This document is published by the BCA Centre for Sustainable Buildings Ltd.
All rights reserved. This document or any part thereof may not be reproduced for any reason whatsoever in any
form or means whatsoever and howsoever without the prior written consent and approval of the BCA Centre for
Sustainable Buildings Ltd.
Whilst every effort has been made to ensure the accuracy of the information contained in this publication, the
BCA Centre for Sustainable Buildings Ltd, its employees or agents shall not be responsible for any mistake or
inaccuracy that may be contained herein and all such liability and responsibility are expressly disclaimed by these
said parties.
ISBN: 978-981-09-1566-7
Being the first in Asia and one of the few collaborating centres with UNEP, the Centre is well equipped to develop
and deliver policy advice and outreach assistance to countries for sustainable development in the building sector.
This assistance would be provided in close consultation with UNEP through the identification of successful policies,
strategies and technologies at the regional and national level as we strive to grow the Centre into a hub for green
buildings in the region, and contribute to global climate mitigation efforts.
Acknowledgements
BCA Centre for Sustainable Buildings would like to thank our collaborating partner the Building and Construction
Authority for their invaluable support in this endeavour.
In addition, the Centre would like to express our gratitude to the following for their contributions to this publication,
and also their consent to use their materials and photographs.
We would also like to thank all the different individuals who have contributed in one way or another to the successful
completion of this publication.
Foreword
Five years ago, the launch of the Zero Energy Building (ZEB) placed the Building
and Construction Authority (BCA) on the research and development (R&D) map for
pioneering this initiative at the Singapore Green Building Week in 2009. Since then,
ZEB has been continuing to operate at net zero.
Since its opening, some 23,000 visitors including building professionals, policy makers, academia, industry, researchers
and students have visited ZEB. I am happy to note that the interest to visit and learn from ZEB remains strong, with many
travelling all the way from Europe, the Far East and the Americas. We are also maintaining the ZEB up-to-date with a
sustained flow of new test-beds of different green building technologies.
This project would not have been possible without the valuable contributions from the funding agencies Ministry of
National Development and Economic Development Board; the researchers from NUS; consultants from DP
Architects, Beca Carter, and Langdon & Seah; the main contractor ACP Construction; the solar integrator
Grenzone; and the operation team.
The experience in developing and operating ZEB have been documented by the BCA Centre for Sustainable Buildings
(BCA CSB) in this second publication Leading the Way to Net Zero, 2009-2014: Inside SE Asia’s First Retrofitted Zero
Energy Building, following from its first publication released in 2013, Using Less, Getting More: An Overview of Building
Energy Efficiency Initiatives in SE Asia Region.
BCA CSB’s key goal is to help raise awareness and to facilitate knowledge transfer. We hope that this publication will be
a useful and valuable reference for all stakeholders in Singapore as well as in the region. Let us all do our utmost to push
the boundaries of building performance to create a better and greener built environment for all.
Dr John Keung
Chairman
BCA Centre for Sustainable Buildings
I am happy to see the Centre’s commitment to raising visibility to and sharing knowledge of sustainable buildings
to partners in the region and beyond, and I look forward to more of such publications from the Centre. I also look
forward to greater collaborations with BCA CSB to address pressing issues of the industry in order to make ours a
quality urban environment.
Director
BCA Centre for Sustainable Buildings
List of abbreviations
and acronyms
ACMV – Air-conditioning and mechanical ventilation
PI – Principal Investigator
PV – Photovoltaic
UV – Ultraviolet
References 68
Introduction
10
Quotes from participating teams
Beca Carter Hollings & Ferner (S.E Asia) Pte Ltd was the M&E Consultant, C&S
Consultant, Project Manager and Green Mark Consultant for the project.
— Ms Irene Yong
Director
Building Services
Beca Carter Hollings & Ferner (S.E Asia) Pte Ltd
My earliest involvement with this project was in 2005 when BCA arranged
with NUS to have a number of overseas academics together with local experts,
provide their insights into the use of energy sustainable designs involving the use
of light shelves, light ducts, photovoltaic panels and alternative air conditioning
systems combining the use of chilled beams and ceiling/under-floor cooling. ……
our firm were the original architect.
— Mr Arthur Loh
Consultant
DP Architects Pte Ltd
[I was the] Researcher and Principal Investigator from NUS of MND research
project on Advanced Daylighting and Building Integrated Photovoltaics.
— Professor Stephen Wittkopf
Professor, Head of Competence Centre Envelopes and Solar Energy
Lucerne School of Engineering and Architecture
Lucerne University of Applied Sciences and Arts
I was the Principal Investigator for the research project called “Future Green
School of ZEB@BCA” funded by MND Research Fund. The research looked into
developing a prototype of future school in the tropics, and implementing passive
cooling and daylighting strategies.
— Professor Wong Nyuk Hien
Professor
Department of Building, School of Design and Environment
National University of Singapore
I was a research assistant to Professor Wong Nyuk Hien under the research
project of “Future Green School of ZEB@BCA”. ...… I joined the project since construction
phase and had assisted in supervising the construction, operation and maintenance
of the related green features as well as data collection and analysis for study.
— Ms Erna Tan
Research Assistant
Department of Building, School of Design and Environment
National University of Singapore
ZerO is the goal
Workshop being conducted in ZEB’s multi-purpose room
With conventional energy resources being depleted of other natural resources, the success of a building in
at an alarming rate globally, the search for means to achieving zero energy is exciting and has tremendous
conserve and renew energy has become increasingly implications for energy usage in all kinds of buildings.
urgent. As buildings are collectively one of the bigger
consumers of energy, the spotlight has fallen on them
and on improving the way they use energy.
