Vous êtes sur la page 1sur 36

Instructions

95-8527
Protect•IR® Multispectrum IR Flame Detector
X3301

Detector Electronics Corporation


6901 West 110th Street • Minneapolis, Minnesota 55438 USA
9.1 Tel: 952.941.5665 or 800.765.3473 • Fax: 952.829.8750 4/07 95-8527
Table Of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Optical Integrity (Oi). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Data Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Integral Wiring Compartment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

General Application Information. . . . . . . . . . . . . . . . . . . . . . . 3


Response Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Important Application Considerations. . . . . . . . . . . . . . . . . . . . . . . . 3

important safety notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Detector Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Detector Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Protection Against Moisture Damage. . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Setting Device Network Addresses (EQP Model Only) . . . . . . . . . . 12

Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Fire Alarm Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Oi Plate Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Periodic Checkout Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Device Repair And Return. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Ordering Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Appendix A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
INSTRUCTIONS

Protect•IR®
Multispectrum IR Flame Detector
X3301

Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.

ATTENTION
The X3301 includes the Automatic Optical Integrity
(oi) feature — a calibrated performance test that
is automatically performed once per minute to
verify complete detector operation capabilities. No
testing with an external test lamp is required.

A multi-color LED on the detector faceplate indicates


DESCRIPTION detector status condition.

The X3301 Protect•IR® is a multispectrum infrared (IR) Microprocessor controlled heated optics increase
flame detector. It provides unsurpassed detection of resistance to moisture and ice.
fires from light to heavy hydrocarbon fuels combined
with the highest degree of false alarm rejection. The
detector has Division and Zone explosion-proof The X3301 housing is available in copper-free
ratings and is suitable for use in indoor and outdoor aluminum or stainless steel, with NEMA 4X and IP66
applications. rating.

The X3301 contains three IR sensors with their Outputs


associated signal processing circuitry. The standard
output configuration includes fire, fault and auxiliary Relays
relays. Output options include: The standard detector is furnished with fire, fault and
– 4 to 20 mA output (in addition to the three relays) auxiliary relays. All three relays are rated 5 amperes
at 30 VDC.
– Pulse output for compatibility with existing controller
based systems (with fire and fault relays) The Fire Alarm relay has redundant terminals and
– Eagle Quantum Premier (EQP) compatible model (no normally open / normally closed contacts, normally
analog or relay outputs). de-energized operation, and latching or non-latching
operation.
* o i is Detector Electronics' Trademark for its patented Optical
Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent The Fault relay has redundant terminals and normally
1,534,969, Canada Patent 1,059,598. open contacts, normally energized operation, and
X3301 technology advancements are covered under the following
U.S. Patents: 5,995,008, 5,804,825 and 5,850,182. latching or non-latching operation.

9.1 ©Detector Electronics Corporation 2007 4/07 95-8527


The Auxiliary relay has normally open / normally LED
closed contacts, and is configurable for energized or
A tricolor LED on the detector faceplate indicates
de-energized operation, and latching or non-latching
normal, fire alarm and fault conditions. Table 2 indicates
operation.
the condition of the LED for each status.

4 to 20 mA Output OPTICAL INTEGRITY (oi)


A 4 to 20 mA output is available as an option (in Automatic oi
addition to the three relays). This option provides a 4 to
The X3301 includes the Automatic Optical Integrity
20 mA dc current output for transmitting detector status
(oi) feature — a calibrated performance test that is
information to other devices. The circuit can be wired in
automatically performed once per minute to verify
either an isolated or non-isolated configuration and can
complete detector operation capabilities. No testing
drive a maximum loop resistance of 500 ohms from 18 to
with an external test lamp is required. The detector
19.9 volts dc and 600 ohms from 20 to 32 volts dc. Table
automatically performs the same test that a maintenance
1 indicates the detector status conditions represented
person with a test lamp would perform — once every
by the various current levels. The output is calibrated at
minute, 60 times per hour. However, a successful
the factory, with no need for field calibration.
automatic oi test does not produce an alarm condition.
NOTE
The Protect•IR signals a fault condition when less than
The output of the 4 to 20 mA current loop is not
half of the detection range remains. This is indicated
monitored by the fault detection circuitry of the
by the Fault relay and is evident by the amber color
X3301. Therefore, an open circuit on the loop will
of the LED on the face of the detector. See the
not cause the fault relay to change state or the
"Troubleshooting" section for further information.
detector status LED to indicate a fault. The status
of the LED always follows the status of the relays.
Magnetic oi / Manual oi
An alarm condition will normally over-ride a fault The detector also incorporates both magnetic oi and
condition, unless the nature of the fault condition manual oi features that provide the same calibrated
impairs the ability of the detector to generate or test as the automatic oi, and in addition actuates the
maintain an alarm output, i.e. loss of operating power. Alarm relay to verify output operation for preventive
maintenance requirements. These features can be
performed at any time and eliminate the need for testing
LON/SLC Output
with a non-calibrated external test lamp.
Table 1—Detector Status Conditions Indicated by Current Level

Current Level (±0.3 mA) Detector Status


CAUTION
These tests require disabling of all extinguishing
0 mA Power Fault
1 mA General Fault
devices to avoid release resulting from a successful
2 mA Oi Fault test.
3 mA Hi Background IR
4 mA Normal Operation
20 mA Fire Alarm
Table 2—Detector Status Indicator

Detector Status LED Indicator


The EQP model is designed for use exclusively with
Power On/Normal Operation Green
the Det-Tronics Eagle Quantum Premier system. The (no fault or fire alarm)
detector communicates with the system controller over
Fault Amber
a digital communication network or LON/SLC (Local
Operating Network / Signalling Line Circuit). The LON/ Fire (Alarm) Red
SLC is a fault tolerant, two wire digital communication
Low Sensitivity One Amber Flash
network arranged in a loop configuration. Analog and During Power-up
relay outputs are not available on this model.
Medium Sensitivity Two Amber Flashes
During Power-up

Very High Sensitivity Four Amber Flashes


During Power-up

9.1  95-8527
The magnetic oi test is performed by placing a magnet General APPLICATION
by the marked location (mag o i ) on the outside of INformation
the detector. The manual oi test is accomplished by
connecting the oi lead (terminal 22) to power supply
Response Characteristics
minus via an external switch. The magnet or switch
must be held in place for a minimum of 6 seconds to Response is dependent on distance, type of fuel,
complete the test. Either of these test methods activates temperature of the fuel, and time required for the fire to
the calibrated IR emitters. If the resulting signal meets come to equilibrium. As with all fire tests, results must
the test criteria, indicating that greater than half of the be interpreted according to an individual application.
detection range remains, the Alarm relay changes state, See Appendix A for fire test results.
the indicating LED changes to red, and the 4-20 mA
current output goes to 20 mA. This condition remains
Important Application Considerations
until the magnet is removed or the switch is released,
regardless of whether the relays are set for latching or In applying any type of sensing device as a fire detector,
non-latching operation. it is important to know of any conditions that can prevent
the device from responding to fire, and also to know
If less than half of the detection range remains, no what other sources besides fire can cause the device to
alarm is produced and a fault is generated. The fault respond.
indication can be reset by momentarily applying the
magnet or manual oi switch.
Welding
NOTE Arc welding should not be performed within 40 feet of
Refer to Appendix A for FM verification of Det- the very high sensitivity detector, 10 feet of the medium
Tronics’ patented Optical Integrity oi™ function. sensitivity detector, or 5 feet of the low sensitivity
detector. It is recommended that the system be
bypassed during welding operations in situations where
communication
the possibility of a false alarm cannot be tolerated.
The X3301 is furnished with an RS-485 interface for Gas welding mandates system bypass, since the gas
communicating status and other information with torch is an actual fire. Arc welding rods can contain
external devices. The RS-485 supports MODBUS organic binder materials in the flux that burn during the
protocol, with the detector configured as a slave device. welding operation and are detectable by the X3301.
Welding rods with clay binders do not burn and will not
NOTE be detected by the X3301. However, system bypass is
The EQP model uses LON/SLC communication. always recommended, since the material being welded
RS-485 communication is not available on the EQP may be contaminated with organic substances (paint,
model. oil, etc.) that will burn and possibly trigger the X3301.

