Académique Documents
Professionnel Documents
Culture Documents
Abstract: - The objective of this work is to analyze a load flow program based on Newton Raphson method and
Fast Decoupled method. MATLAB software is used for this study. The program was run on an IEEE 30-bus
system test network and the results were compared and validated for both the methods. Both the Newton-
Raphson method and the fast decoupled load flow method gave similar results. However, the fast decoupled
method converged faster than the Newton-Raphson method. The bus voltage magnitudes, angles of each bus
along with power generated and consumed at each bus were evaluated. It is estimated that the total power
generated is 192.06 MW whereas the total power consumed is189.2 MW. This indicates that there is very less
line loss of about 2.86 MW. Moreover, the fast decoupled load flow method is verified to be more efficient and
consistent method of obtaining optimum solution for a load flow problem.
Keywords- IEEE 30 bus system, Newton Raphson method, fast decoupled load flow, power losses,
optimal load flow.
and
Qi f i ∑ ( Gij e j − Bij f j ) − ei ∑ ( Gij f j + Bij e j )
n n
=
=j 1 =j 1 V1 . .
where Gij and Bij refers to conductance and VD = . V2 .
∆P ∆θ Pi ,cal= P=
i ∑V j =1
i
= − J
∆Q ∆V
V Gii Vi 2 + ∑ Vi V j ( Gij cos θij + Bij sin θij )
n
Pi =
∆P H N ∆θ j =1
or = − −1
∆Q K L VD ∆V and
∆P J1 J 2
V j ( Gij sin θij − Bij cos θij )
n
∆Q = J J Qi ,cal= Q= ∑V
3 4
i
j =1
i
∆P1 ∆Q1
− Bii Vi 2 + ∑ Vi V j ( Gij sin θij − Bij cos θij )
n
∆P ∆Q Qi =
2 2 j =1
...... ......
where= ∆P =, ∆Q , The powers are computed at any (r + 1)th
...... ......
...... ...... iteration by using the voltages available from
previous iteration. The elements of the Jacobian
∆Pn −1 ∆Qm are found using the above equations as:
∆θ1 ∆V1
∆θ ∆V Elements of J1
2 2
∂Pi
...... ...... V j {Gij (− sin θij ) + Bij cos θij }
n
∆θ
= =, ∆V ,
=
∂θi
∑V i
...... ......
j =1
j ≠i
...... ...... 2
= − Qi − Bii Vi
∆θ n −1 ∆Vm
∂θi
∑V
j =1
i method is an extension of Newton method. This
j ≠i method involves certain assumptions in the
=Pi − Gii Vi
2 traditional load flow equations. Further
physically justifiable simplifications may be
∂Qi
− Vi V j ( Gij cos θij + Bij sin θij )
= carried out to achieve some speed advantage
∂θi without much loss in accuracy of solution using
Elements of J4 (DLF) model [16]. The result is a simple, faster
and more reliable than the (NR) method called
∂Pi the fast decoupled load flow (FDLF) method. If
−2 Vi Bii + ∑ Vi V j ( Gij sin θij − Bij cos θij )
n
2
Vi =
∂ Vi j =1 the coefficient matrices are constant, the need to
2
j ≠i
update the Jacobian per iteration is eliminated.
=Qi − Bii Vi This has resulted in development of fast
∂Qi decoupled load Flow (FDLF). Sub-matrices H
= Vi V j ( Gij sin θij − Bij cos θij ) and L can be further simplified, using the
∂ Vj
guidelines given below to eliminate the need for
Elements of J2 re-computing of the sub-matrices per iteration
[17].
∂Pi
∑ V (G cos θij + Bij sin θij )
n
2
2 Vi Gii + Vi
Vi =
∂ Vi
j ij
j =1 Mathematical model for fast decoupled load
j ≠i
2 flow method
=Pi + Gii Vi The basic equations for fast decoupled load
∂Pi flow method are as
= V j Vi V j ( Gij cos θij + Bij sin θij )
∂ Vj ∆P
V= [ B′][ ∆θ ]
Thus the linearized load flow equation can be
rewritten as ∆Q
V = [ B′′][ ∆V ]
∆θ
∆P H N where [ B′] = negative imaginary elements of
∆Q = K ∆V
L YBUS matrix.
V
To solve the load flow equations using FDLF
method, following assumptions need to be
3 Fast Decoupled Load Flow Method implemented:
The Newton power flow is a robust power flow a) In formation of [ B′] matrix, shunt reactances
algorithm. It is also called full AC power flow and in phase transformer taps are neglected.
since there is no simplification in the b) Line series resistances are neglected in
calculation. However, the disadvantage of the forming [ B′] .
Newton power flow method is that in it the
Based on above assumptions, power flow
terms of the Jacobian matrix needs to be
equations can be rewritten as
recalculated per iteration [15]. Actually, the
∆P J1 . ∆θ
reactance of the branch is generally far greater ∆Q = .