Accolades
With the launch of BCA’s very own ZEB in October
2009, there is little reason to doubt that the idea of zero Standing proudly as an epitome of energy
energy building can be realised. What was originally efficiency, ZEB has earned the distinction of being
a three-storey workshop sitting on BCA Academy the first building in Singapore and Southeast
grounds was radically transformed to become a ZEB Asia successfully retrofitted with green building
that houses classrooms, offices, a library, a multi- technologies and achieving net zero energy. The
purpose hall, as well as a visitor centre. success of ZEB has been recognised with the
following awards:
Zero energy in the context of buildings simply means
that they become fully energy self-sufficient. In other Year 2009
words, the building is able to generate all of the • Singapore Green Mark Platinum Award
energy it needs to use or even more. For a country like
Singapore that is scarce in energy sources and devoid Year 2010
• Ministry of National Development Minister’s
Team Award
• Building Construction Information
Green Design Award
• Institution of Engineers Singapore
Prestigious Engineering Achievement Award
Year 2011
• Minister for National Development’s R&D
Award (Distinguished)
To ensure the entire project got off on the right foot,
the design approach was carefully
considered. The traditional approach
sees specialists working separately The experience of the project
in their own respective areas. team chosen for such a project is
Such compartmentalisation would very important.
not serve this unique project well.
Hence, an integrated approach — Ms Irene Yong
was adopted. All key stakeholders Beca Carter Hollings & Ferner (S.E Asia) Pte Ltd
worked together throughout the
different phases of the project to set
goals and ensure the building meets Coordination and
key parameters such as efficiency, communication among different
environmental sustainability, and parties (e.g. consultants, contractor,
aesthetics. Sharing of experiences, end-users and researchers) are
knowledge and expertise is important to ensure a
encouraged all the way to ensure successful project.
that the goals were fully achieved
(Centre for Sustainable Buildings — Ms Erna Tan
and Construction, 2010a). National University of Singapore
Project gets more intensive as it progresses. Project starts off intensively with time spent on
Less time is spent at the early stages. meetings, charrettes and discussions.
15
Ensure goals
Emphasise the
are met, e.g. via
integrated and
commissioning
‘co-designer’
approach to design
Evaluate
solutions
and iterate Think of the
Key building as
elements a whole
Conduct
assessments,
Work together
e.g. building
as a team from
simulations, life
the beginning
cycle assessments
17
Scoring zero - what it takes
There are many criteria to be met before a building can Energy-efficient M&E services refer to building systems
be net zero energy. Firstly, the building must be super that use energy efficiently both to provide comfort and
energy efficient. This means that the power needs of to facilitate the operation of equipment. In ZEB, energy-
the building will be brought down as much as possible, efficient lighting, energy-efficient air-conditioning and
without having to compromise on the comfort and mechanical ventilation (ACMV) systems have been
productivity of its occupants. Secondly, the building installed to ensure that whenever electricity is needed,
would have to be able to generate renewable energy to it is used most efficiently. To further reduce energy
cover all of its power needs, or in other words, be fully wastage, an intelligent Building Management System
energy self-sufficient. (BMS) and sensors were also installed to optimise the
use of air-conditioning and lighting tailored according to
While achieving great energy efficiency seems a daunting the occupants’ actual demands.
task, taking the right approach can make it much easier
to reach this goal. The team adopted an integrated
design approach that took into account two main RENEWABLE ENERGY
principles: passive design solutions as well as energy-
efficient mechanical and electrical (M&E) services. While cutting down on energy consumption is one
critical requirement for zero energy, it is not enough.
Inevitably, energy would be required to power equipment
PASSIVE DESIGN SOLUTIONS and systems throughout a building; hence, the building
must be able to generate at least sufficient energy to
Through passive design solutions, we are able to leverage meet such needs. Based on the information gathered
and optimise benefits from our natural environment by the team on local conditions, the use of solar PV
and along with a good understanding of geographical was the most logical solution for renewable energy in
principles, this will lead us to achieving comfort in a ZEB. The option of wind turbine was ruled out given
building without having to tap on the power supply. With the very low wind speeds in Singapore. To achieve
passive design, buildings can take advantage of existing desirable electrical outputs from wind turbines would
natural elements such as sunlight, air flow, landscape generally require wind speeds of up to 4.5 m/s (Centre
and even the immediate physical environment to reduce for Sustainable Buildings and Construction, 2010a)
energy consumption to a minimum. whereas average wind speeds in Singapore is less than
3 m/s (National Environment Agency, 2009). Hence, to
An early collaboration on the part of the design team, achieve energy self-sufficiency, ZEB is powered by solar
enabled passive designs to be effectively integrated into PV panels installed at multiple locations in the building.
the overall architectural concept, blending in seamlessly The energy thus generated is one hundred percent
either as part of the facade or as a building feature. clean and renewable.
The passive design solutions found in ZEB can be
categorised into three areas, namely reduction of heat
transmittance, enhancement of daylight and increase of
natural ventilation. It was an interesting experience
moving into the various possibilities
of energy conservation methods and
ENERGY-EFFICIENT M&E SERVICES their applications. It was recognized
that in a hot and humid environment
Unfortunately, passive design while useful, is insufficient. close to the equator, the options are
It is impossible to completely eliminate the use of energy not wide and in fact a single entity,
in a building. For instance, artificial lighting is required at the sun, is the main generator
night when there is no daylight, and cooling provisions of solutions.
in addition to natural ventilation is required to overcome
the island’s warm and humid climate. As such, energy- — Mr Arthur Loh
efficient M&E services were also introduced in ZEB. DP Architects Pte Ltd
18
ZEB
Passive
Energy-efficient Renewable
design
M&E services energy system
solutions
Increase
Reduce heat Enhance Energy-efficient Energy-efficient Solar PV
natural Intelligent BMS
transmittance daylight ACMV lighting system
ventilation
Guiding principles
K e y t akeaway p o in t s
• Zero energy for buildings means that they are fully energy self-sufficient and can generate all of the energy
they need.
