2 X 660 MW SURATGARH SUPERCRITICAL TPS UNIT # 7 & 8
RELAY SETTINGS FOR
GENERATOR, GENERATOR TRANSFORMER, UNIT TRANSFORMER
& STATION TRANSFORMER RELAY PANEL
DOC. NO. PE‐DC‐392‐510‐E004
REVISION 0
BHARAT HEAVY ELECTRICALS LIMITED
POWER SECTOR
PROJECT ENGINEERING MANAGEMENT
NOIDA, INDIA
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT & UAT PROTECTION Date: 27/06/2016
INPUT
Generator
Parameters Value Unit
Rated power 660.5 MW
Rated voltage 21 kV
Power factor 0.85
Rated MVA 777 MVA
Rated current 21362 A
Frequency 50 Hz
Xd" 20.2 %
Xd' 30.2 %
Xd 191.6 %
Tolerance 15 %
I2 6.577 %
2
I2 t 5.67 sec
Overload capability 150 %
Overload duration 30 sec
Generator circuit CT/PT
CT Ratio phase (primary) 24000 A
CT Ratio phase (secondary) 5 A
CT Ratio neutral (primary) 24000 A
CT Ratio neutral (secondary) 5 A
PT-1 Ratio (primary) 21 kV
PT-1 Ratio (secondary) 110 V
IVT Ratio (primary) 110 V
IVT Ratio (secondary) 166.67 V
Generator Transformer
Power rating 825 MVA
HV voltage 420 kV
LV voltage 21 kV
Impedance 16 %
Tolerance 5 %
Vendor group YNd11
configuration 3
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT & UAT PROTECTION Date: 27/06/2016
Grid data
Rated voltage 400 kV
Fault level 50 kA
MVAsc 34640 MVA
NGT, NGR, NGT secondary CT data
NGT (primary) 21 kV
NGT (secondary) 500 V
CT (primary) 900 A
CT (secondary) 5 A
NGR 0.42 Ohm
TRVD 2.5
Unit Transformer
Power rating 40 MVA
HV voltage 21 kV
LV voltage 11.5 kV
Impedance 12 %
Tolerance 10 %
Vendor group Dyn1
Station Transformer
HV Power rating 125 MVA
LV1 Power rating 62.5 MVA
LV2 Power rating 62.5 MVA
HV voltage 21 kV
LV1 voltage 11.5 kV
LV2 voltage 11.5 kV
Impedance HV-LV1/LV2 24 %
Tolerance 10 %
Vendor group Dyn1yn1
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
UNDER VOLTAGE RELAY (27G1/G2):
Under voltage setting : 70 % of VT secondary voltage
Time setting : 0 sec
Action : Trip
GENERATOR OVERVOLTAGE PROTECTION (59 G1):
Overvoltage setting (stage‐1): 115.5 V
Time setting: 2 sec
Action: Alarm
Overvoltage setting (stage‐2): 143 V
Time setting: 0 sec
Action: Trip
GENERATOR OVERVOLTAGE PROTECTION (59 G2):
Overvoltage setting (stage‐1): 121 V
Time setting: 6 sec
Action: Trip
Overvoltage setting (stage‐2): 143 V
Time setting: 0 sec
Action: Trip
UNDER FREQUENCY RELAY (81U G1/G2):
Rated frequency: 50 Hz
Under frequency setting (stage‐1): 97 % of generator rated frequency
Time setting: 2 sec
Action: Alarm
Under frequency setting (stage‐2): 95 % of generator rated frequency
Time setting: 2 sec
Action: Trip
OVER FREQUENCY RELAY (81O G1/G2):
Rated frequency: 50 Hz
GENERATOR DEFINITE TIME OVERLOAD PROTECTION (51 G1/G2):
Generator rated current : 21362 A
Corresponding CT secondary current (Is):
=( 21362 ) x (5/24000)
Is= 4.45 A
Generator overload capability:
Current 150 % of rated current
Time duration 30 Seconds
Overload setting: 110 %
Recommended setting:
Current Set: 4.90 A
Time Delay: 2 sec
Action : Alarm
GENERATOR NEGATIVE SEQUENCE PROTECTION (46 G1/G2)
Rated current : 21362 A
Max. NPS (I2) current 6.577 %
Maximum value of I22t 5.67
Set Value of I22t 90 %
Alarm stage setting: 90 % of Gen. max. negative phase sequence current
Time setting T I2>: 20 sec
I2>1 Set: = 0.9 x 6.577 x (21362/24000) %
5.27 %
Trip stage setting: 65 % of Gen. rated current
I2>> Set: = 65 x (21362/24000) %
57.86 %
Time setting T I2>>: 2.5 sec
K factor: = ( 5.67 x 0.9) x (21362/24000)^2 sec.
