ED-FUW-2014

Catalogue/Engineering Data (50 Hz/60 Hz)

Large-Sized Chilled Water Fan


Coil Unit (50/60 Hz)

FUW015A FUW020A
FUW025A FUW030A
FUW035A FUW040A
FUW050A

DAIKIN INDUSTRIES, LTD.


Literature No.: ED-FUW-1405A
Part No.: M08039130033

Contents

Nomenclature............................................................................................................................2

Features....................................................................................................................................2

Electric Heater Power................................................................................................................3

Specifications............................................................................................................................4

Components data......................................................................................................................5

Sound data................................................................................................................................6

Performance correction coefficient............................................................................................7

Outline and dimensions.............................................................................................................8

Electrical data..........................................................................................................................10

Wiring diagrams......................................................................................................................11

Installation...............................................................................................................................13

Service and maintenance........................................................................................................15

Trouble shooting......................................................................................................................16

Exploded view and part list......................................................................................................17

Note: Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.

Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning: Moving machinery and electrical power hazard. May cause severe personal injury or
death. Disconnect and lock off power before servicing equipment.

1
Nomenclature
FUW  030  A- 4  L -A AA E 

E:export
U:"Made in China" label
Design series
A:220-240V/1Ph/50Hz
K:208-230V/1Ph/60Hz

L-Left hand (Facing discharge)


R-Right hand (Facing discharge)
4-4 coil rows; 6-6 coil rows
A-Design Serial No.
030-Nominal airflow is 3000 m3/h
FUW-Large-Sized FCU

Features
General Information
DAIKIN for years has been committed to provide high quality air handling systems of various models and types,
and has made remarkable achievements in the industry. As a new generation of products, the FUW series slim ceiling
air handling units are launched by DAIKIN to adapt to the increasingly cramped building layout.
In addition to the outstanding performance of previous DAIKIN air handing units, the FUW series slim ceiling air
handling units feature a slim size, only 420mm in height. The airflow is adjustable within the range of three levels to
meet different air flow needs. Powered by a 50 or 60Hz single-phase power supply, this series eliminates the need
for users to expand the power capacity. The FUW series can be mounted in a wide variety of places, especially those
with limited space and high noise. Featuring easy installation and flexible use, the FUW series helps minimize the
indoor space and maximize customers’ benefits.

Structure
The high-strength galvanized steel sheets, coated with electrostatic spraying, are highly corrosion-proof.
Made of a new type of PE material, the heat insulator features ideal thermal insulation, sound absorption, and no
moisture permeability. The insulator is also proof against cold bridge.

Fans
With efficient tilted multi-blade centrifugal fans, this unit provides low noise but high reliability. The fan and the motor
are coupled directly. The high-precision and quality ball bearing eliminate the need for lubricating.

Multi-level Speed Control


Driven by a single-phase capacitor-running asynchronous motor, the unit can be adjusted at three levels to provide
different amounts of air flow.

Filters
The air inlet is equipped with primary nylon filters.

Heat Exchanger
Made on the OAK manufacturing facility the heat exchanger uses thin-walled copper tubes mechanically expanded
into new-type fins, to ensure close contact between the cooper tubes and fins. This enables the coils to provide best
heat exchange and the units to run reliably and efficiently.

Performance
FUW series products feature high external total pressure (ETP) and large cooling capacity. Slim in size and simple in
structure, this series makes it easy for installation and maintenance.
2
Electric Heater Power
Electric Box Model Power Supply Capacity(kW)

MHW-EH-020BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 2

MHW-EH-030BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 3

MHW-EH-040BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 4

MHW-EH-050BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 5

MHW-EH-060BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 6

MHW-EH-075BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 7.5

NOTES:
EACH HEATER BOX CAN ONLY BE USED FOR ONE AIR DISCHARGE DUCT.
1) FUW015/20/025 - ONLY ONE HEATER BOX IS REQUIRED.
2) FUW030/035/040/050 - NEED TO SELECT TWO BOX.