• In developing ZEB, an integrated design approach was adopted which included all key stakeholders in every
aspect of the project from beginning to completion.
• The two main principles guiding the development of ZEB were passive design solutions and energy-
efficient M&E services.
»» Passive design solutions take advantage of natural and geographical conditions to reduce energy
consumption.
»» Energy-efficient M&E services refer to building systems that use energy efficiently to provide comfort and
operate equipment.
• To achieve energy self-sufficiency, ZEB is powered by solar PV panels installed at multiple locations in
the building.
19
Many technologies,
one goal
Green wall
The quest for energy efficiency has produced a myriad of Passive design solutions
technologies spanning many areas of building science,
with many of these already put into active service. To Reducing heat transmittance
bring ZEB to life, a montage of such green technologies
was incorporated into this groundbreaking building. Let Singapore’s tropical heat necessitates the use of air-
us take a closer look at each specific kind of technology conditioning in most commercial buildings. By reducing
used, categorising them according to the guiding the amount of heat entering the building in the first
principles highlighted in the previous section. place will lessen the reliance on air-conditioning and
therefore the amount of energy being used up. ACMV
systems in fact account for a big proportion of the
energy consumed in any building, so design features
This project has become a that minimise the infiltration of heat can help cut down
hands-on in implementing green energy consumption significantly. ZEB flaunts an array
building features. Some of the features of creative features that keep the heat out, energy usage
had not been constructed in Singapore down, and everyone in cool comfort.
before, and it was a good opportunity
to be involved directly in designing, Green wall and green roof
constructing, operating, maintaining as A number of benefits can be realised when greenery
well as studying the performance. is incorporated into a building. Firstly, through
direct shading and evapotranspiration, greenery
— Ms Erna Tan helps to reduce heat transmittance into a building.
National University of Singapore Evapotranspiration is a combination of the processes
of evaporation and transpiration. This involves the
movement of water to the air and movement of water
22
within a plant and the subsequent loss of water as
vapour through its leaves. This process of evaporation
effectively reduces ambient air temperature, and can
thus help to reduce heat transfer into a building.
23
Sunshade devices with integrated PV modules
Sun rays
Bulk of the
heat and
ultraviolet
radiation is
reflected out
Outdoor Indoor
Multi functions
With ZEB facades being exposed to direct sunlight, the sunshade devices used at ZEB helped to save energy.
Each sunshade was installed with a piece of thin film of amorphous PV panel. Each square metre of this panel can
generate enough electricity to power a 45-watt light bulb. With the total area of PV installed on the sunshades,
24 such light bulbs can be powered with the amount of electricity produced.
24
Enhancing daylight
Mirror duct
The mirror duct is a simple yet effective system that
does not require any mechanical parts or electrical
power to light up a space. ZEB is the first building in
Singapore to have mirror ducts installed.
Sun rays
External collector to capture
daylight and reflect the light
into the duct
Light travels
through duct via
multiple reflections
Openings
provided to allow
light to escape the
duct and light up
the space
Indoor Outdoor
25
Mirror ducts
Internal and external light shelves
Light shelves
Light shelves closely resemble sunshade devices except
that they extend into the interior of a building. The entire Sun rays
installation is placed above eye-level, and the upper
surface of the shelf which is highly reflective (National
Institute of Building Sciences, n.d.) will direct daylight
inwards by reflecting it from one surface to another,
similar to mirror ducts.
Reflective ceilings
In order for light to penetrate deeper into each room,
the light shelves in ZEB are enhanced by using
a ceiling material that has a reflective coating on
the surface. This maximises the reflection of light,
allowing it to spread deeper into interior spaces.
Light pipes
Sun rays
Light pipes are pipes used to channel light to the inner
spaces of a building. Placed vertically within a building,
one end of the pipe protrudes from the roof, while the
other leads into the inside of a room.
The performance of the solar chimney, however, could have been better if the
height of the chimney had been greater. Ideally, the height of the solar chimney of
ZEB should have been taller than it is now. However, the existing roof of ZEB was
not designed to take the load of a tall chimney. Consequently, the chimney had to
be reduced to the height that it is now.
Sun rays
Duct
The air fans for fresh and re-circulated air are also
separated, and programmed to channel either form
of air to rooms based on the localised demand for
cooling. This helps the system to further reduce energy ZEB’s cooling towers
wastage and cut down on net total energy usage.
LEGEND
F: Filter V: Fan
Re-circulated air C: Coil M: Mixing Box
F1 C V1
F C V
Fresh air
Fresh Re-circulated
Air Air
F2 V2 M1 M2 M3
31
Displacement ventilation system
Conventional ventilation systems are designed to
supply air from the ceiling. The displacement ventilation
system supplies air from the floor and at a relatively
low velocity. This air which is slightly cooler than the
ambient air will settle downwards and spread out
across the floor uniformly due to gravity.
16000
14000
12000
Amount of cooling (Kilowatt)
10000
8000
6000
2000
0
SCTF only SCTF only SCTF & SCTF,
(Library) (Office 1) displacement underfloor
ventilation cooling &
(Office 2) personalised
ventilation
(Experimental
office)
T5 lights
T5 lights are a type of fluorescent lamp that has a
diameter of 1.59 centimetres (Lighting Research
Center, 2002). The electronic ballasts used in T5 lights
operate in the high frequency range, which is from 40 to
100 kilohertz. The energy consumption of the T5 lights
installed in ZEB is approximately 28 watts excluding
electronic ballast loss.