4.04 Sec.
Cool down time: = (5.67 x 0.9) / (6.577/ 100)^2 Sec.
1179.70 Sec.
Soft timer for Class A Trip: 1 sec
Group 1 & 2 Setting range
No. Settings
Settings Min Max
1701 Unbalance Load Protection ON ON, OFF, BLOCK RELAY
1702 Continously Permissible Current I2 5.27% 3.00% 30.00%
1703 Warning Stage Time Delay 20 s 0 s to 60 s;
1704 Negative Sequence Factor K 4s 0 s to 100 s;
1705 Time for Cooling Down 1180 s 0s 50000 s
1706 I2>> Pickup 58.00% 10% 200%
1707 T I2>> Time Delay 2.5 s 0 s to 60 s;
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GENERATOR BACKUP IMPEDANCE PROTECTION (21 G1/G2)
Rated current : 21362 A
Impedance of GT (Zt) 0.16 pu
Min. Impedance of GT (Zt) 0.152 pu
= 0.152 x 21 x 21/825 Ohm
0.080 Ohm
Impedance Zone (Z2) 70 % of GT impedance (Zt)
= 0.7 x Zt x CT Ratio/ VT Ratio
= 0.7 x 0.08 x (24000/5) x (110/Sqrt(3)/21/Sqrt(3) x 1000)
1.408 Ohm
GENERATOR REVERSE POWER PROTECTION (32 G1/G2)
Generator rated power : 660.5 MW
Rated current : 21362 A
Psec / SN sec = (‐3.3025 X 21 X 21362) / (777 X 21 X 24000)
= ‐0.38 %
Recommended setting:
P> Reverse pickup Setting: ‐0.5 %
Time delay (with stop valve) 2 sec [with turbine trip]
Time delay (with out stop valve) 10 sec [without turbine trip]
Action: Trip
GENERATOR LOW FORWARD POWER PROTECTION (37 G1/G2)
Generator rated power : 660.5 MW
Rated current : 21362 A
Psec / SN sec = (3.3025 X 21 X 21362) / (777 X 21 X 24000)
= 0.38 %
Recommended setting:
P‐forw< Setting: 0.5 %
Time setting 0 sec
GENERATOR DEAD MACHINE PROTECTION (50GDM1/GDM2)
Generator rated current : 21362 A
Corresponding CT secondary current (Is): = 21362 x (5/24000)
Is= 4.450416667 A
Relay current setting: 110 % of generator rated current
Relay is set at 110% of generator rated current as the element will not be enabled during normal operation of machine
Relay voltage setting : 70 % of VT secondary voltage
Recommended setting:
Dead mach I> 4.90 A
Dead mach V< 77 V
Dead mach tPU 1 sec
Dead mach tDO 1 sec
GENERATOR FIELD FAILURE PROTECTION (40 G1/G2)
Generator rated current, Irated: 21362 A
Generator rated voltage, Vgenerator: 21 kV
Generator Synchronous Reactance, Xd: 191.6 %
1/Xdsec =(1/Xd) x (Irated / Vgenerator) x (VT primary line current / CT primary current)
0.46
Characteristic 1 = 1.05 x0.46
0.49
Characteristic 1 Time delay 2 Sec
Characteristic 1 Angle 80 Deg
Characteristic 2 = 0.9 x0.49
0.44
Characteristic 2 Time delay 2 Sec
Characteristic 2 Angle 90 Deg
Characteristic 3 = 2 x0.44
0.88
Characteristic 3 Time delay 0.3 Sec
Characteristic 3 Angle 100 Deg
GENERATOR OUT OF STEP (POLE SLIPPING) RELAY (78 G1/G2)
Base impedance of the generator referred to CT & VT =0.57 x (24000/5) x
secondary (110/sqrt(3)/21/sqrt(3) x 1000)
14.27 Ohm
Max. Transient reactance of the generator (Xd'): 30.2 %
= 30.2 x 14.27/100 Ohm
4.31 Ohm
Maximum GT impedance (ZT): 16 %
= 16 x 14.27/100 Ohm
2.28 Ohm
Grid Voltage: 400 kV
Fault level at grid: 50 kA
= (21)^2/(sqrt(3) x 400 x 50)x
System impedance (Zs): (110/sqrt(3)/21/sqrt(3) x 1000) x
(24000/5)
0.32 Ohm
Zd - Zc : =Zs Ohm
0.32 Ohm
Zb : = Xd' Ohm
4.31 Ohm
Zc : = ZT Ohm
2.28 Ohm
Za : = 0.289 x (Zb + Zc) Ohm
1.91 Ohm
Recommended setting:
GENERATOR DIFFRENTIAL RELAY(87 G1/G2)
Recommended setting:
Pickup setting, IDIFF>: 0.2 In/In0
Time Delay, T IDIFF>: 0 Sec.
