 54, or Model
VEDK, direct drive, sizes 06 through 18, as manufactured at Carnes Company of Verona, Wisconsin.
COMPUTERIZED FAN SELECTION: Make the right choice with CARNES FAN-C-LECT™. The
Models VEDK and VEBK, as well as the comprehensive offering of CARNES powered ventilators, are
included in CARNES user friendly fan selection program.
FAN HOUSING
• Constructed with heavy-gauge
aluminum.
• Designed for maximum weather
Removable
protection, windband and diffusers Motor
prevent the entrance of inclement Cover
weather.
• Fan hoods beaded for rigidity.
• Interior fan hood lip extended to
Positive
prevent the entrance of water. Ventilation
• 3 piece motor cover design (lid, Louvers
Cent. Power Roof Vents
BEARINGS/SHAFT
• Eccentric locking collar bearings
standard on sizes 06-18.
• Dual bearings utilized to properly
support the fan shaft.
• Prelubricated sealed, self-aligning ball
Removable
bearing.
Motor Cover
• Rated at 200,000 hours average
operation.
• Polished CRS fan shaft with rust
Positive
inhibitive coating.
25¾” Dia.
DESIGN DATA
Tip Speed = 2.75 x RPM
VEDK 06 133/8” Std.
21 /8” Extd.
7
Unit Weight (less Motor) = 30 Lbs.
Roof Opening = 11” Sq.
DIRECT DRIVE PRV Curb O. D. = 14” Sq.
Damper Size = 10” Sq.
27/8”
PERFORMANCE DATA 15½” Sq.
F3+ J2+ .000 .125 .250 .375 .500 .625 .750 1.000 1.250
1/20 1/8 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
RPM SONES SONES SONES SONES SONES SONES SONES SONES SONES
155 .01
400
.1
193 .01
500
.1
SPEED CONTROLLABLE MOTORS**
232 .01
600
.5
270 .01 130 .01
700
1.0 1.4
309 .01 202 .01
800
1.6 1.7
348 .02 258 .02
900
2.2 2.1
386 .02 309 .02 194 .03
1000
2.9 2.7 3.7
415 .03 344 .03 251 .03
1075 *
3.5 3.3 4.0
425 .03 356 .03 266 .03
1100
3.7 3.5 4.1
464 .04 401 .04 325 .04 211 .05
1200
4.4 4.3 4.5 5.5
502 .05 446 .05 379 .05 294 .06
1300
5.3 5.1 5.1 5.9
541 .06 489 .06 430 .07 358 .07 259 .07
1400
6.1 5.9 5.8 6.3 7.2
580 .07 532 .08 477 .08 415 .08 339 .09
1500
7.0 6.8 6.6 6.9 7.6
618 .09 573 .09 523 .10 468 .10 404 .10 321 .11
1600 *
7.9 7.7 7.5 7.5 8.2 9.0
ALL OTHER MOTORS 1140 * 440 .03 374 .04 291 .04
(Non-Speed Controllable) 4.0 3.8 4.2
TE, XP, 2 Spd, 230V & All 3 Ph 1725 * 667 .11 625 .12 580 .12 532 .13 475 .13 412 .13 328 .13
9.0 8.9 8.8 8.8 9.2 9.8 10.6
Performance certified is for installation type A - free inlet, free outlet. The sound power level ratings shown are in decibels, referred to 10 -12
Speed (RPM) is nominal. Performance is based on actual speed of test. watts calculated per AMCA Standard 301. Values shown are for inlet LWi
** To be Speed Controllable, motor must have 115/1 ODP. Other sound power levels for installation Type A free inlet, free outlet. Ratings
voltages and enclosures are non-speed controllable. do not include the effects of duct end correction.
* Base Unit - As run motor speeds.
+ RPM range capable with solid state speed control. The sound ratings shown are loudness values in fan sones at 5 feet
Performance ratings do not include the effects of accessories. (1.5m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation Type A, free inlet hemispherical sone
levels.
VEDK 06 AIR PERFORMANCE
VEDK 06 SOUND PERFORMANCE
SOUND POWER RE 10 -12 WATTS
OCTAVE BANDS
RPM SP 1 2 3 4 5 6 7 8 LWA
.000 65 58 55 51 51 47 43 34 56
1075 .125 67 58 54 50 49 45 41 37 54
.250 68 61 56 53 52 47 43 39 57
.000 79 71 69 63 61 58 55 48 67
.125 80 71 69 62 60 57 54 48 67
.250 81 72 68 62 60 56 53 48 66
1600
.375 82 72 68 61 60 56 52 48 66
.500 81 73 69 63 62 57 53 49 68
.625 80 75 71 64 64 59 55 51 69
[ ]
3
Max BHP = .10 x RPM
VEBK 12
1000
25½” Std.
Tip Speed = 3.27 x RPM
30¼” Extd. Max. Motor Frame Size = 145T
BELT DRIVE PRV Unit Weight (less motor) = 35 lbs.