3
Specifications
General data
MODEL FUW015A FUW020A FUW025A FUW030A FUW035A FUW040A FUW050A
NOMINAL AIR FLOW m3/h 1500 2000 2500 3000 3500 4000 5000
EXTERNAL TOTAL PRESSURE Pa 70 100 100 120 120 150 150
POWER SOURCE V/Ph/Hz 220-240/1/50 208-230/1/60
4 ROWS(RETURN AIR) 6 10 12 16 18 23 29
4 ROWS(FRESH AIR) 19 27 31 40 47 57 70
COOLING
6 ROWS(RETURN AIR) 10 15 17 22 26 31 37

NOMINAL 6 ROWS(FRESH AIR) 25 34 39 49 61 70 84


kW
CAPACITY 4 ROWS(RETURN AIR) 11 16 19 24 28 34 42

HEATING 4 ROWS(FRESH AIR) 21 30 34 43 52 61 73


6 ROWS(RETURN AIR) 15 21 23 29 36 42 50
6 ROWS(FRESH AIR) 26 36 41 51 64 74 87
4 ROWS(RETURN AIR) 1.01 1.77 2.40 3.13 3.09 3.91 5.32
4 ROWS(FRESH AIR) 3.26 4.69 6.07 7.65 8.21 9.78 12.89
COOLING
6 ROWS(RETURN AIR) 1.78 2.57 3.36 4.18 4.58 5.36 7.06

WATER 6 ROWS(FRESH AIR) 4.3 5.95 7.61 9.29 10.5 12.15 15.59
m3/h
FLOW 4 ROWS(RETURN AIR) 0.96 1.38 1.80 2.27 2.42 2.91 3.83
4 ROWS(FRESH AIR) 1.85 2.57 3.26 4.07 4.47 5.28 6.83
HEATING
6 ROWS(RETURN AIR) 1.27 1.78 2.28 2.79 3.14 3.64 4.69
6 ROWS(FRESH AIR) 2.30 3.14 3.98 4.84 5.52 6.36 8.10
4 ROWS(RETURN AIR) 5 14 24 14 13 25 40
4 ROWS(FRESH AIR) 39 40 46 32 36 46 74
COOLING
6 ROWS(RETURN AIR) 14 27 54 21 44 45 75
WATER 6 ROWS(FRESH AIR) 77 89 96 76 79 103 113
PRESSURE kPa
DROP 4 ROWS(RETURN AIR) 4 12 10 9 11 19 24
4 ROWS(FRESH AIR) 20 26 24 26 20 31 67
HEATING
6 ROWS(RETURN AIR) 12 24 24 12 32 30 32
6 ROWS(FRESH AIR) 42 49 62 56 53 68 70
LENGTH 750 910 1070 1220 1370 1520 1850
UNIT DIMENSION WIDTH 750 750 750 750 750 750 750
HEIGHT 420 420 420 420 420 420 420
mm
LENGTH 950 1110 1270 1420 1570 1720 2050
PACKING DIMENSION WIDTH 1030 1030 1030 1030 1030 1030 1030
HEIGHT 580 580 580 580 580 580 580
4 ROWS 76 80 86 92 96 102 108
WEIGHT kg
6 ROWS 79 84 90 96 101 107 113

NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY .
3) STANDARD AIR RETURN COOLING CONDITIONS: 27°C DB/19.5°C WB; STANDARD FRESH AIR COOLING CONDITIONS: 34°C DB/28°C WB;
STANDARD COOLING WATER ENTERING/LEAVING CONDITIONS: 7°C/12°C
STANDARD AIR RETURN HEATING CONDITION: 21°C DB; STANDARD FRESH AIR HEATING CONDITION: 0°C DB;
STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60°C/50°C
4) THE PARAMETERS IN THE ABOVE TABLE ARE MEASURED AT THE ALTITUDE OF 0M ABOVE SEA LEVEL, AND MAY VARY WITH
THE ALTITUDE.

4
Components data
MODEL FUW015A FUW020A FUW025A FUW030A FUW035A FUW040A FUW050A

STRUCTURE TYPE Galvanized steel coated with elextrostatic spraying, internal glued with insulator PE

TYPE Corrugated aluminum fin mechanically bonded with copper tube

TUBE DIAMETER(mm) 9.53

FPI 12
COIL
WORK PRESSURE(MPa) 1.6

INLET/OUTLET PIPE R1½’’

CONDENSING WATER PIPE R¾’’