Pickup setting, IDIFF>>: (1/X'd) In/In0
3.31 In/In0
Time Delay, T IDIFF>>: 0 Sec.
Slope 1 of tripping characteristic: 0.25
Base point of slope 1: 0 In/In0
Slope 2 of tripping characteristic: 0.25
Base point of slope 2: 0 In/In0
2nd Harmonic content in I‐DIFF 15 %
GENERATOR AND GT OVER FLUXING PROTECTION (99 G1/G2)
Generator transformer(GT) & Generator Overfluxing withstand capability is tabulated below (Derived from Over
Fluxing curves obtained from Generator manufacturer and GT manufacturer:
Generator
S.No. GT Overfluxing capability overfluxing
capability
Value(pu) Time(sec) Time(sec)
1 1.05 99999 9999
2 1.10 99999 9999
3 1.15 160 150
4 1.20 100 40
5 1.25 60 20
6 1.30 30 12
7 1.35 20 6
8 1.40 5 3
Rated Freq: 50 50
Rated Voltage: 21 21
PT Primary: 21 / sqrt(3) 21 / sqrt(3)
PT Secondary: 110 / sqrt(3) 110 / sqrt(3)
Recommended setting:
Alarm stage
Alarm setting, U/f>: 1.1
Alarm delay, T U/f>: 10 Sec
Trip stage
Trip setting, U/f>>: 1.4
Trip delay, T U/f>>: 1 Sec
95% GENERATOR STATOR EARTH FAULT PROTECTION: (64G1/2)
NGT ratio: NGT primary: 21 kV
NGT secondary: 500 V
TRVD 2.5
Pickup Value of earth fault
=((100%‐95%)/100%) x (NGT SEC VOLTAGE/SQRT(3)) / TRVD
detection:
5.77 V
Recommended setting:
Voltage setting : 5.7 V
Time setting : 0.2 sec
Action: Trip
100% GENERATOR STATOR EARTH FAULT PROTECTION (64 G3)
(THIRD HARMONIC UNDERVOLTAGE PRINCIPLE IN GROUP‐1 RELAY)
P min > setting = 40% of P/ SN, gen
= 40% x 660.5/(SQRT(3) X 21 X 24000)
= 30.3%
* Final settings shall be done during commissioning based on primary tests to determine values
under normal condition. To be carried out at site as per operating instruction of the relay
100% GENERATOR STATOR EARTH FAULT PROTECTION (64 G4)
(LOW FREQUENCY INJECTION PRINCIPLE IN GROUP‐2 RELAY)
NGT Ratio: NGT primary: 21 kV
NGT secondary: 500 V
Voltage deviding resistor (TRVD): 2.5
Transformation factor, K ‐factor: = (NGT ratio)^2 x TRVD/ ICT ratio
= (21000/500)^2 x 2.5 x (5/900)
24.5
Pick up value of the Alarm stage: =10000/ K‐FACTOR Ohm
408 Ohm
Pick up value of the Trip stage: =5000/ K‐FACTOR Ohm
204 Ohm
Pick up value of the current
= 0.2 x NGT secondary voltage/SQRT(3) X (R) x ICT ratio
tripping:
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
0.76 A
Recommended setting:
Alarm stage
Alarm setting: 408 Ohm*
Alarm delay: 5 sec
Trip stage (Ohmic)
Trip setting: 204 Ohm*
Trip delay: 0.5 sec
Trip stage (Over current)
Trip setting: 0.76 A*
Pick‐up threshold of 20 Hz under
1 V
voltage blocking:
Pick‐up threshold of 20 Hz under
10 mA
voltage blocking:
Group 2 Setting range
No. Settings
Settings Min Max
5301 100% Stator-Earth-Fault Protection ON ON, OFF, BLOCK RELAY
5302 Pickup Value of Alarm Stage Rsef< 408 Ohm 20 ohm 700 ohm
5303 Pickup Value of Tripping Stage Rsef<< 20 4Ohm 20 ohm 700 ohm
5304 Time Delay of Alarm Stage Rsef< 10 s 0 s to 60 s;