Task lights
All offices in ZEB have low ambient lighting levels of
around 300 lux. However, each workstation is also
equipped with a task light to supplement an additional
200 lux, should the occupants require a brighter
workspace. Light-emitting diode (LED) tubes were
chosen for use in these lights, as they are long-lasting
and energy efficient.
Dimmers
Lighting fixtures installed along the perimeter of rooms,
near light pipes or mirror ducts are equipped with
dimmers. This allows the amount of artificial lighting
to be automatically reduced when there is sufficient
daylight in the space.
Lighting strategies
In ZEB, a wide selection of complementary strategies was adopted to minimise
lighting energy use. Firstly, spaces that required artificial lighting were fitted with
energy-efficient lamps. These lighting systems are controlled by motion sensors
which do away with unnecessary and wasteful use of artificial lighting. Additionally,
mirror ducts, light pipes, light shelves and reflective ceilings have all contributed to
the harnessing of natural lighting, further decreasing the need for artificial lights.
The offices and library were originally designed to lighting power densities of 7.3
watts per square metre (W/m2) and 6.1 W/m2, respectively. However, with the
various strategies incorporated the actual operational levels at ZEB are lower than
what was designed for, with densities of 6.8 W/m2 and 5.9 W/m2 for offices and
library, respectively.
Motion sensors detect movement in the space under In ZEB, data collected from the sensors are used as
surveillance, which is an indication of the presence of feedback to actively control the various building systems
occupants. When movement is detected, equipment such as the air-conditioning. These data and other
such as lights and fans will be switched on automatically, energy information are also used for benchmarking
and vice versa. studies and to produce audit reports.
35
Sustaining net positive
Screenshot from ZEB’s BMS showing cumulative energy production and consumption, surplus
electricity is approximately 48 MWh
Post-occupancy evaluation
It is of critical importance that any energy has been an increase in the percentage
efficiency measure adopted does not of occupants who are satisfied with
result in quality of the indoor environment their respective spaces. In 2012, for
being compromised. In the case of ZEB, example, more than 80% of occupants
though much focus is on the building’s reported being happy with their indoor
energy performance, precautions are environment.
also taken to ensure the indoor space
remains healthy and conducive. 100
Percentage satisfaction (%)
80
The graph shows the results of two
60
post-occupancy evaluation studies
conducted in 2010 and 2012. The 40
studies sought feedback from occupants
20
on the building’s indoor environmental
quality. With changes and adjustments 0
2010 2012
made throughout the years to further
Office 1 Office 2 Experimental
enhance the indoor environment, there office
36
ZEB versus other high-performance buildings
Just how well has the region’s first net zero energy ZEB was featured as one of the high-performance
building lived up to the high expectations from buildings in the publication “The World’s Greenest
all quarters? Based on the data collected, ZEB Buildings: Promises versus Performance in Sustainable
has surpassed all expectations and exhibited Design” authored by Jerry Yudelson and Ulf Meyer. In this
significant advances in energy efficiency. Its book, 49 high-performance buildings from 18 different
performance is comparable to other leading countries were reviewed and compared. Besides ZEB,
energy-efficient buildings in the world. Nanyang Technological University’s School of Art,
Design and Media was also featured in the book.
During the design stage, the team employed
an energy simulation software to produce an Extracting the EEI, or Energy Use Intensity (EUI),
energy model for ZEB. It was estimated that of the featured buildings from the publication, the
ZEB’s Energy Efficiency Index (EEI) would be various buildings were compared against one another
around 55.2 kilowatt-hour per square metre to assess where Singapore’s ZEB stands globally,
per year (kWh/m2/year) based on the gross with regards to energy performance. The information
floor area (GFA), and a simulated total energy on the sizes of the buildings was also extracted to
consumption of 206.70 megawatt-hour (MWh). give readers an idea of the scale of the buildings
During operation, the team discovered that that are being evaluated. From the benchmarking
ZEB exceeded expectations. In its third year of study, it was found that ZEB’s performance is on
operation, the EEI was 42 kWh/m 2/year based par with other high-performance buildings in the
on GFA, while the total energy consumption was world. In fact, based on the EEI, ZEB’s performance
187.76 MWh. was second only to that of Taiwan’s Magic School
of Green Technology in the National Cheng
Kung University.
250
200
Megawatt-hour (MWh)
150
100
50
0
Simulated Actual
(third year of operation)
37
0
100000
120000
20000
40000
60000
80000
Magic School of Green Technology, National Cheng Kung University, Taiwan
Building size (m2)
Comparison of EEI
Eawag Forum Chriesbach, Switzerland
Transoceanica, Chile
Newark Center for Health Sciences and Technology, Ohlone College, USA
Workplace6, Australia
Hagaporten 3, Sweden
Data retrieved from Yudelson, J., & Meyer, U. (2013). The world’s greenest buildings: promise versus
Thyssenkrupp Quartier, Germany
3 Assembly Square, UK
SAP, Ireland
The Suttie Centre for Teaching and Learning in Healthcare, University of Aberdeen, UK
Regents Hall of Natural and Mathematical Sciences, St. Olaf College, USA
Lintulahti, Finland
Charles E. Fipke Centre for Innovative Research, University of British Columbia, Canada
Oregon Health and Science University, Center for Health and Healing, USA
1000
To add to the visitor
experience an external access
to a roof deck had been created
giving exposure to ...... the roof External access to the roof deck
PV Link way
PV PV Lower
Sunshade Roof
PV CARPARK
41
25000
Annual generation: 201867 kWh Annual generation: 198255 kWh Annual generation: 195018 kWh Average generation
Average generation per day: 553 kWh Average generation per day: 542 kWh Average generation per day: 534 kWh per day: 535 kWh
20000
Kilowatt-hour (kWh)
15000
10000
5000
0
Oct, 10
Nov, 10
Dec, 10
Jan, 11
Feb, 11
Mar, 11
Apr, 11
May, 11
Jun, 11
Jul, 11
Aug, 11
Sep, 11
Oct, 11
Nov, 11
Dec, 11
Jan, 12
Feb, 12
Mar, 12
Apr, 12
May, 12
Jun, 12
Jul, 12
Aug, 12
Sep, 12
Oct, 12
Nov, 12
Dec, 12
Jan, 13
Feb, 13
Mar, 13
Apr, 13
May, 13
Jun, 13
Jul, 13
Aug, 13
Sep, 13
Oct, 12
Nov, 12
Dec, 12
Jan, 13
Feb, 13
Mar, 13
Apr, 13
May, 13
ZEB’s monthly energy generation. The amount of energy produced has remained steady over the years, showing no significant
decline in production or performance over time.