Roof Opening = 13’’ Sq.
Curb O. D. = 16’’ Sq.
PERFORMANCE DATA 175/8” Sq. 51/8” Damper Size = 12’’ Sq.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
RPM SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES
703 .02 396 .02
K2 (1/6) 550 2.4 1.6
830 .03 612 .03
650
K3 (1/6)
3.7 2.8
958 .04 778 .05 479 .04
750 4.8 3.9 3.9
1086 .06 928 .07 735 .07 87 .04
850
L1 (1/4)
2427 .68 2358 .69 2289 .70 2219 .71 2148 .73 2002 .675 1837 .77 1642 .77 1358 .75
1900 25 25 25 25 24 24 24 24 23
2491 .68 2358 .69 2289 .70 2219 .71 2148 .73 2002 .75 1837 .77 1642 .77 1358 .75
1950 27 26 26 26 25 25 25 25 25
2555 .79 2490 .80 2423 .82 2357 .83 2291 .84 2152 .87 2006 .89 1838 .90 1615 .89 620 .69
T1 (1-1/2)
2000 28 28 27 27 27 26 26 26 26 26
2619 .85 2555 .86 2491 .88 2426 .89 2362 .90 2226 .93 2090 .96 1926 .97 1728 .97 1056 .88
2050 29 29 29 28 28 27 27 27 27 27
2682 .92 2620 .93 2558 .94 2495 .96 2432 .97 2300 1.00 2168 1.02 2012 1.04 1840 1.04 1269 .97
2100 30 30 30 30 29 29 28 28 28 28
2746 .98 2686 1.00 2624 1.01 2563 1.02 2501 1.04 2374 1.06 2245 1.09 2098 1.11 1941 1.12 1440 1.06
2150 32 31 31 31 31 30 30 30 30 29
2810 1.05 2751 1.07 2691 1.08 2631 1.09 2571 1.11 2447 1.14 2321 1.17 2183 1.19 2030 1.20 1586 1.16
2200 33 33 33 32 32 32 31 31 31 31
2874 1.13 2816 1.14 2758 1.15 2699 1.17 2640 1.18 2519 1.21 2396 1.24 2267 1.27 2117 1.28 1728 1.27 868 1.06
2250 35 34 34 34 34 33 33 32 32 32 32
2938 1.20 2881 1.22 2824 1.23 2767 1.25 2709 1.26 2592 1.29 2471 1.32 2350 1.35 2204 1.36 1843 1.36 1843 1.36
2300 36 36 36 35 35 35 34 34 34 33 33
3002 1.28 2947 1.30 2890 1.31 2834 1.33 2778 1.34 2664 1.37 2545 1.40 2427 1.44 2289 1.45 1957 1.45 1428 1.36 790 1.15
2350 38 37 37 37 37 36 35 35 35 35 35 35
3066 1.37 3012 1.38 2957 1.40 2902 1.41 2846 1.43 2735 1.46 2619 1.49 2504 1.52 2374 1.54 2069 1.55 1599 1.48 1221 1.42
2400 39 39 39 38 38 38 37 37 37 37 37 37
3129 1.46 3077 1.47 3023 1.49 2969 1.50 2915 1.52 2806 1.55 2693 1.58 2580 1.61 2458 1.64 2180 1.66 1745 1.60 1436 1.53
2450 41 41 41 40 40 40 39 39 39 38 38 38
Performance certified is for installation type A - free inlet, free outlet. The sound ratings shown are loudness values in fan sones at 5 feet (1.5m)
Performance ratings (bhp) do not include transmission losses. in a hemispherical free field calculated per AMCA Standard 301. Values
Performance ratings do not include the effects of accessories. shown are for installation type A, free inlet hemispherical sone levels.
[ ]
3
Max BHP = .282 x RPM
VEBK 15
1000
28½” Std.
Tip Speed = 4.06 x RPM
33¼” Extd. Max. Motor Frame Size = 182T
BELT DRIVE PRV Unit Weight (less motor) = 50 lbs.
Roof Opening = 16’’ Sq.
Curb O. D. = 19’’ Sq.
PERFORMANCE DATA 20½” Sq. 6½” Damper Size = 15’’ Sq.
