Energy Efficiency Best Practices (EEBP)

Sesión Técnica 1:

Eficiencia Energética y Data Centers

Training Workbook
Every effort has been made to ensure that the information contained in this document is true and correct
at the time of going to press. However, the technology, systems, products, processes, specifications
and content in general described in this document are subject to continuous development and
DCProfessional is entitled to change them at any time and to expand on them. DCProfessional cannot
accept liability for any loss or damage of any nature whatsoever arising or resulting from the use of or
reliance on information or particulars in this document.

All names and other data used in examples are fictitious.

The information contained in this document is of a general nature.

No part of this document may be reproduced by any means, other than with the express written
permission of the copyright holder.

© Copyright 2016 by DCProfessional Development

All rights reserved. No part of this manual may be used, reproduced, or transmitted in any form or by any
means, electronic mechanical, including photocopying, recording, or by any information storage and
retrieval system, without the prior agreement and written permission of the publisher, except for the
inclusion of brief quotations in a review.

The contents of this manual are subject to ongoing revision without notice due to continuing
developments in standards, regulations, methodology, design, and manufacturing.

This manual forms part of the DCProfessional Development curriculum, and is presented without
warranty of any kind, including but not limited to implied warranties, for the manual’s quality or fitness for
any particular purpose. DC Professional Development shall not be liable to the purchaser or any other
entity with respect to any liability, loss or damage caused directly or indirectly by this manual.

All brand names and trademarks are the property of their respective owners.
DCProfessional Development
28 Scrutton Street
London EC2A 4RP
United Kingdom

www.dc-professional.com

ACKNOWLEDGEMENTS

DCProfessional Development is indebted to the following organisations and individuals for their
invaluable support in the preparation of this manual:

Organisations: DCD Group, DCD Focus Magazine, DCD Intelligence,

Individuals: Agustín López Neira (Training Project Developer & Content Producer Manager).

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 2


Relación de contenidos

Relación de contenidos .............................................................................................................. 3

Objetivos .................................................................................................................................... 5

Eficiencia Energética y Data Centers.......................................................................................... 5

Introducción ................................................................................................................................ 6

Evolución.................................................................................................................................... 7

Actuales Protagonistas/Referencias ........................................................................................... 8

Necesidades actuales .............................................................................................................. 10

Soluciones ................................................................................................................................ 12

Tendencias............................................................................................................................... 19

Referencias / Saber más .......................................................................................................... 20

ANEXO FIGURAS – Figura 1 ................................................................................................... 23

Evolución del consumo energético en Data Center (EEUU)............................................. 23

ANEXO FIGURAS – Figura 2 ................................................................................................... 24

Evolución del consumo energético en Data Center (Mundial) .......................................... 24

ANEXO FIGURAS – Figura 3 ................................................................................................... 25

Implicaciones ambientales de la industria del Data Center .............................................. 25

ANEXO FIGURAS – Figura 4 ................................................................................................... 26

Factores de adopción de las mejores prácticas ............................................................... 26

ANEXO FIGURAS – Figura 5 ................................................................................................... 27

Orientación al trabajo en grupo ........................................................................................ 27

ANEXO FIGURAS – Figura 6 ................................................................................................... 28

Estructura de las políticas generales ............................................................................... 28

ANEXO FIGURAS – Figura 7 ................................................................................................... 29

Implicación de las estrategias de redundancia en el diseño ............................................. 29

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 3


ANEXO FIGURAS – Figura 8 ................................................................................................... 30

Evolución tecnológica en términos de eficiencia energética ............................................. 30

Ejercicio Práctico 1: .................................................................................................................. 31

Cálculo consumos en servidores con baja carga o inactivos .................................................... 31

Uso apropiado del Workbook


Este workbook ha sido diseñado para un uso conjunto en las sesiones presenciales, casos de estudio y
workshops de este módulo, de modo que los asistentes puedan adquirir conocimientos de aplicación
práctica en un entorno de la industria de los Data Center.

El curso está estructurado para que el Tutor exponga funcionalidades y ejemplos de casos prácticos con
el apoyo del material del Tutor (proyecciones, videos, simulaciones, técnicas de aprendizaje acelerado).

Siempre que sea posible, los asistentes deben participar de forma activa individual o en grupos
reducidos para desarrollar y completar ejercicios orientados a consolidar su aprendizaje Se ha
dispuesto de un entorno de aprendizaje adecuado para que pueda actuar de modo seguro.

El objetivo del workbook es ser un documento de trabajo orientado al refuerzo de la información


presentada por el Tutor. Cada asistente debe disponer de una copia digital o en papel de este workbook
con antelación al curso de modo que pueda ayudar a la preparación previa del curso, especialmente en
los casos de aquellos asistentes menos familiarizados con algunas temáticas del curso, además de
servir durante y después de la formación como documento de consulta.

No está diseñado en cualquier caso para proporcionar de modo detallado todos los aspectos teóricos ni
fundamentos de una tecnología o aplicación, sino específicamente aquellos especialmente relevantes
para el desarrollo del curso y los objetivos concretos de aprendizaje.

Cualquier consulta, aclaración o incidencia sobre DCProfessional training courses puede dirigirla a:

agustin.lopez@datacenterdynamics.com

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 4


Objetivos
Eficiencia Energética y Data Centers
Al finalizar este módulo, será capaz de:

 Explicar las tendencias globales en el consumo de energía en los centros de datos

 Entender los facilitadores corporativos y el enfoque para el trabajo en equipo en aspectos de


eficiencia energética

 Identificar consideraciones energéticas importantes para iniciar un plan de eficiencia energética


en el data center

También dispone de la oportunidad de:

- Compartir sus conocimientos y opiniones

- Exponer casos reales y problemáticas en experiencias vividas o conocidas

- Escuchar atentamente las opiniones del resto de los asistentes

- Aportar comentarios de manera activa, respetando el enfoque del resto de participantes en la


aplicación de soluciones o puntos de vista concretos, incluso cuando sean opuestos a sus
propias valoraciones y entendimiento como base del enriquecimiento del grupo

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 5


Introducción

La eficiencia energética es un aspecto clave en los costes de operación de un data center, de tal modo
que el consumo de energía se está convirtiendo en un factor cada vez más importante y que forma
parte de las consideraciones de construcción de los modernos data center desde la fase inicial del
diseño.

En contraste, el estado general de la industria es muy pobre si atendemos a los datos de uso y
consumo promedio en instalaciones reales debido al descuido histórico en el tema de la eficiencia y en
favor de otros aspectos relacionados con el aumento de la fiabilidad, del rendimiento y de la capacidad.

Como resultado, el desperdicio de energía es de dos tercios o más de la energía total suministrada a las
instalaciones si atendemos a diversos informes y mediciones promedio procedentes de casos reales.

La lectura positiva en este escenario de desatención generalizada es que se pueden obtener grandes
mejoras y ahorros de manera prácticamente inmediata en un corto plazo, aplicando soluciones sencillas
y sin poner en riesgo la disponibilidad de los servicios proporcionados.

En cualquier caso, la optimización de aspectos energéticos en unas instalaciones que requieren de la


intervención multidisciplinar en las diversas áreas que componen la actividad de operación de un data
center requieren de un enfoque holístico y coordinado si no se quiere poner en riesgo la disponibilidad
de los servicios.

Es esencial por tanto la coordinación de todos los responsables en áreas relevantes relacionadas con
elementos electromecánicos de igual modo que aquellas personas involucrados en la adquisición y
mantenimiento de los sistemas electrónicos (hardware), sistemas operativos, máquinas virtuales,
middleware, aplicaciones y de los sistemas de monitorización.

Incluso cuando existen diversos avances en relación a mejora de la eficiencia de los componentes
concretos que integran cada uno de los diversos sistemas, la realidad es que existen finalmente
demasiados elementos en cada sistema dentro de la cadena de provisión de los diferentes servicios
(energía, frío, monitorización, comunicaciones, computación, ….) que componen un data center como
para pretender que se produzca una perfecta coordinación y armonía intrínseca entre todos ellos por sí
sola sin una intención y monitorización continua por parte de todo el personal al cargo.

*Figura 1*
Por tanto, las mejoras en la eficiencia energética pasan obligatoriamente por un paso inicial de
coordinación entre el personal de las diversas áreas que intervienen y por la formación a nivel individual
en relación un marco común de buenas prácticas que integre todas las disciplinas y sus relaciones, de
modo que, se pueda implementar en un único equipo de trabajo el mismo lenguaje y entendimiento de
la eficiencia energética para el entorno específico de trabajo y prestación de servicios críticos como es
el de los data center.

Una correcta y clara definición de los roles y responsabilidades de las personas que integran cada una
de las áreas de operación y mantenimiento, junto a los mecanismos y herramientas de coordinación
entre las diversas áreas que construyan un único equipo son esenciales en los data center actuales.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 6


Evolución

En los años 90 del pasado siglo XX se concibió la idea de un mundo mejor gracias a los avances
tecnológicos y el uso intensivo de Internet como habilitadores de ahorros considerables en un uso global
más eficiente de la energía.

La posibilidad de no tener que desplazarse físicamente para realizar tareas administrativas rutinarias y
gestiones habituales por un número de elevado de personas, especialmente en sectores como la banca,
sanitario, compras de productos o servicios multimedia, consultas a servicios documentales, entre otros,
permitiría un mundo más eficiente en términos energéticos y de impacto ambiental.

Aunque efectivamente se ha reducido la necesidad de imprimir información en papel y su distribución


física como es el caso del material de marketing y de comunicación o de álbumes de música y de
películas, finalmente no se han sustituido del todo estas actividades.

Pero especialmente hay que destacar esta visión limitada de los años 90 por los servicios entonces
conocidos, ya que las nuevas tecnologías y su democratización han impulsado finalmente un consumo
más intensivo en términos energéticos.

Hay que considerar que el mantenimiento de una información digitalizada en soporte electrónico para
permitir su acceso simultáneo por el público objetivo es más costoso generalmente en términos de
consumo energético que el mantenimiento en un soporte físico como el papel pero además hay que
contemplar la suma de los nuevos servicios que han ido aparecido con el cambio de paradigma en las
sociedades actuales, con las redes sociales y los servicios multimedia como los más demandados entre
la población a nivel global y que siguen creciendo.

*Figura 2*
Las actividades de construcción y operación de un data center tienen asociado un alto impacto
ambiental que debe ser reducido. A modo de ejemplo, se estima que un data center enterprise consume
10 y 100 veces más de energía que un espacio de oficinas corporativo.

El impacto ambiental de la actividad en un DC no sólo es energético sino más amplio y está en el punto
de mira en las regulaciones de los estados. La despreocupación en aspectos de eficiencia durante la
primera década del actual siglo XXI en favor del despliegue acelerado de infraestructura TI hace que la
aplicación actual de medidas en aspectos de eficiencia energética habilite ahorros estimados entre un
20% y un 40%.

Incluso mayores a un 50% si se aborda una aplicación intensiva de las mejores prácticas y en base a
estimaciones para los data center del US Department of Energy.

*Figura 3*

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 7


Actuales Protagonistas/Referencias

La sensibilidad de los propios clientes y usuarios de los servicios soportados desde un data center
hacen que la eficiencia sea un factor a considerar más allá de los aspectos relacionados con el propio
ahorro económico que aportan a la organización que aplica las medidas.

Adicionalmente, la aplicación de regulaciones específicas en los diferentes países o regiones a nivel


mundial a las industrias más contaminantes se ha convertido en un factor de riesgo a considerar. La
Convención Marco de las Naciones Unidas sobre el Cambio Climático celebrado en París en Diciembre
2015 impulsa la adopción de medidas en relación a la eficiencia energética en todas las industrias.

http://unfccc.int/resource/docs/2015/cop21/spa/l09s.pdf

Adicionalmente al tratado, ya han sido adoptadas medidas y regulaciones relacionadas con emisiones
de CO2 y de control específico del uso y consumo de la energía tanto en EEUU (Executive Order 13693
de 19 de Marzo, 2015) como en la Unión Europea (Directiva 2012/27/UE del Parlamento Europeo y del
Consejo, de 25 de octubre de 2012, relativa a la eficiencia energética).

https://www.whitehouse.gov/the-press-office/2015/03/19/executive-order-planning-federal-sustainability-
next-decade

http://www.minetur.gob.es/energia/desarrollo/EficienciaEnergetica/directiva2012/Paginas/directiva-2012-
27UE.aspx

Un data center tiene un periodo de amortización estimado de 20 años. Aquel operador responsable un
data center que piense que en su país o región no se van a aplicar medidas legales o regulatorias en
aspectos de eficiencia energética que le obliguen a considerar aspectos relacionados con la aplicación
de mejores prácticas está muy equivocado.

Entre las referencias principales en aspectos de aplicación de mejores prácticas y herramientas para la
industria del data center podemos destacar:

- CEEDA (Certifed Energy Efficient Data Center Award): primer esquema de certificación en la
industria del data center en la consideración de aplicación de las mejores prácticas reconocidas
a nivel internacional para los centros de datos. http://www.ceedacert.com/

- EU CoC (European Union Code of Conduct): creado en respuesta al aumento del consumo de
energía en centros de datos y la necesidad de reducir los impactos en aspectos ambientales,
económicos y energéticos relacionados. Cuenta con más de 120 participantes y 245 promotores
en la aplicación de las buenas prácticas reconocidas por la industria.
http://iet.jrc.ec.europa.eu/energyefficiency/ict-codes-conduct/data-centres-energy-efficiency

- COE (Center of Expertise for Energy Efficiency in Data Centers): Promovido por Lawrence
Berkeley National Laboratory (LBNL) y esponsorizado por U.S. Department of Energy (DOE)
dispone de herramientas y una master list con acciones recomendadas como mejores prácticas
a implementar en los data center. https://datacenters.lbl.gov/

- DOE (US Department of Energy) Better Buildings: con suite de herramientas para la adopción de
líneas base, formación, casos de estudio y programa de reconocimiento a los mayores
ahorradores de energía. http://energy.gov/eere/better-buildings

- EPA (United States Environmental Protection Agency): métricas, clasificación de equipamiento


de red, UPS y servidores y reconocimiento ENERGY STAR; Data center benchmarking.

https://www.energystar.gov/index.cfm?c=prod_development.server_efficiency

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 8


- FEMP (US Federal Energy Management Program): talleres, casos de estudio, políticas,
intercambio de información y asistencia técnica. http://energy.gov/eere/femp/energy-efficiency-
data-centers

- The Green Grid: métricas y herramientas de aplicación de modelos de madurez en eficiencia


energética para data centers. http://www.thegreengrid.org/

- Information technology industry council: Políticas de uso de la eficiencia energética en


dispositivos TIC. https://www.itic.org/

- ASHRAE: Estándares de referencia en aspectos ambientales relacionados con el equipamiento


TI y de telecomunicaciones para los data center. https://www.ashrae.org/

- AFCOM: Asociación de profesionales en la industria del data center con capítulos en EEUU,
APAC y Reino Unido. https://www.afcom.com/

- Uptime Institute: Informes con datos sobre la eficiencia energética en la industria de los data
center. https://uptimeinstitute.com/

- Open compute Project: Comunidad global de líderes tecnológicos que trabajan juntos de modo
abierto en la infraestructura de TI con el objetivo de lograr mayores ahorros, ampliar las
posibilidades de personalización del equipamiento y disminución de los costes.
http://www.opencompute.org/

- SINGAPORE STANDARD SS 564 Series: Singapore Standard for green data centres.
https://www.singaporestandardseshop.sg/product/Package.aspx?ID=5dfe0c1e-eeca-4cd6-9a8d-
5fe9cdc2eac6

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook 9


Necesidades actuales

Atendiendo a las demandas de las partes internas y externas interesadas en la adopción de un mayor
grado de eficiencia en las operaciones del data center podemos indicar de manera esquemática y
resumidas los siguientes factores:
• Oportunidad de Ingresos: Está en aumento el número de clientes que exige requisitos de
sustentabilidad en sus RFP (solicitudes de propuesta). Entre los motivos principales se
encuentra la reducción por parte de las empresas de las emisiones procedentes a nivel interno
pero también de su cadena de suministros. Atender a aspectos de eficiencia energética
proporciona por tanto ventajas competitivas desde el punto de vista que se demuestra una mejor
gestión de los costes y menor índice de emisiones que otros competidores de mercado. En
muchos países los requisitos actuales en las RFP son solo informativos pero comienzan ya a
formar paso de las obligaciones a cumplir con la necesidad de aplicar auditorías regulares
adicionalmente. Empresas líderes, como Toyota, GE, The Timberland Company y Starbucks
Coffee Company han considerado la sustentabilidad como una oportunidad de crecimiento del
negocio en vez de posicionar esta cuestión como una gestión del riesgo.

• Reducción de los Costes operativos: La reducción del consumo energético tiene un impacto
directo sobre los costes operativos. Podemos realizar un cálculo grosero atendiendo a un
escenario inicial con unas cargas TI de 5MW y considerando 0,10 céntimos de dólar el coste de
la energía. En este supuesto, un data center que de soporte a estas cargas críticas con un PUE
de 2 o con un PUE menor de 1.4 supondrá una diferencia de 2.7 millones de dólares anuales de
diferencia (Whitepaper 25 de The Green Grid – Estudio sobre políticas energéticas para Data
Centers).

• Reducción de costes: El consumo eléctrico en el Data Center continúa tendencia ascendente


junto a un aumento constante del coste del kilovatio hora en todo el mundo. El foco está en la
implementación de tecnologías que aporten una mayor eficiencia energética pero sin olvidar la
reducción de los consumos en las tecnologías que actualmente estén en operación.

• Marca: El posicionamiento y la construcción de marca es esencial para lograr un valor en el


comportamiento de los clientes y alcanzar un número mayor de ventas en la actualidad. La
marca es la principal fuente de creación de valor para la empresa y que vas más allá de los
productos o servicios que la organización proporciona. Asociados a la marca existen tablas de
clasificación entre diferentes marcas en las que destacan las marcas más ecológicas a nivel
global. Ligado a las inversiones el DJSI (Índice de sustentabilidad del Dow) selecciona los
valores de las empresas más sostenibles de todo el mundo, divididas en 24 sectores industriales
eligiendo únicamente a un 10% de entre las más de 3400 empresas encuestadas. El informe
parte de una evaluación anual de las compañías y, posteriormente, junto con las variantes
regionales de Norteamérica, Europa, Asia Pacífico y Corea, sirve para elaborar productos
financieros que prestan atención a la creación de valor a largo plazo.