Appropriate siting and orientation are equally critical in optimising performance and minimising issues such as
glare, which tends to occur at higher tilt angles.
While the roof is the best location, care should be taken to avoid shading from trees and neighbouring buildings
as far as possible. The system on the main roof of ZEB recorded the highest performance ratio (PR)* of above
0.8, in line with international best practices.
* Defined as the ratio of final yield to reference yield and represents the overall effect of losses on the array’s rated output due to array
temperature, incomplete utilisation of the irradiation and system component inefficiencies or failures.
K e y t akeaway p o in t s
43
ZEB the living lab
The quest for greener, more energy-efficient building In the absence of mechanical fans or moveable
technologies is constantly ongoing. ZEB is also parts, the air is supplied at a relatively low velocity
playing its part in the search by serving as a live test- which eliminates undesirable draft. The absence of
bed, constantly trying out new and innovative green mechanical parts in the system that need power supply
building technologies, testing their viability. Details of also adds to energy savings and makes it virtually
two such test-bedding projects are elaborated in the maintenance-free.
following sections.
Completed in November 2011, six cooling coils were
integrated in cupboard modules and installed in a
Passive displacement classroom on the second floor of ZEB as a test-bed
ventilation project. The PDV system is connected to the existing
chilled water piping from the chillers.
Passive displacement ventilation, or PDV, is an
innovative air distribution system that closely resembles
the displacement ventilation system. In both systems, Chilled water piping
air is supplied at the floor level and extracted from
the room at the ceiling level. However, with PDV, no
mechanical fans are used to propel air into the room. PDV coils Warm air inlet
PDV systems rely completely on the process of natural (no fans) to PDV coils
convection to deliver the chilled air to the end user.
46
Temperature measurement data confirmed that the replaced with energy-saving LED lighting along with a
PDV system can create a satisfactory environment at control system test-bed to study the impact on energy
24°C. Smoke tests showed that the airflow created by performance and visual comfort.
natural convective force was able to distribute the cold
air across the classroom floor effectively and uniformly. Each LED panel is equipped with an intelligent sensor
User comfort surveys to gauge thermal comfort were grid that can determine lighting levels, presence of
also encouraging, indicating a 90% acceptance of the motion, and temperature. This enables occupancy
thermal comfort levels offered by the PDV system. sensing and effective daylight harvesting by intelligently
controlling the amount of light required in the space.
In the absence of mechanical parts, the PDV system Lights can be also be dimmed or brightened according
is able to save approximately 210 watts of electricity to the preference of users. In ZEB, the system has
per hour. This is derived from comparing with an been programmed to turn off lights during lunch hours
identical classroom next door whose conventional on weekdays to further cut energy use.
air-conditioning system setup requires 210 watts of
electricity at every hour of operation to run its fan coil Another feature of the system is the use of low-voltage
unit. The amount of energy savings is approximate data cables to power and control lightings. Not only does
and varies depending on the fan coil unit requirements this save on wiring costs and space, it also resolves the
for the space. The system caught the attention of the problem of messy wires thus simplifying maintenance.
international community, and received the ASEAN This system is ideal for small or new buildings.
Energy Awards under the Special Submission category
in 2012. The installation and commissioning of the LED lighting
system took place in February 2013. Preliminary
findings showed a 40% energy reduction based on
Smart LED lighting system typical office usage. Prior to the retrofit, the average
monthly lighting energy used in the office was 176
The lighting selected for indoor and outdoor areas kWh, and it dropped to 105 kWh.
at ZEB consisted of mainly T5 fluorescent tubes
with a conventional setup. Although T5 lighting was It is worth noting that the ancillary power of the control
considered a relatively more energy efficient solution system accounted for a relatively significant portion of
during the last decade, advances in lighting technology energy use in this small-scale test-bed. But in a larger
have further pushed the frontiers especially with the scale project, this would be reduced substantially
introduction of high quality and cost effective LED leading to higher energy savings overall.
lighting. In one of the offices in ZEB, the T5 lights were
250
200
176
Kilowatt-hour (kWh)
150
100 105
50
0
Sep-12 Oct-12 Nov-12 Dec-12 Jan-13 Feb-13 Mar-13 Apr-13 May-13 Jun-13 Jul-13 Aug-13 Sep-13 Oct-13 Nov-13
47
To investigate the photometry performance of the light, 600
illuminance readings were taken at 52 points in the
500
work area at 8PM. Prior to the retrofit, lighting levels
ranged from 69 lux to 493 lux, with an average of 314 400
Lux
lux. Post retrofit saw an increase in lux levels, with 300
314 333
Level 3 office with T5 lighting (top) versus with the smart LED lighting system (bottom)
48
Facade, roof, shading Cooling and ventilation Lighting Others
Displacement ventilation
Sunshade devices T5 lights Cool paint
system
Solar film coating Underfloor cooling system Task lights Cool pavement
Personalised ventilation
Inflector screens Dimmers Waterless urinals
system
Daylight redirecting
Electrochromic glass
film
Reflective ceiling
Technologies were studied in their entirety, but where necessary detailed testing was conducted on certain items.