5305 Time Delay of Tripping Stage Rsef<< 0.5 s 0 s to 60 s;
5306 Pickup Value of I SEF>> Stage 0.76 A 0.02 A 1.50 A
5307 Supervision Threshold of 20Hz Voltage 1V 0.3 V 15.0 V
5308 Supervision Threshold of 20Hz Current 10 mA 5 mA 40 mA
* Final settings shall be done during commissioning based on primary tests to determine values
under normal condition. To be carried out at site as per operating instruction of the relay
Document No: PE-
2X660MW SURATGARH TPP
DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GENERATOR ROTOR EARTH FAULT PROTECTION (64 F1/F2)
Recommended setting:
Alarm stage
Alarm setting: 80 k Ohm*
Alarm delay: 10 sec
Trip stage
Trip setting: 5 k Ohm*
Trip delay: 1 sec
* Final settings shall be done during commissioning based on primary tests to determine values under normal
condition. To be carried out at site as per operating instruction of the relay
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GT BACK UP EARTH FAULT PROTECTION (51NGT):
Relay type: SIEMENS 7UT633
Device No. GTR1/ GTR3
Recommended setting:
Current Set IE: 0.1 A
Time Delay T IE: 2 sec *
TIME DELAY RELAY FOR 51NGT – CLASS‐A1 TRIP (SOFT TIMER) = 1 sec
*: The above time setting shall be coordinated at site with line side protection.
Document No: PE-
2X660MW SURATGARH TPP
DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
GENERATOR INTERTURN FAULT PROTECTION (64GIT):
Relay type: SIEMENS 7SJ802
Device No. 64GIT
Faulty phase voltage during single
0.908 p.u.
interturn fault:
In case of single turn inter turn fault, unbalance produced in faulty phase leads to a voltage 0.908 p.u. in the faulty
phase, with other two phase voltages being normal.
Voltage across open delta secondary
= (VR + VY + VB) N
(VOD):
where, N is transformation ratio of IVT
VOD = N [V(0.908) + VCos 120 + jVSin 120 + VCos 240 + jVSin240]
N (110/sqrt(3)) / (166.67/sqrt(3)) = 0.66
V 110 / sqrt(3)
VOD ‐3.856 V
Recommended setting:
Voltage setting : 4 V
Time setting : 0.2 sec
Action: Trip
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GT HV OVERCURRENT PROTECTION (51GT):
Relay type: SIEMENS 7UT633
Device No. GTR1/ GTR3
GT HV side current : =825X1000/( 1.732 x 420)
1134 A
Corresponding CT secondary
=1134.11 x (1/1250)
current (Is):
Is= 0.91 A
CT seconday current with 10% O/L= 0.998 A
Recommended setting:
Current Seting: 1 A
Time Delay: 2 sec*
*Time setting shall be co‐ordinated at site such that 51GT shall operate after setting of distance protection
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GT RESTRICTED EARTH FAULT PROTECTION (64RGT):
Relay type: SIEMENS 7SJ802
Device No. GTR2/ GTR4
Maximum fault current (HV side): =(825x1000) / (1.732x420x0.16x0.95)
7461.28 A
Corresponding CT secondary current
= 7461.28 x (1/1250)
(If):
If= 5.97 A
Voltage across the relay under
= If (Rct + 2RL) V
through fault condition
Cable size used for CT connection: 4 sq. mm.