• Ambiental: El cambio climático pone en peligro los elementos básicos vitales para las personas
de todo el mundo: acceso al agua, a la comida, salud y el uso de la tierra y el medio ambiente.
Con las tendencias actuales, la temperatura media global podría aumentar 2-3 ºC durante los
próximos 50 años, lo cual supondría graves impactos, a menudo por mediación del agua,
incluyendo sequías e inundaciones más frecuentes. La mitigación del proceso del cambio
climático considera acciones para la reducción de los niveles atmosféricos y emisiones de los
volúmenes actuales de dióxido de carbono para evitar el aumento de los dos grados en la
temperatura global lo cual supondría cambios permanentes en la climatología.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


10
• Legal: En los últimos años se han incorporado factores legislativos para reducir el consumo
energético y/o aumentar la cantidad de energía procedente de fuentes con menor contenido de
carbono. Entre estas medidas podemos mencionar la aplicación de medidas específicas en los
códigos de edificación e impuestos “verdes” como ocurre con las emisiones de dióxido de
carbono con dos tipos impuestos: los directos (se carga directamente al consumidor por el coste
asociado a la huella ambiental de emisiones como en el caso de Compromiso de Reducción del
Carbono del Reino Unido con tasas aplicadas a los data center) y los indirectos (se transfiere el
coste a alguien de la cadena de suministro)

*Figura 4*
Relacionadas con estas cuestiones indicadas, la eficiencia energética se ve reflejada en como una las
tres preocupaciones principales de los operadores de los data center a nivel mundial en la actualidad
según se reflejan en diversos estudios.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


11
Soluciones

El momento de diseño para la construcción de una nueva instalación proporciona una ventana de
oportunidad única para poder tomar decisiones relevantes y positivas en relación al uso de la energía,
especialmente atendiendo al largo plazo en el que se van a desarrollar las operaciones del data center.

Otra oportunidad puede producirse en el momento de adaptación y remodelación de un data center


existente, incluso es posible adoptar medidas puntuales en unas instalaciones en operación como
tercera opción disponible.

Lógicamente, en un data center nuevo permite la aplicación de medidas de eficiencia energética desde
las primeras fases del diseño de modo que es el momento perfecto para analizar y refinar los requisitos
de diseño de sistemas para reducir al mínimo el consumo de energía en atención a todos los sistemas y
condiciones que afectarán el uso de energía en el data center.

La ubicación, el nivel de fiabilidad, la topología del sistema, el tipo de equipamiento y la flexibilidad de


los sistemas para adaptarse a una dinámica de cambio constante en atención a la variación más o
menos rápida en el nivel de carga TI instalada a nivel de sala, exigen una visión en la evolución del
diseño del data center a lo largo del tiempo.

Tanto si es un nuevo data center como si está en estos momentos ya en operación, para poder habilitar
de forma correcta cualquier cuestión relacionada con la eficiencia energética el primer paso es la
implicación de todos las áreas relevantes de la organización

Implicación de las áreas de la organización

Es necesario crear un consejo de aprobación con representantes de todas las disciplinas


(software, TI, electromecánica, adquisición) y exigir la aprobación de este grupo para cualquier
decisión importante con vista a garantizar que el impacto de la misma se haya comprendido de
forma adecuada y que se alcance una solución efectiva.

Este consejo podría decidir aspectos relevantes tales como la definición de un listado de
hardware estándar en dispositivos TI en atención a las consideraciones e implicaciones
relacionadas con aspectos electromecánicos para un control efectivo sobre los distintos tipos de
hardware.

Este grupo podría considerarse como el equivalente funcional a un consejo para los cambios con
responsabilidades en la definición, aplicación, establecimiento y revisión de las políticas
generales en eficiencia energética.

*Figura 5*
Ejemplo de implantación

Se puede crear un consejo o comité específico, incluso aprovechar ya alguno activo procedente
de alguna implantación de norma ISO (p.ej. ISO 20000, ISO 9001, ISO 50001) o procedente de
otras buenas prácticas en la prestación del servicio (p.ej. ITIL) y completarlo con los roles y
responsables relevantes a las actividades que pudieran no estar inicialmente incluidos.

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Copias de las actas de reunión con temas tratados y aprobaciones relevantes

 Lista de distribución de las actas/decisiones.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


12
 Documentos que describen el mecanismo utilizado para informar a los usuarios/clientes
de los cambios y las gestiones relacionadas con temas de eficiencia energética a nivel
interno/externo

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


13
Beneficios

El paso importante hacia un funcionamiento más eficiente de la energía es crear un equipo


integrado que pueda fijar metas para la mejora de la eficiencia energética en el data center y
reducir el consumo de energía en atención a objetivos internos y/o externos por obligaciones
legales o contractuales.

Al incluir representantes de todas las partes relevantes:

 Se resuelven típicas brechas de comunicación entre los grupos

 Se evita que los objetivos particulares en cada área o nivel individual perjudique a otras
áreas y/o los objetivos comunes (p.ej. adquisición de hardware al menor precio sin
considerar aspectos de eficiencia amortizables en un periodo corto-largo plazo)

 Se establecer una meta común para mejorar la eficiencia energética del data center y
reducir el consumo de energía

 Se resuelven posibles lagunas de comunicación entre áreas internas y/o con


proveedores de servicios externos. Las lagunas proceden habitualmente por problemas
organizacionales o diferencias culturales (especialmente entre los empleados y la gestión
externalizada).

 Se asegura que las actividades y servicios en operación están bien definidos y discutidos
entre todas las partes (por ejemplo, la aplicación de medidas de eficiencia energética,
tales como la instalación y puesta en marcha de nuevos sistemas)

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


14
Formación continuada del personal

Es necesaria la elaboración y aplicación de una política de desarrollo continuado de la


concienciación y conocimientos del personal para mantener el nivel adecuado de las habilidades
en las operaciones directamente relacionadas con la eficiencia energética del data center.

Los programas de desarrollo profesional deben comprenden cursos reconocidos de la industria


o, en el caso de acciones internas de formación se debe asegurar una estandarización en los
contenidos e impartición.

Ejemplo de implantación

En función de los roles y responsabilidades del personal se debe definir y revisar las
necesidades de formación de manera periódica, típicamente con carácter anual. En aquellas
organizaciones que esta gestión se desarrolle con la colaboración o participación directa del
departamento de recursos humanos se deberá implicar a los responsables de este
departamento para definir los objetivos y comprobar el grado de eficacia de la formación.

La asistencia presencial a sesiones formativas internas y/o externas se pueden completar con
sesiones online que permitan un formación continuada del personal más allá de las acciones
puntuales típicas.

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Certificados de capacitación por servicios externos o plataformas online relacionadas con


el desarrollo profesional a nivel individual

 Programación en tiempo y contenido de las sesiones de los cursos emprendidos junto a


la documentación de soporte

 Registros de actividad relacionados con la revisión periódica del programa de formación


del personal

Beneficios

Las actividades de formación permiten desarrollar una conciencia común en todo el personal del
data center sobre el impacto financiero y medioambiental positivo que implica el ahorro de
energía.

Entre la lista de prioridades del personal del data center el mantenimiento continuo del
funcionamiento de los sistemas ocupa generalmente el primer puesto, seguido por el suministro
de la capacidad para el crecimiento futuro.

La eficiencia energética empieza a ganar consideración en las organizaciones más avanzadas al


comprobar que la implementación y preservación del funcionamiento del data center en términos
de eficiencia energética ayuda eficazmente en la posibilidad de aumentar la capacidad del data
center, ahorrar dinero además de apoyar los objetivos ambientales generales de la empresa

Las mayores eficiencias de energía en un data center se consiguen cuando existe una formación
en eficiencia energética de los propios implicados en las decisiones del diseño y de los sistemas
de apoyo (distribución eléctrica, refrigeración, iluminación) desde el inicio del proyecto.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


15
Políticas globales

El establecimiento y revisión de una políticas globales relacionadas con la eficiencia energética


es clave para determinar el grado alcance del marco de actuación y la toma de decisiones por
parte de representantes en el órgano de decisión común establecido.

*Figura 6*
Como consecuencia de una falta de políticas los esfuerzos en aspectos energéticos quedan
generalmente limitados a mejoras en sistemas o áreas muy concretas con alcance puntual que
impiden el logro de avances más ambiciosos y efectivos a lo largo de unos más periodos mucho
más extensos de tiempo. La duplicación de funciones, actividades y esfuerzos económicos en
las organizaciones son también frecuentes cuando estas políticas se acometen sin una
coordinación entre los responsables designados.

Las siguientes políticas aplican a diferentes aspectos relacionados con el data centre y su
operación.

Considerar el impacto ambiental que representan los dispositivos instalados (TI + M & E)

Realizar una auditoría de los equipos existentes para maximizar su uso mediante la
consideración de cualquier capacidad integrada existente y que esté siendo utilizada. El objetivo
es garantizar que se identifiquen todas las áreas de optimización, consolidación y agregación
antes de realizar inversiones sustanciales en nuevo equipamiento. Los equipos TI son los
importantes este aspecto por su impacto potencial que está ligado a la frecuencia de su
actualización y reemplazo. Se debería considerar aspectos relacionados con legislación
aplicable en un futuro próximo.

Rangos medioambientales de operación en equipamiento mecánico y eléctrico

Se trata de seleccionar y desplegar equipamiento electromecánico que no requiera por si misma


de la aplicación de una refrigeración en su operación habitual. Esta práctica se refiere a
compresores mecánicos y bombas de calor o cualquier otro dispositivo que utiliza energía para
elevar la temperatura del calor residual.

Se puede mencionar las baterías de una UPS como excepción a esta recomendación.

Considere que esto se refiere a compresores mecánicos y bombas de calor, cualquier dispositivo
que utilice energía para elevar la temperatura del calor de salida.

Modelos de facturación de los servicios

Los proveedores de servicios gestionados y de colocación deberían emplear modelos de


facturación y de tarificación que promuevan el uso de las mejores prácticas y de la mejora en la
eficiencia energética. Los operadores de data center enterprise debería asegurar que el coste
real de los servicios prestados desde el data center es informado y claramente entendido.

Gestión medioambiental

Introducir un plan de gestión medioambiental alineado con las directrices emergentes en las
distintas regiones y con las metodologías internacionales estandarizadas (p.ej. ISO 14001).

Gestión energética

Introducir un plan de gestión energético alineado con las directrices emergentes en las distintas
regiones y con las metodologías internacionales estandarizadas (p.ej. ISO 50001).

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


16
Gestión de activos

Asegurar la implantación de un sistema de gestión de activos tanto en el área TI como en el área


electromecánica que esté controlado y alineado con una metodología estándar aceptada (p.ej.
ISO 55000). Conocer las cantidades, tipologías y propósito de los activos desplegados en un
data center es la base de un gestión efectiva de la energía.

Uso de energía sustentable

Considerar la proporción de energía utilizada en un data center procedente de fuentes


sustentables o renovables. El registro e informe de la energía sustentable o renovable utilizada
en relación al total de energía consumida en un data center es previsible que se convierta en un
requisito necesario en el tiempo. Las métricas estándar para esta práctica están en proceso de
desarrollo con una referencia útil en los estándares ISO/IEC 30134.

Análisis del ciclo de vida

Introducir un plan de análisis del ciclo de vida alineado con las directrices locales/regionales
(p.ej. EN 15978) y metodologías estandarizadas internacionales (p.ej. ISO 14040). El objetivo de
esta práctica es reducir la huella global de dióxido de carbono y mejorar la sustentabilidad más
que estar directamente relacionada con aspectos de mejora de la energía.

Tecnologías alternativas para la generación eléctrica

Se debería considerar el suministro de energía desde fuentes de energía alternativa y


sustentable como las pilas de combustible, generación eólica o fotovoltaica y generación de uso
y aplicación local como la biomasa o bio-fuel. De este modo se podría favorecer la reducción de
la huella ambiental del dióxido de carbono pero también son atractivas a nivel económico y
pueden servir de fuente alternativa fiable de suministro eléctrico. El objetivo de esta práctica es
reducir la huella global de dióxido de carbono y mejorar la sustentabilidad más que estar
directamente relacionada con aspectos de mejora de la energía.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


17
Nivel de resiliencia y aprovisionamiento

Una de las más importantes fuentes de ineficiencia en los centros de datos es el exceso de
provisión de espacio, energía o refrigeración y la operación de las instalaciones con cargas
parciales. A diferencia de los diseños modulares, un diseño monolítico de las instalaciones
representa un gasto de capital significativo y con frecuencia innecesario.

Además, el nivel de capacidad de resiliencia del data center aumenta las ineficiencias si
atendemos al aumento de los gastos fijos generales y que se ven agravados por una pobre
utilización.

*Figura 7*
Diseño de una resiliencia efectiva

Aplicar los niveles de resiliencia apropiados a nivel de data center, de los equipos TI, del
software y de red para alcanzar el nivel de resiliencia y disponibilidad que realmente requiere el
servicio. Una resiliencia alta a nivel físico rara vez resulta efectiva como solución general.

Diseño para maximizar la eficiencia a carga parcial una vez aprovisionada (M&E)

El diseño de todas las áreas del data center debería maximizar la eficiencia alcanzada por las
instalaciones en condiciones de utilización parcial y cargas eléctricas variables de TI. Además de
las consideraciones respecto a un aprovisionamiento modular se considera la capacidad de
respuesta de las infraestructuras ante cargas dinámicas (p.ej. mediante el control apropiado de
dispositivos con variadores de frecuencia (o velocidad) en bombas, ventiladores y compresores).

Crear una resiliencia adecuada para los requisitos empresariales

Sólo debería construirse (o comprarse en el caso de clientes de colocación) el nivel de


resiliencia realmente justificado por los requisitos del negocios y el análisis de impacto. Las
infraestructuras 2N son frecuentemente innecesarias e inapropiadas.

Si únicamente estuviera disponible en el data center un único nivel “N” de resiliencia se podría
aumentar la resiliencia o la disponibilidad en los servicios críticos segregando la plataforma TI en
diversos emplazamientos de modo que las aplicaciones sean resilientes incluso a la
indisponibilidad de un emplazamiento particular.

Aprovisionamiento Lean de energía y enfriamiento para un máximo de 18 meses en la


capacidad del espacio técnico

El exceso de aprovisionamiento de capacidad en la energía y enfriamiento en un data center


genera importantes pérdidas asociados a los gastos fijos y resulta innecesario. La planificación
del data center para una expansión modular (escalable) y la posterior construcción de esta
capacidad dentro de un programa continuado de despliegues resulta más eficiente. Esto también
permite resolver mejor las distintas "generaciones" tecnológicas de los equipos de TI con las
infraestructuras de M&E que les dan soporte, mejorando tanto la eficiencia como la capacidad
para responder a los requisitos empresariales.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


18
Tendencias

Se han realizado importantes progresos en la aplicación de medidas de eficiencia energética dentro de


la industria de los centros de datos que podemos observar mediante diversos ejemplos ultra eficientes.

Estos ejemplos liderados por empresas como Google, Microsoft y Facebook muestran que es posible
construir data centers con registros de PUE cercanos a 1.1.

Sin embargo, la amplia adopción de las mejores prácticas aún tiene que llevarse a cabo en todo el
sector, específicamente dentro de los tres segmentos principales:

- Las pequeñas salas de servidores de pequeñas y medianas organizaciones

- Los centros de datos corporativos / empresariales

- Los centros de datos multi-arrendatario

Muchas de las claves en eficiencia para derribar las barreras comunes ya han sido identificadas,
discutidas y demostradas de manera exhaustiva en diversas publicaciones. Sin embargo, siguen
estando presentes en gran medida estas mismas barreras dificultando el logro final de conseguir
instalaciones realmente rentables, de alto rendimiento y de reducido impacto ambiental.

Controlar el estado de los servicios y los activos que los soportan para poder saber qué y cuándo se
pueden desconectar o decomisionar equipamiento no es una tarea ni mucho menos sencilla en muchos
casos. Un proceso de coordinación y de ticketing ágil y funcional es otro elemento requerido para el uso
por los distintos equipos que intervienen en las operaciones.

Atendiendo por tanto al ritmo de adopción de las medidas energéticas y, al mismo tiempo, el ritmo de
crecimiento en la demanda de las capacidades de almacenamiento y tratamiento de la información en el
mundo actual es fácil determinar que se requieren soluciones técnicas para almacenar la cantidad cada
vez mayor de datos de Internet de forma segura y con el mínimo consumo de energía.

En el escenario actual, con una eficiencia de consumo de energía promedio (PUE) de 1,8, el consumo
de energía de la industria de los data center en todo el mundo llegará a 507,9 TWh en 2020.

Para hacer frente a las situaciones de más urgencia la reducción en el consumo de energía se puede
lograr mediante mejoras en el diseño arquitectónico, el equipamiento, el sistema de refrigeración, entre
otros y que además cuentan con una mayor participación de los fabricantes.

Por otra parte, una nueva generación de data center incorporarán algunas de las arquitecturas de
centros de datos modernos más eficientes (modularidad en Corriente Alterna (AC) y grids de corriente
continua directa (DC)), así como algunas tecnologías futuras tales como la fotónica de silicio, materiales
Wide Band Gap (GBM) o memorias emergentes Non-Volatile Memory (NVM), podrían reducir el
consumo de energía.

Una de las ventajas intrínsecas de la fotónica es el ahorro de energía, lo cual es una gran ventaja para
las interconexiones que son una parte significativa del consumo de energía. Por ejemplo, con un enlace
de 10 Gb/s, una interconexión de cobre consumirá 10W, mientras que la fotónica de silicio o soluciones
VCsELs consumirán 0.2W. Esto equivale a una reducción de costos anuales desde USD 3500/año para
el cobre respecto a USD 70/año para la solución fotónica.

*Figura 8*
Todas estas nuevas tecnologías abren espacios para aliviar la congestión del tráfico en las líneas de
transmisión de datos y mejorar significativamente la eficiencia energética dependiente de las redes de
distribución de energía.