K e y t akeaway p o in t s
• ZEB serves as a live test-bed to try out new and innovative green building technologies to see if they are
viable. Two such test-bedding projects were introduced.
»» PDV is an innovative air distribution system that relies completely on the process of natural convection
to deliver the chilled air to the end user.
»» In one of the offices, a smart LED lighting system is being test-bedded. Each LED panel on the lighting
system is equipped with an intelligent sensor grid that can determine lighting levels, presence of motion,
and temperature.
49
Challenges overcame,
lessons learned
One of the delegates from Quezon City, Philippines trying out
the inflector screen installed in a classroom in ZEB
As with any pioneering project, the path towards ZEB and weather conditions. Thus, to predict energy
was challenging. Nevertheless, each challenge offered loads accurately would require the use of an energy
an opportunity for the team to rethink issues and craft modelling software.
new solutions. With many technologies tested for the
first time locally, some areas required more adjustments One of the most important factors when creating an
and improvement. It provided valuable lessons that could energy model is the inputting of occupancy density
help to realise the concept of net zero or low energy and usage behaviour. To reasonably predict this data,
buildings more viable and practical when they eventually building owners must have
become the norm in today’s built environment. a good understanding of the
movement of the occupants.
Simulations on
energy savings
Eventually, predictions made
[The] main difficulty was the and yields were
from the energy model created
lack of experience in installing instrumental in
for ZEB were quite close to
green building technologies sizing the
reality. This was possible due
properly in Singapore. For example, different energy
to the detailed investigation
the solar chimney in ZEB was the systems.
and documentation of each
first one to be installed in
sub-system and component.
Singapore. Together, with architect — Professor
Furthermore, a high degree of
and contractor, we worked out the Stephen Wittkopf
accuracy was also achieved in
details of construction and quality Lucerne University
projecting the user behaviour
testing before research study could of Applied Sciences
and functionality of the spaces
be started. and Arts
involved.
— Ms Erna Tan
National University of Singapore
Enabling monitoring and
verification
Generating accurate One of the most critical systems in ZEB is the wide
energy models array of sensors and the BMS used for monitoring
and verification. This system is required to provide
a clear understanding of how ZEB is performing.
One of the key challenges in designing ZEB was Without an accurate and reliable monitoring system,
being able to accurately predict the expected energy it would be impossible to know whether ZEB is
loads. Energy loads depend on several dynamic performing according to its design. Hence, high
factors, such as occupancy density, usage patterns, resolution sensors and monitoring systems have
52
been installed in ZEB, to ensure that accurate year had increased by about 7% from the previous
information is provided without interference by year while solar energy generation output levels have
environmental factors. Every sensor in ZEB is also steadily decreased at a rate of about 1% per annum
continuously calibrated to make sure that the data since the first year due to inherent system degradation
remains correct. All the data collected is archived in and losses over time.
the BMS.
Megawatt-hour (MWh)
150
53
Lighting The LED lighting system features intelligent sensor
In the case of ZEB, strategies to cut down on lighting grids, which allows for fine-grain tuning of each LED
energy usage consisted largely of replacing the existing light. However, when the system is installed in an
T5 lights with LED lights. open office where workstations are closely arranged,
the motion signals that are detected might be just
In one of the offices, the T5 lights were replaced with inconsequential “noise”. For example, the lights at one
a smart LED lighting system mentioned in the previous workstation could be turned on unnecessarily by the
chapter. This served a dual purpose. While the primary movement of a neighbouring officer. If the lights are
objective is to test-bed the LED lighting system to turn on and off too frequently, the affected occupants
gauge its performance, this switch also became part may feel discomfort due to the constant flickering.
of our ongoing efforts to reduce lighting energy usage Further studies are required to determine the optimal
within the building. zoning and dimming strategies for such lights.
54
Original T5 lights (left) versus new LED lights (right) along the corridor
1400
1200
1000
Kilowatt-hour (kWh)
800
42%
lower
600
400
200
0
Jan-13
Feb-13
Mar-13
Apr-13
May-13
Jun-13
Jul-13
Aug-13
Sep-13
Oct-13
Nov-13
Dec-13
Jan-14
Feb-14
Mar-14
55
Power The PDV was introduced in ZEB chiefly as a test-bedding
Power consumption for plug loads accounts for about project. At the same time, it also served as a means to
17% to 20% of ZEB’s total energy usage. International cut down on energy usage for cooling purposes.
research studies have shown the potential for sizeable
energy savings from receptacles including standby plug A final measure incorporated was the design
loads that, when accumulated over a year, constitutes optimisation of the air diffuser outlets in the
a significant portion of a building’s energy use. In displacement ventilation system. Cooled air from the
ZEB, data shows that standby plug loads for office SCTF system is channelled via the underfloor air ducts
equipment contribute up to 1% of the building’s to the air diffuser outlets and into the office space.
