IUSYS Version 1 Issued: KPSK / 12-Apr-2016
Type: FQ41 Frequency Converter, Uni-directional
Options: NO No Options
Document: IUSYS_ACS580_V1A_en_spec_SIE_FQ41_NO.pdf Version: 1.A (Standard)

IUSYS Specifications (Local Part)

Contents

Hardware Section L.1

Field Bus Data Exchange Section L.2

Device Parameters Section L.3

IUSYS Specifications (Local Part) Source file:


FLS IUSYS_ACS580_V1A_spec_SIE.xls
ACS580 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
IUSYS Version 1 Issued: KPSK / 12-Apr-2016
Type: FQ41 Frequency Converter, Uni-directional
Options: NO No Options
Document: IUSYS_ACS580_V1A_en_spec_SIE_FQ41_NO.pdf Version: 1.A (Standard)

L.1 Hardware
General
Basic Unit: ACS580
Expansion Unit: None
Operator Panel: ACS-AP-I / ACS-AP-S
Converter Type: FPBA-01

Terminal
Name No. Tag Ext. Signal Description Functionality Type

Intelligent Unit Control Voltage Supply


+ 24VI XPOW:1 0 + UPS Supply Incoming PSU
GND XPOW:2 0 - UPS Supply Incoming PSU
DIIL XD24:1 0 Not Used Outgoing PSU
+24VD XD24:2 0 + VFD Control Voltage Outgoing PSU
DICOM XD24:3 0 - VFD Control Voltage Outgoing PSU
+24VD XD24:4 0 Not Used Outgoing PSU
DIOGND XD24:5 0 Not Used Outgoing PSU

Intelligent Unit Main Power Supply


1L1 1L1 0 Line Supply 1 Incoming PSU
1L2 1L2 0 Line Supply 1 Incoming PSU
1L3 1L3 0 Line Supply 1 Incoming PSU
2L1 2L1 0 Line Supply 2 Incoming PSU
2L2 2L2 0 Line Supply 2 Incoming PSU
2L3 2L3 0 Line Supply 2 Incoming PSU
PE1 PE 0 PE Incoming PSU
U2 T1/U1 0 Motor Outgoing PSU
V2 T2/V 0 Motor Outgoing PSU
W2 T3/W 0 Motor Outgoing PSU
PE PE 0 PE Outgoing PSU

Intelligent Unit STO Safe Torque Off


OUT1 XSTO:1 0 STO N/A PSU
SGND XSTO:2 0 Not Used N/A PSU
IN1 XSTO:3 0 STO 1=OK Bool
IN2 XSTO:4 0 Jumper to XSTO:3 N/A Bool

Field Bus Terminals


A1 A1 0 Profibus cable 1 Incoming N/A
B1 B1 0 Profibus cable 1 Incoming N/A
PE1 PE1 0 PE Incoming N/A
A2 A2 0 Profibus cable 2 Outgoing N/A
B2 B2 0 Profibus cable 2 Outgoing N/A
PE2 PE2 0 PE Outgoing N/A

IUSYS Specifications (Local Part) Source file:


FLS IUSYS_ACS580_V1A_spec_SIE.xls
ACS580 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
IUSYS Version 1 Issued: KPSK / 12-Apr-2016
Type: FQ41 Frequency Converter, Uni-directional
Options: NO No Options
Document: IUSYS_ACS580_V1A_en_spec_SIE_FQ41_NO.pdf Version: 1.A (Standard)

L.1 Hardware

Terminal
I/O Name No. Tag Ext. Signal Description Functionality Type

Intelligent Unit Inputs Basic Unit


DI1 XDI:1 CC41 Feeder Ready 0=Trip DI
DI2 XDI:2 None Not Used N/A DI
DI3 XDI:3 None Not Used N/A DI
DI4 XDI:4 None Not Used N/A DI
DI5 XDI:5 None Not Used N/A DI
DI6 XDI:6 None Not Used N/A DI
AI1+/- XAI.4,5 CLnn Not Used N/A Conf.
AI2+/- XAI.6,7 CLnn Not Used N/A Conf.

L.1 Hardware

Terminal
I/O Name No. Tag Ext. Signal Description Functionality Type

Intelligent Unit Outputs Basic Unit


RO1_NC XRO1:1 CLnn Not Used N/A DO
RO1_COM XRO1:2 N/A + 24 VDC Supply (XD24:4) N/A PSU
RO1_NO XRO1:3 CLnn Not Used N/A DO
RO2_NC XRO2:4 CLnn Not Used N/A DO
RO2_COM XRO2:5 N/A + 24 VDC Supply (XD24:4) N/A PSU
RO2_NO XRO2:6 CLnn Not Used N/A DO
RO3_NC XRO3:7 CLnn Not Used N/A DO
RO3_COM XRO3:8 N/A + 24 VDC Supply (XD24:4) N/A PSU
RO3_NO XRO3:9 CLnn Not Used N/A DO
AO1 XAO:1 CLnn Not Used N/A Conf.
AGND XAO:2 CLnn Not Used N/A Conf.
AO2 XAO:3 CLnn Not Used N/A Conf.
AGND XAO:4 CLnn Not Used N/A Conf.