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


19
Referencias / Saber más

- Masanet, E, Brown, R E, Shehabi, A, Koomey, J G, and B Nordman (2011). “Estimating the


Energy Use and Efficiency Potential of U.S. Data Centers. Proceedings of the IEEE, Volume 99,
Number 8
- Koomey, J.G. (2011). Growth in Data Center Electricity Use 2005 to 2010. Analytics Press,
Oakland, California. http://www.analyticspress.com/datacenters.html
- Upton, F (2015). North American Energy Security and Infrastructure Act of 2015. H.R. 8, 114th
Congress. https://www.congress.gov/bill/114th-congress/house-bill/8
- Koomey, Jonathan. 2008. Worldwide electricity used in data centers. Environmental Research
Letters. vol. 3, no. 034008. September 23. [http://stacks.iop.org/1748-9326/3/034008]
- Koomey, Jonathan G. 2007. Estimating Total Power Consumption by Servers in the U.S. and the
World. February 15.
http://www.mediafire.com/file/exywo1hf6ionskw/AMDserverpowerusecomplete-final.pdf.
- The Green Grid, Data Centre Life Cycle Assessment Guidelines. White Paper #45, v2, 2012.
http://www.thegreengrid.org/~/media/WhitePapers/WP45v2DataCentreLifeCycleAssessmentGuid
elines.pdf
- Van Heddeghem, W., Lambert, S., Lannoo, B., Colle, D., Pickavet, M., & Demeester, P. (2014).
Trends in worldwide ICT electricity consumption from 2007 to 2012. Computer Communications,
50, 64-76.
- NRDC and WSP (2012). The Carbon Emissions of Server Computing for Small- to Medium-Sized
Organizations: A Performance Study of On-Premise vs.The Cloud. WSP Environment &Energy,
LLC and Natural Resources Defense Council. October 2012.
- Barroso, L. A., Clidaras, J., & Hölzle, U. (2013). The datacenter as a computer: An introduction to
the design of warehouse-scale machines. Synthesis lectures on computer architecture, Morgan
Claypool Publishers
- Cadmus (2015). New York State Data Center Market Characterization. New York State Energy
Research and Development Authority (NYSERDA) Report Number 15-06. October 2015.
- Lanzisera, S., Nordman, B., & Brown, R. E. (2012). Data network equipment energy use and
savings potential in buildings. Energy Efficiency, 5(2), 149-162.
- Villars, Richard L (2014). “U.S. Datacenter Census and Construction 2014-2018 Forecast:
Realigning Workloads, Managing Obsolescence, and Leveraging Hyperscale”. IDC #252712.
- Venture Outsource, 2015. ODM Quanta focus on white boxes bypasses Dell, HP, Cisco
traditional model for OEMs. VentureOutsource.com: https://www.ventureoutsource.com/contract-
manufacturing/focus-odm-quanta-it-shift-cloudinfrastructure-leaving-dell-hp-traditional
- The Green Grid datacenter power efficiency metrics: PUE and DCiE. Available at
http://www.thegreengrid.org/sitecore/content/Global/Content/white-papers/The-Green-Grid-Data-
Center-Power-Efficiency-Metrics-PUE-and-DCiE.aspx.
- Uptime Institute, Important to recognize the dramatic improvement in data center efficiency.
http://blog.uptimeinstitute.com/2012/09/important-to-recognize-thedramaticimprovement-in-data-
center-efficiency/
- Cheung, I. H., Greenberg, S., Mahdavi, R., Brown, R., & Tschudi, W. (2014, August). Energy
Efficiency in Small Server Rooms: Field Surveys and Findings. Proceedings the 2014 ACEEE
Summer Study on Energy Efficiency in Buildings. LBNL- 6952E
- Google 2015. “Our energy-saving data centers.” Accessed December 2, 2015.
http://www.google.com/about/datacenters/efficiency/internal/index.html#measuring-efficiency
- Gelber, R. 2012. “Facebook showcases green datacenter.” HPCwire. Accessed December 2,
2015. http://www.hpcwire.com/hpcwire/2012-04-26/facebook_showcases_green_datacenter.html
- Masanet, E., Shehabi, A., Ramakrishnan, L., Liang, J., Ma, X., Walker, B., & Mantha, P. (2013).
The Energy Efficiency Potential of Cloud-Based Software: A US Case Study. Lawrence Berkeley
National Laboratory, Berkeley, California.
- Shehabi, A., Masanet, E., Price, H., Traber, K., Horvath, A., and W.W. Nazaroff. 2011. “Data
Center Design and Location: Consequences for Electricity Use and Greenhouse-Gas Emissions.”
Building and Environment, Volume 46, Issue 5.
- Koomey, J.G., Berard, S., Sanchez, M. and Wong, H., 2011. Implications of historical trends in
the electrical efficiency of computing. Annals of the History of Computing, IEEE, 33(3), pp.46-54.
- Koomey, Jonathan, and Samuel Naffziger. 2015. "Efficiency's brief reprieve: Moore's Law
slowdown hits performance more than energy efficiency." In IEEE Spectrum. April. pp.
Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook
20
http://spectrum.ieee.org/computing/hardware/moores-law-might-be-slowing-down-but-not-
energyefficiency
- Fitzgerald, D. 2015. Data Centers and Hidden Water Use. The Wall Street Journal.
http://www.wsj.com/articles/SB10007111583511843695404581067903126039290
- Federal Data Center Consolidation Initiative (FDCCI), 2014. GSA FDCCI Inventory Data Fields.
https://cio.gov/wp-content/uploads/downloads/2012/10/FDCCI-Inventory-Data-Fields-Release-
2.pdf
- Boyd, A. 2015. Experts: Data center consolidation goals not aggressive enough. Federal
Times.com. http://www.federaltimes.com/story/government/it/datacenter/2015/02/17/data-center-
consolidation-goals-not-aggressive/23556995/
- Top500. 2016. Top500 List – November 2015. http://www.top500.org/lists/2015/11/
- Kaplan, JM., Forrest, W., Kindler, N. 2008. Revolutionizing Data Center Efficiency McKinsey and
Company.
http://www.mckinsey.com/clientservice/bto/pointofview/pdf/revolutionizing_data_center_efficiency
.pdf
- Delforge, P., & Whitney, J. 2014. Issue Paper: Data Center Efficiency Assessment Scaling up
Energy Efficiency Across the Data Center Industry: Evaluating Key Drivers and Barriers. Natural
Resources Defense Council (NRDC).
- Ourghanlian, B. 2010. Improving Energy Efficiency: And End User Perspective. The Green Grid.
The Green Grid Technical Form 2010.
http://www.thegreengrid.org/~/media/EMEATechForums2010/Improving%20Energy%20Efficienc
y%20-%20An%20End%20User%20Perspective_Paris.pdf?lang=en
- United EIF, Inc. 2015. Advanced Configuration and Power Interface Specification.
http://www.uefi.org/sites/default/files/resources/ACPI_6.0.pdf
- Lo, D., Cheng, L., Govindaraju, R., Ranganathan, P., & Kozyrakis, C. (2015, June). Heracles:
improving resource efficiency at scale. In Proceedings of the 42nd Annual International
Symposium on Computer Architecture (pp. 450-462). ACM.
- Masanet, E., Shehabi, A., Ramakrishnan, L., Liang, J., Ma, X., Walker, B., Hendrix, V., and P.
Mantha (2013). The Energy Efficiency Potential of Cloud-Based Software: A U.S. Case Study.
Lawrence Berkeley National Laboratory, Berkeley, California.
- Heller, B., Seetharaman, S., Mahadevan, P., Yiakoumis, Y., Sharma, P., Banerjee, S., &
McKeown, N. (2010, April). ElasticTree: Saving Energy in Data Center Networks. In NSDI (Vol.
10, pp. 249-264).
- Masanet, E., A. Shehabi, L. Ramakrishnan, J. Liang, X. Ma, B. Walker, V. Hendrix, and P.
Mantha (2013). The Energy Efficiency Potential of Cloud-Based Software: A U.S. Case Study.
Lawrence Berkeley National Laboratory, Berkeley, California.
- Hilty, L.M., Aebischer, B. (Eds.), 2015. ICT Innovations for Sustainability, Advances in Intelligent
Systems and Computing. Springer International Publishing, Cham.
- Erdmann, L., Hilty, L., Goodman, J., Arnfalk, P., 2004. The Future Impact of ICTs on
Environmental Sustainability (Technical Report No. EUR 21384 EN). Institute for Prospective
Technological Studies, Seville, Spain.
- Elliott N, Molina, M., and Trombley, D. 2012, A defining framework for intelligent efficiency
(Washington, DC: American Council for an Energy-Efficient Economy)
http://aceee.org/sites/default/files/publications/researchreports/e125.pdf
- Accenture. 2015. SMARTer2030: ICT Solutions for 21st Century Challenges
http://smarter2030.gesi.org/downloads/Full_report2.pdf
- Börjesson Rivera, M., Håkansson, C., Svenfelt, Å., Finnveden, G., 2014. Including second order
effects in environmental assessments of ICT. Environ. Model. Softw. 56, 105-
115.doi:10.1016/j.envsoft.2014.02.005
- Erdmann, L., Hilty, L.M., 2010. Scenario Analysis: Exploring the Macroeconomic Impacts of
Information and Communication Technologies on Greenhouse Gas Emissions. J. Ind. Ecol. 14,
826–843. doi:10.1111/j.1530-9290.2010.00277.
- Azevedo, I.M.L., 2014. Consumer End-Use Energy Efficiency and Rebound Effects. Annu.Rev.
Environ. Resour. 39, 393–418. doi:10.1146/annurev-environ-021913-153558
- Gillingham, K., Rapson, D., Wagner, G., 2015. The rebound effect and energy efficiency policy.
- Borenstein, S., 2013. A microeconomic framework for evaluating energy efficiency rebound and
some implications. National Bureau of Economic Research.
- Harrington, D., 2015. From first mile to last mile: Global industrial & logistics trends. Colliers
International.
Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook
21
- Shorr Packaging Corp, 2015. The Amazon Effect: Impacts on Shipping and Retail
http://www.shorr.com/packaging-news/2015-06/amazon-effect-impacts-shipping-and-retail
- Williams, E., 2011. Environmental effects of information and communications technologies.
Nature 479, 354–358. doi:10.1038/nature10682
- Shehabi, A., Walker, B. & Masanet, E. The energy and greenhouse-gas implications of internet
video streaming in the United States. Environ. Res. Lett. 9, 054007 (2014).
- Kitou, E. & Horvath, A. External air pollution costs of telework. Int. J. Life Cycle Assess. 13, 155–
165 (2008).
- Henderson, P. & Waitner, M. Real-time energy management: A case study of three large
commercial buildings in Washington, D.C. (Natural Resources Defense Council, 2013). At
http://www.nrdc.org/business/casestudies/files/tower-companies-case-study.pdf
- Seidel, S. and Ye, J. 2012. Leading by example: using information and communication
technologies to achieve Federal sustainability goals (Center for Climate and Energy Solutions)
http://www.c2es.org/docUploads/federal-sustainability-ict.pdf
- Laitner, J.A., McDonnell, M.T., and Keller, R.M. 2015. ICT-Enabled Intelligent Efficiency: Shifting
from device-specific approaches to system optima. Online: http://cda.iea-4e.org/document/11/ict-
enabled-intelligent-efficiency-shifting-from-device-specific-approachesto-system-optima
- Pouchet, J. 2016. Time for a Server Idle Performance Standart – Introducing 10 Minus. Emerson
Network Power Blog. http://blog.emersonnetworkpower.com/efficiency/time-for-a-server-idle-
performance-standard/
- Horner, N., Azevedo, I. 2016. Power usage effectiveness in data centers: overloaded and
underachieving. The Electricity Journal, Volume 29, Issue 4, May 2016, Pages 61-69
- Azevedo, D., Rawson, A. 2008. Measuring Data Center Productivity. Metrics and Measurements
Work Group. The Green Grid.
http://www.thegreengrid.org/~/media/TechForumPresentations2008/Measuring_Data_Center_Pr
oductivity.pdf?lang=en
- McKinsey & Company. http://www.sallan.org/pdfdocs/McKinsey_Data_Center_Efficiency.pdf

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


22
ANEXO FIGURAS – Figura 1

Evolución del consumo energético en Data Center (EEUU)

http://eta.lbl.gov/publications/united-states-data-center-energy-usag

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


23
ANEXO FIGURAS – Figura 2

Evolución del consumo energético en Data Center (Mundial)

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


24
ANEXO FIGURAS – Figura 3

Implicaciones ambientales de la industria del Data Center

http://perspectives.mvdirona.com/2015/06/data-center-power-water-consumption/

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


25
ANEXO FIGURAS – Figura 4

Factores de adopción de las mejores prácticas

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


26
ANEXO FIGURAS – Figura 5

Orientación al trabajo en grupo

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


27
ANEXO FIGURAS – Figura 6

Estructura de las políticas generales

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


28
ANEXO FIGURAS – Figura 7

Implicación de las estrategias de redundancia en el diseño

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


29
ANEXO FIGURAS – Figura 8

Evolución tecnológica en términos de eficiencia energética

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


30
Caso Práctico 1: Cálculo consumos en servidores con baja carga
o inactivos

En un data center se acaba de finalizar una inventario de activos con el propósito de iniciar
un plan de eficiencia energética en las instalaciones. Como resultado detecta que:

- 200 servidores se pueden apagar totalmente al no estar en uso

- 250 servidores están activos con un pico máximo de uso del 25% (n = 25)

1. Calcular el consumo eléctrico en kWh y monetario para todas las unidades de servidores
TI activas atendiendo al nivel de carga que desarrollan

2. Calcular los ahorros en consumo eléctrico que supone el apagado de los servidores
inactivos

3. ¿Cuánto sería el coste global en los casos anteriores considerando un PUE promedio de
1,8?

El cálculo estimativo del consumo en el uso de un procesador específico (n) se puede


calcular conociendo la potencia consumida a máximo rendimiento (P-max) y en estado de
carga nula (P-idle) mediante la fórmula:

Partiendo de servidores del mismo fabricante y considerando para cada servidores:

- P-max =400 watts

- P-idle = 200 watts

- Coste típico del kWh = 0,12 USD

Issue 1.0 EEBP – Sesión Técnica 1 - Training Workbook


31
Energy Efficiency Best Practices (EEBP)

Sesión Técnica 2:

Planificación y gestión de la EE

Training Workbook
Every effort has been made to ensure that the information contained in this document is true and correct
at the time of going to press. However, the technology, systems, products, processes, specifications
and content in general described in this document are subject to continuous development and
DCProfessional is entitled to change them at any time and to expand on them. DCProfessional cannot
accept liability for any loss or damage of any nature whatsoever arising or resulting from the use of or
reliance on information or particulars in this document.

All names and other data used in examples are fictitious.

The information contained in this document is of a general nature.

No part of this document may be reproduced by any means, other than with the express written
permission of the copyright holder.

© Copyright 2016 by DCProfessional Development

All rights reserved. No part of this manual may be used, reproduced, or transmitted in any form or by any
means, electronic mechanical, including photocopying, recording, or by any information storage and
retrieval system, without the prior agreement and written permission of the publisher, except for the
inclusion of brief quotations in a review.

The contents of this manual are subject to ongoing revision without notice due to continuing
developments in standards, regulations, methodology, design, and manufacturing.

This manual forms part of the DCProfessional Development curriculum, and is presented without
warranty of any kind, including but not limited to implied warranties, for the manual’s quality or fitness for
any particular purpose. DC Professional Development shall not be liable to the purchaser or any other
entity with respect to any liability, loss or damage caused directly or indirectly by this manual.

All brand names and trademarks are the property of their respective owners.
DCProfessional Development
28 Scrutton Street
London EC2A 4RP
United Kingdom

www.dc-professional.com

ACKNOWLEDGEMENTS

DCProfessional Development is indebted to the following organisations and individuals for their
invaluable support in the preparation of this manual:

Organisations: DCD Group, DCD Focus Magazine, DCD Intelligence,

Individuals: Agustín López Neira (Training Project Developer & Content Producer Manager).

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 2


Relación de contenidos

Relación de contenidos .............................................................................................................. 3

Objetivos .................................................................................................................................... 6

Eficiencia Energética y Data Centers........................................... ¡Error! Marcador no definido.

Introducción ................................................................................................................................ 7

Evolución.................................................................................................................................... 8

Actuales Protagonistas/Referencias ......................................................................................... 10

Necesidades actuales .............................................................................................................. 11

Soluciones ................................................................................................................................ 13

Sistemas TIC ................................................................................................................... 13

Componentes de la infraestructura .................................................................................. 15

Tendencias............................................................................................................................... 17

Referencias / Saber más .......................................................................................................... 18

ANEXO FIGURAS – Figura 1 ................................................................................................... 21

Áreas de soporte a los equipos TI.................................................................................... 21

ANEXO FIGURAS – Figura 2 ................................................................................................... 22

Relación global en PUEs ................................................................................................. 22

ANEXO FIGURAS – Figura 3 ................................................................................................... 23

Áreas de actuación en eficiencia energética en el DC ..................................................... 23

ANEXO FIGURAS – Figura 4 ................................................................................................... 24

Diseño e influencia de los ahorros ................................................................................... 24

ANEXO FIGURAS – Figura 5 ................................................................................................... 25

Tipos de pérdidas ............................................................................................................ 25

ANEXO FIGURAS – Figura 6 ................................................................................................... 26

Distribución total del consumo ......................................................................................... 26

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 3


ANEXO FIGURAS – Figura 7 ................................................................................................... 27

Funcionalidades internas de los dispositivos.................................................................... 27

ANEXO FIGURAS – Figura 8 ................................................................................................... 28

Equipos TI “comatosos” ................................................................................................... 28

ANEXO FIGURAS – Figura 9 ................................................................................................... 29

Virtualización TI ............................................................................................................... 29

ANEXO FIGURAS – Figura 10 ................................................................................................. 30

Crecimiento adaptado a la necesidad real ....................................................................... 30

ANEXO FIGURAS – Figura 11 ................................................................................................. 31

Gestión ambiental ............................................................................................................ 31

ANEXO FIGURAS – Figura 12 ................................................................................................. 32

Gestión del aire................................................................................................................ 32

ANEXO FIGURAS – Figura 13 ................................................................................................. 33

Ineficiencias en el sistema eléctrico ................................................................................. 33

ANEXO FIGURAS – Figura 14 ................................................................................................. 34

Relación de consumos TI y pérdidas eléctricas ............................................................... 34

ANEXO FIGURAS – Figura 15 ................................................................................................. 35

Consideraciones en el equipamiento ............................................................................... 35

ANEXO FIGURAS – Figura 16 ................................................................................................. 36

Equipamiento eficiente..................................................................................................... 36

ANEXO FIGURAS – Figura 17 ................................................................................................. 37

Tendencias – TI como última frontera .............................................................................. 37

Caso Práctico 1: Aplicación de medidas básicas de eficiencia ................................................. 38

Caso Práctico 2: Costes asociados a PUE ............................................................................... 39

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 4


Uso apropiado del Workbook
Este workbook ha sido diseñado para un uso conjunto en las sesiones presenciales, casos de estudio y
workshops de este módulo, de modo que los asistentes puedan adquirir conocimientos de aplicación
práctica en un entorno de la industria de los Data Center.

El curso está estructurado para que el Tutor exponga funcionalidades y ejemplos de casos prácticos con
el apoyo del material del Tutor (proyecciones, videos, simulaciones, técnicas de aprendizaje acelerado).