.000 .125 .250 .375 .500 .750 1.000 1.250 1.500 2.000 2.500 2.750
K1 (1/6)
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
RPM SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES
1279 .04 976 .05
550
K2 (1/6)
3.3 2.6
1395 .05 1129 .06 716 .06
600 4.0 3.3 3.2
1511 .07 1272 .08 943 .08
650
L1 (1/4)
2906 .50 2791 .51 2674 .52 2548 .54 2401 .55 2082 .55 1669 .54
1250 14.5 14.1 13.6 13.4 13.2 12.7 12.5
3022 .56 2912 .57 2799 .59 2685 .60 2543 .61 2241 .62 1885 .62 1266 .56
1300 15.6 15.1 14.7 14.4 14.2 13.8 13.5 13.6
3138 .63 3032 .64 2924 .65 2815 .67 2684 .68 2398 .70 2075 .69 1641 .67
1350 16.6 16.1 15.7 15.5 15.3 14.9 14.6 14.6
3255 .70 3135 .71 3048 .73 2943 .74 2823 .75 2553 .77 2261 .77 1877 .76 1084 .62
T1 (1-1/2)
1400 17.7 17.3 16.9 16.6 16.4 16.1 15.8 15.7 15.8
3371 .77 3273 .79 3171 .81 3070 .82 2961 .83 2707 .86 2425 .86 2095 .86 1610 .79
1450 18.8 18.4 18.0 17.8 17.6 17.2 16.9 16.8 16.8
3488 .86 3392 .87 3294 .89 3197 .90 3097 .92 2852 .95 2585 .96 2285 .95 1898 .92
1500 20 19.5 19.2 18.9 18.7 18.4 18.1 17.9 17.9
3604 .95 3512 .96 3417 .98 3322 1.00 3228 1.01 2995 1.04 2742 1.05 2472 1.05 2132 1.04
1550 21 21 20 20 20 19.0 19.0 19.0 19.0
3720 1.04 3631 1.06 3539 1.07 3448 1.09 3356 1.11 3137 1.14 2897 1.16 2643 1.16 2339 1.15
1600 22 22 21 21 21 21 20 20 20
V1 (2)
3836 1.14 3747 1.16 3661 1.18 3572 1.19 3483 1.21 3278 1.24 3049 1.27 2804 1.27 2529 1.26 1650 1.15
1650 23 23 23 22 22 22 21 21 21 21
3953 1.25 3866 1.27 3783 1.28 3697 1.30 3610 1.32 3417 1.35 3201 1.38 2962 1.39 2715 1.38 2038 1.33
1700 24 24 24 24 23 23 23 22 22 22
4069 1.36 3985 1.38 3904 1.40 3820 1.42 3736 1.44 3555 1.47 3345 1.50 3118 1.51 2886 1.52 2276 1.48
1750 25 25 25 25 24 24 24 24 23 23
4185 1.48 4104 1.50 4025 1.52 3944 1.54 3862 1.56 3692 1.59 3488 1.62 3273 1.65 3047 1.65 2510 1.63 1280 1.28
1800 27 26 26 26 26 25 25 25 24 24 24
4301 1.61 4222 1.63 4146 1.65 4067 1.67 3987 1.69 3828 1.73 3629 1.76 3425 1.79 3206 1.79 2711 1.78 1890 1.58
1850 28 28 27 27 27 27 26 26 26 25 25
4417 1.74 4340 1.76 4266 1.78 4189 1.80 4112 1.82 3958 1.86 3770 1.90 3577 1.93 3363 1.94 2900 1.92 2276 1.86 1536 1.59
1900 29 29 29 28 28 28 28 27 27 26 26 27
4534 1.88 4459 1.90 4387 1.92 4311 1.95 4236 1.97 4086 2.01 3909 2.04 3721 2.08 3518 2.09 3087 2.09 2514 2.04 2066 1.88
1950 30 30 30 30 29 29 29 28 28 28 27 27
4592 1.96 4518 1.98 4447 2.00 4372 2.02 4298 2.04 4150 2.08 3979 2.12 3793 2.15 3595 2.17 3180 2.17 2632 2.13 2279 2.02
1975 31 31 30 30 30 30 29 29 29 28 28 28
Performance certified is for installation type A - free inlet, free outlet. The sound ratings shown are loudness values in fan sones at 5 feet (1.5m)
Performance ratings (bhp) do not include transmission losses. in a hemispherical free field calculated per AMCA Standard 301. Values
Performance ratings do not include the effects of accessories. shown are for installation type A, free inlet hemispherical sone levels.
[ ]
3
Max BHP = 7.54 x RPM
VEBK 30
1000
423/8” Std.
Tip Speed = 8.25 x RPM
491/8” Extd. Max. Motor Frame Size = 254T
BELT DRIVE PRV Unit Weight (less motor) = 190 lbs.
Roof Opening = 35½’’ Sq.
Curb O. D. = 38½’’ Sq.
PERFORMANCE DATA 401/8” Sq. 107/8” Damper Size = 34’’ Sq.
