1 MX321
1. SPECIFICATION
Sensing Input Soft Start Ramp Time
Voltage 190 ~ 264 VAC Max, 2 or 3 phase 0.4 ~ 4 sec.
Frequency 50 / 60 Hz, selectable
Analogue Input
Power Input (PMG) Max. Input ± 5 VDC
Voltage 170 ~ 220 VAC Max, 3 phase 3 wire Sensitivity 1V for 5% generator volt
Current 3A / Phase Input Resistance 1K ohm
Frequency 100 ~ 120 Hz, nominal
Droop Input
Output Burden 10 ohm
Voltage Max. 120 VDC Max. sensitivity 0.22 A for 5% droop (PF=0)
Current Continuous 4A Max. input 0.33 A
Intermittent 7A for 60 sec
Resistance Min. 15 ohm Over Voltage Detector Input
Set point 300V. Time delay 1 sec (fixed)
Voltage Regulation CB trip coil volt 10 ~ 30 VDC / 0.5 Amp
< ± 0.5% RMS ( with 4% engine governing ) CB trip coil resistance 20 ~ 60 ohms
2. GENERAL DESCRIPTION
● EA321 is a two phase sensed Automatic Voltage ● The AVR senses the voltage in the main
Regulator and forms part of the excitation system generator winding and controls the power fed to
for a brush-less generator. Excitation power is the exciter stator and hence the main rotor to
derived from a three-phase permanent magnet maintain the generator output voltage within the
generator (PMG), to isolate the AVR control specified limits, compensating for load, speed,
circuits from the effects of nonlinear loads and to temperature and power factor of the generator.
reduce radio frequency interference on the
● Soft start circuitry is included to provide a smooth
generator terminals. Sustained generator short
controlled build up of generator output voltage.
circuit current is another feature of the PMG
system.
______________________________________________________________________________________
2
MX321
● A frequency measuring circuit continually ● The AVR has the facility for droop CT connection,
monitors the shaft speed of the generator and to allow parallel running with other similarly
provides under-speed protection of the excitation equipped generators.
system by reducing the generator output voltage
proportionally with speed below a pre-settable NOTE :
threshold. A further enhancement of this feature
1. Derate linearly from 3.7A at 50 °C to 2.7A at 70 °C.
is an adjustable volt per Hertz slope to improve
engine recovery time on turbo charged engines. 2. The stated voltage regulation may not be
Soft start circuitry is included to provide a smooth maintained in the presence of certain transmitted
controlled build up of generator output voltage. radio signals. Any change in regulation will fall
within the limits in criteria B of S.EN.61000-6-2 :
● Uncontrolled excitation is limited to a safe period
2001.
by internal shutdown of the AVR output device.
This condition remains latched until the generator 3. After 10 minutes.
has stopped.
4. Applies to Mod status E onwards. Generator
● Provision is made for the connection of a remote de-rate may apply. Check with factory. Factory
voltage trimmer, allowing the user fine control of set, semi-sealed, jumper selectable.
the generator’s output.
5. Any device connected to the analogue input must
● An analogue input is provided allowing be fully looting (galvanically isolated from
connection to a controller or other external ground), with an insulation strength of 500V ac.
devices with compatible output.
6. Non condensing.
______________________________________________________________________________________
4
MX321
4.7 DIP Adjustment 4.9 Current Limit (I LIMIT) Adjustment
This feature is mostly used when the generator is This feature is mostly used to limit short circuit
coupled to turbo charged engines with limited block current or to provide a current limit on motor starting.
load acceptance. The feature works by increasing To use this feature, current limit CT’s of the correct
the V/Hz slope to give greater voltage roll off in ratio need to be connected to the AVR S1 S2
proportion to speed. terminals. There is an internal time limit of 10
seconds. Consult the factory before using this
With the DIP control fully anti-clockwise, the feature.
generator voltage will follow the normal V/Hz line as
the speed falls below nominal. Turning the DIP 4.10 Over Voltage (OVER V) Adjustment
control clockwise provides greater voltage roll off
This adjustment is set and sealed in the works and
aiding engine recovery.
should not be tampered with. An over voltage
condition is indicated by the illumination of the red
4.8 DWELL LED which also indicates under-speed running and
over-excitation. The generator must be stopped to
This feature is mostly used when the generator is
reset an over-voltage trip.
coupled to turbo charged engines with limited block
load acceptance. The feature works by introducing a
delay between speed recovery and voltage recovery 4.11 RAMP
and allows a greater DIP setting without instability. The AVR includes a soft start or voltage ramp-up
circuit to control the rate of voltage build up, when
With the DWELL control fully anti-clockwise, the the generator runs up to speed. This is normally
generator voltage will follow the V/Hz line. Turning pre-set and sealed to give a voltage ramp-up time of
the DWELL control clockwise increase the delay approximately 3 seconds. If required, this can be
time between speed recovery and voltage recovery. adjusted between the limits defined in the
specification.
ATTENTION
Resistor
UFRO
panel, or any position that will not
affects operation. For dimension
reference, please see Figure 1.
STABILITY RMS
3. All voltage readings are to be taken
with an average-reading voltmeter
DROOP Meggers and high-potential test
VOLTS
______________________________________________________________________________________
5
MX321
K2 K1 P2 P3 P4 XX X 6 7 8 1 2
No link 6P50HZ
Ramp Indicator 6P60HZ
Volts
4P50HZ
LED 4P60HZ I Limit
UFRO 321 Frequency
Selection
Dip
Rms
Dwell
Stability
Stability >550KW
Selection 90-550KW
<90KW
Over V Droop Trim
Exc. U V W
S1S2 S1S2
E0 E1 B0 B1 C BA S1S2 A1A2
主主主主主
PMG 勵勵勵
Exciter 整整整
3Ø Bridge Generator 220V
C.T
R
C.T
G S
~ C.T
T
E0 E1 6 7 8 S1 S2 S1 S2 S1 S2
P2 P3 P4 XX X
U V W
K1 K2 B0 B1 2 1 1 2 3 A B C
1K 歐歐 1KΩ
For
外外外整external adjusted
※ Use only original supplied spare protection fuse for fuse replacement.
※ Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.
______________________________________________________________________________________
6
MX321