Siempre que sea posible, los asistentes deben participar de forma activa individual o en grupos
reducidos para desarrollar y completar ejercicios orientados a consolidar su aprendizaje Se ha
dispuesto de un entorno de aprendizaje adecuado para que pueda actuar de modo seguro.

El objetivo del workbook es ser un documento de trabajo orientado al refuerzo de la información


presentada por el Tutor. Cada asistente debe disponer de una copia digital o en papel de este workbook
con antelación al curso de modo que pueda ayudar a la preparación previa del curso, especialmente en
los casos de aquellos asistentes menos familiarizados con algunas temáticas del curso, además de
servir durante y después de la formación como documento de consulta.

No está diseñado en cualquier caso para proporcionar de modo detallado todos los aspectos teóricos ni
fundamentos de una tecnología o aplicación, sino específicamente aquellos especialmente relevantes
para el desarrollo del curso y los objetivos concretos de aprendizaje.

Cualquier consulta, aclaración o incidencia sobre DCProfessional training courses puede dirigirla a:

agustin.lopez@datacenterdynamics.com

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 5


Objetivos
Planificación y Gestión de la EE
Al finalizar este módulo, será capaz de:

 Distinguir los diferentes usos de la energía eléctrica en los centros de datos

 Identificar modos de ahorro mediante distintas medidas típicas de reducción del consumo
energético

 Proponer estrategias prácticas para conseguir que los centros de datos existentes y los nuevos
sean eficientes

También dispone de la oportunidad de:

- Compartir sus conocimientos y opiniones

- Exponer casos reales y problemáticas en experiencias vividas o conocidas

- Escuchar atentamente las opiniones del resto de los asistentes

- Aportar comentarios de manera activa, respetando el enfoque del resto de participantes en la


aplicación de soluciones o puntos de vista concretos, incluso cuando sean opuestos a sus
propias valoraciones y entendimiento como base del enriquecimiento del grupo

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 6


Introducción

La principal función de los data center es la de contener equipos electrónicos utilizados para el
procesamiento de datos (servidores), el almacenamiento de datos (equipo de almacenamiento) y las
comunicaciones (equipos de red).

En conjunto, todo este equipamiento procesa, almacena y transmite información digital y que es
conocido como "tecnologías de la información y las comunicaciones" (TIC).

Los data center también contienen generalmente equipamiento de soporte para la conversión específica
de la energía requerida por el equipamiento TIC, así como equipamiento de respaldo adicional para
mantener la fiabilidad y la alta calidad tanto en la parte eléctrica como en el equipamiento dispuesto
para el control ambiental que mantiene la temperatura adecuada y la humedad requerida para el buen
funcionamiento del equipamiento TI.

*Figura 1*
La situación óptima sería que el consumo eléctrico de un data center se produjera únicamente en el
equipamiento mínimo requerido, idealmente en un data center sin necesidades de enfriamiento
mecánico y con un mínimo número de transformaciones y acumuladores de la energía. Todo esto sin
poner en riesgo la disponibilidad comprometida de los servicios.

Se revisará a continuación cuales son las consideraciones básicas a tener en cuenta, especialmente en
el caso de instalaciones que ya están en operación e inicialmente en peor posición para poder aplicar
cambios en los sistemas.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 7


Evolución

El modo en que se diseñaban los data center era mucho menos exigente durante el pasado siglo,
momento en que la densidad de carga térmica en los racks era muy baja e incluso las salas técnicas
eran utilizadas al mismo tiempo por el personal que las gestionaba estableciendo criterios para el
confort de las personas en 21ºC en estas salas.

En el inicio del presente siglo la explosión de servicios online y el acceso desde múltiples dispositivos
por miles de millones de personas ha obligado a la construcción y diseño de los data center con un
enfoque industrializado y con la necesidad del mayor aprovechamiento del espacio físico disponible
para atender a demandas de capacidad con curvas de crecimiento exponencial.

Esta urgencia en la capacidad no ha permitido una integración y adopción generalizada de


consideraciones en la eficiencia energética durante prácticamente la primera década del siglo. Sin
embargo, las diversas consideraciones económicas y medioambientales impulsan en los últimos años la
necesidad de atender urgentemente a estas cuestiones si se quiere atender a las demandas previstas
en los próximos años.

La falta de formación de temas de eficiencia energética, intereses en el crecimiento rápido de la


capacidad y la dinámica de seguir aplicando ciertas prácticas y políticas del pasado (únicamente por
costumbre sin tener en consideración la especificaciones técnicas actuales de los equipos y de las
instalaciones que les dan soporte) son algunos de los retos que implican un cambio de actitud en el
personal que gestiona las instalaciones, en las prioridades que se marcan desde la alta dirección de las
organizaciones e incluso de la cultura de los clientes/usuarios de las data center.

Estos motivos que tienen que ver más con una dinámica de cambio en las personas que en la parte
técnica, explican realmente la lentitud en que se han ido abordando la aplicación de las buenas
prácticas en eficiencia energética hasta este momento y que las propias necesidades actuales han ido
elevando al nivel de las principales consideraciones a tener en cuenta en estos momento.

*Figura 2*
Históricamente, los resultados obtenidos en métricas comúnmente utilizadas como el PUE han arrojado
datos promedio realmente pobres. De acuerdo con un estudio realizado en 2006 el 85% de los centros
de datos de entonces disponían de una estimación de PUE mayor a 3,0. Esto quiere decir, un consumo
en los sistemas mecánicos y eléctricos del edificio de más del doble que la carga TI a la que daban
soporte. Sólo el 5% tenían un PUE de 2.0 o mejor.

Aunque el Green Grid ha publicado directrices detalladas sobre cómo medir e informar PUE, muchos de
los valores publicados en diferentes medios no son directamente comparables entre distintas
instalaciones. Además, los valores de PUE a veces se utilizan en los documentos de marketing para
mostrar los valores mejor de los casos que no son reales.

En este sentido, las mayores consideraciones respecto a los valores representados por el PUE:

- No todas las mediciones consideran necesariamente los mismos consumos. La nueva definición
presentadas por el TGG limita en este sentido consumos en las instalaciones que se podrían
imputar a los consumos de la parte TI (por ej. medir los consumos de los equipos TI a la entrada
de las PDU en vez de la salida de las PDU o a nivel de fuente de alimentación del propio equipo
TI a nivel de rack)

- PUE instantáneos difieren del PUE promedio. En términos generales, los promedios anuales son
más útiles para las comparaciones y evitan las distorsiones puntales que pueden introducir un
día más frío o caluroso en ciertos periodos.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 8


- PUE no corresponden a medidas del mundo real. A menudo, se publican valores procedentes de
las pruebas realizadas durante la fase de diseño con cargas de prueba, en consideración
únicamente a los periodos con las condiciones óptimas de operación o con los valores
nominales de funcionamiento.

- Tasas de error elevadas al ser registrado el PUE en función de lecturas manuales poco
frecuentes y/o en relación a medidores generales ubicados a cierta distancia unos de otros y que
apuntan más a una estimación del PUE que una medición formal.

En la práctica, los valores de PUE se deben medir en tiempo real. Esto no sólo proporciona una mejor
imagen de las variaciones diurnas y estacionales, sino que también permite al operador reaccionar ante
lecturas inusuales durante las operaciones del día a día.

La métrica PUE ha sido criticada porque no siempre representa una mejoría en el rendimiento
energético debido a que el PUE normalmente empeora a medida que disminuye la carga TI. Esto quiere
decir que una mejor gestión del rendimiento en el equipamiento TI (p.ej. por consolidación o cambio de
equipos TI más eficientes) y para la misma carga de trabajo útil aumentaría el valor PUE aunque en la
realidad se haya mejorado la eficiencia en las operaciones.

Sin embargo, hay que interpretar correctamente la métrica con sus limitaciones respecto a medir
aspectos adicionales como trabajo útil o la eficiencia a nivel de equipamiento TI y reconocer que, en
general, la adopción amplia de las mediciones de PUE ha sido un impulsor de las mejoras en la
eficiencia de los data center en la última década.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook 9


Actuales Protagonistas/Referencias

Entre las referencias principales en aspectos de aplicación de mejores prácticas y herramientas para la
industria del data center podemos destacar:

- CEEDA (Certifed Energy Efficient Data Center Award): primer esquema de certificación en la
industria del data center en la consideración de aplicación de las mejores prácticas reconocidas
a nivel internacional para los centros de datos. http://www.ceedacert.com/

- EU CoC (European Union Code of Conduct): creado en respuesta al aumento del consumo de
energía en centros de datos y la necesidad de reducir los impactos en aspectos ambientales,
económicos y energéticos relacionados. Cuenta con más de 120 participantes y 245 promotores
en la aplicación de las buenas prácticas reconocidas por la industria.
http://iet.jrc.ec.europa.eu/energyefficiency/ict-codes-conduct/data-centres-energy-efficiency

- COE (Center of Expertise for Energy Efficiency in Data Centers): Promovido por Lawrence
Berkeley National Laboratory (LBNL) y esponsorizado por U.S. Department of Energy (DOE)
dispone de herramientas y una master list con acciones recomendadas como mejores prácticas
a implementar en los data center. https://datacenters.lbl.gov/

- DOE (US Department of Energy) Better Buildings: con suite de herramientas para la adopción de
líneas base, formación, casos de estudio y programa de reconocimiento a los mayores
ahorradores de energía. http://energy.gov/eere/better-buildings

- EPA (United States Environmental Protection Agency): métricas, clasificación de equipamiento


de red, UPS y servidores y reconocimiento ENERGY STAR; Data center benchmarking.

https://www.energystar.gov/index.cfm?c=prod_development.server_efficiency

- FEMP (US Federal Energy Management Program): talleres, casos de estudio, políticas,
intercambio de información y asistencia técnica. http://energy.gov/eere/femp/energy-efficiency-
data-centers

- The Green Grid: métricas y herramientas de aplicación de modelos de madurez en eficiencia


energética para data centers. http://www.thegreengrid.org/

- Information technology industry council: Políticas de uso de la eficiencia energética en


dispositivos TIC. https://www.itic.org/

- ASHRAE: Estándares de referencia en aspectos ambientales relacionados con el equipamiento


TI y de telecomunicaciones para los data center. https://www.ashrae.org/

- AFCOM: Asociación de profesionales en la industria del data center con capítulos en EEUU,
APAC y Reino Unido. https://www.afcom.com/

- Uptime Institute: Informes con datos sobre la eficiencia energética en la industria de los data
center. https://uptimeinstitute.com/

- Open compute Project: Comunidad global de líderes tecnológicos que trabajan juntos de modo
abierto en la infraestructura de TI con el objetivo de lograr mayores ahorros, ampliar las
posibilidades de personalización del equipamiento y disminución de los costes.
http://www.opencompute.org/

- SINGAPORE STANDARD SS 564 Series: Singapore Standard for green data centres.
https://www.singaporestandardseshop.sg/product/Package.aspx?ID=5dfe0c1e-eeca-4cd6-9a8d-
5fe9cdc2eac6

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


10
Necesidades actuales

La aplicación de medidas de eficiencia energética en un data center afecta a todos los sistemas de
soporte y de equipamiento TIC.

Los modelos simplistas convencionales para calcular la eficiencia de los data center subestiman
enormemente las pérdidas energéticas en muchos de los sistemas, especialmente en relación a
equipamiento TIC centrándose en muchos casos en la parte de gestión específica de aire. Aunque los
sistemas de enfriamiento son una parte importante de ahorro lo ciertos es que la oportunidad de mejorar
la eficiencia es mucho mayor de lo que se cree comúnmente si aplicamos un enfoque holístico a todos
los sistemas.

*Figura 3*
Para poder explorar el ámbito de la eficiencia y consumo de la energía se deben tener claros y
comprender bien algunos conceptos fundamentales.

Energía vs potencia
Es muy importante comprender la diferencia entre potencia y energía cuando se emprende el análisis
de los costes energéticos de un data center.

La potencia instalada se mide en vatios (W) o kilovatios (kW) y está asociada a los sistemas que
suministran energía. Para el acceso al suministro eléctrico por parte de un proveedor existen unos
costes asociados a la potencia contratada que típicamente aumentan con el nivel de sofisticación de
diseño del sistema. En la actividad de consumo de la energía podremos consumir hasta el límite de
potencia contratado pero no podremos superarlo típicamente en ningún momento aunque sí podremos
hacer uso de un consumo por debajo esta potencia contratada.

Por otra parte, la energía eléctrica se vende en unidades de energía denominadas kilovatio hora (kWh).
Un kilovatio hora es la cantidad de energía desarrollada en una hora a un régimen de potencia de 1.000
vatios (1 kW).

En un paralelismo con las viviendas residenciales: en el momento que activamos el consumo en varios
dispositivos de elevada potencia a la vez (horno, lavadora junto a los otros habituales) en el momento
que se desarrolla en el conjunto de consumos y en un momento del tiempo determinado una demanda
de energía superior a la potencia contratada entonces salta la protección del sistema principal instalado
por la compañía.

Por tanto, cuando logramos reducir el consumo de energía (kWh) se pueden reducir los costes de
potencia instalada (kW) además de los propios asociados a la del consumo de la energía.

Por el contrario, cuanto más ineficiente sean las cargas eléctricas del data center mayor será el nivel de
costes asociados a las infraestructuras físicas, tanto por ineficiencias en la transformación y pérdidas en
la parte eléctrica como en la parte mecánicas que disipen el calor residual de cargas TI para mantener
el equilibrio de temperatura en el data center.

Otro aspecto relevante ligada al ahorro de costes es la habitual confusión entre acciones que permiten
reducciones temporales en el consumo energético y las estrategias que permiten conseguir reducciones
permanentes.

Los ahorros temporales, como la interrupción de la carga o la gestión de potencia a nivel de servidor,
reducen los costes de consumo de la energía pero no reducen necesariamente la potencia nominal de
los sistemas de infraestructura física ni los costes de mantenimiento asociados.

*Figura 4*
Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook
11
Los cambios permanentes o estructurales, como los servidores de alta eficiencia o los sistemas SAI de
alta eficiencia, sí reducen los costes asociados tanto al consumo de la energía como en la parte de las
infraestructuras.

Por tanto, el tema de la eficiencia de los centros de datos está mucho más claro cuando se indica el
consumo eléctrico en kilovatios y cuando se utilizan los kilovatios como medida para tratar la eficiencia.

Tipos de pérdidas
En el entorno del data center podemos contemplar tres tipos de pérdidas asociadas al suministro
eléctrico.

- Pérdida sin carga: es la potencia de entrada que utiliza un determinado dispositivo independiente
de la carga y por tanto es constante a cualquier nivel de carga.

- Pérdida proporcional: A medida que aumenta la carga hay una pérdida adicional que es
proporcional a la carga.

- Pérdida en relación con el cuadrado: es el caso de las pérdidas que se producen cuando un
incremento de la carga produce una pérdida proporcional al cuadrado de la carga.

*Figura 5*
Para entender mejor las pérdidas tomaremos el Sistema de Alimentación Ininterrumpido (SAI) como
ejemplo.

La pérdidas sin carga (una carga del 0%) en el SAI A implica que toda la potencia de entrada es
consumida por el propio SAI, de ahí el término de pérdidas "sin carga". Esto también puede recibir otros
nombres como tara, carga constante, carga fija, desviación y carga paralela. Se trata de pérdidas que
no dependen de la carga y se atribuyen a la alimentación de dispositivos tales como transformadores,
condensadores, circuitos lógicos y tarjetas de comunicaciones. Las pérdidas sin carga pueden
representar más del 40% de todas las pérdidas de SAI y constituyen, con diferencia, la mayor
oportunidad de mejorar la eficacia de SAI.

A medida que aumenta la carga de un SAI, también aumenta la cantidad de potencia que los diferentes
componentes necesitan "procesar" a lo largo del recorrido de la electricidad. Por ejemplo, las pérdidas
por conmutación de los transistores y las pérdidas por resistencia de capacitores e inductores; todo ello
contribuye a las pérdidas proporcionales.

A medida que crece la carga de un SAI, también aumenta la corriente eléctrica que atraviesa sus
componentes. Esto genera pérdidas en el SAI que se conocen en ocasiones con el nombre de pérdidas
de "R al cuadrado de I". Las pérdidas de potencia disipada en forma de calor son proporcionales al
cuadrado de la corriente. Las pérdidas en relación al cuadrado resultan significativas (1-4%) a cargas de
SAI más elevadas.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


12
Soluciones

Muchos responsables de centros de datos ignoran a cuánto asciende la factura eléctrica mensual a
pesar que los gastos de electricidad a lo largo de la vida útil de un data center pueden superar otros
costes más visibles en equipamiento.

Se debe por tanto tomar medidas al respecto con el objetivo de:

- Vincular más claramente los gastos con determinadas decisiones relacionadas con la instalación
de nuevas zonas, equipamientos o actividades del personal de mantenimiento. No se puede
gestionar lo que no se mide.

- Comunicar la información relevante a todas las áreas relevantes como forma de dar visibilidad al
estado actual y posibles cambios producidos en el paso, que sirvan como base para la mejora
en el futuro.

- Desafectar la factura eléctrica del data center de otros consumos por actividades no
relacionadas como otros consumos generales del edificio o de actividades diversas de la misma
organización

- Una toma de decisiones en la que exista información y sensibilidad suficiente por parte de los
responsables para acometer las medidas de eficiencia desde los momentos iniciales de
planificación y compra

Aproximadamente la mitad de la energía utilizada en un data center es para las cargas de IT, mientras
la otra mitad es para los equipos de infraestructura física, incluido el equipo eléctrico, el equipo de
refrigeración y la iluminación.

*Figura 6*
Desde el conocimiento de la situación del consumo se pasa a continuación a mencionar aspectos de
carácter general que se desarrollan de manera específica en sesiones técnicas complementarias del
curso.

Sistemas TIC

El consumo eléctrico del equipo de IT interviene directamente en la factura de la compañía


eléctrica e indirectamente en el uso de diversos equipos de alimentación y refrigeración que
también consumen cantidades de electricidad comparables. Por ello, estos equipos deberían
estar en el punto de mira de todo el personal y bajo control en el consumo eléctrico.

Sin embargo, tradicionalmente las medidas aplicadas para controlar el consumo eléctrico en el
equipamiento TIC han sido inexistentes. La necesidad de aumentar rápidamente la capacidad
aunque fuera de forma ineficiente y la falta de información sobre las opciones disponibles y
cómo aplicarlas de un modo rápido y directo por parte de los fabricantes y proveedores de
equipos de IT no han ayudado en este sentido.

Los usuarios no suelen conocer o incluso no se fían (por falta de generalizada de aplicación de
las medidas a este nivel) de las posibles opciones en el equipamiento TIC que pueden afectar al
consumo eléctrico.