IUSYS Specifications (Local Part) Source file:


FLS IUSYS_ACS580_V1A_spec_SIE.xls
ACS580 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
IUSYS Version 1 Issued: KPSK / 12-Apr-2016
Type: FQ41 Frequency Converter, Uni-directional
Options: NO No Options
Document: IUSYS_ACS580_V1A_en_spec_SIE_FQ41_NO.pdf Version: 1.A (Standard)

L.2 Field Bus Data Exchange


General
Field Bus Type: Profibus DP
Definition Files: IUSYS_ACS580_V1_GSD.zip
Subnet Type: None

Net Subnet
No. Address Address Tag Ext. Signal Description Functionality Type

Data to Main PLC Cyclical Data


1 0 None SW00 Identification Parameter Integer
2 2 None SW02 Index Parameter Integer
3 4 None SD04 Value Parameter DInt.
5 8.0 None SB08_0 Operating 1=OK Bool
6 8.1 None SB08_1 Remote 1=OK Bool
7 8.2 None SB08_2 Speed/Freq. >= Supervision 1=OK Bool
8 8.3 None SB08_3 External Control 1/2 (0/1) N/A Bool
9 8.4 None SB08_4 Run Enabled 1=OK Bool
10 8.5 None SB08_5 Not Used N/A Bool
11 8.6 None SB08_6 Not Used N/A Bool
12 8.7 None SB08_7 Communication Error 1=Fault Bool
13 9.0 None SB09_0 Ready to Switch ON 1=OK Bool
14 9.1 None SB09_1 Ready to Operate 1=OK Bool
15 9.2 None SB09_2 Operation Enabled 1=OK Bool
16 9.3 None SB09_3 Fault 1=Trip Bool
17 9.4 None SB09_4 OFF2 inactive 1=Active Bool
18 9.5 None SB09_5 OFF3 inactive 1=Active Bool
19 9.6 None SB09_6 Switch-ON Inhibited 1=Active Bool
20 9.7 None SB09_7 Warning/Alarm 1=Warning Bool
21 10 None SW10 Motor Speed Parameter Integer
22 12 None SD12 Motor Power [kW] Real
24 16 None SD16 Motor Current [A] Real
26 20 None SW20 Last Fault Code Parameter Integer
27 22 None SW22 Last Warning Code Parameter Integer
28 24.0 None SB24_0 Not Used N/A Bool
29 24.1 None SB24_1 Not Used N/A Bool
30 24.2 None SB24_2 Not Used N/A Bool
31 24.3 None SB24_3 Not Used N/A Bool
32 24.4 None SB24_4 Not Used N/A Bool
33 24.5 None SB24_5 Not Used N/A Bool
34 24.6 None SB24_6 Not Used N/A Bool
35 24.7 None SB24_7 Not Used N/A Bool
36 25.0 None SB25_0 Feeder Ready 0=Trip Bool
37 25.1 None SB25_1 Not Used N/A Bool
38 25.2 None SB25_2 Not Used N/A Bool
39 25.3 None SB25_3 Not Used N/A Bool
40 25.4 None SB25_4 Not Used N/A Bool
41 25.5 None SB25_5 Not Used N/A Bool
42 25.6 None SB25_6 Not Used N/A Bool
43 25.7 None SB25_7 Not Used N/A Bool
44 26 None SW26 Not Used N/A Integer
45 28 None SD28 Motor Torque [%] Real

IUSYS Specifications (Local Part) Source file:


FLS IUSYS_ACS580_V1A_spec_SIE.xls
ACS580 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
IUSYS Version 1 Issued: KPSK / 12-Apr-2016
Type: FQ41 Frequency Converter, Uni-directional
Options: NO No Options
Document: IUSYS_ACS580_V1A_en_spec_SIE_FQ41_NO.pdf Version: 1.A (Standard)

L.2 Field Bus Data Exchange

Net Subnet
No. Address Address Tag Ext. Signal Description Functionality Type

Data from Main PLC Cyclical Data


46 0 None CW00 Identification Parameter Integer
47 2 None CW02 Index Parameter Integer
48 4 None CD04 Value Parameter DInt.
49 8.0 None CB08_0 Not Used N/A Bool
50 8.1 None CB08_1 Not Used N/A Bool
51 8.2 None CB08_2 Fieldbus Control Enable 1=Active Bool
52 8.3 None CB08_3 External Control 2 Select 1=Active Bool
53 8.4 None CB08_4 User Bit 0 (Not Used) N/A Bool
54 8.5 None CB08_5 User Bit 1 (Not Used) N/A Bool
55 8.6 None CB08_6 User Bit 2 (Not Used) N/A Bool
56 8.7 None CB08_7 User Bit 3 (Not Used) N/A Bool
57 9.0 None CB09_0 Ready to Operate 1=Active Bool
58 9.1 None CB09_1 OFF2 Inactive 1=Active Bool
59 9.2 None CB09_2 OFF3 Inactive 1=Active Bool
60 9.3 None CB09_3 Operation Enabled 1=Active Bool
61 9.4 None CB09_4 Ramp Function Output Enable 1=Active Bool
62 9.5 None CB09_5 Ramp Function Accelerator Enable 1=Active Bool
63 9.6 None CB09_6 Operating 1=Active Bool
64 9.7 None CB09_7 Reset Fault 1=Active Bool
65 10 None CW10 Speed Setpoint Parameter Integer
66 12 None CW12 Torque Setpoint Parameter Integer
67 14 None CW14 Not Used N/A Integer
68 16 None CW16 Lock Local Panel Parameter Integer
69 18 None CW18 Not Used N/A Integer
70 20 None CW20 Not Used N/A Integer
71 22 None CW22 Not Used N/A Integer
72 24 None CW24 Not Used N/A Integer
73 26 None CW26 Not Used N/A Integer
74 28 None CW28 Not Used N/A Integer
75 30 None CW30 Not Used N/A Integer

IUSYS Specifications (Local Part) Source file:


FLS IUSYS_ACS580_V1A_spec_SIE.xls