.000 .125 .250 .375 .500 .625 .750 1.000 1.250 1.500 2.000 2.500
P1 (1/2)
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
RPM SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES SONES
4812 .14 3503 .16
275
P2 (1/2)
4.8 3.2
5249 .18 4124 .20 1666 .15
300 5.6 4.2 3.3
5686 .22 4674 .25 2917 .23
325 6.5 5.2 3.9
6124 .28 5192 .31 3818 .31
350
R1 (3/4)
7436 .50 6691 .54 5850 .57 4558 .56 2405 .43
425 10.4 9.1 7.9 6.6 6.4
7874 .59 7177 .64 6408 .68 5348 .68 3729 .61
450 11.4 10.1 9.0 7.7 7.1
8311 .70 7651 .74 6931 .79 6034 .80 4710 .75 2678 .60
T1 (1-1/2)
9623 1.09 9053 1.14 8454 1.19 7824 1.24 7006 1.25 5927 1.21 4518 1.10
550 15.7 14.6 13.6 12.7 11.5 10.5 10.3
10061 1.24 9515 1.30 8951 1.35 8348 1.40 7633 1.42 6719 1.41 5514 1.31
575 16.9 15.8 4.9 14.1 13.0 12.0 11.2
10498 1.41 9975 1.47 9443 1.52 8865 1.58 8247 1.62 7453 1.62 6412 1.57 3332 1.21
600 18.1 17.1 16.2 15.5 14.4 13.4 12.5 12.2
W1 (3)
10935 1.59 10434 1.65 9931 1.71 9376 1.77 8821 1.82 8088 1.83 7207 1.81 4776 1.58
625 19.4 18.4 17.6 16.8 15.9 15.0 14.0 13.3
11373 1.79 10890 1.85 10408 1.92 9881 1.97 9348 2.03 8711 2.06 7977 2.06 5835 1.87
650 21 19.7 18.9 18.2 17.4 16.4 15.6 14.4
X1 (5)
11810 2.01 11346 2.07 10881 2.14 10382 2.20 9869 2.25 9323 2.30 8616 2.30 6782 2.16 4002 1.77
675 22 21 20 19.5 18.8 17.9 17.0 15.5 15.5
12248 2.24 11800 2.31 11352 2.37 10879 2.44 10384 2.50 9888 2.56 9244 2.57 7635 2.50 5394 2.22
700 23 22 22 21 20 19.4 18.5 17.0 16.6
12685 2.49 12253 2.56 11820 2.63 11372 2.69 10894 2.76 10415 2.82 9861 2.85 8426 2.82 6457 2.59 2624 1.67
725 25 24 23 22 22 21 20 18.4 17.6 17.6
13123 2.75 12704 2.83 12286 2.90 11861 2.97 11399 3.03 10937 3.10 10468 3.16 9197 3.16 7407 2.94 5076 2.57
750 26 25 24 24 23 22 22 20 18.7 18.7
Y1 (7-1/2)
13560 3.04 13155 3.11 12751 3.19 12346 3.26 11900 3.33 11453 3.39 11005 3.46 9837 3.48 8291 3.37 6267 3.07
775 28 27 26 25 24 24 23 21 20 20
13997 3.34 13605 3.42 13213 3.50 12822 3.57 12398 3.64 11964 3.71 11531 3.78 10467 3.83 9088 3.77 7297 3.51
800 29 28 27 26 26 25 24 23 21 21
14435 3.67 14055 3.74 13675 3.82 13295 3.90 12892 3.98 12472 4.05 12051 4.12 11087 4.20 9870 4.18 8242 3.93 1407 1.73
825 30 29 28 28 27 26 26 24 23 22 22
14872 4.01 14503 4.09 14134 4.17 13766 4.25 13383 4.33 12975 4.40 12567 4.48 11699 4.60 10578 4.60 9116 4.46 4810 3.46
850 32 31 30 29 28 28 27 26 24 23 22
15310 4.37 14951 4.46 14593 4.54 14235 4.62 13871 4.71 13475 4.78 13079 4.86 12286 5.01 11214 5.02 9913 4.93 6362 4.24
875 33 32 31 30 30 29 28 27 26 24 24
15747 4.76 15399 4.85 15050 4.93 14702 5.02 14353 5.10 13971 5.18 13586 5.26 12816 5.41 11842 5.46 10696 5.42 7458 4.86
900 35 34 33 32 31 30 30 28 27 26 25
16184 5.17 15845 5.26 15506 5.34 15168 5.43 14829 5.52 14465 5.60 14090 5.68 13341 5.84 12461 5.92 11430 5.92 8473 5.44 1922 2.65
925 36 35 34 33 33 32 31 30 28 27 26 26
16622 5.60 16292 5.69 15962 5.78 15632 5.87 15302 5.96 14956 6.05 14591 6.13 13861 6.29 13072 6.42 12069 6.42 9419 5.98 5356 4.82
950 38 37 36 35 34 34 33 32 30 29 27 27
17059 6.05 16738 6.14 16416 6.24 16094 6.33 15773 6.42 15444 6.51 15089 6.60 14378 6.77 13666 6.93 12699 6.94 10320 6.70 6967 5.82
975
39 39 38 37 36 35 35 33 32 30 28 28
17497 6.53 17183 6.62 16870 6.72 16556 6.81 16242 6.91 15929 7.01 15584 7.09 14890 7.26 14197 7.44 13322 7.49 11118 7.33 8068 6.59
1000 41 40 39 39 38 37 36 35 34 32 29 29
Performance certified is for installation type A - free inlet, free outlet. The sound ratings shown are loudness values in fan sones at 5 feet (1.5m)
Performance ratings (bhp) do not include transmission losses. in a hemispherical free field calculated per AMCA Standard 301. Values
Performance ratings do not include the effects of accessories. shown are for installation type A, free inlet hemispherical sone levels.