En cualquier caso, esta situación está mejorando por parte de usuarios y fabricantes para poder
tomar medidas que reduzcan los consumos eléctricos mediante herramientas de configuración
del rendimiento que informan del consumo eléctrico en base a las distintas configuraciones.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


13
*Figura 7*

Fuera de la consideración de posibles explotaciones de funcionalidades en los propios equipos,


otro aspecto preocupante son las plataformas de tecnología antigua también denominada
“legados” que siguen funcionando por necesidad de ciertas tareas aún en activo o por
necesidades de consulta histórica.

En estos casos, se puede descubrir que realmente muchos de estos servidores de aplicaciones
que están funcionando no tienen realmente usuarios activos pero tampoco hay un responsable
definido con el que abordar posibles acciones de apagado o de decomisionamiento de los
sistemas.

Estudios recientes confirman que 1 de cada 3 servidores consume energía “haciendo nada” en
una situación que no ha variado en relación a estudios anteriores en este aspecto desde 2008.

*Figura 8*
La necesidad de un control en la gestión del cambio en el equipamiento TIC extensible al resto
de equipos electromecánicos es fundamental y habrá que realizar y/o actualizar un inventario de
estos sistemas para poder progresar en un plan de apagado controlado aunque no se retiren
físicamente.

Opciones adicionales de consolidar aplicaciones legadas en nuevos servidores permiten incluso


reducir el número total de equipos optimizando el espacio e beneficiarse de un mejor
rendimiento de componentes como las fuentes de alimentación eléctrica de los nuevos sistemas.

Además, se evitan fallos de hardware que podrían inhabilitar la disponibilidad de estos sistemas
por obsolescencia de sus componentes y garantías en el suministro de posibles componentes de
recambio.

Además de los sistemas “legado”, la aplicación de medidas de consolidación en servidores que


disponen de elementos comunes de alta eficiencia (p.ej. tipo Blade) para equipos de baja
densidad o que estén incluso en sus últimos años de amortización (típicamente entre el tercer y
quinto año) son medidas que no se deben despreciar ya que pueden llegar a reducción de hasta
el 20% del consumo eléctrico asociado.

La aplicación generalizada de la virtualización en los data center abunda en el concepto de


consolidación aplicando además una intensidad de carga media-alta en los equipos TI que
soportan la funcionalidades de virtualización. De este modo se reduce el número de servidores
instalados y un consumo estructural de 200-400 W asociado a cada equipo aproximadamente,
dependiendo de la tecnología.

La consolidación de servidores puede ser de un nivel de 10:1, en muchos casos, incluso de


100s:1 en el caso del hardware más potente. Además de la eficiencia, la virtualización aporta
otras ventajas como la escalabilidad y despliegue progresivo de las capacidades, amplía la
disponibilidad de los servicios por al evitar puntos de fallo críticos, así como el movimiento de los
trabajos en ejecución a diferentes servidores físicos para una mejor gestión de las cargas.

*Figura 9*

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


14
Componentes de la infraestructura

La reducción del consumo energético del equipo de infraestructura física se consigue mediante:

 Uso eficiente de los dispositivos de infraestructura física

 El correcto dimensionamiento del sistema de infraestructura física respecto a la carga

 Diseño que atienda a la eficiencia energética.

El correcto dimensionamiento y el diseño del sistema tienen mucha mayor repercusión en el


consumo eléctrico que la selección de los dispositivos de infraestructura física ya que la
información de los fabricantes no suele ser suficiente por sí misma para determinar diferencias
reales más allá de un cierto punto de detalle sobre las funcionalidades principales.

Hay pérdidas fijas en los sistemas de alimentación y refrigeración que se producen


independientemente de la presencia de cierto nivel de carga TI y que son proporcionales a la
potencia nominal general del sistema.

En las instalaciones que tienen cargas de IT bajas, las pérdidas fijas de los equipos de
infraestructura física suelen superar a la carga de IT. Siempre que el sistema de infraestructura
física está sobredimensionado, las pérdidas fijas se convierten en un alto porcentaje de la
factura eléctrica total.

*Figura 10*
El correcto dimensionamiento tiene el potencial de reducir hasta el 50% de la factura eléctrica en
instalaciones del mundo real. La convincente ventaja económica del correcto dimensionamiento
es una razón clave de por qué la industria está yendo hacia soluciones de infraestructura física
modulares y escalables.

Entre los problemas en el diseño del sistema que suelen reducir la eficiencia de los centros de
datos se puede mencionar:

 Unidades de distribución de potencia y/o transformadores que funcionan muy por debajo
de su capacidad a plena carga.

 Acondicionadores de aire forzados a consumir excesiva potencia para dirigir aire contra
altas presiones a grandes distancias.

 Elementos en sistemas mal ajustados (p.ej. válvulas de mariposa que reducen


drásticamente la eficiencia, settings por defecto) o mantenidos (p.ej. compresores y
niveles de gases refrigerantes)

Adicionalmente, el uso de una arquitectura de aire acondicionado más eficiente como la


refrigeración orientada por filas puede conseguir una mayor eficiencia para aplicaciones de alta
densidad. Las arquitecturas que concentran mejor la refrigeración con los servidores ofrecen
vías de distribución de aire más cortas y necesitan menos potencia de los ventiladores.

Muchos centros de datos tienen múltiples acondicionadores de aire que, en realidad, luchan
entre sí en vez de aplicar las mismas políticas de funcionamiento al mismo tiempo (p.ej. es
posible que uno caliente mientras otro enfría o que uno humidifique mientras otro deshumidifica).

Si las temperaturas de suministro y retorno de la unidad de aire acondicionado son mayores,


aumenta la eficiencia y la capacidad, y se evita la dehumectación con la consiguiente reducción
de los costes de humidificación. Aunque algunos data center tienen acondicionadores de aire
con función de ahorro de energía, a menudo está desactivada.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


15
*Figura 11*
En data center con suelo técnico para el paso de aire enfriado, la ubicación y grado de apertura
correcta de las baldosas de ventilación aporta beneficios positivos para el sistema general.
Aunque pueda parecer sencillo, realmente se detectan muchas baldosas de ventilación mal
ubicadas o instaladas en el suelo de los data center.

*Figura 12*
La instalación de paneles ciegos en los racks es una forma barata de reducir la temperatura de
entrada del servidor, aumentar la temperatura del aire de retorno del CRAC y aplicara más
ahorros adicionales.

Los equipos de suministro eléctrico nuevos y más eficientes como los mejores sistemas SAI
tienen porcentajes menores de pérdida de potencia que los SAI tradicionales comparables con
cargas típicas con los consiguientes ahorros.

La eficiencia a carga baja es habitualmente el parámetro clave y no la eficiencia a plena carga


que suelen publicar los fabricantes, especialmente en diseños N+1 o 2N. Además, las pérdidas
de SAI penalizan doblemente porque deben enfriarse.

*Figura 13* - *Figura 14* - *Figura 15*


La instalación de alumbrado de bajo consumo tipo LED, con temporizadores o alumbrado
activado por el movimiento son ejemplos de tecnología de alumbrado más eficiente. La potencia
de alumbrado también requiere refrigeración, lo que duplica su coste. La ventaja del alumbrado
de bajo consumo es mayor en centros de proceso de datos de baja densidad o parcialmente
llenos. La iluminación comprende del 1-3% de la carga de energía del data center pero es
también una de las áreas de actuación más fácil de acometer y aporta ventajas adicionales en el
caso del LED como:

 Menor consumo eléctrico

 Genera menos calor

 Es regulable en intensidad

 Evita componentes de riesgo como balastros

 Al elevar la temperatura en sala la iluminación no pierde eficiencia ni brillo

*Figura 16*
Estas estrategias son eficaces para centros de proceso de datos nuevos y algunas pueden
implantarse inmediatamente en los CPD existentes o con el tiempo. No prestar la atención
adecuada a la aplicación de soluciones a estas consideraciones suelen provocar que los centros
de datos consuman el doble de potencia de la que necesita realmente la infraestructura física
cuando unas simples decisiones en el diseño pueden evitar estos problemas con apenas o sin
ningún gasto.

Por ejemplo, asegurarse de que el diseño se haya configurado completamente y haya pasado
pruebas como las de modelización de dinámica de fluidos computacional y una puesta en
servicio completa ayuda a poner el data center en condiciones de funcionamiento mucho más
eficientes.

Conseguir un sistema de infraestructura física integral basado en un diseño estándar formado


por módulos que se han configurado y probado previamente también puede contribuir de forma
significativa al nivel de eficiencia general.
Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook
16
Tendencias

A medida que el número de centros de datos sigue aumentando la buena noticia es que se están
convirtiendo en mucho más eficientes en términos de consumos de la energía.

Un nuevo informe del Departamento de Laboratorio de Energía Nacional Lawrence Berkeley (Berkeley
Lab) ha encontrado que el consumo de electricidad en los centros de datos en EEUU, después de haber
aumentado rápidamente durante más de una década, comenzó a estabilizarse en 2010 y se ha
mantenido estable en poco menos de 2 por ciento del consumo total de electricidad en Estados Unidos.

En el informe se analiza el periodo 2010 a 2014, cuando el consumo aumentó en un 4 por ciento, y de
2014 a 2020 se prevé que aumente otro 4 por ciento. Esto contrasta con un aumento del 90 por ciento
de 2000 a 2005 y el aumento registrado del 24 por ciento desde 2005 y 2010.

Igualmente, se localiza que los centros de datos más grandes son los que han hecho avances
significativos en el funcionamiento más eficiente. Sin embargo, los centros de datos más pequeños así
como los corporativos e institucionales, los cuales no están aumentando en número, pero que aún
representara el 60 por ciento de todo el consumo de energía de los data center en 2020, siguen siendo
generalmente ineficaces.

Los investigadores encontraron tres razones principales para las mejoras en la eficiencia energética:

- Las estrategias de refrigeración y alimentación han mejorado paulatinamente: estrategias de


refrigeración más avanzadas en base al aislamiento de pasillo caliente, economizadores y
refrigeración líquida hacen que el proceso de enfriamiento resulte mucho menos intensivo en
energía

- El escalado y proporcionalidad de la alimentación eléctrica: La mayoría de los servidores


permanecen inactivos la mayor parte del tiempo pero tradicionalmente no fueron diseñados a
reducir su empate electricidad cuando están haciendo menos procesamiento Eso ha ido
mejorando con un mejor software de gestión de energía, así como un mejor hardware que
permite que los servidores pueden adoptar consumos de energía distintos cuando están en
reposo o no son utilizados al máximo de su capacidad. Otra forma de abordar este problema es
reducir la cantidad de tiempo que los servidores están inactivos mediante la reducción del
número total de servidores por la consolidación de servidores, de modo que en lugar de tener
cinco servidores que ejecutan en un 10 por ciento, se pueda disponer de un único funcionando
cerca de un 50 por ciento

- La virtualización: tendencia de la industria que ha impulsado el aumento de servicios en la nube


ya que los data center utilizados en el entorno de nube deben ofrecer un coste menor que el
servidor en propiedad que permita beneficios al proveedor y la energía es una de las cuestiones
a optimizar.

Esta tendencia registrada en EEUU marca la tendencia en la aplicación generalizada a nivel mundial,
especialmente teniendo en cuenta los diversos factores económicos y compromisos medioambientales
que organizaciones y países tienen que enfrentar en la actualidad sin posibilidad de demoras.

Como se ha observado en años anteriores, los esfuerzos de eficiencia energética en gran medida se
han limitado a la gestión de las instalaciones del data center y el diseño de los equipos de diseño y muy
poco se ha hecho para abordar las ineficiencias sistémicas en la parte de equipamiento TI.

*Figura 17*
A medida que los altos ejecutivos presionan por más mejoras en la eficiencia llegarán a los aspectos en
la mejora de la utilización del equipamiento TI como aspecto estratégico a nivel operativo y económico.

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


17
Referencias / Saber más

- Masanet, E, Brown, R E, Shehabi, A, Koomey, J G, and B Nordman (2011). “Estimating the


Energy Use and Efficiency Potential of U.S. Data Centers. Proceedings of the IEEE, Volume 99,
Number 8
- Koomey, J.G. (2011). Growth in Data Center Electricity Use 2005 to 2010. Analytics Press,
Oakland, California. http://www.analyticspress.com/datacenters.html
- Upton, F (2015). North American Energy Security and Infrastructure Act of 2015. H.R. 8, 114th
Congress. https://www.congress.gov/bill/114th-congress/house-bill/8
- Koomey, Jonathan. 2008. Worldwide electricity used in data centers. Environmental Research
Letters. vol. 3, no. 034008. September 23. [http://stacks.iop.org/1748-9326/3/034008]
- Koomey, Jonathan G. 2007. Estimating Total Power Consumption by Servers in the U.S. and the
World. February 15.
http://www.mediafire.com/file/exywo1hf6ionskw/AMDserverpowerusecomplete-final.pdf.
- The Green Grid, Data Centre Life Cycle Assessment Guidelines. White Paper #45, v2, 2012.
http://www.thegreengrid.org/~/media/WhitePapers/WP45v2DataCentreLifeCycleAssessmentGuid
elines.pdf
- Van Heddeghem, W., Lambert, S., Lannoo, B., Colle, D., Pickavet, M., & Demeester, P. (2014).
Trends in worldwide ICT electricity consumption from 2007 to 2012. Computer Communications,
50, 64-76.
- NRDC and WSP (2012). The Carbon Emissions of Server Computing for Small- to Medium-Sized
Organizations: A Performance Study of On-Premise vs.The Cloud. WSP Environment &Energy,
LLC and Natural Resources Defense Council. October 2012.
- Barroso, L. A., Clidaras, J., & Hölzle, U. (2013). The datacenter as a computer: An introduction to
the design of warehouse-scale machines. Synthesis lectures on computer architecture, Morgan
Claypool Publishers
- Cadmus (2015). New York State Data Center Market Characterization. New York State Energy
Research and Development Authority (NYSERDA) Report Number 15-06. October 2015.
- Lanzisera, S., Nordman, B., & Brown, R. E. (2012). Data network equipment energy use and
savings potential in buildings. Energy Efficiency, 5(2), 149-162.
- Villars, Richard L (2014). “U.S. Datacenter Census and Construction 2014-2018 Forecast:
Realigning Workloads, Managing Obsolescence, and Leveraging Hyperscale”. IDC #252712.
- Venture Outsource, 2015. ODM Quanta focus on white boxes bypasses Dell, HP, Cisco
traditional model for OEMs. VentureOutsource.com: https://www.ventureoutsource.com/contract-
manufacturing/focus-odm-quanta-it-shift-cloudinfrastructure-leaving-dell-hp-traditional
- The Green Grid datacenter power efficiency metrics: PUE and DCiE. Available at
http://www.thegreengrid.org/sitecore/content/Global/Content/white-papers/The-Green-Grid-Data-
Center-Power-Efficiency-Metrics-PUE-and-DCiE.aspx.
- Uptime Institute, Important to recognize the dramatic improvement in data center efficiency.
http://blog.uptimeinstitute.com/2012/09/important-to-recognize-thedramaticimprovement-in-data-
center-efficiency/
- Cheung, I. H., Greenberg, S., Mahdavi, R., Brown, R., & Tschudi, W. (2014, August). Energy
Efficiency in Small Server Rooms: Field Surveys and Findings. Proceedings the 2014 ACEEE
Summer Study on Energy Efficiency in Buildings. LBNL- 6952E
- Google 2015. “Our energy-saving data centers.” Accessed December 2, 2015.
http://www.google.com/about/datacenters/efficiency/internal/index.html#measuring-efficiency
- Gelber, R. 2012. “Facebook showcases green datacenter.” HPCwire. Accessed December 2,
2015. http://www.hpcwire.com/hpcwire/2012-04-26/facebook_showcases_green_datacenter.html
- Masanet, E., Shehabi, A., Ramakrishnan, L., Liang, J., Ma, X., Walker, B., & Mantha, P. (2013).
The Energy Efficiency Potential of Cloud-Based Software: A US Case Study. Lawrence Berkeley
National Laboratory, Berkeley, California.
- Shehabi, A., Masanet, E., Price, H., Traber, K., Horvath, A., and W.W. Nazaroff. 2011. “Data
Center Design and Location: Consequences for Electricity Use and Greenhouse-Gas Emissions.”
Building and Environment, Volume 46, Issue 5.
- Koomey, J.G., Berard, S., Sanchez, M. and Wong, H., 2011. Implications of historical trends in
the electrical efficiency of computing. Annals of the History of Computing, IEEE, 33(3), pp.46-54.
- Koomey, Jonathan, and Samuel Naffziger. 2015. "Efficiency's brief reprieve: Moore's Law
slowdown hits performance more than energy efficiency." In IEEE Spectrum. April. pp.
Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook
18
http://spectrum.ieee.org/computing/hardware/moores-law-might-be-slowing-down-but-not-
energyefficiency
- Fitzgerald, D. 2015. Data Centers and Hidden Water Use. The Wall Street Journal.
http://www.wsj.com/articles/SB10007111583511843695404581067903126039290
- Federal Data Center Consolidation Initiative (FDCCI), 2014. GSA FDCCI Inventory Data Fields.
https://cio.gov/wp-content/uploads/downloads/2012/10/FDCCI-Inventory-Data-Fields-Release-
2.pdf
- Boyd, A. 2015. Experts: Data center consolidation goals not aggressive enough. Federal
Times.com. http://www.federaltimes.com/story/government/it/datacenter/2015/02/17/data-center-
consolidation-goals-not-aggressive/23556995/
- Top500. 2016. Top500 List – November 2015. http://www.top500.org/lists/2015/11/
- Kaplan, JM., Forrest, W., Kindler, N. 2008. Revolutionizing Data Center Efficiency McKinsey and
Company.
http://www.mckinsey.com/clientservice/bto/pointofview/pdf/revolutionizing_data_center_efficiency
.pdf
- Delforge, P., & Whitney, J. 2014. Issue Paper: Data Center Efficiency Assessment Scaling up
Energy Efficiency Across the Data Center Industry: Evaluating Key Drivers and Barriers. Natural
Resources Defense Council (NRDC).
- Ourghanlian, B. 2010. Improving Energy Efficiency: And End User Perspective. The Green Grid.
The Green Grid Technical Form 2010.
http://www.thegreengrid.org/~/media/EMEATechForums2010/Improving%20Energy%20Efficienc
y%20-%20An%20End%20User%20Perspective_Paris.pdf?lang=en
- United EIF, Inc. 2015. Advanced Configuration and Power Interface Specification.
http://www.uefi.org/sites/default/files/resources/ACPI_6.0.pdf
- Lo, D., Cheng, L., Govindaraju, R., Ranganathan, P., & Kozyrakis, C. (2015, June). Heracles:
improving resource efficiency at scale. In Proceedings of the 42nd Annual International
Symposium on Computer Architecture (pp. 450-462). ACM.
- Masanet, E., Shehabi, A., Ramakrishnan, L., Liang, J., Ma, X., Walker, B., Hendrix, V., and P.
Mantha (2013). The Energy Efficiency Potential of Cloud-Based Software: A U.S. Case Study.
Lawrence Berkeley National Laboratory, Berkeley, California.
- Heller, B., Seetharaman, S., Mahadevan, P., Yiakoumis, Y., Sharma, P., Banerjee, S., &
McKeown, N. (2010, April). ElasticTree: Saving Energy in Data Center Networks. In NSDI (Vol.
10, pp. 249-264).
- Masanet, E., A. Shehabi, L. Ramakrishnan, J. Liang, X. Ma, B. Walker, V. Hendrix, and P.
Mantha (2013). The Energy Efficiency Potential of Cloud-Based Software: A U.S. Case Study.
Lawrence Berkeley National Laboratory, Berkeley, California.
- Hilty, L.M., Aebischer, B. (Eds.), 2015. ICT Innovations for Sustainability, Advances in Intelligent
Systems and Computing. Springer International Publishing, Cham.
- Erdmann, L., Hilty, L., Goodman, J., Arnfalk, P., 2004. The Future Impact of ICTs on
Environmental Sustainability (Technical Report No. EUR 21384 EN). Institute for Prospective
Technological Studies, Seville, Spain.
- Elliott N, Molina, M., and Trombley, D. 2012, A defining framework for intelligent efficiency
(Washington, DC: American Council for an Energy-Efficient Economy)
http://aceee.org/sites/default/files/publications/researchreports/e125.pdf
- Accenture. 2015. SMARTer2030: ICT Solutions for 21st Century Challenges
http://smarter2030.gesi.org/downloads/Full_report2.pdf
- Börjesson Rivera, M., Håkansson, C., Svenfelt, Å., Finnveden, G., 2014. Including second order
effects in environmental assessments of ICT. Environ. Model. Softw. 56, 105-
115.doi:10.1016/j.envsoft.2014.02.005
- Erdmann, L., Hilty, L.M., 2010. Scenario Analysis: Exploring the Macroeconomic Impacts of
Information and Communication Technologies on Greenhouse Gas Emissions. J. Ind. Ecol. 14,
826–843. doi:10.1111/j.1530-9290.2010.00277.
- Azevedo, I.M.L., 2014. Consumer End-Use Energy Efficiency and Rebound Effects. Annu.Rev.
Environ. Resour. 39, 393–418. doi:10.1146/annurev-environ-021913-153558
- Gillingham, K., Rapson, D., Wagner, G., 2015. The rebound effect and energy efficiency policy.
- Borenstein, S., 2013. A microeconomic framework for evaluating energy efficiency rebound and
some implications. National Bureau of Economic Research.
- Harrington, D., 2015. From first mile to last mile: Global industrial & logistics trends. Colliers
International.
Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook
19
- Shorr Packaging Corp, 2015. The Amazon Effect: Impacts on Shipping and Retail
http://www.shorr.com/packaging-news/2015-06/amazon-effect-impacts-shipping-and-retail
- Williams, E., 2011. Environmental effects of information and communications technologies.
Nature 479, 354–358. doi:10.1038/nature10682
- Shehabi, A., Walker, B. & Masanet, E. The energy and greenhouse-gas implications of internet
video streaming in the United States. Environ. Res. Lett. 9, 054007 (2014).
- Kitou, E. & Horvath, A. External air pollution costs of telework. Int. J. Life Cycle Assess. 13, 155–
165 (2008).
- Henderson, P. & Waitner, M. Real-time energy management: A case study of three large
commercial buildings in Washington, D.C. (Natural Resources Defense Council, 2013). At
http://www.nrdc.org/business/casestudies/files/tower-companies-case-study.pdf
- Seidel, S. and Ye, J. 2012. Leading by example: using information and communication
technologies to achieve Federal sustainability goals (Center for Climate and Energy Solutions)
http://www.c2es.org/docUploads/federal-sustainability-ict.pdf
- Laitner, J.A., McDonnell, M.T., and Keller, R.M. 2015. ICT-Enabled Intelligent Efficiency: Shifting
from device-specific approaches to system optima. Online: http://cda.iea-4e.org/document/11/ict-
enabled-intelligent-efficiency-shifting-from-device-specific-approachesto-system-optima
- Pouchet, J. 2016. Time for a Server Idle Performance Standart – Introducing 10 Minus. Emerson
Network Power Blog. http://blog.emersonnetworkpower.com/efficiency/time-for-a-server-idle-
performance-standard/
- Horner, N., Azevedo, I. 2016. Power usage effectiveness in data centers: overloaded and
underachieving. The Electricity Journal, Volume 29, Issue 4, May 2016, Pages 61-69
- Azevedo, D., Rawson, A. 2008. Measuring Data Center Productivity. Metrics and Measurements
Work Group. The Green Grid.
http://www.thegreengrid.org/~/media/TechForumPresentations2008/Measuring_Data_Center_Pr
oductivity.pdf?lang=en
- McKinsey & Company. http://www.sallan.org/pdfdocs/McKinsey_Data_Center_Efficiency.pdf