Resistance of cable: 5.53 Ohms/kM
Length of Connecting cable: 250 Meters
Lead Resistance, RL: = (5.53 x0.25)
1.3825 Ohms
Voltage across the relay under
=5.97 x (2.22 + 2x 1.3825)
through fault condition, Vf:
29.76 V
Recommended Setting:
Current Setting: 10 %
0.10 A
Value of stabilising resistor: = 29.76/0.1
297.56 Ohm
SELECTED VALUE 300.00 OHM
* Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
GT DIFFERENTIAL PROTECTION (87GT):
Relay type: SIEMENS 7UT633
Device No. GTR1/ GTR3
GT Impedance 16 %
Impedance Tolerance 5 %
Transformer through fault current =1/(0.16x0.95)
6.58 In
Recommended setting:
Pick up value of differential current, IDIFF> 0.2 I/INO
Time delay T IDIFF> 0 sec
High set setting, Idiff>>: 8 I/INO
Time delay T IDIFF>> 0 sec
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
GT OVER FLUXING PROTECTION (99 GT)
Relay type: SIEMENS 7UT633
Device No. GTR1/ GTR3
Settings for 99GT shall be same as the settings for 99G1/ G2.
Relay type: SIEMENS 7SJ804
Device No. 59NGT
Recommended setting:
Voltage Seting: 5.5 V
Time Delay: 0.1 sec
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
UTA/ UTB DIFFERENTIAL PROTECTION (87UTA/ UTB):
Relay type: SIEMENS 7UT633
Device No. UTAR1/ UTAR3/ UTBR1/ UTBR3
UT Impedance 12 %
Impedance Tolerance 10 %
Transformer through fault current =1/(0.12x0.9)
9.26 In
Recommended setting:
Pick up value of differential current, IDIFF> 0.2 I/INO
Time delay T IDIFF> 0 sec
High set setting, Idiff>>: 10 I/INO
Time delay T IDIFF>> 0 sec
Slope 1 of tripping characteristic 0.25
Base Point of Slope 1 0 I/INO
Slope 2 of tripping characteristic 0.5
Base Point of Slope 2 2.5 I/INO
Pick up for Add‐on stabilization 4 I/INO
Duration of Add‐on stabilization 15 CYCLES
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
UT LV BACK UP EARTH FAULT PROTECTION (51NSUTA/UTB ):
Relay type: SIEMENS 7UT633
Device No. UTAR1/ UTAR3/ UTBR1/ UTBR3
Recommended setting:
Current Set IE: 0.25 A
Time Delay T IE: 1.5 sec *
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
UT HV INST O/C PROTECTION (50UTA/UTB ):
Relay type: SIEMENS 7UT633
Device No. UTAR1/ UTAR3/ UTBR1/ UTBR3
= 10182.8 A
FAULT CURRENT ON CT SECONDARY SIDE = 8.1 A
Recommended setting:
Current Set 10 A
Time Delay 0.1 sec *
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
UT HV O/C PROTECTION (51UTA/UTB ):
Relay type: SIEMENS 7UT633
Device No. UTAR1/ UTAR3/ UTBR1/ UTBR3
Recommended setting:
Current Set 1.5 A
Time Delay 1.5 sec
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
UT LV RESTRICTED EARTH FAULT PROTECTION (64RUTA/ 64RUTB):
Relay type: SIEMENS 7SJ802
Device No. UTAR2/ UTAR4/ UTBR2/ UTBR4
UT Rating: 40 MVA
UT LV Side Voltage: 11.5 kV
UT Impedance: 12 %
Tolerance in Impedance: 10 %
CT Details:
LV Side CT details:
CT primary : 2500 A
CT secondary : 1 A
Neutral Side CT Details:
CT primary : 2500 A
CT secondary : 1 A
CT Resistance, Rct: 6.5 Ohm *
Maximum fault current (LV side): =(40x1000) / (1.732x11.5x0.12x0.9)
18594.76 A
Corresponding CT secondary = 18594.76 x (1/2500)
If= 7.44 A
Voltage across the relay under
= If (Rct + 2RL) V
through fault condition
Cable size used for CT connection: 2.5 sq. mm.