data logging Artificial Lighting


Data logging capability is also provided. Status The X3301 should not be located within 3 feet of artificial
conditions such as normal, power down, general and lights. Excess heating of the detector could occur due
oi faults, pre-alarm, fire alarm, time and temperature are to heat radiating from the lights.
recorded. Each event is time and date stamped, along
with the temperature and input voltage. Event data is
EMI/RFI Interference
stored in non-volatile memory when the event becomes
active, and again when the status changes. Data is The X3301 is resistant to interference by EMI and RFI,
accessible using the RS-485 port or the EQP controller. and is EMC Directive compliant. It will not respond to a
5 watt walkie-talkie at distances greater than 1 foot. Do
not operate a walkie-talkie within 1 foot of the X3301.
integral wiring compartment
All external wiring to the device is connected within the
Non-Carbon Fires
integral junction box. The screw terminals accept wiring
from 14 to 24 AWG. The detector is furnished with The X3301 is a multiple spectrum IR device with
four conduit entries, with either 3/4 inch NPT or 25 mm detection limited to carbonaceous fuels. It should not
threads. be used to detect fires from fuels that do not contain
carbon, such as hydrogen, sulfur and burning metals.

9.1 3 95-8527
IMportant safety notes • The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain. See
Warning Figure 1. The detector should be positioned so
Do not open the detector assembly in a hazardous that its field of view does not cover areas outside
area when power is applied. The detector contains the hazardous area. This will minimize the possibility
limited serviceable components and should never of false alarms caused by activities outside the area
be opened. Doing so could disturb critical optical requiring protection.
alignment and calibration parameters, possibly
causing serious damage. This type of damage • For best performance, the detector should be
could be undetected and could result in failure to mounted on a rigid surface in a low vibration area.
see a fire and/or false alarm.
• Dense fog, rain or ice can absorb IR radiation and
reduce the sensitivity of the detector.
Caution
The wiring procedures in this manual are intended • Although IR detectors are less affected by smoke
to ensure proper functioning of the device under than other detectors, the X3301 should not be placed
normal conditions. However, because of the where rising combustion products can obscure its
many variations in wiring codes and regulations, vision. If smoke is expected before fire, smoke or
total compliance to these ordinances cannot be other alternative detectors should be used in
guaranteed. Be certain that all wiring complies conjunction with the X3301. For indoor applications, if
with the NEC as well as all local ordinances. If dense smoke is expected to accumulate at the onset
in doubt, consult the authority having jurisdiction
of a fire, mount the detector on a side wall at least
before wiring the system. Installation must be
a few feet (approximately 1 meter) down from the
done by a properly trained person.
ceiling.
Caution • If possible, fire tests should be conducted to verify
To prevent unwanted actuation or alarm, correct detector positioning and coverage.
extinguishing devices must be disabled prior to
performing system tests or maintenance.

Attention
Remove the protective cap from the front of the
detector before activating the system.

Attention
Observe precautions for handling electrostatic
sensitive devices.
CENtER AXIs
OF DEtECtOR
FIELD OF VIEw

INSTALLATION

Detector Positioning INCORRECt

Detectors should be positioned to provide the best


unobstructed view of the area to be protected.
The following factors should also be taken into
consideration:
• Identify all high risk fire ignition sources. CENtER AXIs
OF DEtECtOR
FIELD OF VIEw
• Be sure that enough detectors are used to adequately
cover the hazardous area.
B1974

• Be sure that the unit is easily accessible for cleaning CORRECt

and other periodic servicing. NOtE: DEtECtOR Must ALwAYs BE AIMED


DOwNwARD At LEAst 10 tO 20 DEGREEs.
• Locate and position the detector so that the
fire hazard(s) are within both the field of view and
detection range of the device. Refer to Appendix A Figure 1—Detector Orientation Relative to Horizon
for specific information.

9.1  95-8527
Conduit raceways should be inclined so that water will
Oi PLATE
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
PLACE MAGNET install conduit drains above the seals to prevent the
HERE TO INITIATE
MAGNETIC Oi
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
VIEWING WINDOW (3)

Conduit seals are not required for compliance with


Oi MAGNET
explosion-proof installation requirements, but are highly
DETECTOR
recommended to prevent water ingress in outdoor
E2068 STATUS INDICATOR applications. Units with M25 thread must use an IP66
washer to prevent water ingress.
Figure 2—Front View of the X3301
Wiring Procedure

Wire Size and Type


detector Orientation The system should be wired according to local codes.
The wire size selected should be based on the number
Refer to Figure 2 and ensure that the oi plate will be
of detectors connected, the supply voltage and the
oriented as shown when the X3301 is mounted and
cable length. Typically 14 AWG (2.08 mm2) or 16 AWG
sighted. This will ensure proper operation of the oi
(1.31 mm2) shielded cable is recommended. Wires
system and will also minimize the accumulation of
should be stripped 3/8 inch (9 mm). A minimum input
moisture and contaminants between the oi plate and
voltage of 18 vdc must be present at the X3301.
the viewing windows. The oi plate includes an arrow,
which should be pointed in the up direction, indicating
note
that the oi plate and detector are correctly oriented.
Refer to “Power Consumption” in the
“Specifications” section of this manual.
IMPORTANT
The oi plate must be securely tightened to ensure
The use of shielded cable is required to protect against
proper operation of the oi system (40 oz./inches
interference caused by EMI and RFI. When using
recommended).
cables with shields, terminate the shields as shown in
Figures 7 through 12, and Figure 14. Consult the factory
Protection Against Moisture Damage if not using shielded cable.
It is important to take proper precautions during
In applications where the wiring cable is installed in
installation to ensure that moisture will not come in
conduit, the conduit must not be used for wiring to other
contact with the electrical connections or components
electrical equipment.
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
If disconnection of power is required, separate
operation and is the responsibility of the installer.
disconnect capability must be provided.
If conduit is used, drains must be installed at water
CAUTION
collection points to automatically drain accumulated
Installation of the detector and wiring should be
moisture. Conduit breathers should be installed at
performed only by qualified personnel.
upper locations to provide ventilation and allow water
vapor to escape. At least one breather should be used
with each drain. Detector Mounting
Install the swivel mounting bracket assembly on the wall.
The installation surface should be free of vibration and
suitable to receive 1/4 inch (M6) screws with a length of
at least 1 inch (25 mm), and have sufficient capacity to
hold the detector and bracket weight. Refer to Figure 3
for dimensions.