total yearly energy consumption. Upon close inspection, it was found that the design
of the air diffusers can be further optimised to improve
At the ZEB library, a timer was installed for the detection air flow to the space. Hence, modifications to the units
gates at the entrance to power the system only during were experimented to observe the effect on indoor
operational hours, as the main doors of the library are air quality and flow, which were found to have been
closed after hours. Also, two out of three dehumidifier improved. Consequently, most of the air diffusers in the
cabinets in the library were unplugged as they were of office were modified at minimal cost. As a result of this
non-critical usage. These dehumidifiers are used for the change, the SCTF system’s motor fan speeds could
preservation of tapes. However, most of these tapes be reduced whilst still maintaining the required air flow
can now be electronically uploaded and saved as soft rate to the space, thereby cutting down energy usage
copies. This allows for the use of just one dehumidifier from both the SCTF system and the chillers. The team
cabinet in the library instead of three. These measures, will continue to explore other types or designs of air
though simple, brought about significant improvements, diffusers for further test-bedding in ZEB.
helping to cut the monthly power usage of the library by
about 26%. This series of mitigating measures demonstrated that,
it is possible to achieve significant energy savings
In addition to altering equipment operation patterns, through closer monitoring and minor improvement
it is equally important for occupants to learn and to works. The strategies mainly involved lighting retrofit
adjust their energy consumption behaviour to energy-saving LED lighting, mitigation of standby
accordingly. For the offices in ZEB, the last person plug loads, as well as improvement of air distribution
to leave is encouraged to turn off all power outlets in system design to optimise overall energy use. ZEB will
the premises. Reminders are also issued to all staff to be continuously monitored for its performance and
switch off their office equipment when not in use. regular system checks will be conducted to rectify any
faults and ensure prudence in energy usage.
56
Other challenges faced and lessons learned…
The most challenging part of the project was to integrate some of the state-of-the-
art technologies, which were not the conventional M&E systems and installations,
into the building. There is a learning curve for the M&E consultants as well as for
the PIs, as both the consultants and PIs have to work hand-in-hand and “meet in
the middle” to bring concepts into reality.
Another challenge posed was also that ZEB was an existing building, whereby the
cores and spaces were more or less defined. Hence, the designers will need to
work within the constraints and have good services co-ordination to ensure the
integration of old and new is seamless.
— Ms Irene Yong
Beca Carter Hollings & Ferner (S.E Asia) Pte Ltd
Touching on what we have learned from ZEB, we can see how important it is
to start the thinking process of being energy smart at the very initial stage of
conceptualisation of any building project. As more and more energy saving
technologies and devices are being made available for application in buildings, it is
of vital importance that the Architect in his role as the inceptor, be knowledgeable
of such availability and endeavour to explore the creative possibilities in their use
to shape and produce meaningful spaces in buildings, and an efficiently functional
and creatively enjoyable built environment.
— Mr Arthur Loh
DP Architects Pte Ltd
Location of technologies in ZEB
Classroom
Open classroom
(Converted
into an office)
Common corridor
Classroom
(Converted
into an office)
Mirror ducts
SCTF system
T5 lights
Sensors and dimmers
Multi-purpose
room
T5 lights
(Now changed to
LED lighting)
Visitor
centre
BMS
Low-E glass
Green wall
Sunshade devices with PV panels
(A portion of the green
wall is now removed and T5 lights
replaced with cool paint)
Sensors and dimmers
First floor
58
Solar assisted stack
ventilation system
(System now disconnected)
Classroom
PDV
Light shelves
Open T5 lights
classroom Sensors and dimmers
Low-E glass
Sunshade devices with PV panels
Light shelves
SCTF system
T5 lights
Common corridor
Library
T5 lights
(Now changed to
LED lighting)
Second floor
59
Solar assisted stack
ventilation system
T5 lights
Sensors and dimmers
T5 lights
(Now changed to LED lighting)
Low-E glass
Solar film coating
School hall Light pipe
(Portion of the hall
is now converted Light shelves
Common corridor
into a gallery )
Task lights
SCTF system
Displacement ventilation
T5 lights
(Now changed to smart
LED lighting system)
Sensors and dimmers
Low-E glass
Office 2 Solar film coating
Light pipe
Light shelves
Experimental Task lights
office
SCTF system
Underfloor cooling
Personalised ventilation
T5 lights
Sensors and dimmers
Low-E glass
Office 1
Sunshade devices
with PV panels
Task lights
SCTF system
T5 lights
(Now changed to
LED lighting)
Sensors and
dimmers
Third floor
60
K e y t akeaway p o in t s
This chapter highlights the main challenges faced and lessons learned in ZEB, as follows.
61
Taking the next step
Mr Abdul Matheen Mohamed, Minister of State for
Environment and Energy of Maldives (left), trying out
the displays available at the ZEB visitor centre
It was a good project and together we delivered the first zero energy office
building retrofit in the tropics. I am proud to have been a member of the team and to
have been able to publish good journal papers. BCA as owner and operator was a very
approachable and flexible project partner, so that we were able to solve problems
together. BCA also negotiated the various possible energy efficiency approaches well,
so that a clear road map (increase HVAC efficiency, maintain comfort and use
photovoltaics) could be set early.
64
HE Al Mazrouei, Minister of Energy, United
Arab Emirates (middle), was briefed on some
A practical research project of the technologies used in a classroom
such as ZEB which involved the
whole building life cycle with users’
survey provided an invaluable
experience. It provided the Year 2009
opportunity to further our research • Singapore Green Mark Platinum Award
study and of course, our portfolio.