Resistance of cable: 8.87 Ohms/kM
Length of Connecting cable: 210 Meters
Lead Resistance, RL: = (8.87 x0.21)
1.8627 Ohms
Voltage across the relay under =7.44 x (6.5 + 2x 1.8627)
76.06 V
Recommended Setting:
Current Setting: 10 %
0.10 A
Value of stabilising resistor: = 76.06/0.1
760.56 Ohm
SELECTED VALUE 770.00 OHM
* Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
UT OVER FLUXING PROTECTION (99 UTA/UTB)
Relay type: SIEMENS 7UT633
Device No. UTAR1/ UTAR3/ UTBR1/ UTBR3
UT Overfluxing shall be only used for alarm. Alarm settings shall be as below.
ST DIFFERENTIAL PROTECTION (87ST):
Relay type: SIEMENS 7UT633
Device No. STR1/ STR4
ST Impedance 24 %
Impedance Tolerance 10 %
Transformer through fault current =1/(0.24x0.9)
4.63 In
Recommended setting:
Pick up value of differential current, IDIFF> 0.2 I/INO
Time delay T IDIFF> 0 sec
High set setting, Idiff>>: 5 I/INO
Time delay T IDIFF>> 0 sec
Slope 1 of tripping characteristic 0.25
Base Point of Slope 1 0 I/INO
Slope 2 of tripping characteristic 0.5
Base Point of Slope 2 2.5 I/INO
Pick up for Add‐on stabilization 4 I/INO
Duration of Add‐on stabilization 15 CYCLES
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
ST LV‐1 BACK UP EARTH FAULT PROTECTION (51NSTLV1/LV2 ):
Relay type: SIEMENS 7UT633
Device No. STR1/ STR4
Recommended setting:
Current Set IE: 0.25 A
Time Delay T IE: 1.5 sec *
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
ST HV INST O/C PROTECTION (50ST ):
Relay type: SIEMENS 7UT633
Device No. STR1/ STR4
= 15910.7 A
FAULT CURRENT ON CT SECONDARY SIDE = 4.0 A
Recommended setting:
Current Set 5 A
Time Delay 0.1 sec *
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL
Date: 27/06/2016
ST HV O/C PROTECTION (51ST ):
Relay type: SIEMENS 7UT633
Device No. STR1/ STR4
Recommended setting:
Current Set 1.5 A
Time Delay 1.5 sec
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
ST LV1 RESTRICTED EARTH FAULT PROTECTION (64RSTLV1/LV2)
Relay type: SIEMENS 7SJ802
Device No. STR2/ STR3/ STR5/ STR6
Maximum fault current (LV side): =(125x1000) / (1.732x11.5x0.24x0.9)
29054.31 A
Corresponding CT secondary = 29054.31 x (1/3500)
If= 8.30 A
Voltage across the relay under = If (Rct + 2RL) V
Cable size used for CT connection: 2.5 sq. mm.
Resistance of cable: 8.87 Ohms/kM
Length of Connecting cable: 210 Meters
Lead Resistance, RL: = (8.87 x0.21)
1.8627 Ohms
Voltage across the relay under =8.3 x (6.5 + 2x 1.8627)
84.88 V
Recommended Setting:
Current Setting: 10 %
0.10 A
Value of stabilising resistor: = 84.88/0.1
848.83 Ohm
SELECTED VALUE 850.00 OHM
* Note: Value of stabilizing resistor shall be recalculated at site by considering actual values of Rct and RL.
Document No:
2X660MW SURATGARH TPP
PE-DC-392-510-E004
RELAY SETTING CALCULATIONS Revison: 0
FOR GENERATOR, GT, UT & ST PROTECTION PANEL Date: 27/06/2016
ST OVER FLUXING PROTECTION (99 ST)
Relay type: SIEMENS 7UT633
Device No. STR1/ STR4
ST Overfluxing shall be only used for alarm. Alarm settings shall be as below.
Setting range
No. Settings
Settings Min Max
4301 Overexcitation Protection (U/f) ON ON, OFF, BLOCK RELAY
4302 U/f > Pickup 1.1 1.00 1.20
4303 T U/f > Time Delay 10 s 0 s to 60 s;