9.1  95-8527
Relay and 4-20 mA Output Models EOL Resistors (Not Used with EQP Model)
Follow the instructions below to install the X3301. To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
1. Make field connections following local ordinances by EOL resistors, observe the following guidelines when
and guidelines in this manual. installing the resistors.
– Figure 4 shows the wiring terminal strip located
1. Required EOL resistor power rating must be 5 watts
inside the detector’s integral junction box.
minimum.
– Figure 5 shows the wiring terminal identification
for the X3301 detector. note
EOL resistors must be ceramic, wirewound
– Figure 6 shows an EOL resistor installed within
type, rated 5 watts minimum, with actual power
the integral wiring compartment of the detector
dissipation not to exceed 2.5 watts.
(refer to “EOL Resistors” for details).
– Figures 7 and 8 provide examples of typical 2. Resistor leads should be cut to a length of
installations with a X3301 wired to a fire alarm approximately 1 1/2 inches (40 mm).
panel.
3. Bend the leads and install the EOL resistor as
– If the detector is equipped with a 4 to 20 mA
shown in Figure 6.
output, refer to Figures 9 through 12.
4. Maintain a 3/8 inch (10 mm) minimum gap between
2. Check all field wiring to be sure that the proper
the resistor body and the terminal block or any other
connections have been made.
neighboring parts.
Important
NOTE
Do not test any wiring connected to the detector
All cable entry devices and blanking elements shall
with a meg-ohmmeter. Disconnect wiring at
be certified to “E-generation” or “ATEX” standards,
the detector before checking system wiring for
in type of explosion protection increased safety
continuity.
“e” or flameproof enclosure “d” (as applicable),
suitable for the conditions of use and correctly
3. Make the final sighting adjustments and ensure that
installed. They shall maintain the degree of
the mounting bracket hardware is tight.
ingress protection IP66 for the apparatus. Unused
apertures shall be closed with suitable blanking
elements.

4.0
(10.2)
4X ø0.42 3.0 12.9
(1.1) (7.6) (32.7)

3.0
(7.6)
4.0
(10.2)

10.3
(26.2)

C2069

Figure 3—Q9033B Mounting Bracket Dimensions in Inches (cm)


(See Figure 1 for Correct Detector Orientation.)

9.1  95-8527
Figure 4—X3301 Terminal Block

9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

7 COM FIRE 17 COM FIRE COM AUX 27

6 N.O. FIRE 16 N.O. FIRE N.O. AUX 26

5 N.C. FIRE 15 N.C. FIRE N.C. AUX 25

4 COM FAULT 14 COM FAULT RS-485 A 24

3 N.O. FAULT 13 N.O. FAULT RS-485 B 23

2 24 VDC + 12 24 VDC + MAN Oi 22

1 24 VDC – 11 24 VDC – 24 VDC – 21


B2061

Figure 5—X3301 Wiring Terminal Identification

3/8 INCh (10 MM) GAp MINIMuM

19 18 17 16 15 14 13 12 11

BuLkhEAD

A2126

Figure 6—EOL Resistor Installation

9.1  95-8527
X3301 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

7 COM FIRE2 COM FIRE 17 COM AUX 27

6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26


E.O.L.
DEVICE4
5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25
ALARM
4 COM FAULT1 COM FAULT 14 RS-485 A 24

3 N.O. FAULT1 N.O. FAULT 13 RS-485 B 23


+
2 24 VDC + 12 24 VDC + MAN Oi 22
24 VDC

1 24 VDC – 11 24 VDC – 24 VDC – 21

oi TEST 3

B2107 WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.

Figure 7—EEx d Wiring Option

X3301 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

EOL ALARM 7 COM FIRE2 COM FIRE 17 COM AUX 27


DEVICE 4

ALARM 6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26

5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25

4 COM FAULT1 COM FAULT 14 RS-485 A 24

3 N.O. FAULT1 13 N.O. FAULT RS-485 B 23


+
2 24 VDC + 12 24 VDC + MAN Oi 22
24 VDC

1 24 VDC – 11 24 VDC – 24 VDC – 21

oi TEST 3

B2109 WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 EOL RESISTOR SUPPLIED BY PANEL.

Figure 8—EEx e Wiring Option

9.1  95-8527
X3301 IR DETECTOR X3301 IR DETECTOR
PLC PLC

600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29


AT 24 VDC AT 24 VDC
+ 8 4-20 mA + REF 18 28 + 8 18 4-20 mA – REF 28

– 7 17 27 – 7 17 27

4 TO 20 mA 6 16 26 4 TO 20 mA 6 16 26

5 15 25 + 5 15 25
+
24 VDC 24 VDC
4 14 24 4 14 24
– –

3 13 23 3 13 23

24 VDC + MAN Oi 2 24 VDC + 12 MAN Oi 22


2 12 22
C2064
C2063
1 24 VDC – 11 21 1 24 VDC – 11 21

Oi TEST1 Oi TEST1

Figure 9—X3301 Detector Wired for Non-Isolated 4 to 20 mA Figure 10—X3301 Detector Wired for Non-Isolated 4 to 20 mA
Current Output (Sourcing) Current Output (Sinking)

24 VDC 24 VDC
X3301 IR DETECTOR
– + + – X3301 IR DETECTOR
PLC PLC

600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29


AT 24 VDC AT 24 VDC
+ 8 18 28 + 8 18 28

– 7 17 27 – 7 17 27

4 TO 20 mA 6 16 26 4 TO 20 mA 6 16 26

+ 5 15 25 5 15 25
+
24 VDC 24 VDC
4 14 24 4 14 24
– –
3 13 23 3 13 23

2 24 VDC + 12 MAN Oi 22 2 24 VDC + 12 MAN Oi 22


C2065 C2066
1 24 VDC – 11 21 1 24 VDC – 11 21

Oi TEST1 Oi TEST1

Figure 11—X3301 Detector Wired for Isolated 4 to 20 mA Figure 12—X3301 Detector Wired for Isolated 4 to 20 mA
Current Output (Sourcing) Current Output (Sinking)

NOTES: 1. INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE


INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.

9.1  95-8527
EQP Model 5. Check all field wiring to be sure that the proper
connections have been made.
1. Connect external wires to the appropriate
terminals inside the device junction box. (See
6. Replace the device cover.
Figure 13 for terminal identification.)
7. Make the final sighting adjustments and ensure that
2. Connect the shield of the power cable to “earth
the mounting bracket hardware is tight.
ground” at the power source.
NOTE
3. Connect shields for the LON cable as indicated.
Refer to the Eagle Quantum Premier system
See Figure 14.
manual (number 95-8533) for information
regarding power and network communication
NOTE
cable requirements.
DO NOT ground any shields at the detector
housing.

4. Set the device network address. (See “Setting


Device Network Addresses” section of this manual
for switch setting procedure.)

COM SHIELD 6 16 COM SHIELD

COM 1 A 5 15 COM 2 A

COM 1 B 4 14 COM 2 B

POWER SHIELD 3 13 POWER SHIELD

24 VDC + 2 12 24 VDC +

24 VDC – 1 11 24 VDC –
A2089

Figure 13—Wiring Terminal Identification for X3301 EQP Model

9.1 10 95-8527
9.1
+ +
– –
– POWER –
+ DISTRIBUTION +
+

+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX3301 EQPX3301 EQPX3301 EQPX3301
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3

4 24 VDC – 2 5 24 VDC – 2 6 24 VDC – 7 11 24 VDC – 1 11 24 VDC – 1 11 24 VDC – 1 11 24 VDC – 1

3 24 VDC + 1 4 24 VDC + 1 5 24 VDC + 8 12 24 VDC + 2 12 24 VDC + 2 12 24 VDC + 2 12 24 VDC + 2


P7 P2
COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1

51 SHIELD 48 6 SHIELD 3 12 SHIELD 1 16 SHIELD 6 16 SHIELD 6 16 SHIELD 6 16 SHIELD 6

52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4

53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2207
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –

CH 1

CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3

11
59 TxD A 56 A + SUPPLY A
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE

CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B

CH 3

CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+ 8+ 19

DIGITAL INPUTS
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B

CH 4

CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34

RELAY 5
RELAY 1
23 NC NC 35

24 C C 36
25 NO NO 37

RELAY 6
RELAY 2
26 NC NC 38

27 C C 39
28 NO NO 40

RELAY 7
RELAY 3
29 NC NC 41

30 C C 42
31 NO NO 43

RELAY 4

RELAY 8
32 NC NC 44

95-8527
Figure 14—A Typical EQP System
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING

A2191

Figure 15—Location of Address Switches

Setting Device network addresses disassembly of the device. Always observe


(EQP Model Only) precautions for handling electrostatic sensitive
devices.
Overview of Network Addresses
The address number is binary encoded with each
Each device on the LON must be assigned a unique
switch having a specific binary value with switch 1
address. Addresses 1 to 4 are reserved for the
being the LSB (Least Significant Bit). (See Figure 16)
controller. Valid addresses for field devices are from
The device’s LON address is equal to the added value
5 to 250.
of all closed rocker switches. All “Open” switches are
ignored.
IMPORTANT
If the address is set to zero or an address above
Example: for node No. 5, close rocker switches 1
250, the switch setting will be ignored.
and 3 (binary values 1 + 4); for node No. 25, close
rocker switches 1, 4 and 5 (binary values 1 + 8 + 16).
Duplicated addresses are not automatically detected.
Modules given the same address will use the number
Note
given and report to the controller using that address.
The field device sets the LON address only when
The status word will show the latest update, which
power is applied to the device. Therefore, it is
could be from any of the reporting modules using that
important to set the switches before applying
address.
power. If an address is ever changed, system
power must be cycled before the new address
Setting Field Device Addresses will take effect.
Selection of the node address is done by setting
After setting address switches, record the address
rocker switches on an 8 switch “DIP Switch Assembly”
number and device type.
within the detector’s housing. Refer to Figure 15 for
switch location.
ON
WARNING
The network address switches are located 1 2 3 4 5 6 7 8

within the detector housing. Disassembly of the BINARY


VALuE 1 2 4 8 16 32 64 128
detector head that contains powered electrical
circuits is required to gain access to the network NODE ADDREss EQuALs thE ADDED VALuE OpEN = OFF
address switches. For hazardous areas, the OF ALL CLOsED ROCkER swItChEs CLOsED = ON
A2190
area must be de-classified before attempting
Figure 16—Address Switches for X3301

9.1 12 95-8527
STARTUP PROCEDURE Table 3—Current Level Output Troubleshooting Guide

Current Level Status Action


When installation of the equipment is complete, perform
(±0.3 mA)
the “Fire Alarm Test” below.
0 mA Power Fault Check system
wiring.
Allow 20 to 30 minutes for the detector’s heated optics
1 mA General Fault Cycle power.1
to reach equilibrium.
2 mA Oi Fault Clean windows.2
3 mA Hi Background IR Remove IR source or
Fire Alarm Test aim detector away
from IR source.
1. Disable any extinguishing equipment that is 4 mA Normal Operation
connected to the system. 20 mA Fire Alarm
1If fault continues, return device to factory for repair.
2. Apply input power to the system. 2See “Maintenance” section for cleaning procedure.

3. Initiate an oi test. (See “Magnetic oi / Manual oi”


under Optical Integrity in the Description section of
this manual.
3. Check input power to the unit.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting” 4. If the fire system has a logging function, check the
section. fire panel log for output status information. See
Table 3 for information regarding 4 to 20 mA output.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Det-Tronics 5. Turn off the input power to the detector and check
Q1201C Laser Aimer is recommended for this all wiring for continuity. Important: Disconnect
purpose.) wiring at the detector before checking system
wiring for continuity.
6. Enable extinguishing equipment when the test is
complete. 6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background IR radiation by covering
TROUBLESHOOTING the detector with the factory supplied cover or
aluminum foil. If the fault condition clears within 6
Warning minutes or less, extreme background IR is present.
The sensor module (“front” half of the detector) Re-adjust the view of the detector away from the IR
contains no user serviceable components source or relocate the detector.
and should never be opened. The terminal
compartment is the only part of the enclosure If none of these actions corrects the problem, return the
that should be opened by the user in the field. detector to the factory for repair.

1. Disable any extinguishing equipment that is NOTE


connected to the unit. It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
2. Inspect the viewing windows for contamination continuous protection.
and clean as necessary. The detector is relatively
insensitive to airborne contaminants, however, thick
deposits of ice, dirt, or oil will reduce sensitivity.
(Refer to the “Maintenance” section for complete
information regarding cleaning of the detector
viewing windows.)

9.1 13 95-8527
MAINTENANCE LOOsEN twO CAptIVE sCREws

IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of
the flamepaths.
GRAsp VIsOR AND
Warning REMOVE Oi pLAtE
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal A2106

compartment is the only part of the enclosure


that should be opened by the user in the field. Figure 17—Oi Plate Removal

To maintain maximum sensitivity and false alarm


resistance, the viewing windows of the X3301 must be
kept relatively clean. Refer to the procedure below for
oi plate Removal
cleaning instructions.
1. Disable any extinguishing equipment that is
connected to the unit.
Cleaning PROCEDURE
2. Loosen the two captive screws, then grasp the oi
CAUTION plate by the visor and remove it from the detector.
Disable any extinguishing equipment that is See Figure 17.
connected to the unit to prevent unwanted
actuation. 3. Thoroughly clean the oi plate reflective surfaces,
holding it by its edges to avoid leaving fingerprints
To clean the windows and oi plate, use Det-Tronics on the inside reflective surface.
window cleaner (part number 001680-001) and a soft
cloth, cotton swab or tissue and refer to the following 4. Re-install the oi plate. Ensure that the plate is
procedure. flat on the detector surface. Tighten the oi plate
screws securely (40 oz/inches).
1. Disable any extinguishing equipment that is
connected to the unit. NOTE
If the oi plate is removed, be sure to install the
2. Since the X3301 is less affected by contamination original oi plate. oi plates are not interchangeable
than other detectors, removal of the o i plate is and should not be mixed with o i plates from
needed only under extreme conditions. In addition, other detectors. If corrosive contaminants in
it is not necessary to achieve perfect cleanliness, the atmosphere cause the o i plate surface to
because IR is not significantly absorbed by slight deteriorate to the extent that it is no longer possible
films of oil and/or salt. If a fault condition is still to restore it to its original condition, it must be
indicated after cleaning, remove and clean the oi replaced. Consult factory for oi plate replacement
plate using the following procedure. procedure.

3. Clean all three viewing windows and reflector


surfaces thoroughly using a clean cloth, cotton
swab or tissue and Det-Tronics window cleaning
solution. If a stronger solution is needed, isopropyl
alcohol may be used.

9.1 14 95-8527
PERIODIC CHECKOUT PROCEDURE FEATURES
A checkout of the system using the manual or magnetic
• Long detection range to carbonaceous fires.
o i feature should be performed on a regularly
scheduled basis to ensure that the system is operating • Unequaled false alarm rejection.
properly. To test the system, perform the “Fire Alarm
• Responds to a fire in the presence of modulated
Test” as described in the “Startup Procedure” section of
blackbody radiation (i.e. heaters, ovens, turbines)
this manual.
without false alarm.
• Microprocessor controlled heated optics for increased
Clock Battery
resistance to moisture and ice.
(Not used with EQP Model)
• Automatic, manual or magnetic optical integrity (oi)
The real time clock has a backup battery that will
testing.
operate the clock with no external power for nominally
10 years. It is recommended that the battery be • Easily replaceable oi plate.
replaced every 7 years. Return the device to the factory
• Fire, fault and auxiliary relays standard.
for battery replacement.
• 4 to 20 mA isolated output (optional).
NOTE
• Eagle Quantum Premier LON/SLC output (optional).
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time • Tricolor LED indicates normal operation, fire and fault
stamping of the data log may be affected. conditions.
• Operates under adverse weather conditions and in
dirty environments.
• Mounting swivel allows easy sighting.
• Integral wiring compartment for ease of installation.
• Explosion-proof/flame-proof detector housing. Meets
FM, CSA, CENELEC (ATEX Directive Compliant) and
CE certification requirements.
• Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under 0.5
second (available when model selected).
• 5 year warranty.
• RFI and EMC Directive Compliant.