TYPE/MATERIAL Centrifugal forward curved blower and galvanized steel

FAN NO. 1 2
FAN
DRIVE TYPE Direct drive

AIR DISCHARGE Lower horizontal air discharge

TYPE Single phase capacitor running

QUANTITY 1 2
MOTOR
INDEX OF PROTECTION(IP) IP20

INSULATION CLASS B

TYPE/MATERIAL Primary nylon

THICKNESS 21
FILTER
SIZE HEIGHT mm 345

LENGTH 536 696 856 1006 1156 1306 1636

TYPE/MATERIAL Cold-rolled steel plate

DRAIN PAN THICKNESS(mm) 1.0

INSULATION 5mm PE

NOTES:
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

5
Sound data
1/1 Octave Sound pressure level (dB(A), ref 20μPa)
Overall
Unit ESP Speed dB(A)
63 125 250 500 1k 2k 4k 8k

High 24 36 34 40 38 34 27 19 44.1

FUW015A 70Pa Medium 21 33 30 37 34 30 21 15 40.7

Low 19 31 27 34 30 27 17 14 37.7

High 28 43 43 43 46 41 33 27 50.6

FUW020A 100Pa Medium 27 41 41 41 42 38 30 23 48.0

Low 25 38 37 39 40 35 26 20 45.1

High 37 49 49 50 48 46 37 27 55.7

FUW025A 100Pa Medium 34 46 46 46 44 42 33 23 52.2

Low 28 45 40 42 39 36 28 18 48.4

High 29 45 46 46 46 40 33 25 52.5

FUW030A 120Pa Medium 27 43 46 44 43 37 29 21 50.5

Low 26 42 44 42 40 34 26 17 48.5

High 37 46 45 47 46 45 43 36 53.5

FUW035A 120Pa Medium 35 45 43 46 45 44 41 35 52.1

Low 33 43 41 44 43 42 40 33 50.2

High 30 45 44 48 49 44 35 27 53.6

FUW040A 150Pa Medium 29 43 42 46 47 41 32 24 51.5

Low 27 43 40 45 43 38 29 21 49.5

High 35 49 49 50 52 48 40 33 57.0

FUW050A 150Pa Medium 34 49 48 49 51 47 39 32 56.0

Low 31 49 47 48 49 45 37 30 54.9

NOTE:
SOUND PRESSURE LEVELS ARE TESTED IN BAFFLE CHAMBER, WITH BACKGROUND NOISE LEVEL: 11.5 dB(A), MICROPHONE
POSITION IS 1 METER IN FRONT AND 1 METER BELOW THE UNIT.

6
Performance correction coefficient
Cooling capacity performance curve

The above curve shows the cooling capacity variations at different The above curve shows the cooling capacity variations at different
entering water temperatures. entering water temperatures.
Standard return air: 27ºC DB/19.5ºC WB; Standard return air: 34ºC DB/28ºC WB;
Temperature difference between entering and leaving water: 5ºC Temperature difference between entering and leaving water: 5ºC
The cooling capacity correction factors are based on the cooling The cooling capacity correction factors are based on the cooling
capacity (using 1 as the coefficient) in standard cooling water entering/ capacity (using 1 as the coefficient) in standard cooling water entering/
leaving conditions (7ºC for entering water/12ºC for leaving water). leaving conditions (7ºC for entering water/12ºC for leaving water).

Heating capacity performance curve

The above curve shows the heating capacity variations at different The above curve shows the heating capacity variations at different
entering water temperatures. entering water temperatures.
Standard return air: 21ºC DB; Standard return air: 0ºC DB;
Temperature difference between entering and leaving water: 10ºC. Temperature difference between entering and leaving water: 10ºC
The heating capacity correction factors are based on the heating The heating capacity correction factors are based on the heating
capacity (using 1 as the coefficient) in standard cooling water entering/ capacity (using 1 as the coefficient) in standard cooling water entering/
leaving conditions (60ºC for entering water/50ºC for leaving water). leaving conditions (60ºC for entering water/50ºC for leaving water).

NOTES:
1) THE BLACK CURVE SHOWS THE CAPACITY OF A 4-ROW-COIL UNIT AND THE GRAY CURVE THE CAPACITY OF A 6-ROW-COIL UNIT.
2) COMPARED WITH THE COEFFICIENT (SET TO 1) OF THE UNIT IN STANDARD OPERATING CONDITIONS (ENTERING WATER
AT 60ºC, AND LEAVING WATER AT 50ºC), THE VARIATION COEFFICIENT VARIES AS FOLLOWS WHEN THE ENTERING WATER
TEMPERATURE RETAINS AT 45ºC AND THE LEAVING WATER TEMPERATURE AT 40ºC:
STANDARD AIR RETURN CONDITION: 0.65 FOR A 4-ROW-COIL UNIT AND 0.64 FOR A 6-ROW-COIL UNIT; STANDARD FRESH AIR
CONDITION: 0.8 FOR A 4-ROW-COIL UNIT AND 0.78 FOR A 6-ROW-COIL UNIT.