VEBK 10 VEBK 10
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
650 .000 49 53 50 49 47 41 34 27 51
.000 56 66 66 60 60 56 49 42 64
1050
.500 59 63 61 55 53 53 48 43 59
.000 65 71 74 70 66 64 58 51 72
1400 .375 66 71 72 67 73 60 55 50 69
Cent. Power Roof Vents
.750 64 70 70 65 60 59 56 51 68
.000 73 75 80 78 71 70 65 58 79
1750 .625 70 76 78 75 68 66 62 56 76
1.250 68 75 76 72 65 63 63 58 74
.000 78 79 85 83 76 75 71 64 84
.500 76 80 84 82 75 72 69 63 82
2100
1.000 74 81 83 80 73 70 67 62 81
2.000 72 79 81 78 71 68 68 63 79
.000 80 84 87 88 81 78 75 69 88
1.000 77 85 87 86 79 75 72 67 86
2450 2.000 74 84 86 84 77 72 71 67 84
2.500 74 83 85 83 76 72 71 68 84
3.000 76 83 85 83 76 72 71 68 84
The sound power level ratings shown are in decibels, referred to 10 -12 watts
calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance certified is for installation type A - free inlet, free outlet.
Performance ratings (bhp) do not include transmission losses. power levels for installation Type A free inlet, free outlet. Ratings do not
Performance ratings do not include the effects of accessories. include the effects of duct end correction. The A-weighted sound raitings
shown have been calculated per AMCA International Standard 301.
VEBK 12 VEBK 12
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
550 .000 55 55 47 47 49 42 34 26 52
.000 71 71 67 60 61 60 52 44 66
950
.375 71 72 67 58 54 52 48 43 63
.000 81 82 82 70 66 71 64 56 77
1350 .375 80 82 82 70 64 65 59 52 76
.750 80 82 83 68 63 61 58 53 76
.000 85 89 87 81 73 75 72 65 84
1750 .750 85 89 87 81 72 70 67 60 83
1.500 85 89 88 80 70 66 64 61 83
.000 89 94 93 88 78 78 78 71 90
.500 88 94 93 89 78 76 75 68 89
2100
1.000 88 94 93 89 78 74 72 66 89
2.000 88 94 94 89 76 72 69 66 89
.000 91 98 98 95 83 80 83 76 95
.500 91 98 98 95 83 79 81 74 95
2450 1.000 91 98 98 95 83 78 78 72 95
2.000 90 98 98 96 82 77 75 71 95
2.750 90 98 98 96 80 76 73 70 95
The sound power level ratings shown are in decibels, referred to 10 -12 watts
Performance certified is for installation type A - free inlet, free outlet. calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance ratings (bhp) do not include transmission losses. power levels for installation Type A free inlet, free outlet. Ratings do not
Performance ratings do not include the effects of accessories. include the effects of duct end correction. The A-weighted sound raitings
shown have been calculated per AMCA International Standard 301.
VEBK 15 VEBK 15
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
550 .000 61 56 54 52 52 45 38 32 56
.000 71 72 67 64 62 59 52 45 67
850
.500 76 70 64 59 57 55 52 46 64
.000 75 77 75 72 70 68 63 55 76
1150 .500 76 78 75 69 66 64 60 54 73
Performance certified is for installation type A - free inlet, free outlet. The sound power level ratings shown are in decibels, referred to 10 -12 watts
Performance ratings (bhp) do not include transmission losses. calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance ratings do not include the effects of accessories. power levels for installation Type A free inlet, free outlet. Ratings do not
include the effects of duct end correction. The A-weighted sound raitings
shown have been calculated per AMCA International Standard 301.