9.1 15 95-8527
SPECIFICATIONS CURRENT OUTPUT (Optional)—
4 to 20 milliampere (±0.3 mA) dc current, with a
OPERATING VOLTAGE— maximum loop resistance of 500 ohms from 18 to 19.9
24 volts dc nominal (18 vdc minimum, 32 vdc volts dc and 600 ohms from 20 to 32 volts dc.
maximum). Maximum ripple is 2 volts peak-to-peak.
LON Output—
POWER CONSUMPTION— Digital communication, transformer isolated (78.5 kbps).
Without heater: 4 watts at 24 vdc nominal;
5.2 watts at 24 vdc in alarm. TEMPERATURE RANGE—
4.5 watts at 32 vdc nominal; Operating: –40°F to +167°F (–40°C to +75°C).
6.5 watts at 32 vdc in alarm. Storage: –67°F to +185°F (–55°C to +85°C).
Heater only: 8 watts maximum. Hazardous location ratings from –55°C to +125°C.
Total power: 17 watts at 32 vdc with EOL resistor installed
and heater on maximum. HUMIDITY RANGE—
EOL resistor must be ceramic, wirewound type, rated 0 to 95% relative humidity, can withstand 100%
5 watts minimum, with actual power dissipation not to condensing humidity for short periods of time.
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8577. CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
POWER UP TIME— the highest sensitivity lying along the central axis.
Fault indication clears after 0.5 second; device is ready Unlike conventional detectors, the X3301 provides
to indicate an alarm condition after 30 seconds. full coverage at a minimum of 70% of the maximum
detection distance.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 vdc: Perfect cone of vision for methane fire detection — 100
The Fire Alarm relay has redundant terminals and feet on and off axis on “very high” setting.
normally open / normally closed contacts, normally
de-energized operation, and latching or non- Refer to Appendix A for FM Approved cone of vision
latching operation. data.

Fault relay, Form A, 5 amperes at 30 vdc: RESPONSE TIME—


The Fault relay has redundant terminals and Typical response times are under 10 seconds. Models
normally open contacts, normally energized are available that can respond to automotive paint
operation, and latching or non-latching operation. gun fires in under 0.5 seconds. See Appendix A and
“Automotive Addendum” (form number 95-8534) for
Auxiliary relay, Form C, 5 amperes at 30 vdc: actual response times.
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized DIMENSIONS—
operation, and latching or non-latching operation. See Figure 18.

4.7
(11.9)

10.0 4.8
(25.4) (12.2)
B2067

Figure 18—X3301 Dimensions in Inches (cm)

9.1 16 95-8527
ENCLOSURE MATERIAL— Conforms with: Low Voltage Directive (73/23/EEC).
Copper-free aluminum (red-painted) or 316 stainless Electromagnetic Compatibility Directive
steel. (89/336/EEC).
Explosive Atmosphere Directive
Vibration— (94/9/EC).
Conformance per FM 3260: 2000, MIL-STD 810C (Curve Construction Product Directive
AW), DNV Note 2.4 (Class B). (89/106/EEC).

WIRING— VdS Performance verified per EN54-10,


14 AWG (2.08 mm2) or 16 AWG (1.31 mm2) shielded Certificate G-202136.
cable is recommended.
Important: 18 vdc minimum must be available at the DNV Type Approval Certificate Number A-8837.
detector. For ambient temperatures below –10°C and
above +60°C use field wiring suitable for both minimum IECEx Certificate of Conformity
and maximum ambient temperature. IECEx ULD 06.0017X
Ex d IIC T6 or Ex de IIC T6
Thread SIZE— T6 (Tamb = –55°C to +60°C).
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required. NOTE
Operational performance verified from –40°C to
SHIPPING WEIGHT (Approximate)— +75°C.
Aluminum: 6 pounds (2.7 kilograms).
Stainless Steel: 10 pounds (4.5 kilograms). note
Swivel Mount: 14 pounds (6.4 kilograms). An optional third party addressable module can
only be used within the EEx d flameproof model
WARRANTY PERIOD— unless the addressable module is component
5 years. certified as EEx e for use within the EEx de
increased safety model.
CERTIFICATION—
For complete FM certification details, refer to Appendix A. NOTE
Refer to “EOL Resistors” section for installation
Class I, Div. 1, Groups B, C and D;
FM ® details. All cable entry devices and blanking
Class II, Div. 1, Groups E, F, and G;
AppROVED
elements shall be certified to “E-generation” or
Class I, Div. 2, Groups A, B, C and D (T3C);
“ATEX” standards, in type of explosion protection
FM ®
Class II, Div. 2, Groups F and G (T3C);
increased safety “e” or flameproof enclosure “d”
Class III.
AppROVED

(as applicable), suitable for the conditions of use


Enclosure NEMA/Type 4X.
and correctly installed. They shall maintain the
(ULC Listed for models with relay outputs degree of ingress protection IP66 for the apparatus.
and HART model.) Unused apertures shall be closed with suitable
blanking elements.
Increased Safety Model
0539 II 2 GD
FM
AppROVED
®

®
EEx de IIC T5–T6 replacement parts
DEMKO 01 ATEX 130204
D

T6 (Tamb = –55°C to +60°C). The detector is not designed to be repaired in the field.
T5 (Tamb = –55°C to +75°C). If a problem should develop, refer to the Troubleshooting
IP66. section. If it is determined that the problem is caused
by an electronic defect, the device must be returned to
Flameproof Model
the factory for repair.
0539 II 2 GD
FM
AppROVED
®

EEx d IIC T4–T6


DEMKO 01 ATEX 130204
T6 (Tamb = –55°C to +60°C).
T5 (Tamb = –55°C to +75°C).
T4 (Tamb = –55°C to +125°C).
IP66.

9.1 17 95-8527
DEVICE REPAIR AND RETURN ORDERING INFORMATION
Prior to returning devices, contact the nearest local When ordering, please specify:
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A X3301 IR Flame Detector
written statement describing the malfunction must
accompany the returned device or component to Refer to the X3301 OS Matrix for details.
assist and expedite finding the root cause of the
failure.
accessories
Pack the unit properly. Always use sufficient packing Q9033B Swivel Mount Assembly is required for
material. Where applicable, use an antistatic bag as mounting the detector.
protection from electrostatic discharge. Q1116A Air Shield for use in dirty environments.

note Q1201C Laser Aimer is recommended for verifying


Inadequate packaging that ultimately causes detector aiming.
damage to the returned device during shipment Q2000 Weather Shield is available for outdoor
will result in a service charge to repair the damage environments.
incurred during shipment.

Return all equipment transportation prepaid to the Replacement Parts


factory in Minneapolis.
Part Number Description
NOTE 001680-001 Window cleaner squeeze bottle
It is highly recommended that a complete spare (package of six bottles)
be kept on hand for field replacement to ensure 005003-001 Silicone-free grease
continuous protection.

X3301 OS Matrix
MODEL DESCRIPTION
X3301 Multispectrum IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 Port, Metric M25
4N 4 ort, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 4-20 mA
14 Eagle Quantum Premier
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)
21 Relay–Automotive
23 Relay, 4-20 mA and HART
TYPE APPROVAL AGENCY
T SIL Certification
W FM/CSA/ULC*/CENELEC/CE
TYPE CLASSIFICATION**
1 Division/Zone Ex de
2 Division/Zone Ex d

*The LON output (Type 14) is not part of the ULC approval.
**Detectors are always Class I, Div. 1.

9.1 18 95-8527
APPENDIX A
FM Approvals Description and Performance Report

THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:

• Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Explosion-proof for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
• Explosion-proof for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).