7
Outlines and dimensions
FUW015A, FUW020A, FUW025A

Unit: mm
Dimensions A B C D
Model
FUW015A 750 540 238 667

FUW020A 910 700 318 827

FUW025A 1070 860 398 987

FUW030A, FUW035A, FUW040A, FUW050A

Unit: mm
Dimension A B C D E
Model
FUW030A 1220 1010 268 176 1137

FUW035A 1370 1160 323 216 1287

FUW040A 1520 1310 333 346 1437

FUW050A 1850 1640 398 546 1767

8
Electric Box

Scheme of Electric Box Installation

Electrical Heater

Flexile Pipe Connection

FUW Unit

NOTE:
THE FLEXIBLE PIPE CONNECTION
NEEDS FIELD SUPPLIED.

9
Electrical data
MODEL FUW015A FUW020A FUW025A FUW030A FUW035A FUW040A FUW050A

POWER SOURCE 220-240V/1Ph/50Hz

TYPE Asynchronous single phase

INSULATION CLASS B

PROTECTION CLASS IP20

MOTOR 4 ROWS 373 614 787 797 905 1248 1533


RATED INPUT W
POWER
6 ROWS 397 653 823 845 1016 1362 1699

4 ROWS 1.72 2.96 3.61 3.62 4.22 5.68 6.98


RATED INPUT A
CURRENT
6 ROWS 1.81 3.01 3.78 3.96 5.10 6.29 7.86

NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL DATA ARE BASED ON HIGH SPEED,STANDARD ESP.

MODEL FUW015A FUW020A FUW025A FUW030A FUW035A FUW040A FUW050A

POWER SOURCE 208-230V/1Ph/60Hz

TYPE Asynchronous single phase

INSULATION CLASS B

PROTECTION CLASS IP20

MOTOR 4 ROWS 279 387 945 619 733 1584 2063


RATED INPUT W
POWER
6 ROWS 273 445 1137 681 1222 1607 2134

4 ROWS 1.28 1.79 4.35 2.83 3.41 7.59 9.55


RATED INPUT A
CURRENT
6 ROWS 1.25 2.03 5.29 3.19 5.97 7.73 9.89

NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL DATA ARE BASED ON HIGH SPEED,STANDARD ESP.

10
Wiring diagrams
FUW015A, FUW020A, FUW025A

MODEL: FUW015A/020A/025A

HF

MF M~

LF

FUW030A, FUW035A, FUW040A, FUW050A

MODEL: FUW030A/035A/040A/050A

HF

MF M~

LF

M~

11
WIRING OF ELE-HEATER

ć
ć

12
Installation
Important Notice
Installation and maintenance are to be performed only by technicians who are familiar with local rules and regulations,
and experienced with this type of equipment.
Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate.
Cut off all power supplies before mounting or maintaining the unit.
Electric connections must conform to local laws and regulations.
The voltage should fluctuate within the range of ± 10% of the rated voltage.
The unit must be well earthed to prevent insulation failures.
All the wires must be securely connected.
The design of water pipes and ducts must conform to the specifications of heating, ventilation and air conditioning
norms and regulations.

Mounting Location
Make sure it’s convenient to connect wires and pipes in the selected mounting location. The minimum space reserved
around FUW units is shown in Figure 1.

Figure 1

13
Suspending Installation
During suspending installation, please handle the unit or packing case with care, to avoid damage to any part.
Before leaving the factory, the unit or its packing case already has forklift handling holes or hoisting holes. During the
hoisting, the lifting poles should be strong enough to bear the unit weight. Please handle the FUW unit as shown in
Figure 2.

Figure 2

Storage
When a unit is placed outdoors before it is installed in an equipment room, please protect it from dirt, rain, snow and
even animals. Be sure not to damage the protective film on its surface.

Base Setup
Adjust the base level.
The base, if not on a level surface, may result in water leakage or break the dynamic balance of the fan due to poor
drainage of condensing water, or cause the bearing malfunction or vibrate.
The base height should match the U-shaped pipe bend. The drain pipe should be connected with the U-shaped water
seal, as shown in Figure 3.

TRAP INSTALLATION
DRAIN PIPE
H

NOT MORE THAN 1/2H

DRAIN PLUG

H is more than the negative pressure of unit + 20 mm


1mm H 2 O = 9.8 Pa
Figure 3

14
Service and maintenance
Notices
Responsibilities and Obligations
This product comes to you with the DAIKIN service warranty. Only DAIKIN technicians or experienced technicians
authorized by DAIKIN are allowed to install, test or maintain these products.