VEBK 18 VEBK 18
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
AVOID SELECTION
3 LEFT OF CURVE INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
STATIC PRESSURE (INCHES WG)
550 .000 68 72 63 59 57 54 43 39 63
1550 RPM
2.5 .000 73 80 75 68 65 62 55 48 72
750
.625 72 79 74 67 61 56 51 47 70
1400 .000 77 84 82 75 71 69 65 56 79
2
950 .500 76 82 81 73 68 65 60 54 76
1250 1.000 76 82 80 72 67 63 59 54 76
1.5 .000 84 85 83 78 74 75 73 66 82
1150 1.000 83 83 79 74 69 70 68 65 78
1100
1.500 82 82 78 72 68 68 67 64 76
950 .000 86 89 89 83 78 78 77 71 86
1
1.000 85 88 87 80 75 75 73 70 84
800 1350
1.750 85 87 85 78 73 71 71 68 82
2.250 85 87 85 77 72 71 70 68 81
0.5 650
.000 87 93 93 86 81 80 80 74 90
1.000 86 92 92 84 79 78 77 73 88
1500 1.750 86 91 90 82 77 75 74 72 86
0 1 2 3 4 5 6
0 2.250 87 90 90 81 75 73 73 71 85
CFM (CUBIC FT/MIN) (Thousands) 2.750 87 90 90 81 75 73 73 71 85
Performance certified is for installation type A - free inlet, free outlet. The sound power level ratings shown are in decibels, referred to 10 -12 watts
Performance ratings (bhp) do not include transmission losses. calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance ratings do not include the effects of accessories.
power levels for installation Type A free inlet, free outlet. Ratings do not
include the effects of duct end correction. The A-weighted sound raitings
shown have been calculated per AMCA International Standard 301.
VEBK 30 VEBK 30
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
275 .000 64 62 60 60 56 49 44 38 61
.000 73 72 66 67 66 59 53 47 69
375
.375 71 64 58 56 55 52 48 44 60
.000 78 78 74 72 71 66 60 54 75
475 .375 76 74 68 65 64 61 56 52 69
The sound power level ratings shown are in decibels, referred to 10 -12 watts
calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance certified is for installation type A - free inlet, free outlet.
Performance ratings (bhp) do not include transmission losses. power levels for installation Type A free inlet, free outlet. Ratings do not
Performance ratings do not include the effects of accessories. include the effects of duct end correction. The A-weighted sound raitings
shown have been calculated per AMCA International Standard 301.
VEBK 36 VEBK 36
Air Performance Sound Performance
SP SOUND POWER RE 10 -12 WATTS
INCH OCTAVE BANDS
RPM W.G. 1 2 3 4 5 6 7 8 LWA
250 .000 70 67 64 60 56 57 61 65 68
.000 79 77 73 69 65 64 67 71 75
350
.500 75 68 62 59 56 53 49 42 62
.000 85 83 78 74 70 68 70 74 79
425 .375 83 80 74 69 66 64 64 65 74
.625 83 76 69 64 62 59 56 51 69
.000 89 88 83 79 75 71 72 76 83
500 .500 88 85 79 73 70 67 68 69 78
1.000 90 80 74 67 66 62 60 53 73
.000 92 92 87 83 79 75 75 78 86
.500 91 90 85 78 75 72 72 73 83
575
1.000 93 87 81 73 71 68 66 63 79
1.500 94 85 78 71 70 66 64 58 77
.000 94 95 91 86 82 78 77 80 89
.500 94 94 89 83 79 76 75 77 87
650 1.000 94 92 87 80 76 73 72 71 84
1.500 96 91 83 76 73 70 67 63 81
1.750 96 90 82 75 72 69 67 61 81
The sound power level ratings shown are in decibels, referred to 10 -12 watts
calculated per AMCA Standard 301. Values shown are for inlet Lwi sound
Performance certified is for installation type A - free inlet, free outlet.
power levels for installation Type A free inlet, free outlet. Ratings do not
Performance ratings (bhp) do not include transmission losses.
include the effects of duct end correction. The A-weighted sound raitings
Performance ratings do not include the effects of accessories.
shown have been calculated per AMCA International Standard 301.
Self Flashing
Flashing
Roof Curb
By Others
(Insulated)
Damper
Roof Curb Flashing
(Insulated) By Others
Damper Duct
By Others
Roof Opening
Roof Opening
Figure 1 Figure 2
POWER ROOF VENTILATOR POWER ROOF VENTILATOR
(NON-DUCTED INSTALLATION) (DUCTED INSTALLATION)
Figure 1 shows a typical Model VEBK power roof Figure 2 shows a typical Model VEBK power roof
ventilator installation without duct work. The roof flashing ventilator installation with an exhaust duct. The duct is
is shown installed over standard canted style roof curb. A shown extending through the roof opening and inside a
gravity operated backdraft damper is shown installed on typical self flashing style roof curb. A gravity operated
the damper shelf which is located at the base of the roof backdraft damper is shown fastened to a 3/4” x 3/4” sheet
curb. Power wiring is extended through the roof opening, metal angle installed inside the exhaust duct.
through the damper conduit knockout, into the fan wiring
chase and to the factory wired disconnect switch.
Proper fan performance requires uniform and stable air flow at the fan inlet. Avoid transitions,
obstructions, elbows or other duct fittings near the fan inlet.
Typical roof curb height is 8” to 12” above the roof deck. Additional height reduces the
likelihood of snow or rain entering through the roof opening.
Installation and electrical work should be performed by qualified personnel and must be in
accordance with all applicable code requirements.