Year 2010
— Ms Erna Tan • MND Minister’s Team Award
National University of Singapore • Building Construction Information (BCI) Green
Design Award
• Institution of Engineers Singapore (IES)
Being the first building in Singapore and Southeast Prestigious Engineering Achievement Award
Asia to achieve net zero energy, the success of ZEB
has not gone unnoticed, having won many awards Year 2011
globally. ZEB is also featured in Jerry Yudelson and Ulf • Minister for National Development’s R&D Award
Meyer’s “The World’s Greenest Buildings: Promises (Distinguished)
versus Performance in Sustainable Design”, along • ASEAN Energy Awards, Special Submission
with 48 other high performance buildings around category for the SCTF system
the world. The innovative technologies adopted
and test-bedded in ZEB also drew attention from Year 2012
the international community, and have separately • ASEAN Energy Awards, Special Submission
garnered their own honours. category for the PDV system
The success of the Zero Energy Building in Singapore not only affirms
Singapore’s capabilities in the green building arena but is also testament to
Singapore’s commitment towards achieving a sustainable built environment.
— Sun Haiyan. (2014). Zero Energy Building: Test bedding for the new technology.
Eco-nomy: The Tao of Sustainable Business, Winter 2013/2014(12), 5-6.
Artist’s impression of the new BCA Academy building
Butler, D. Air conditioning using displacement ventilation National Environment Agency. (2009). Weatherwise Singapore.
to maximize free cooling. Chartered Institution of Building Retrieved May 30, 2011, from http://app2.nea.gov.sg/data/
Services Engineers. Retrieved March 5, 2014, from http:// cmsresource/20090721544571208250.pdf
www.cibse.org/pdfs/David Butler.pdf
National Institute of Building Sciences. Light shelf. Whole
Centre for Sustainable Buildings and Construction. (2010a). Building Design Guide. Retrieved March 5, 2014, from
Building planning and massing. Singapore: Building and http://www.wbdg.org/ccb/ARMYCOE/COETN/technote02.pdf
Construction Authority. Retrieved March 10, 2014, from http://
www.bca.gov.sg/GreenMark/others/bldgplanningmassing.pdf Ng, P.K., Wittkopf, S., & Sun, W. (2011, November 14 -16).
Modelling the impact of glazing selection on daylighting
Centre for Sustainable Buildings and Construction. (2010b). performance of an office building in Singapore using
Existing building retrofit. Singapore: Building and Construction EnergyPlus. 12th Conference of International Building
Authority. Retrieved March 10, 2014, from http://www.bca. Performance Simulation Association. Sydney, Australia.
gov.sg/GreenMark/others/existingbldgretrofit.pdf
Singapore Power Ltd. (2014). Average Electricity Consumption.
Cheong, D., Sekhar, C., & Tham, K.W. (2013, June 27). Retrieved June 20, 2014, from http://www.singaporepower.
The Single-Coil Twin Fan (SCTF) system: An energy-efficient com.sg/irj/servlet/prt/portal/prtroot/docs/guid/d06e53be-
air-conditioning system for better indoor air quality in the 040d-2f10-81a5-beb38060addd?spstab=Our%20Services
tropics. Urban Sustainability R&D Congress 2013. Singapore.
Tan, A.Y.K., & Wong, N.H. (2012). Natural ventilation
Grobe, L.O., Wittkopf, S., Pandey, A.R., Yang, X., Ang, performance of classroom with solar chimney system. Energy
K.S., Scartezzini, J.L., & Selkowitz, S. (2010, March 21- and Buildings, 53, 19-27.
23). Singapore’s Zero-Energy Building’s daylight monitoring
system. International Conference on Applied Energy. Singapore. Wittkopf, S., Valliappan, S., Liu, L., Ang, K.S., & Cheng, S.C.J.
(2012). Analytical performance monitoring of a 142.5 kWp
Hamilton , S. D., Roth, K. W., & Brodrick, J. (2004). grid-connected rooftop BIPV system in Singapore. Renewable
Displacement ventilation. ASHRAE Journal. Retrieved March Energy, 47, 9-20.
10, 2014, from http://bookstore.ashrae.biz/journal/download.
php?file=emerging_7.pdf Wong, N.H., & Tan, E. (2011). Performance of shading
device in classrooms of Zero Energy Building in Singapore.
Kishnani, N. (2012). Greening Asia: Emerging principles for 27th International Conference on Passive and Low Energy
sustainable architecture. Singapore: BCI Asia. Architecture.
Lee, S.E. (2013). Final report: Zero Energy Building at the Wong, N.H., Tan, E., Ang, K.S., Mok, S., & Goh, A. (2011,
Building and Construction Authority’s Academy. National March 23-25). Performance of greenery systems in Zero
University of Singapore. Energy Building of Singapore. International Conference on
Sustainable Design and Construction 2011. Kansas City,
Lee, S. E. (2013, June 26). The Design, Development and Missouri.
Performance of a Retrofitted Net Zero Energy Building in
Singapore. High Energy Performance Buildings: Design Yudelson Associates. (2011). BCA Zero Energy Building,
and Evaluation Methodologies. Brussels. Retrieved June 2, Singapore. Retrieved February 20, 2014, from http://www.
2014, from http://iet.jrc.ec.europa.eu/energyefficiency/sites/ greenbuildconsult.com/pdfs/case-study_singapore.pdf
energyefficiency/files/events/High-Performance-Buildings-
June-2013/Presentations/session4/47_lee_zeb_260613.pdf Yudelson, J., & Meyer, U. (2013). The world’s greenest
buildings: promise versus performance in sustainable design.
Level. Passive design. Retrieved March 4, 2014, from New York: Routledge/Taylor & Francis Group.
http://www.level.org.nz/passive-design/
68
Editorial team
BCA Centre for Sustainable Buildings
Ang Kian Seng Executive Director
Jeffery Neng Operations Director
Cui Tingting Project Coordinator