Use the Unit


After installing the piping system, please first flush the pipes. To do so, be sure to shut off the valve connected to the
unit, to prevent contamination in the pipes from entering the coils or blocking the loop.
After the installation, please check there is anything sundries inside the fan. Turn the blades by hand. If no unusual
noise is heard, turn on the fan, to see if it is running properly.
Before turning on the water flow, please open the exhaust valve to let the air out of the pipe till water flows from the
pipe.
When the unit stops running, fill the coil with water or by other means to prevent pipe corrosion.
When the environment temperature falls below 0°C in the winter, drain the pipe to prevent it from freezing.
Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every 2 or 3
years. If possible, please use soft water in the coils.
Check the unit filter for dust regularly; if possible, please use a pressure difference gauge. Once the resistance
reaches the limit, wash or replace the filter media in time.
After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.

Service and Maintenance


A good maintenance schedule helps reduce operational failures.
A dirty filter may worsen the performance and air flow of the unit. Thus, replace or wash the filter in time. Be sure to
check the filter every month to see if it is clean enough.
Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum cleaner
to clean the dust.
Do the following on a regular basis:
Clean up the fans every 6 months, to keep them in good balance.
Check and clean the drain pan. Check the drain pipe in case dust or sundries block the pipes.
Clean the dirt in the water coils at regular intervals.

15
Trouble shooting
Common Location Possible causes Solutions
failures
Blower offset Contact the dealer
Loose bearing due to big gap Contact the dealer
Blower is loose Contact the dealer
1. Blower
Blower is damaged Contact the dealer
The fastening fan screw is loose Fasten the screw
There are sundries inside fans Remove sundries
2. Drive The screw fixing the motor to the motor base is loose Fasten the screw
There are sundries inside housing Remove sundries
3. Fan housing Housing is loose Contact the dealer
Air intake housing is damaged Contact the dealer
Incoming wire is loose Fasten the incoming wire
4. Electric appliances
Motor gives AC hum Contact the dealer
Bent or distorted Replace shaft
Abnormal 5. Shaft Balance weight is loose Fasten the balance weight
sound
Shaft is loose Fasten shaft
6. Air speed is too Duct is too small Re-design the duct
high Static pressure doesn't reach the designed ESP value Use the lower fan speed.
Duct is too small Re-design the duct
7. Periodical vibration System is unstable Adjust the system
Duct vibrates as the fan pulsates Adjust the fan speed
8. Noise caused by
hi-speed wind Duct leaks Seal it with glue
passing the gap &
holes
Duct bends abruptly Re-design duct
Duct expands sharply Re-design duct
9. When blocked, the
high-speed air Duct shrinks sharply Re-design duct
rattles or howls
Air speed is too high inside duct Re-design duct
Anti-vibration joint is too high Re-adjust the damping connector
1. Fan Blower is mounted incorrectly Contact the dealer.
Actual resistance exceeds the designed value. Re-design the system
2. Duct system Duct is poorly sealed Seal it with glue
Fireproof damper is shut off Turn on the fireproof damper
3. Filter Too dirty or blocked Clean or replace the filter
4. Coil Too dirty or blocked Clean coils
Fan
operates 5. Air flow is The air inlet and air outlet are not properly isolated. Thus, the air Add air separator
normally short-circuited. runs directly to the air inlet
but the
air flow is Elbow at the air return area fan outlet are too close to the unit Move the fan
insufficient 6. Fan inlet is blocked wallboard
The fan outlet is blocked Remove the obstructions
A length of straight tube is mounted at the fan outlet during fan
7. No straight tube at testing. Without straight tube, the fan performance might be
the fan air outlet worsened. Thus, the fan may run faster to overcome the resistance Install straight tube
(check the fan speed)
8. There are sundries The fan outlet is blocked Remove the obstructions
inside fan system There is an elbow tube at the fan outlet Re-design duct
Improper duct size Re-design
The access door is open Close the access door
The fan is The system is not well balanced and the actual resistance is lower Re-design the system
functioning 1. System than the set resistance
but the air
supply is No air damper or air damper blade Install air damper or air damper
too large blade.
Filter falls off or no filter installed Re-mount the filter
2. Duct Return duct leaks Seal with glue
1. Filter Filter is too dirty or blocked Clean or replace filter
The air in
the air-
conditioned
room is 2. Fresh air No enough fresh air Supply more fresh air
not fresh
enough

16
The air conditioners manufactured The airconditioning factories of
by Daikin Industries have received Daikin Industries have received
ISO 9001 series certification for environmental management system
quality assurance. standard ISO 14001 certification.
Certificate Number. 9601019 Certificate Number. EMS80362

Cautions on product corrosion


1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the
unit close to the sea shore, contact your local distributor.

DAIKIN INDUSTRIES, LTD.


Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/

© All rights reserved

Printed with soy ink.

Literature No.: ED-FUW-1405A

Vous aimerez peut-être aussi