For protection of personnel, inlet guards are recommended when the fan is within reach
(or within 7 feet) of occupied areas or work areas.
V E B K 1 2 L 1 A 1 N A 2 0
V - Centrifugal A - Aluminum
1
R - Aluminum
2
06 w/Standard
E - Spun (Roof) 3 Diffuser & Spun
08 4
Ventilator One Piece Cover
10 5 (Sizes 6-18, ODP
SCREEN
P - 1/2 X .041 Galv. (Default) 1 - Disconnect (Default)
NOTE: Disconnects are standard on all units except those supplied
K - 1/2 x .063 Aluminum with explosion proof motors or units supplied without motors.
E - Aluminum Insect Screen 2 - Speed Control (3 Amp) - Less Disconnect
X - Stainless Steel Birdscreen 3 - Speed Control (6 Amp) - Less Disconnect
Y - Stainless Steel Insect Screen 4 - Firestat & Speed Control (3 Amp)
5 - Disconnect & Speed Control (3 Amp)
6 - Firestat & Disconnect
7 - Firestat & Speed Control (6 Amp)
8 - Disconnect & Speed Control (6 Amp)
9 - Less Disconnect
F - Speed Control (10 Amp) - Less Disconnect
M - Disconnect & Speed Control (10 Amp)
N - Disconnect & Speed Control (5 Amp)
L - Firestat & Speed Control (10 Amp)
S - Speed Control (10 Amp R3 Motor Less Disconnect)
V - Disconnect & Speed Control (10 Amp, R3 Motor)
T - Firestat & Speed Control (10 Amp R3)
J - NEMA 3R Disconnect
Dampers
Design
Model Series Type Width (Size) Length (Size) Finish OPTION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J D H A M 0 1 0 1 0 1 0 0 2 0
J - Air
Movement
Accessory
Cent. Power Roof Vents
Curbs
Design
Model Series Mat’l Width (Size) Length (Size) Height OPTION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
J C F A G 0 1 4 0 0 1 4 0 A
J - Air A
Movement B D - Damper Shelf
Accessory L - Liner (Galvanized)
G - Galvanized Inches Inches M - Liner (Aluminum)
C - Curb A - Aluminum O. D. O. D. HEIGHT T - Liner (Galvanized)
A - 8” w/Damper Shelf
B - 10” T - Liner (Aluminum)
S - Sound Curb
C - 12” w/Damper Shelf
M - Sound Curb
FRACTIONAL FRACTIONAL D - 14”
w/Raised Cant
SIZE SIZE E - 16”
R - Raised Cant
0 - 0’’ 0 - 0’’ F - 17”
E - Extended Base
1 - 1/8” 1 - 1/8” G - 18”
F - Standard
2 - 1/4” 2 - 1/4” H - 20”
H - Self-Flashing
3 - 3/8” 3 - 3/8” I - 22”
V - Vented
4 - 1/2” 4 - 1/2” J - 24”
5 - 5/8” 5 - 5/8” N - 25”
6 - 3/4” 6 - 3/4” P - 26”
7 - 7/8” 7 - 7/8” R - 28”
S - 36”
J C A A A 2 0 4 2 0 4 1 5 2 1 5 2
J - Air
Movement
Accessory
Inches Inches Inches Inches
A - Adapter A - Aluminum
G - Galvanized FRACTIONAL FRACTIONAL FRACTIONAL FRACTIONAL
SIZE SIZE SIZE SIZE
0 - 0’’ 0 - 0’’ 0 - 0’’ 0 - 0’’
1 - 1/8” 1 - 1/8” 1 - 1/8” 1 - 1/8”
2 - 1/4” 2 - 1/4” 2 - 1/4” 2 - 1/4”
3 - 3/8” 3 - 3/8” 3 - 3/8” 3 - 3/8”
4 - 1/2” 4 - 1/2” 4 - 1/2” 4 - 1/2”
5 - 5/8” 5 - 5/8” 5 - 5/8” 5 - 5/8”
6 - 3/4” 6 - 3/4” 6 - 3/4” 6 - 3/4”
7 - 7/8” 7 - 7/8” 7 - 7/8” 7 - 7/8”
Electrical Accessories
Design Design
Model Series Model Series
1 2 3 4 1 2 3 4
J X U A J T C A
J - Air J - Air
Movement Movement
Accessory Accessory
X - Shipped T - Thermostat
Separately Shipped
Separately
Electrical Accessories
Design
Model Series
1 2 3 4 5
V X F A A
V - Ventilator
X - Accessory
Cent. Power Roof Vents
Model VNBL
The Carnes model VNBL is a belt drive, roof mounted supply air fan designed to provide filtered,
non-tempered air for a variety of applications.
• Available in sizes from 10” to 20” with CFM capabilities ranging from 1,000 to 13,000 and static pressures
up to 1.5 inches W. G.
• Double width, forward curved blowers are designed to maximize efficiency.
• Washable aluminum filters are standard to provide long operational life.