The following performance criteria were verified:

OPTICAL INTEGRITY TEST:


The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a
calibrated Automatic Optical Integrity (oi) test for each sensor. Upon removal of the contamination, the detector fault
was cleared and the detector was verified to detect a fire.

The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.

9.1 19 95-8527
FM Approvals Description and Performance Report – Continued

RESPONSE CHARACTERISTICS:

Very High Sensitivity


Fuel Size Distance Average Response Time
feet (m) (seconds)***

n-Heptane 1 x 1 foot 210 (64)* 11


n-Heptane** 1 x 1 foot 210 (64)* 6
n-Heptane 1 x 1 foot 100 (30.5) 3
n-Heptane 6 in. x 6 in. 80 (24.4) 3
Isopropanol 6 in. x 6 in. 70 (21.3) 4
Diesel** 1 x 1 foot 150 (45.7)* 14
Methanol 6 in. x 6 in. 40 (12.2) 3
Methanol 1 x 1 foot 150 (45.7)* 18
Methanol** 1 x 1 foot 150 (45.7)* 7
Methane 30 inch plume 100 (30.5) 3
JP-5** 1x1 foot 150 (45.7)* 2
JP-5** 2 x 2 foot 210 (64)* 4
JP-5** 2 x 2 foot 100 (30.5) 2
Office 19” x 19” x 8” 100 (30.5) 4
Paper 0.5 lb.
Corrugated 18” x 36” 100 (30.5) 8
Panel

* Outdoor test condition.


** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.

Medium Sensitivity
Fuel Size Distance Average Response Time
feet (m) (seconds)***

n-Heptane 1 x 1 foot 100 (30.5) 12


n-Heptane 1 x 1 foot 50 (15.2) 2
Diesel** 1 x 1 foot 70 (21.3) 4
Methanol 1 x 1 foot 70 (21.3) 10
Methane 30 inch plume 65 (19.8) 3
Methane 30 inch plume 55 (16.8) 2
JP-5** 2 x 2 foot 100 (30.5) 3

Office 19” x 19” x 8” 50 (15.2) 6


Paper 0.5 lb.

Corrugated 18” x 36” 50 (15.2) 2


Panel

** Pre-burn from ignition.


*** Add 2 seconds for EQP Model.

9.1 20 95-8527
FM Approvals Description and Performance Report – Continued

Low Sensitivity
Fuel Size Distance Average Response Time
feet (m) (seconds)***

n-Heptane 1 x 1 foot 50 (15.2) 10


Methanol 1 x 1 foot 20 (6.1) 10
Methane 32 inch plume 15 (4.6) 9

*** Add 2 seconds for EQP Model.

RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES:

Very High Sensitivity

False Alarm Source Distance Fire Source Distance Average Response Time
feet (m) feet (m) (seconds)***

Sunlight, direct, modulated, reflected — 6-inch propane 6 (1.8) < 10


Vibration N/A 3-inch propane 10.5 (3.2) < 10
Radio frequency interference 1 (0.3) 3-inch propane 12 (3.7) < 10
Arc welding, #7014 40 (12.2) 1 x 1 foot n-Heptane 40 (12.2) 4
6 kw heater, modulated 80 (24.4) 1 x 1 foot n-Heptane 80 (24.4) 2
6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4) 3
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 2
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 7
500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4) 2
500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4) 3
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4) 5
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 3

*** Add 2 seconds for EQP Model.

9.1 21 95-8527
FM Approvals Description and Performance Report – Continued

Medium Sensitivity

False Alarm Source Distance Fire Source Distance Average Response Time
feet (m) feet (m) (seconds)***

Sunlight, direct, modulated, reflected — 6-inch propane 6 (1.8) <4


Vibration* N/A N/A N/A N/A
Radio frequency interference 1 (0.3) 6-inch propane 6 (1.8) <1
Arc welding, #7014 10 (3) 1 x 1 foot n-Heptane 40 (12.2) 4
6 kw heater, modulated 60 (18.3) 1 x 1 foot n-Heptane 60 (18.3) 2
6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 2
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1
500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1
500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 6
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 2

* Fire was verified with very high sensitivity only.


*** Add 2 seconds for EQP Model.

Low Sensitivity

False Alarm Source Distance Fire Source Distance Average Response Time
feet (m) feet (m) (seconds)***

Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) <13


Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) <14
Arc welding, steady, #7014 5 (1.5) 1 x 1 foot n-Heptane 50 (15.2) 11
Arc welding, modulated, #7014 5 (1.5) 1 x 1 foot n-Heptane 30 (9.1) 10
70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 16
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18
500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12
500 w shielded quartz halogen lamp, modulated 10 (3) 1 x 1 foot n-Heptane 50 (15.2) 11
1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 30 (9.1) 11
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 14

* Outdoor test conditions.


*** Add 2 seconds for EQP Model.

9.1 22 95-8527
FM Approvals Description and Performance Report – Continued

FALSE ALARM IMMUNITY:

Very High Sensitivity

False Alarm Source Distance Modulated Response Unmodulated Response


feet (m)

Sunlight, direct, reflected — No alarm No alarm


Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 40 (12.2) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 8 (2.4) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm

Medium Sensitivity

False Alarm Source Distance Modulated Response Unmodulated Response


feet (m)

Sunlight, direct, reflected — No alarm No alarm


Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 10 (3) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm

9.1 23 95-8527
FM Approvals Description and Performance Report – Continued

Low Sensitivity

False Alarm Source Distance Modulated Response Unmodulated Response


feet (m)

Sunlight, direct — No alarm No alarm


Sunlight, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Arc welding 5 (1.5) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w mercury vapor lamp 3 (0.9) No alarm No alarm
300 w clear incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric quartz heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm

9.1 24 95-8527
FM Approvals Description and Performance Report – Continued

FIELD of view:

Very High Sensitivity

Fuel Size Distance Horizontal Avg. Horiz. Response Time Vertical Avg. Vert. Response Time
(feet (m) (degrees) (seconds)*** (degrees) (seconds)***

n-Heptane 1 x 1 foot 150* +45 12 +45 13


(45.7) –45 14 –30 5
n-Heptane 1 x 1 foot 100 +45 6 +45 3
(30.5) –45 3 –30 2
n-Heptane 6 in. x 6 in. 80 +45 5 +45 4
(24.4) –45 6 –30 4
Isopropanol 6 in. x 6 in. 70 +45 5 +45 4
(21.3) –45 5 –30 6
Diesel** 1 x 1 foot 100 +45 2 +45 4
(30.5) –45 3 –30 3
Methanol 6 in. x 6 in. 40 +45 4 +45 3
(12.2) –45 6 –30 3
Methanol 1 x 1 foot 110 +45 9 +45 9
(33.5) –45 7 –30 3
Methane 30 inch plume 100 +45 7 +45 2
(30.5) –45 3 –30 2
JP-5** 1 x 1 foot 100 +45 2 +45 3
(30.5) –45 4 –30 2
JP-5** 2 x 2 feet 180* +45 2 +45 3
(54.9) –45 5 –30 2
JP-5** 2 x 2 feet 90 +45 2 +45 1
(27.4) –45 3 –30 2
Office 19” x 19” x 8” 80 +45 4 +45 2
Paper 0.5 lb. (24.4) –45 2 –30 1
Corrugated 18” x 36” 80 +45 1 +45 3
Panel (24.4) –45 1 –30 2

* Outdoor test condition.


** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.

9.1 25 95-8527
FM Approvals Description and Performance Report – Continued

Medium Sensitivity

Fuel Size Distance Horizontal Avg. Horiz. Response Time Vertical Avg. Vert. Response Time
feet (m) (degrees) (seconds)*** (degrees) (seconds)***

n-Heptane 1 x 1 foot 75 +45 9 +45 10


(22.9) –45 6 –30 7
n-Heptane 1 x 1 foot 50 +45 4 +45 3
(15.2) –45 3 –30 3
Diesel** 1 x 1 foot 60 +45 4 +45 4
(18.3) –45 4 –30 2
Methanol 1 x 1 foot 50 +45 9 +45 9
(15.2) –45 3 –30 1
Methane 30 inch plume 45 +45 3 +45 7
(13.7) –45 3 –30 1
JP-5** 2 x 2 feet 90 +45 4 +45 2
(27.4) –45 2 –30 2

Office 19” x 19” x 8” 40 +45 2 +45 1


Paper 0.5 lb. (12.2) –45 1 –30 1

Corrugated 18” x 36” 40 +45 2 +45 1


Panel (12.2) –45 1 –30 1

* Outdoor test condition.


** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.

Low Sensitivity

Fuel Size Distance Horizontal Avg. Horiz. Response Time Vertical Avg. Vert. Response Time
feet (m) (degrees) (seconds)*** (degrees) (seconds)***

n-Heptane 1 x 1 foot 35 +45 13 +45 9


(10.7) –45 13 –30 18
Methanol 1 x 1 foot 15 +45 14 +45 10
(4.6) –45 12 –30 8
Methane 32 inch plume 15 +45 10 +45 8
(4.6) –45 11 –30 10

*** Add 2 seconds for EQP Model.

9.1 26 95-8527
FM Approvals Description and Performance Report – Continued

HIGH RESOLUTION FIELD OF VIEW


0° 0°
15° 210 ft 15° 15° 100 ft 15°
30° 30° 30° 90 ft 30°
180 ft
80 ft
45° 45° 45° 45°
150 ft 70 ft
120 ft 60 ft
50 ft
90 ft 40 ft
60 ft 30 ft
20 ft
10 ft

30 ft 10 ft
20 ft
60 ft 30° 30°
30 ft
90 ft 40 ft
15° 50 ft 15°
120 ft
60 ft
150 ft 70 ft
0° 0°
80 ft
180 ft
DETECTOR VERTICAL 90 ft 15°
DETECTOR VERTICAL
15° FIELD OF VIEW FIELD OF VIEW
210 ft 100 ft WITH DETECTOR AT
30° WITH DETECTOR AT 30°
45° 45° FROM HORIZONTAL. 45° 45° FROM HORIZONTAL.

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
n-Heptane at Very High Sensitivity (1 x 1 foot) Methane at Very High Sensitivity (30 inch plume)

0° 0°
15° 15° 15° 70 ft 15°
80 ft
30° 30° 30°
30° 60 ft
70 ft
45° 60 ft 45° 45° 50 ft 45°
50 ft 40 ft
40 ft 30 ft
30 ft
20 ft
20 ft
10 ft
10 ft

10 ft
10 ft
20 ft 30°
20 ft 30°
30 ft 30 ft

40 ft 40 ft 15°
15°
50 ft 50 ft
0° 0°
60 ft 60 ft
70 ft 15° DETECTOR VERTICAL
DETECTOR VERTICAL
15° FIELD OF VIEW 70 ft FIELD OF VIEW
80 ft 30° WITH DETECTOR AT
30° WITH DETECTOR AT 45° 45° FROM HORIZONTAL.
45° 45° FROM HORIZONTAL.

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
n-Heptane at Very High Sensitivity (6 in. x 6 in.) Isopropanol at Very High Sensitivity (6 in. x 6 in.)

9.1 27 95-8527
FM Approvals Description and Performance Report – Continued


15° 150 ft 15°
0° 30° 135 ft 30°
15° 40 ft 15°
120 ft
30° 30° 45° 45°
35 ft 105 ft
45° 30 ft 45° 90 ft
75 ft
25 ft
60 ft
20 ft 45 ft
15 ft 30 ft
10 ft 15 ft

5 ft
Field of View at Indicated Distance in Feet for
Methanol at Very High Sensitivity (1 x 1 foot)


5 ft 15° 150 ft 15°
10 ft 30° 30° 135 ft 30°
120 ft
15 ft 45° 45°
105 ft
20 ft 15° 90 ft
25 ft 75 ft
30 ft 0° 60 ft
45 ft
35 ft DETECTOR VERTICAL
15° FIELD OF VIEW
30 ft
40 ft 30° WITH DETECTOR AT 15 ft
45° 45° FROM HORIZONTAL.

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Methanol at Very High Sensitivity (6 in. x 6 in.) Diesel at Very High Sensitivity (1 x 1 foot)

0° 0°
15° 210 ft 15° 15° 100 ft 15°
30° 30° 30° 90 ft 30°
180 ft
80 ft
45° 150 ft 45° 45° 45°
70 ft
120 ft 60 ft
50 ft
90 ft 40 ft
60 ft 30 ft
20 ft
30 ft
10 ft

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
JP-5 at Very High Sensitivity (2 x 2 feet) n-Heptane at Medium Sensitivity (1 x 1 foot)

9.1 28 95-8527
FM Approvals Description and Performance Report – Continued

0° 0°
15° 65 ft 15° 15° 70 ft 15°
30° 60 ft 30° 30° 30°
60 ft
50 ft 45° 45°
45° 45° 50 ft
40 ft
40 ft
30 ft 30 ft
20 ft 20 ft

10 ft 10 ft

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Methane at Medium Sensitivity (30 inch plume) Methanol at Medium Sensitivity (1 x 1 foot)

0° 0°
15° 70 ft 15° 15° 100 ft 15°
30° 30° 30° 90 ft 30°
60 ft
80 ft
45° 45° 45° 45°
50 ft 70 ft
40 ft 60 ft
50 ft
30 ft 40 ft
20 ft 30 ft
20 ft
10 ft
10 ft

Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Diesel at Medium Sensitivity (1 x 1 foot) JP-5 at Medium Sensitivity (2 x 2 feet)

NOTE
FM Approvals minimum requirements are
response distance measurements at 0° (on
axis) and the limits of the field of view. These
high resolution field of view diagrams show the
measured response distances at all the indicated
angles in the horizontal plane.

9.1 29 95-8527
Printed in USA

Detector Electronics Corporation


6901 West 110th Street • Minneapolis, Minnesota 55438 USA
Tel: 952.941.5665 or 800.765.3473 • Fax: 952.829.8750
SAFETY MANUAL

Protect•IR®
Multispectrum IR Flame Detector
SIL 2 Certified X3301

SAFETY-CERTIFIED MODEL X3301


MULTISPECTRUM INFRARED DETECTOR
This manual addresses the specific requirements and
recommendations applicable to the proper installation,
operation, and maintenance of all Safety‑Certified
(SIL‑Certified) X3301 Multispectrum Infrared Flame
Detectors. For complete information regarding
performance, installation, operation, maintenance and
specifications of the X3301, refer to instruction manual
95-8527.