J 4 ∆V
than the resistance of the branch in a p ractical
power system. Thus there exists a strong ∂P
∆P = J1∆θ = ∆θ
relationship between the real power and the ∂θ
voltage angle, but weak coupling between the ∂Q
∆Q = J 4 ∆V = ∆V
real power and the magnitude of voltage. To ∂V
solve load flow problems, many decoupled From the above equations, it is clear that the
versions of Newton Raphson method have been general load flow equation has been decoupled
developed from time to time. Fast decoupled leading to simpler calculations and reduced
START
NEWTON
RAPHSON Are ΔPi and ΔQi >ɛ
FDLF
YES
J 2 ∆θ ∆θ
∆P J1 ∆P J1 0
∆Q = J Calculate line flows and line losses ∆Q = 0 ∆V
3 J 4 ∆V J 4
V
STOP
Table 1: Load bus data for IEEE 30 bus system using NR method
nl nr nl to nr nr to nl P Q
MW Mvar
1 2 1.778+j-0.221 -1.723+j0.327 0.055 0.105
1 3 0.832+j0.051 -0.804+j0.02 0.028 0.071
2 4 0.457+j0.027 -0.446+j0.032 0.011 -0.005
3 4 0.780+j-0.032 -0.772+j0.045 0.008 0.013
2 5 0.830+j0.017 -0.8+j0.065 0.03 0.082
2 6 0.619+j-0.01 -0.599+j0.032 0.02 0.023
4 6 0.701+j-0.175 -0.695+j0.187 0.006 0.012
5 7 -0.142+j0.105 0.144+j-0.122 0.002 -0.017
6 7 0.375+j-0.019 -0.372+j0.013 0.004 -0.006
6 8 0.295+j-0.038 -0.294+j0.032 0.001 -0.006
6 9 0.277+j-0.297 -0.277+j0.331 0 0.034
6 10 0.158+j-0.113 -0.158+j0.134 0 0.021
9 11 -0+j-0.157 0.000+j0.161 0 0.005
9 10 0.277+j0.067 -0.277+j-0.059 0 0.008
4 12 0.441+j-0.46 -0.441+j0.561 0 0.101
12 13 -0+j-0.103 0.000+j0.104 0 0.001
12 14 0.079+j0.024 -0.078+j-0.023 0.001 0.002
12 15 0.179+j0.069 -0.176+j-0.065 0.002 0.004
12 16 0.072+j0.034 -0.072+j-0.033 0.001 0.001
14 15 0.016+j0.007 -0.016+j-0.007 0 0.000
16 17 0.037+j0.015 -0.036+j-0.014 0 0.000
15 18 0.060+j0.017 -0.06+j-0.017 0 0.001
18 19 0.028+j0.008 -0.028+j-0.008 0 0.000
19 20 -0.067+j-0.026 0.067+j0.027 0 0.000
10 20 0.090+j0.036 -0.089+j-0.034 0.001 0.002
10 17 0.054+j0.044 -0.054+j-0.044 0 0.000
10 21 0.157+j0.098 -0.156+j-0.096 0.001 0.002
10 22 0.076+j0.045 -0.075+j-0.044 0.001 0.001
21 22 -0.019+j-0.016 0.019+j0.016 0 0.000
15 23 0.050+j0.03 -0.05+j-0.029 0 0.001
Table 5: Optimal power flow results for IEEE 30 bus system using NR method
Lambda($/MVA-
Voltage Generation Load hr)
Bus
P Q P Q P Q
Mag(p.u) Ang(deg) (MW) (Mvar) (MW) (Mvar) (MW) (Mvar)
1 0.982 0 41.54 -5.44 - - 3.662 -
2 0.979 -0.763 55.4 1.67 21.7 12.7 3.689 -
3 0.977 -2.39 - - 2.4 1.2 3.754 -0.016
4 0.976 -2.839 - - 7.6 1.6 3.771 -0.021
5 0.971 -2.486 - - - - 3.744 -0.001
6 0.972 -3.229 - - - - 3.779 -0.02
7 0.962 -3.491 - - 22.8 10.9 3.801 0.003
8 0.961 -3.682 - - 30 30 5.383 1.405
9 0.99 -4.137 - - - - 3.823 0.02
10 1 -4.6 - - 5.8 2 3.846 0.039
11 0.99 -4.137 - - - - 3.823 0.02
12 1.017 -4.498 - - 11.2 7.5 3.81 -
13 1.064 -3.298 16.2 35.93 - - 3.81 -
14 1.007 -5.04 - - 6.2 1.6 3.868 0.018
15 1.009 -4.814 - - 8.2 2.5 3.856 0.018
16 1.003 -4.839 - - 3.5 1.8 3.849 0.031
17 0.995 -4.887 - - 9 5.8 3.862 0.047
18 0.993 -5.484 - - 3.2 0.9 3.911 0.047
19 0.987 -5.688 - - 9.5 3.4 3.926 0.058
20 0.99 -5.472 - - 2.2 0.7 3.91 0.055
21 1.009 -4.621 - - 17.5 11.2 3.854 0.017
22 1.016 -4.503 22.74 34.2 - - 3.843 -
23 1.026 -3.756 16.27 6.96 3.2 1.6 3.813 -
24 1.017 -3.885 - - 8.7 6.7 3.884 0.028
25 1.044 -2.072 - - - - 3.932 0.022
26 1.027 -2.476 - - 3.5 2.3 3.999 0.067
27 1.069 -0.715 39.91 31.75 - - 3.916 -
28 0.982 -3.215 - - - - 4.106 0.25
29 1.05 -1.849 - - 2.4 0.9 3.966 -0.059
30 1.039 -2.643 - - 10.6 1.9 4.051 -0.012
Total: 192.06 105.08 189.2 107.2
Fig. 4: Graph showing losses as per active and reactive powers due to bus branches in
IEEE 30 bus system.