• All VNBL units are licensed to bear the AMCA seal to assure accurate performance specifications. Testing
is performed in an AMCA Accredited Laboratory.
• VNBL units incorporate the Carnes SLIDE-RITE design. This drastically reduces the amount of fasteners
required while resulting in an easy to maintain, durable, aesthetically superior design.
• The optional UL/cUL 705 listing insures that the units meet strict manufacturing and operational safety
guidelines.
TYPICAL SPECIFICATIONS
• All fans bear the AMCA certified ratings seal for sound and air performance.
CONSTRUCTION FEATURES
GALVANIZED MOTORS
ADJUSTABLE MOTOR PLATE DISCONNECT SWITCH
STEEL HOUSING Heavy-duty Ball Bearing
Pivots for Maintaining Proper Standard On All Units
Encloses Blower, Motor, Motors Matched To The
Belt Tension NEMA 1 Mounted
Drives and Filters Specified Fan Load
Model
VNBL Shown
TM
COMPUTERIZED FAN SELECTION: Make the right choice with Carnes FAN-C-LECT . The Model VNBL,
as well as the comprehensive offering of CARNES powered ventilators, are included in CARNES user
friendly fan selection program.
TYPICAL INSTALLATION
When using the VNBL for kitchen supply applications it is recommended that supply CFM be 80-90% of
exhaust CFM. This creates a light vacuum in the kitchen keeping odors out of the dining area.
Performance and sound certification is for installation type B - free inlet, ducted outlet.
Performance ratings (bhp) do not include transmission losses.
Performance ratings do not include the effects of accessories.
The sound ratings shown are loudness values in sones at 1.5 m (5 ft) in a hemispherical free field calculated per AMCA
International Standard 301. Values shown are for: installation type B: free inlet hemispherical sone levels.
AVOID SELECTING TO
THE LEFT OF THIS LINE.
2.0
850 RPM
1.5
700
Ps
1.0
500
0.5
300
0.0
0 1 2 3 4 5 6 7 8 9
CFM (THOUSANDS)
ACCESSORIES
AIR AIR
FLOW FLOW
Duct Adapter VXGA Curb Mtd. Damper VXHA Duct Mtd. Damper
(Requires 1-1/2” damper shelf) Shown with optional motor pack
Shown with optional motor pack
DIMENSIONS
OPTIONS
90° Intake
E
C
20 57-1/8 1-7/8
V N B L 1 0 P 2 A 1 N
V - Centrifugal
1
2 H - 1” Filters (Default)
LISTING
3 K - 2” Filters
N - Non-Listed (Default)
4 L - 1” Filters, 90 Deg. Intake
C - cULus
5 M - 2” Filters, 90 Deg. Intake
6
* - N/A
Electric Accessories
Design
Model Number Series
1 2 3 4
J X A A
J - Air Movement
Accessory
X - Shipped
Separately
A - Firestat
L - 2 Pole, 1 Ph, Disconnect (NEMA 1)
Disconnect
M - 3 Pole, 3 Ph, Disconnect (NEMA 1)
Switches
F - 2 Pole, 1 Ph, Disconnect (NEMA 3R)
H - 3 Pole, 3 Ph, Disconnect (NEMA 3R)
R - 1 or 3 Ph to 1 HP, for 2 Speed
2 Winding Motors
S - 1 Ph to 1/2 HP, for 2 Speed Hi - Low - Off
2 Winding Motors Switches
T - 3 Ph to 2 HP, for 2 Speed
2 Winding Motors
Curbs
Design Size
Model Number Series Type Width Length Height OPTION
Filtered Supply Vents
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
J C F A G 0 1 4 0 0 1 4 0 A 0
J - Air Movement
Common
Accessories
Inches Inches
C - Curb G - Galvanized
A - Aluminum FRACTIONAL FRACTIONAL D - Damper Shelf (1-1/2”)
SIZE SIZE L - Liner (Galv.)
0 - 00” 0 - 00” M - Liner (Alum.)
1 - 1/8” 1 - 1/8” R - Liner (Galv. w/Damper
F - Standard
2 - 1/4” 2 - 1/4” Shelf)
S - Sound
3 - 3/8” 3 - 3/8” S - Liner (Alum. w/Damper
N - Sound Curb
4 - 1/2” 4 - 1/2” Shelf)
w/Raise Cant
5 - 5/8” 5 - 5/8”
R - Raised Cant
6 - 3/4” 6 - 3/4”
E - Extended Base
7 - 7/8” 7 - 7/8”
H - Self Flashing
HEIGHT
A - 8”
C - 12”
D - 14”
E - 16”
Dampers
Design
Model Number Series Type Size Finish OPTIONS
1 2 3 4 5 6 7 8 9 10
V X G A
V - Centrifugal
Nominal Size
Inches Square
X - Accessory
20 - Mill Finish
(Standard)
PREVIOUS APPROVALS