SAFETY MESSAGES
Procedures and instructions in this section may
require special precautions to ensure the safety of
personnel performing the operations. Information that
raises potential safety issues is indicated by the word
“Warning”. Always read and understand these safety
messages. DESIGN

WARNING The model X3301 Multispectrum IR Flame Detector is


The X3301 Multispectrum Flame Detector is an infrared flame detector that is classified as a Type
intended for use in hazardous environments B smart device according to IEC61508. The standard
that may include explosive levels of flammable model provides an isolated 4-wire, 4-20 mA output,
gases and vapors. This product must be properly together with on-board Alarm and Fault relay contacts.
installed, operated and maintained. Improper These outputs serve to indicate normal operating
installation or use could result in an explosion or condition of the detector, fault, or the presence of
fire resulting in death or serious injury. a flame alarm. The X3301 contains extensive self-
diagnostics and is programmed to send the current
• Do not remove the detector cover in explosive output to a specified state (1 mA, 2 mA or 3 mA) upon
environments when device power is on and internal detection of a failure or fault condition.
circuits are live.
• Detector must be properly installed, and wiring The EQP model is designed for use exclusively with
compartment cover must be fully engaged the Det-Tronics Eagle Quantum Premier system. The
to meet hazardous area explosion-proof/ detector communicates with the system controller
nonincendive requirements. over a digital communication network or EQPSL/SLC

3.1
3.1 © Detector Electronics Corporation 2008  2/08 95-8582
95-8582
(Eagle Quantum Premier Safety Loop / Signalling INSTALLATION
Line Circuit). The EQPSL/SLC is a fault tolerant, two
note
wire digital communication network arranged in a
For complete information regarding performance,
loop configuration. Analog and relay outputs are not
installation, operation, maintenance and
available on this model. For information regarding the
specifications of the X3301, refer to instruction
use of the SIL 2 Certified X3301 in an EQP system, refer
manual 95-8527.
to the EQP Safety Manual 95-8599.
Tools Required:
The X3301 is designed for operation with a supply
voltage from 18-32 volts DC. Proper operation outside • 14 mm hexagonal wrench
this range cannot be assumed.
No special installation requirements exist above
The standard relay with analog output version, as and beyond the standard installation practices
well as the EQP version are included within the Safety documented in the X3301 instruction manual (95‑8527).
Certification for the X3301 Multispectrum IR Flame Environmental specification limits are also as published
Detector. in the general specifications section in the X3301
instruction manual.
Safety-Certification of the X3301 Multispectrum IR
Flame Detector does not include: The X3301 operating power distribution system must
be designed and installed so the terminal voltage does
• Pulse Output
not drop below 18 Vdc when measured at any specific
• External/remote HART communication control location. The maximum current limit must be less than
systems 2 amperes. The over-voltage protection must be set
• RS-485 Modbus signal. for 33 Vdc.

User modification of device configuration is only START-UP AND COMMISSIONING


permitted via the SIL Certified EQP Controller.
The Safety Certified X3301 Multispectrum IR Flame
Detector can be commissioned by any qualified person
VALID INPUT RANGE with knowledge of flame detection instruments and the
X3301 fault annunciation is provided on the 4-20 mA configuration device being used. Refer to the Start‑Up
signal output loop by signaling to a 1 mA, 2 mA, or 3 and Commissioning section provided in the X3301
mA current output level. The receiving device must be instruction manual.
programmed to indicate a fault condition when current
levels go below 3.7 mA. OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
DIAGNOSTIC RESPONSE TIME Tools Required:
X3301 Multispectrum IR Flame Detector will perform • 3 mm hexagonal wrench
all critical diagnostic functions within 58 minutes, worst
• Magnetic oi test tool (part number 102740-002)
case diagnostic detection time.
• Window cleaner (part number 001680-001 or
isopropanol)
CERTIFICATION
• Lens tissue and cotton swabs
The X3301 Safety-Certified version is certified by TÜV
• 4 mm flat blade screwdriver
to IEC61508 for single input use in low demand SIL 2
Safety Instrumented Systems.
After normal installation and start-up have been
completed as recommended within the X3301 manual,
SAFETY-CERTIFIED PRODUCT IDENTIFICATION Proof Tests must be performed for every Safety-Certified
X3301 detector installed.
All Safety Certified X3301 models are identified by the
TUV-approved logo on the product label. In addition,
Personnel performing Proof Test procedures shall be
the model number printed on the label will include the
competent to perform the task. All Proof Test results
character suffix “T” in the model number string, indicating
must be recorded and analyzed. Any corrective actions
TUV approval. Example: Model X33011A4N13T1.
taken must be documented in the event that an error is
found in the safety functionality. The Proof Tests must
be performed at a frequency as shown in Table 1:

3.1  95-8582
Table 1—Frequency of Proof Tests

Proof Test Name Commissioning Frequency per Year

Visual Field Inspection Proof Test Yes 52

Detector Response Mag Oi Proof Test Yes 1

Visual Field Inspection Proof test Fault/Failure Action Plan


Visual inspection of all Safety-Certified X3301 In the event of a non-alarm condition result with the Mag
Multispectrum IR Flame Detectors shall be conducted oi test, the standard Maintenance and Troubleshooting
weekly to confirm that there are no obstructions in procedures listed in the X3301 instruction manual must
the optical field of view. Corrective action will include be followed. In the event that the condition cannot
removal of such impediments should they exist. be resolved, the standard Device Repair and Return
procedures listed in the X3301 instruction manual must
Completion of Visual Field Inspection Proof test will be be followed.
recorded and documented in the SIS logbook.
Any and all failures to successfully complete the alarm
test must be recorded and documented in the SIS
Detector Response Mag Oi Proof Test
logbook.
Warning
Any external alarm equipment, systems or
Product Repair
signaling devices that could be automatically
initiated by performing this test must be disabled The X3301 is not field-repairable, and any internal
or bypassed before performing this test! device repairs must be conducted at the factory. No
firmware changes are permitted or authorized. All
Tools Required: failures indicated by internal diagnostics or Proof Tests
• Magnetic oi test tool (part number 102740-002) that cannot be resolved through the troubleshooting
and maintenance procedures described in the X3301
All flame detectors must be performance tested using manual must be reported to the manufacturer.
the Mag oi Procedure and inspected to ensure that
they are capable of providing expected performance OPERATING, ENVIRONMENTAL and
and protection. Note that the Mag oi Procedure and PERFORMANCE SPECIFICATIONS
Manual oi Tests are not interference free. During these
tests the unit is not performing normal flame detection The Safety-Certified X3301 product versions fully
functions. Model X3301 provides an onboard status comply with, and must be operated in accordance with
LED, which indicates Green color when internal the functional and performance specifications provided
operational parameters are normal. The LED changes in the instruction manual. A 24 hour mean time to repair
to a Red color to indicate a successful proof test. The should be assumed for safety availability calculations.
Alarm and Auxiliary relays indicate alarm condition All X3301 diagnostics have a maximum 2 hour test
and the current output indicates 20 mA. These results interval.
should be verified on the control device. In the event
the proof test is unsuccessful, the LED remains Green,
the Alarm and Auxiliary relays remain in their non-alarm
condition, and the current output is 4 mA.

3.1  95-8582
SPARE PARTS Analog Output
Safe Failure Fraction (SFF) = 93.2%.
Refer to the spare parts section of the X3301 manual.
PFDavg @ 1 year consumes 9.7% of the allowable
Safety certification is based on a sufficient number of
SIL 2 budget.
spares to achieve a 24 hour mean time to repair.
Relay Output
CERTIFICATION AND FAILURE RATE DATA Safe Failure Fraction (SFF) = 95.9%.
PFDavg @ 1 year consumes 5.7% of the allowable
All Safety-Certified X3301 models are certified
SIL 2 budget.
compliant to:

IEC61508: 2000 Product Certifications


SIL 2 certified
FM, CSA, DEMKO/ATEX, CE.
Safety Accuracy: Not applicable.
Refer to the X3301 Instruction Manual for details.
Product Life: 13-22 years, based on manufacturer
data.
FMEDA Report available.

For complete information regarding performance,


installation, operation, maintenance and specifications
of the X3301, refer to instruction manual 95-8527.

Detector Electronics Corporation


6901 West 110th Street • Minneapolis, Minnesota 55438 • Operator (952) 941-5665 or (800) 765-FIRE
Customer
3.1 Service (952) 946-6491 • Fax (952) 829-8750 • www.det-tronics.com • E-mail: detronics@detronics.com
95-8582

Vous aimerez peut-être aussi