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


20
ANEXO FIGURAS – Figura 1

Áreas de soporte a los equipos TI

https://www.google.com/about/datacenters/efficiency/internal/

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


21
ANEXO FIGURAS – Figura 2

Relación global en PUEs

Uptime Institute survey of PUE for 1100+ datacenters

https://www.google.com/about/datacenters/efficiency/internal/

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


22
ANEXO FIGURAS – Figura 3

Áreas de actuación en eficiencia energética en el DC

ASHRAE «save energy now series»

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


23
ANEXO FIGURAS – Figura 4

Diseño e influencia de los ahorros

http://www.schneideruniversities.com/energy-university

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


24
ANEXO FIGURAS – Figura 5

Tipos de pérdidas

http://www.apcmedia.com/

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


25
ANEXO FIGURAS – Figura 6

Distribución total del consumo

Emerson «Energy Logic: Reducing Data Center Consumption by creating savings that cascade across systems»

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


26
ANEXO FIGURAS – Figura 7

Funcionalidades internas de los dispositivos

http://www.storagereview.com/hp_proliant_dl360_gen9_review

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


27
ANEXO FIGURAS – Figura 8

Equipos TI “comatosos”

http://anthesisgroup.com/wp-content/uploads/2015/06/Case-Study_DataSupports30PercentComatoseEstimate-FINAL_06032015.pdf

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


28
ANEXO FIGURAS – Figura 9

Virtualización TI

Energy Star: Data Center Energy Efficiency Opportunities

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


29
ANEXO FIGURAS – Figura 10

Crecimiento adaptado a la necesidad real

http://it-resource.schneider-electric.com/i/482656-wp-114-implementing-energy-efficient-data-centers/7

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


30
ANEXO FIGURAS – Figura 11

Gestión ambiental

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


31
ANEXO FIGURAS – Figura 12

Gestión del aire

Energy Star: Data Center Energy Efficiency Opportunities

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


32
ANEXO FIGURAS – Figura 13

Ineficiencias en el sistema eléctrico

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


33
ANEXO FIGURAS – Figura 14

Relación de consumos TI y pérdidas eléctricas

Fuente: The Green Grid, Emerson

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


34
ANEXO FIGURAS – Figura 15

Consideraciones en el equipamiento

Energy Star: Data Center Energy Efficiency Opportunities

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


35
ANEXO FIGURAS – Figura 16

Equipamiento eficiente

Energy Star: Server Efficiency Rating Tool


https://www.spec.org/sert/

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


36
ANEXO FIGURAS – Figura 17

Tendencias – TI como última frontera

https://www.youtube.com/watch?v=OdpDWck_h4g

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


37
Caso Práctico 1: Aplicación de medidas básicas de eficiencia

Retrofit en 5 data centers (Google)


El siguiente video introducido por el instructor muestra la mejora progresiva en unas
instalaciones para reducir consumos eléctricos evitables.

En base a las indicaciones de la exposición que se irán indicando en el video, indique al final
del video las medidas adoptadas atendiendo a las siguientes categorías:

- Monitorización

- Cooling

- Power

- Equipos IT y electromecánicos (configuraciones internas)

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


38
Caso Práctico 2: Costes asociados a PUE

Utilizando la calculadora disponible en

http://www.42u.com/efficiency/energy-efficiency-calculator.htm

Realice:

1. El cálculo que supondría la reducción en unas instalaciones de un PUE 2.3 a un valor de


1.6 para unas instalaciones con una carga IT de 400kW y un coste kWh de 0,10EUR

2. Un cálculo estimativo con valores reales atendiendo a sus instalaciones reales

Issue 1.0 EEBP – Sesión Técnica 2 - Training Workbook


39
Energy Efficiency Best Practices (EEBP)

Sesión Técnica 3:

Eficiencia Energética – Base Camp

Training Workbook
Every effort has been made to ensure that the information contained in this document is true and correct
at the time of going to press. However, the technology, systems, products, processes, specifications
and content in general described in this document are subject to continuous development and
DCProfessional is entitled to change them at any time and to expand on them. DCProfessional cannot
accept liability for any loss or damage of any nature whatsoever arising or resulting from the use of or
reliance on information or particulars in this document.

All names and other data used in examples are fictitious.

The information contained in this document is of a general nature.

No part of this document may be reproduced by any means, other than with the express written
permission of the copyright holder.

© Copyright 2016 by DCProfessional Development

All rights reserved. No part of this manual may be used, reproduced, or transmitted in any form or by any
means, electronic mechanical, including photocopying, recording, or by any information storage and
retrieval system, without the prior agreement and written permission of the publisher, except for the
inclusion of brief quotations in a review.

The contents of this manual are subject to ongoing revision without notice due to continuing
developments in standards, regulations, methodology, design, and manufacturing.

This manual forms part of the DCProfessional Development curriculum, and is presented without
warranty of any kind, including but not limited to implied warranties, for the manual’s quality or fitness for
any particular purpose. DC Professional Development shall not be liable to the purchaser or any other
entity with respect to any liability, loss or damage caused directly or indirectly by this manual.

All brand names and trademarks are the property of their respective owners.
DCProfessional Development
28 Scrutton Street
London EC2A 4RP
United Kingdom

www.dc-professional.com

ACKNOWLEDGEMENTS

DCProfessional Development is indebted to the following organisations and individuals for their
invaluable support in the preparation of this manual:

Organisations: DCD Group, DCD Focus Magazine, DCD Intelligence,

Individuals: Agustín López Neira (Training Project Developer & Content Producer Manager).

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 2


Relación de contenidos

Relación de contenidos .............................................................................................................. 3

Objetivos .................................................................................................................................... 7

Base camp – Practicas fundamentales ....................................................................................... 7

Introducción ................................................................................................................................ 8

Evolución.................................................................................................................................... 9

Actuales Protagonistas/Referencias ......................................................................................... 11

Necesidades actuales .............................................................................................................. 12

Soluciones ................................................................................................................................ 13

Cooling ............................................................................................................................ 14

Diseño – Pasillos calientes/fríos ......................................................................... 14

Gestión del flujo de aire de rack - placas ciegas ............................................... 15

Gestión del flujo de aire de rack – otras aberturas ............................................ 15

Gestión del flujo de aire en suelos técnicos ...................................................... 16

Revisar la refrigeración antes de hacer cambios en los equipos de TI ............ 16

Revisión de la estrategia de refrigeración .......................................................... 17

Mantenimiento regular de la planta de enfriamiento ......................................... 17

Revisar y, si es posible, elevar la temperatura de entrada del aire a los equipos de TI


............................................................................................................................... 18

Revisar y aumentar el rango de humedad operativo ......................................... 19

Data Center Building ..................................................................................................... 20

Apagar luces......................................................................................................... 20

Iluminación de bajo consumo ............................................................................. 20

IT …………………………………………………………………………………………………21

Nuevo hardware TI – Rangos esperados de operación en temperatura y humedad


............................................................................................................................... 21

Auditar el estado de los servicios y las infraestructuras de soporte existentes22

Desmantelamiento de los servicios no utilizados.............................................. 23

Auditoría de los requisitos medioambientales TI existentes ............................ 24

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 3


Política de gestión de datos ................................................................................ 24

Métricas y monitorización................................................................................................. 25

Medidor del consumo de energía entrante ......................................................... 25

Medidor del consumo de energía de TI............................................................... 26

Tendencias............................................................................................................................... 27

Referencias / Saber más .......................................................................................................... 28

ANEXO FIGURAS – Figura 1 ................................................................................................... 29

Partes interesadas ........................................................................................................... 29

ANEXO FIGURAS – Figura 2 ................................................................................................... 30

Áreas de actuación – Marco CEEDA ............................................................................... 30

ANEXO FIGURAS – Figura 3 ................................................................................................... 31

CEEDA – Adopción internacional..................................................................................... 31

ANEXO FIGURAS – Figura 4 ................................................................................................... 32

Auditoría energética ......................................................................................................... 32

ANEXO FIGURAS – Figura 5 ................................................................................................... 33

Órganos de coordinación ................................................................................................. 33

ANEXO FIGURAS – Figura 6 ................................................................................................... 34

Proyecto de mejora .......................................................................................................... 34

ANEXO FIGURAS – Figura 7 ................................................................................................... 35

Fundamentos ................................................................................................................... 35

ANEXO FIGURAS – Figura 8 ................................................................................................... 36

Cooling – Sellado de aberturas ........................................................................................ 36

ANEXO FIGURAS – Figura 9 ................................................................................................... 37

Cooling – Pasillo caliente/frío ........................................................................................... 37

ANEXO FIGURAS – Figura 10 ................................................................................................. 38

Cooling – Relación de caudales....................................................................................... 38

ANEXO FIGURAS – Figura 11 ................................................................................................. 39

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 4


Cooling – Diseños “Non-Shadowed” ................................................................................ 39

ANEXO FIGURAS – Figura 12 ................................................................................................. 40

Cooling – Compactación TI .............................................................................................. 40

ANEXO FIGURAS – Figura 13 ................................................................................................. 41

Cooling - Mantenimientos ................................................................................................ 41

ANEXO FIGURAS – Figura 14 ................................................................................................. 42

Cooling/TI - Relación de operación de equipos en alta temperatura ............................... 42

ANEXO FIGURAS – Figura 15 ................................................................................................. 43

TI – Servidores no utilizados ............................................................................................ 43

ANEXO FIGURAS – Figura 16 ................................................................................................. 44

Equipamiento TI – Gestión del dato ................................................................................. 44

ANEXO FIGURAS – Figura 17 ................................................................................................. 45

Medición – Puntos de referencia PUE.............................................................................. 45

ANEXO FIGURAS – Figura 18 ................................................................................................. 46

Tendencias – Evolución progresiva en las mejoras.......................................................... 46

Caso Práctico 1: Auditoría en Fundamentos en EE - CEEDA Bronze....................................... 47

Caso Práctico 2: Ineficiencias en la gestión del aire ................................................................. 48

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 5


Uso apropiado del Workbook
Este workbook ha sido diseñado para un uso conjunto en las sesiones presenciales, casos de estudio y
workshops de este módulo, de modo que los asistentes puedan adquirir conocimientos de aplicación
práctica en un entorno de la industria de los Data Center.

El curso está estructurado para que el Tutor exponga funcionalidades y ejemplos de casos prácticos con
el apoyo del material del Tutor (proyecciones, videos, simulaciones, técnicas de aprendizaje acelerado).

Siempre que sea posible, los asistentes deben participar de forma activa individual o en grupos
reducidos para desarrollar y completar ejercicios orientados a consolidar su aprendizaje Se ha
dispuesto de un entorno de aprendizaje adecuado para que pueda actuar de modo seguro.

El objetivo del workbook es ser un documento de trabajo orientado al refuerzo de la información


presentada por el Tutor. Cada asistente debe disponer de una copia digital o en papel de este workbook
con antelación al curso de modo que pueda ayudar a la preparación previa del curso, especialmente en
los casos de aquellos asistentes menos familiarizados con algunas temáticas del curso, además de
servir durante y después de la formación como documento de consulta.

No está diseñado en cualquier caso para proporcionar de modo detallado todos los aspectos teóricos ni
fundamentos de una tecnología o aplicación, sino específicamente aquellos especialmente relevantes
para el desarrollo del curso y los objetivos concretos de aprendizaje.

Cualquier consulta, aclaración o incidencia sobre DCProfessional training courses puede dirigirla a:

agustin.lopez@datacenterdynamics.com

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 6


Objetivos
Base camp – Practicas fundamentales
Al finalizar este módulo, será capaz de:

 Identificar las mejores prácticas iniciales fundamentales en todas las áreas electromecánicas,
TIC y de monitorización de las instalaciones

 Conocer los fundamentos de las mejores prácticas iniciales fundamentales en todas las áreas
electromecánicas, TIC y de monitorización de las instalaciones

 Reconocer las ventajas y posible adaptación en distintos entornos de los data center de las
mejores prácticas iniciales fundamentales en todas las áreas electromecánicas, TIC y de
monitorización de las instalaciones

 Identificar las métricas y actividades de monitorización fundamentales que permiten habilitar un


proceso común en el equipo y terceras partes

También dispone de la oportunidad de:

- Compartir sus conocimientos y opiniones

- Exponer casos reales y problemáticas en experiencias vividas o conocidas

- Escuchar atentamente las opiniones del resto de los asistentes

- Aportar comentarios de manera activa, respetando el enfoque del resto de participantes en la


aplicación de soluciones o puntos de vista concretos, incluso cuando sean opuestos a sus
propias valoraciones y entendimiento como base del enriquecimiento del grupo

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 7


Introducción

La aplicación de medidas en eficiencia energética con un enfoque holístico requiere de una planificación
definida y detallada en un tiempo determinado y en relación a unos objetivos realistas.

Una vez la organización ha decidido los representantes de cada área funcional y operativa que
participarán en las comisiones para la mejora de la eficiencia energética, una de las primeras cuestiones
que se suelen plantear es la del conocimiento del estado actual de las instalaciones.

Para poder establecer una línea base objetiva la comparación con otros data centers de una misma
organización o, incluso de otras organizaciones no es una referencia útil. Comenzando por las
diferencias en la propia ubicación geográfica de cada data center, existen innumerables particularidades
que hacen difícil esta comparación.

Del mismo modo, no existe por tanto un data center “patrón” con el que comparar el resto y ver si se
está progresando adecuadamente en la dirección de la mejora desde los niveles más básicos hasta
alcanzar los niveles máximos de aplicación de las medidas.

Por el contrario, establecer nuestros propios objetivos de mejora podría ser una idea inicialmente válida
pero que tiene el inconveniente típico de un avance a ciegas que tiende a frenarse con el tiempo por
una visión parcial de las medidas que se pueden aplicar y la propia incertidumbre en la eficacia real final
de las medidas a acometer o la autocomplacencia tras los primeros ahorros procedentes de medidas
temporales y de poco calado a medio-largo plazo.

Finalmente, el reconocimiento del trabajo determinado y aplicado por la propia organización en favor de
la eficiencia energética suele no estar totalmente alineado con requisitos legales, regulatorios o
contractuales que puedan ser fácilmente reconocidos por las distintas partes interesadas (ciudadanos,
clientes, distribuidores, accionistas, inversores, propietarios, aseguradoras, administración pública,
reguladores, suministradores de servicios, medios de comunicación, grupos de interés comercial,
vecinos en las comunidades donde se construyen los data center, grupos de presión, servicios de
emergencia, otras agencias, servicios de transporte, la propia plantilla de la organización, .... ).

*Figura 1*
La solución es este caso se resuelve, como en otros casos análogos, mediante la aplicación de marcos
de buenas prácticas establecidos por representantes y casos de puesta en práctica desde la propia
industria de los data center.

En esta sesión se plantean las medidas de aplicación fundamentales a considerar inicialmente de cara a
un cumplimiento formal de unos mínimos que pongan disposición a los gestores de las instalaciones en
la base de la montaña con el objetivo de poder crecer en la aplicación de medidas más ambiciosas pero
que dependerán en mayor o menor de medida de las iniciales aquí presentadas.

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 8


Evolución

Durante la última década se ha ido produciendo diversos trabajos formales e informales de presentación
de experiencias en relación a la eficiencia energética en los data center. Trabajos en que algunos casos
han sido novedosos por el estudio y comparación de dispositivos en sistema eléctricos, de climatización
y de TI, entre otros o que han retomado y enriquecido trabajos anteriores para ir confeccionando en
todo este conjunto una serie de buenas prácticas que han demostrado funcionar generalmente de
manera adecuada en su aplicación.

Especificaciones procedentes de las métricas de ASHRAE, Energy Star, ETSI, EUCoC y The Green
Grid, y de la propia industria fueron compilados y formalizados por grupos de trabajo establecidos desde
el BCS the Chartered Institute for IT en el Reino Unido pero con representantes de primera línea de la
industria de los centros de datos y con experiencia reconocida a nivel internacional.

El resultado de este trabajo de selección es el programa de CEEDA, gestionado de manera exclusiva


por DatacenterDynamics y que cuenta con un posicionamiento neutral desafectado de intereses
comerciales con fabricantes y vendedores de equipamiento a nivel global.
Certified Energy Efficient Datacenter Award (CEEDA) es el primer marco de mejores prácticas en
eficiencia energética con posibilidad de certificación de Data Centers y reconocimiento internacional que
presenta una hoja de ruta completa de benchmarking y mejora en todas las áreas de manera integral
puesto que trata de aspectos de gestión operativas, de gestión mecánica y eléctrica (M&E) y gestión de
las tecnologías de la información (TI).

Después de varios años de explotación más o menos perversa del concepto “green” lo cierto es que ha
llegado el momento de la verdad impulsado por factores reales de regulación, reducción de costes,
marca y reputación y demostrar de manera tangible la eficiencia en las operaciones a las diversas
partes interesadas en las actividades de cada Data Center en función del peso de todos estos aspectos
claves.

CEEDA acomete todos estos factores clave de manera directa y eficaz cumpliendo adicionalmente con
regulaciones como la Directiva Europea Directiva 2012/27/UE del Parlamento Europeo y del Consejo de
la Unión Europea, marcos de referencia del propio Departamento de Energía de los EEUU,
reconocimiento directo por asociaciones como ICREA presente en diversos países y regiones a nivel
internacional y en consideración de estándares de actuación reconocidos como ASHRAE, ETSI, Energy
Star, The Green Grid, o The International Telecommunication Union (ITU), entre otros actores de
relevancia en la industria de los data center y que disponen de capítulos locales con representantes y
asociados en regiones de todo el mundo.

La mejora en los costes operativos ha venido tradicionalmente impulsada por acciones rápidas y
centradas en aspectos puntuales. Desde estrategias de compra más económica en base a subasta o
fragmentación de las compras hasta la reducción de las plantillas y labores de mantenimientos se
localiza una variedad de actividades que finalmente ponen en riesgo la disponibilidad del servicio en la
búsqueda reducir los costes operativos con factor principal.

Diversas charlas profesionales prescriben también prácticas de ahorro en puntos concretos pero que
son típicamente difíciles de extrapolar a otros entornos de Data Center, suponen un riesgo a la
disponibilidad del servicio y/o no consiguen el nivel de ahorro esperado finalmente, trasladando
problemas de un área a otra en vez de solucionarlos y mejorar las situaciones relacionadas con el
rendimiento.

Nadie discute a estas alturas de madurez de la industria que en el Data Center convergen múltiples
actividades que pueden ser muy distintas entre sí pero que tienen lugar y actúan en espacios físicos
comunes con influencia directa de todas ellas finalmente en el espacio TI.

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook 9


Por tanto, el enfoque más apropiado, lógico y eficaz debe pasar por la consideración desde todas las
áreas y por todos los equipos humanos involucrados desde el diseño hasta la construcción, instalación y
mantenimiento de los sistemas que componen y operan en el Data Center. Esto no significa ni mucho
menos que Data Center legados tengan que resignare a ser demolidos y construidos de nuevo para
poder obtener ganancias.

En este sentido, la aplicación de medidas en sistemas de enfriamiento (por ejemplo, en atención al tipo
de equipamiento interno y externo actual y mejoras posibles; gestión de las temperaturas y humedades
a nivel de configuración y de eficiencia en la entrega y retorno a equipos TI; sustitución incluso
anticipada por equipos más eficientes; mejora del entorno ambiental en que funcionan, entre otros) será
más eficiente y bastante menos arriesgada si acompañamos las medidas con la disposición de equipos
TI en sala de manera ordenada (p.ej. segregando espacios físicos según las necesidades de
condiciones ambientales del tipo de equipamiento o por diferencias en densidad de carga, evitando
bypass/recirculaciones/presiones negativas en la gestión de aires frío/caliente, …).

*Figura 2*
Del mismo modo, el control en la instalación de equipamiento TI y de las cargas a nivel de cómputo
(.p.ej. evitando la virtualización de equipos “comatosos” o no controlados; consolidando o repartiendo
cargas de procesamiento entre equipos del mismo o distintos racks; aprovechando funcionalidades del
software/hardware) multiplica las ventajas anteriores pero, a su vez, mejora si además aplicamos
mecanismos para la coordinación de los distintos equipos técnicos y operativos (p.ej. planificando las
capacidades y mejor estrategia de instalación en sala; compra lean en suministros diversos como el
eléctrico; estudio de estrategias de resiliencia más eficientes atendiendo a posibles opciones electro-
mecánicas pero también de TI;…) con un soporte desde el área de suministro eléctrico ininterrumpido
de origen limpio (p.ej. sin emisiones de carbono) y más eficiente (p.ej. eliminando pérdidas en la
distribución; mediante generación local; UPS con factores de conversión y modos de uso más
eficientes).

CEEDA permite este punto de partida integrado desde todas las áreas para estos y otros aspectos
(además de los mencionados en estas líneas) atendiendo a un modelo dinámico de progresión (se
puede certificar en un nivel inicial para recertificar posteriormente en otro nivel superior) adoptando las
medidas al ritmo que cada Data Center quiera/pueda permitirse en relación a un modelo de madurez en
las medidas a aplicar.

CEEDA es además un esquema internacional que ya dispone de Data Center certificados en diversas
regiones del mundo y cuyas medidas de mejora son reconocidas y aplicadas por centenares de
instalaciones y profesionales.

*Figura 3*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


10
Actuales Protagonistas/Referencias

Entre las referencias principales en aspectos de aplicación de mejores prácticas y herramientas para la
industria del data center podemos destacar:

- CEEDA (Certifed Energy Efficient Data Center Award): primer esquema de certificación en la
industria del data center en la consideración de aplicación de las mejores prácticas reconocidas
a nivel internacional para los centros de datos. http://www.ceedacert.com/

- EU CoC (European Union Code of Conduct): creado en respuesta al aumento del consumo de
energía en centros de datos y la necesidad de reducir los impactos en aspectos ambientales,
económicos y energéticos relacionados. Cuenta con más de 120 participantes y 245 promotores
en la aplicación de las buenas prácticas reconocidas por la industria.
http://iet.jrc.ec.europa.eu/energyefficiency/ict-codes-conduct/data-centres-energy-efficiency

- COE (Center of Expertise for Energy Efficiency in Data Centers): Promovido por Lawrence
Berkeley National Laboratory (LBNL) y esponsorizado por U.S. Department of Energy (DOE)
dispone de herramientas y una master list con acciones recomendadas como mejores prácticas
a implementar en los data center. https://datacenters.lbl.gov/

- DOE (US Department of Energy) Better Buildings: con suite de herramientas para la adopción de
líneas base, formación, casos de estudio y programa de reconocimiento a los mayores
ahorradores de energía. http://energy.gov/eere/better-buildings

- EPA (United States Environmental Protection Agency): métricas, clasificación de equipamiento


de red, UPS y servidores y reconocimiento ENERGY STAR; Data center benchmarking.

https://www.energystar.gov/index.cfm?c=prod_development.server_efficiency

- FEMP (US Federal Energy Management Program): talleres, casos de estudio, políticas,
intercambio de información y asistencia técnica. http://energy.gov/eere/femp/energy-efficiency-
data-centers

- The Green Grid: métricas y herramientas de aplicación de modelos de madurez en eficiencia


energética para data centers. http://www.thegreengrid.org/

- Information technology industry council: Políticas de uso de la eficiencia energética en


dispositivos TIC. https://www.itic.org/

- ASHRAE: Estándares de referencia en aspectos ambientales relacionados con el equipamiento


TI y de telecomunicaciones para los data center. https://www.ashrae.org/

- AFCOM: Asociación de profesionales en la industria del data center con capítulos en EEUU,
APAC y Reino Unido. https://www.afcom.com/

- The Telecommunication Standarization Sector (ITU-T): Órgano permanente de la International


Telecommunication Union (ITU) se encarga de estudiar asuntos técnicos, operativos y tarifarios
relacionados con las recomendaciones y normalización de las telecomunicaciones a nivel
mundial.

https://www.itu.int/rec/T-REC-L/recommendation.asp?lang=en&parent=T-REC-L.1300

- SINGAPORE STANDARD SS 564 Series: Singapore Standard for green data centres.
https://www.singaporestandardseshop.sg/product/Package.aspx?ID=5dfe0c1e-eeca-4cd6-9a8d-
5fe9cdc2eac6

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


11
Necesidades actuales

La aplicación de medidas de eficiencia energética a nivel práctico requiere del conocimiento del punto
de estado actual respecto a un marco de referencia.

Por tanto, el primer paso hacia un funcionamiento más eficiente de la energía es cuantificar la eficiencia
con que su instalación está funcionando actualmente.

Auditoría Energética
Una auditoría revela cómo se distribuye el consumo de energía total de la instalación entre los equipos
de TI y sus sistemas de apoyo - la distribución de energía, refrigeración, control de humedad, etc. La
obtención de los resultados puede indicar donde existen las mejores oportunidades de mejora y la
eficacia en el tiempo con estimaciones adicionales de distintas actuaciones y su retorno de inversión.

*Figura 4*
Plan de gestión de la energía
El siguiente paso sería la creación de un plan de gestión de la energía para un mantenimiento de las
actuaciones a largo plazo en las instalaciones. El plan identificará las partes responsables y las metas
en la gestión de la energía. Este plan debe especificar adicionalmente cómo se tomarán las mediciones
de rendimiento del sistema, cómo se usan e interpretan los datos y el proceso de identificación,
financiación y la implementación de las acciones de eficiencia energética.

*Figura 4*
En el primer momento comentado de la creación de un órgano de gestión (p.ej. consejo o comité) que
representa a todas las áreas representativas suele designarse específicamente un responsable para la
gestión de la energía en el caso de que no exista ya uno por la aplicación de otras políticas de empresa
relacionadas y que se pueden integrar de manera beneficiosa.

La figura del gestor energético es un aspecto que en la práctica se demuestra clave para que dirigir y
coordinar al resto de miembros del órgano de gestión establecido por la organización, además de
preocuparse de que los compromisos adquiridos por las distintas partes se cumplan en tiempo y forma.

Tanto el propio órgano de gestión como la figura del gestor energético deben de contar con un apoyo
claro e inequívoco de la alta dirección. Hay medidas que su aplicación supone poco o nulo esfuerzo en
tiempo y/o dinero pero en otras por el contrario no será el caso y necesitarán de la conveniente
consideración por parte de la alta dirección.

*Figura 5*
Adicionalmente, el apoyo de la dirección a los responsables designados para liderar el proyecto de
mejora energética facilita enormemente el avance en las labores diarias requeridas y la atención del
todo el personal a la eficiencia energética en su agenda particular según sea requerido.

*Figura 6*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


12
Soluciones

Para establecer un criterio concreto en los planes de mejora energética tomaremos el esquema de
CEEDA “Enterrprise” como referencia y con el objetivo de cubrir un escenario de un data center ya en
operación y, por otra parte, tomar la referencia de los sistemas TI y que en esquemas como CEEDA
Colocation o CEEDA Telco no estarían representados. La relación de las mejores prácticas indicadas a
continuación se corresponden con el nivel CEEDA Bronze para este esquema de data center
corporativo y organizados por área funcional para mayor claridad (*Figura 7*)

Nombre de la mejor práctica Sección Área funcional

Implicación de los grupos relevantes Bronze 01 Personal

Nuevo hardware TI – Rangos esperados de operación en temperatura y Bronze 02 TI: Equipamiento servicios
humedad

Auditar el estado de los servicios y las infraestructuras de soporte Bronze 03 TI: Equipamiento servicios
existentes

Desmantelamiento de los servicios no utilizados Bronze 04 TI: Equipamiento servicios

Auditoría de los requisitos medioambientales TI existentes Bronze 05 TI: Equipamiento servicios

Política de gestión de datos Bronze 06 TI: Equipamiento servicios

Diseño – Pasillos calientes/fríos Bronze 07 Cooling

Gestión del flujo de aire de rack - placas ciegas Bronze 08 Cooling

Gestión del flujo de aire de rack – otras aberturas Bronze 09 Cooling

Gestión del flujo de aire en suelos técnicos Bronze 10 Cooling

Revisar la refrigeración antes de hacer cambios en los equipos de TI Bronze 11 Cooling

Revisión de la estrategia de refrigeración Bronze 12 Cooling

Mantenimiento regular de la planta de enfriamiento Bronze 13 Cooling

Revisar y, si es posible, elevar la temperatura de entrada del aire a los Bronze 14 Cooling
equipos de TI

Revisar y aumentar el rango de humedad operativo (ASHRAE CLASS A2) Bronze 15 Cooling

Apagar luces Bronze 16 Equipamiento - Otros

Iluminación de bajo consumo Bronze 17 Equipamiento - Otros

Medidor del consumo de energía entrante Bronze 18 Monitoring

Medidor del consumo de energía de TI Bronze 19 Monitoring

Desarrollo de la formación continua del personal Bronze 20 Personal

Aquellos interesados de modo específico en las buenas prácticas establecidas para los tres niveles
Bronze, Silver, Gold y para el resto de esquemas (Colocation, Design&Operations, Telco) pueden
contactar con personal de DCProfessional y acceder sin coste adicional a las especificaciones
específicas correspondientes.

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


13
Cooling

Diseño – Pasillos calientes/fríos

Puesto que las densidades energéticas y los volúmenes de flujo de aire de los equipos de TI han
aumentado, se ha hecho necesario garantizar que los equipos compartan una dirección común
del flujo de aire, dentro del rack, en racks adyacentes y entre los pasillos.

El concepto de pasillo caliente/frío alinea el flujo de aire de los equipos para crear pasillos entre
los racks a los que se suministra el aire enfriado que es captado por todos los equipos con la
misma orientación y que, consecuentemente comparten en la parte opuesta pasillos sin
suministro de aire al que todos los equipos expulsan el aire caliente de salida.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Distribución de los racks en base a alineaciones claras en pasillos comunes caliente/frío


consecutivos

 Marcas en los suelos de la sala técnica para mantener una relación de la distribución a
cumplir

 Etiquetas en los bastidores o el suelo indican la designación del pasillo (calor/frío


rojo/azul, etc.)

 Elementos adicionales de refuerzo como paneles ciegos o puestas sólidas (no


perforadas) que permiten la segregación de aire entre los pasillos cuando los racks no
han sido totalmente ocupados o incluso para dar continuidad a filas de equipamiento con
pocos racks o huecos de racks que hayan quedado libres

Beneficios

 El diseño en pasillos permite gestionar un nivel de densidad medio-bajo por rack mayor
que en estrategias de enfriamiento orientadas a toda la sala en conjunto (sólo
densidades bajas) y más económicas y sencillas que el enfriamiento individual por rack
(dedicado a densidades de carga altas)

 Los pasillos permiten aplicar soluciones de cerramientos posteriores si se alcanzan altas


densidades por rack aportando flexibilidad y cierta escalabilidad

 La disposición en pasillo es además una manera sencilla de poder aplicar labores de


mantenimiento del personal en los rack y adaptada a las formas cuadradas
estandarizadas de los propios rack

*Figura 8*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


14
Gestión del flujo de aire de rack - placas ciegas

Se debería instalar placas ciegas en las separaciones y espacios libres dentro del rack que
eviten el paso de aire enfriado donde realmente no hay equipos que puedan hacer uso de este
aire. Esto también reduce la cantidad de aire calentado por un equipo que es absorbido por los
demás, lo que aumenta la temperatura de entrada y reduce la eficiencia.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 La aplicación visible de soluciones de placas ciegas en ubicaciones vacías de los rack

 Las actividades de instalación de los equipamientos en rack activos no debería ser una
excusa para no aplicar estas soluciones una vez acabados los trabajos aunque no se
haya finalizado completamente

Beneficios

 Evitar bypass de aire enfriado que es desaprovechado

 Evitar que el aire caliente expulsado se mezcle con aire más frío reduciendo la eficiencia
de las unidades aire al reducir el delta de temperatura entre el retornos la impulsión y por
extensión al sistema de enfriamiento en general

 Aprovechamiento del caudal de aire enfriado en unidades activas que requieren


realmente de un enfriamiento

Gestión del flujo de aire de rack – otras aberturas

Instalación de cepillos de apertura (eliminadores de paso de aire) o cubiertas para cubrir todas
las posibles fugas de aire en cada rack.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Cepillos pasa cables, piezas de espuma o de soluciones similares aplicadas a posibles


aberturas en el suelo en la base del rack

 Paneles o soluciones de cerramiento similares en los laterales del rack

 Sellado o deflectores de pequeñas aberturas en la parte inferior (p.ej. por mantener en el


rack ruedas) y la parte superior del rack entre los equipos o los raíles de montaje y el
perímetro del rack

Beneficios

 Evita bypass de aire enfriado que quedaría desaprovechado

 Evitar recirculaciones de aire en el interior de los equipos de aire caliente

 Evitar que el aire caliente expulsado se mezcle con aire más frío de entrada a los equipos
TI reduciendo la eficiencia del sistema de enfriamiento

 Aprovechamiento del caudal de aire enfriado en unidades activas que requieren


realmente de un enfriamiento

*Figura 9*
Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook
15
Gestión del flujo de aire en suelos técnicos

Cerrar todas las aberturas no deseadas en el suelo técnico elevado. Revisar los grados de
apertura aplicados en las rejillas y su ubicación para evitar el bypass.

Gestionar filas interrumpidas es especialmente importante en los entornos de pasillo frío y


caliente. Cualquier abertura entre los pasillos degradará la separación del aire frío y caliente

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Medidas para evitar que el aire de bypass

 Mantener filas ininterrumpidas de racks para evitar la recirculación del aire; si es preciso,
completar espacios con racks totalmente vacíos.

Beneficios

 Segregación de los aires fríos y calientes

 Mantener presurizado el suelo aplicando salidas del caudal de aire frío únicamente donde
requiere ser utilizado para retirar el calor de los equipos TI

*Figura 10*
Revisar la refrigeración antes de hacer cambios en los equipos de TI

Se debería revisar la disponibilidad del nivel de refrigeración requerido incluyendo la colocación


de las rejillas para el caudal ventilación adecuado antes de introducir cambios en los equipos TI.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Información documentada con las actividades de revisión específicas (p.ej. actividades


dentro del programa de gestión de cambios)

 Políticas de compromiso con los usuarios o contratos de servicio con indicaciones


específicas de que las actividades de revisión tienen lugar antes de dar paso al nuevo
equipamiento

Beneficios

 Optimizar el uso de recursos de refrigeración

 Coordinación entre las partes internas y/o externas de provisión de servicios

*Figura 11*
*Figura 12*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


16
Revisión de la estrategia de refrigeración

Revisión periódica del despliegue de los equipos TI y de la refrigeración en relación a la


estrategia.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Actas en las reuniones periódicas de los responsables de la gestión donde se discuten


las actividades de revisión y las actividades de revisión regulares.

Beneficios

 Coordinación entre las partes

 Detectar posibles desviaciones de forma prematura y evitar la pérdida de control

 Mantener la observancia de todo el personal interno y externo en las actividades diarias


sabiendo que existen revisiones periódicas de verificación

Mantenimiento regular de la planta de enfriamiento

Se deberían aplicar actividades de mantenimiento regular del sistema de climatización para


preservar las condiciones iniciales óptimas y como parte esencial del mantenimiento de la
eficiencia del sistema de enfriamiento diseñado para el data center.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Comprobaciones de elementos como la tensión de las correas, limpieza de los


serpentines de la condensadora y del evaporador, cambios de filtros, nivel de
refrigerante, …

Beneficios

 Detectar posibles desviaciones de forma prematura y evitar ineficiencias, incluso fallos


graves irrecuperables en el sistema

 Mantener la observancia de todo el personal interno y externo en las actividades diarias


sabiendo que existen revisiones periódicas de verificación

*Figura 13*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


17
Revisar y, si es posible, elevar la temperatura de entrada del aire a los equipos de TI

Los centros de datos deben diseñarse y operarse a su máxima eficiencia para aportar
temperaturas de admisión en los equipos TI dentro un rango ambiental entre 10ºC y 35ºC (50ºF
a 95ºF).

La norma relevante actual es el rango recomendado por ASHRAE para los centros de datos de
Clase A2 que se describe en las directrices medioambientales. Las operaciones en este rango
permiten ahorrar energía reduciendo o eliminando la sobre-refrigeración.

Tenga en cuenta que algunos centros de datos podrían alojar equipamiento legado con rangos
ambientales reducidos; las temperaturas en estas instalaciones quedarían restringidas a las
máximas adecuadas para este equipamiento hasta que una medida de segregación pueda ser
aplicada.

Debe tenerse en cuenta que puede ser preciso implementar al mismo tiempo otras buenas
prácticas para la gestión del flujo de aire (contención, pasillo frío/caliente, placas ciegas, bloqueo
y sellado de fugas) para garantizar el éxito de las operaciones.

Debe tenerse en cuenta que algunos equipos TI pueden presentar importantes incrementos en
el consumo de energía de los ventiladores cuando la temperatura se eleva (p. ej. 25°C).
Compruebe que sus equipos TI no consumen más energía que la que se ahorra en el sistema de
refrigeración.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Actas en las reuniones periódicas de los responsables de la gestión donde se discuten


las actividades de revisión y las actividades de revisión regulares

 Registros de las temperaturas operativas

 Listado actualizado de los equipos en funcionamiento y los rangos operativos

Beneficios

 Gestión óptima ambiental

*Figura 14*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


18
Revisar y aumentar el rango de humedad operativo

Reducir los puntos de consigna inferior de humedad en el data center y dentro del rango
indicado por ASHRAE para Clase A2 (20% de humedad relativa) para reducir la demanda de
humidificación.

Revisar y, si es viable, elevar los puntos superiores de consigna de humedad dentro del rango
ambiental actual de 21ºC (69.8ªF) para el punto de rocío y 80% de humedad relativa para reducir
el esfuerzo en la dehumectación dentro de las instalaciones. La norma relevante actual es el
rango recomendado por ASHRAE para los data center de Clase A2.

Tenga en cuenta que algunos centros de datos podrían alojar equipamiento legado con rangos
ambientales más reducidos; el rango de humedad en estas instalaciones estarán restringidas a
las adecuadas para este equipamiento y hasta que una segregación pueda ser aplicada.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Actas en las reuniones periódicas de los responsables de la gestión donde se discuten


las actividades de revisión y las actividades de revisión regulares

 Registros de las humedades operativas

 Listado actualizado de los equipos en funcionamiento y los rangos operativos

Beneficios

 Gestión óptima ambiental

 Evitar costes elevados por la activación constante de funciones de humidificación y


dehumectación en las unidades de aire acondicionado de la sala, incluso situaciones de
lucha opuesta donde unas unidades aportan y otras trabajan para reducir los niveles al
mismo tiempo

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


19
Data Center Building
Apagar luces

Las luces deberían permanecer apagadas, preferiblemente por sistemas automáticos, siempre
que las zonas del edificio no estén ocupadas. La iluminación basada en detectores de
movimiento suele bastar como respaldo de los sistemas de cámaras de seguridad

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Aplicación de temporizadores que apaguen las luces tras un tiempo especificado


después de su encendido manual

 Información documentada de la revisión y mantenimiento periódico de los sistemas de


apagado automático

 Aplicación de políticas por parte del personal en el caso de los apagados manuales

Beneficios

 Reducción de los consumos eléctricos en áreas de poco tránsito y/o estancia del
personal

Iluminación de bajo consumo

En los centros de datos se deberían utilizar sistemas de iluminación de bajo consumo

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Aplicación de LED o luminarias de bajo consumo en su defecto

 Registros del tipo y la especificación de la bombilla utilizada, por ejemplo extraída de los
embalajes

 Revisión de los componentes del sistema utilizado, manuales de operación y


mantenimiento, los números de modelo de los equipos instalados y las copias de los
planos de instalación con revisiones para verificar si hay omisiones o cambios.

Beneficios

 Reducción de los consumos eléctricos en áreas de tránsito y/o estancia más prolongada
el del personal

 Generación de menos calor

 LED es regulable en intensidad

 LED evita componentes de riesgo como balastros

 LED al elevarse la temperatura en sala la iluminación no pierde eficiencia ni brillo como sí


ocurre en las lámparas fluorescentes

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


20
IT

Nuevo hardware TI – Rangos esperados de operación en temperatura y humedad

Se debería incluir en el proceso de compra o licitación las consideraciones sobre los rangos
operativos de temperatura y humedad respecto a la admisión de aire del nuevo hardware TI
como factores de decisión de alta prioridad.

El equipamiento debería ser capaz de resistir con garantía el rango comprendido entre 10°C y
35°C de temperatura de entrada (50 °F a 95°F) y de humedad relativa entre 20% y 80% o 21°C
(69,8°F) en el punto de rocío. Estos rangos están definidos como permitidos por ASHRAE para
equipamiento de Clase 2.

Los vendedores están obligados a publicar (no sólo por una petición específica) cualquier
restricción operativa en las horas de funcionamiento en relación a este rango y para cualquier
modelo, así como publicar el rango que restringiría las garantías por un funcionamiento
continuado dentro del rango indicado como permitido.

Para hacer frente a los tipos de equipamiento que deben ser adquiridos pero que no pueden
cumplir con la especificación operativa inicial se deberían aplicar prácticas compensatorias (p.ej.
aislamiento con otros equipos similares o refrigeración dedicada) que en definitiva eviten
restringir los rangos operativos a un número más amplio de equipamiento que comparten el
mismo ambiente.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Establecimiento de políticas de contratación de equipamiento TI donde la mejor práctica


se indique de forma explícita

 Ante la imposibilidad de formalizar políticas, elaboración de directrices de contratación en


equipamiento detallando que la organización sigue buenas prácticas o referencias como
Energy Star o equivalentes y que cualquier elemento suministrado por defecto deba
cumplir con esta buena práctica

Beneficios

 Unificación de los rangos ambientales bajo los que operan los equipos

 Evitar restricciones en el ambiente operativo de los equipos en un volumen importante


del equipamiento al ser penalizado por un número mucho menor de equipos con
características especiales y más restringidas

 Simplificación en las operaciones aumentando incluso los rangos ambientales de manera


gradual, conjunta y más controlada

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


21
Auditar el estado de los servicios y las infraestructuras de soporte existentes

Auditar el estado físico y lógico existente para determinar qué equipos están en funcionamiento y
que servicio(s) ofrecen.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Considerar la implementación de un catálogo de servicios y una base de datos de gestión


de la configuración de tipo ITIL

 Listado de estado de los activos instalados y retirados en el caso de un plan de


actualización

 Auditorías regulares de la CMDB o del sistema de control de activos implantado

 Uso de estándares en la aplicación de esta práctica como ISO 55000

Beneficios

 El control básico de los activos TI instalados para que sólo permanezcan activos aquellos
realmente necesarios para la prestación de servicios.

 Conocer rápidamente sobre una CMDB posibles actualizaciones hardware y/o software
para localizar y valorar exactamente posibles mejoras en la eficiencia por actualizaciones
de componentes o versiones concretas, incluso por una sustitución prematura de
equipamiento que habilite ahorros energéticos

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


22
Desmantelamiento de los servicios no utilizados

Desmantelamiento completo y retirada física de cualquier equipamiento no requerido o asociado


a servicios que ya no están en uso. El hardware instalado debería ser examinado regularmente
para garantizar que es aún requerido y que da soporte a servicios aún activos.

Ejemplo de implantación

La evidencia incluye copias de los documentos dentro del alcance del proyecto o del antes y el
después en la CMDB o una lista de los servidores retirados dentro del proyecto. La evidencia
física sería la ausencia de equipo de cómputo en estado Off/Stand-by dentro de bastidores o con
cables retirados todavía in situ. Alternativamente, el equipo fuera de servicio puede estar
ubicado en las salas de preparación o de almacenamiento antes de su eliminación, la evidencia
fotográfica se puede utilizar en apoyo de esta buena práctica.

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Proyectos de decomisionamiento de equipos con las actuaciones previas y posteriores


registradas en la CMDB

 Ausencia de equipamiento en los racks en estado off/standby

 Ausencia de equipamiento sin cableado conectado pero aún en los racks

 Equipo decomisionado emplazado en salas de almacenamiento esperado por su retirada


física final

Beneficios

 Reducir el equipamiento en sala al estrictamente necesario para los servicios

 Evitar consumos y costes adicionales de mantenimiento del personal e instalaciones


innecesarios

 Disponer de espacios libres rápidamente para comisionar nuevos equipos agrupándolos


por el mismo tipo de tipología o necesidades ambientales y de suministro eléctrico

 Contener las necesidades y ajustar el dimensionamiento de las instalaciones a la


infraestructura realmente necesaria

*Figura 15*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


23
Auditoría de los requisitos medioambientales TI existentes

Identificar los rangos de temperatura y de humedad admisibles en los equipos TI existentes.

Aquellos equipos con una admisión de aire dentro de rangos de temperatura restringidos
deberían estar identificados para que puedan ser reemplazados por nuevos equipos capaces de
admitir un rango más amplio de temperaturas o bien sean trasladados y tratados en zonas
ambientales segregadas.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Listado actualizado

 Revisión interna de los manuales de especificación de los equipos de este listado

 Extracción de los rangos de operación del manual (5-40C).

Beneficios

 Unificación de los rangos ambientales bajo los que operan los equipos

 Evitar restricciones en el ambiente operativo de los equipos en un volumen importante


del equipamiento al ser penalizado por un número mucho menor de equipos con
características especiales y más restringidas

 Simplificación en las operaciones aumentando incluso los rangos ambientales de manera


gradual, conjunta y más controlada

Política de gestión de datos

Desarrollar una política de gestión de datos para definir qué datos deberían mantenerse, durante
cuánto tiempo y con qué nivel de protección. Debería prestarse especial atención a posibles
impactos de cualquier requisito relacionado con la retención de datos

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Implantar y establecer una política documentada con la comunicación a los usuarios

 Aplicación de políticas para el almacenamiento y uso aceptable en gestión de datos


como cuotas para el uso de las telecomunicaciones o almacenamiento

Beneficios

 Concienciación de los usuarios sobre el coste de los servicios de la organización y el


esfuerzo relacionado con el aumento de las capacidades

 Racionalización en el uso de los recursos de la organización

 Crecimientos más moderados en las capacidades en relación a la demanda

 Más tiempo disponible para desarrollar las estrategias de adquisición de equipamiento y


energía y en relación a las estrategias del propio negocio

*Figura 16*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


24
Métricas y monitorización

Medidor del consumo de energía entrante

Instalar equipos de medición capaces de medir el consumo total de energía del data center,
incluidos todos los sistemas de acondicionamiento energético, distribución y refrigeración. Estos
equipos deberían discriminar cualquier otra cargas que no pertenezca a la actividad del propio
data center. Téngase en cuenta que esto es necesario para elaborar informes precisos.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Vista a los componentes del sistema en uso

 Pruebas adicionales como la revisión de manuales de operación y mantenimiento y/o los


números de modelo de los equipos instalados.

 Registros diarios manuales o procedentes de sistemas de consola DCIM

 En el caso de que el DC es parte de un entorno de una instalación más amplia y no se


mida por separado, la metodología utilizada y los cálculos deberían ser proporcionados
de forma documentada

Beneficios

 Conocer con precisión los consumos totales de las instalaciones desde el punto inicial de
responsabilidad en el uso

 Discriminar aberraciones introducidas por elementos ajenos a la actividad del data center

 Conocer los costes totales, el patrón de evolución de los consumos de la energía en


detalle a lo largo del tiempo y afectación positiva o negativa en base a las actuaciones de
mejora que se vayan produciendo

 Cálculo preciso del PUE

*Figura 17*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


25
Medidor del consumo de energía de TI

Instalar equipos de medición capaces de medir la energía total suministrada a los sistemas de
TI.

Esto podría puede incluir otros tipos de alimentación desde donde se suministra energía a los
racks y que no están protegidas por UPS. Téngase en cuenta que esto es necesario para
elaborar los informes.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Vista a los componentes del sistema en uso

 Pruebas adicionales como la revisión de manuales de operación y mantenimiento y/o los


números de modelo de los equipos instalados.

 Registros diarios manuales o procedentes de sistemas de consola DCIM

 En el caso de que el DC es parte de un entorno de una instalación más amplia y no se


mida por separado, la metodología utilizada y los cálculos deberían ser proporcionados
de forma documentada

Beneficios

 Conocer con precisión los consumos imputables a los equipos TI como parte de la
fórmula para el cálculo preciso del PUE

 Discriminar aberraciones introducidas por elementos ajenos a la actividad del data center

 Conocer los costes totales, el patrón de evolución de los consumos de la energía en


detalle a lo largo del tiempo y afectación positiva o negativa en base a las actuaciones de
mejora que se vayan produciendo

*Figura 17*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


26
Tendencias

Una vez resuelto el análisis gap inicial y haber trabajado en cubrir y mejorar los aspectos relevantes de
un nivel CEEDA Bronze el trabajo se centra típicamente en cumplir con los niveles establecidos en el
siguiente nivel CEEDA Silver.

Del mismo modo que nunca se parte un punto “cero” en el que no hay nada hecho, existirán mejores
práctica aplicadas aunque sea parcialmente y no sólo para el nivel Bronze incluso consideraciones de
niveles superiores.

En cualquier caso, haber fortalecido y satisfecho ampliamente el nivel básico nos sitúa en una mejor
posición de alcanzar el siguiente nivel de manera menos costosa y mucho más eficaz y controlada.

No disponer de un aplicación de estas mejores prácticas básicas compromete la rentabilidad de la


explotación del data center así como los cumplimientos de los requisitos legales, contractuales y
regulatorios presentes y venideros según la región y que son por tanto inevitables considerar en algún
momento.

Poder abordar estas mejores prácticas lo antes posible, entre otras actuaciones complementarias, pone
en una mejor posición la gestión y adaptación de los data center cuando los requisitos se hacen
obligatorios, ya que en ese momento sólo habrá que focalizar los esfuerzos en los aspectos que falten
por formalizar y no el marco completo de los requerimientos.

Un marco organizado como CEEDA permite además atender de manera integrada diversas normativas
y requerimientos que afecten directa o indirectamente al data center al ser un marco de buenas
prácticas generadas por la propia industria y considerar todas las actividades en las áreas funcionales
relevantes.

*Figura 18*

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


27
Referencias / Saber más

- CEEDA website: http://www.ceedacert.lat/

- EU Code of Conduct on Data Center Energy Efficiency Best Practice Guidelines:


http://iet.jrc.ec.europa.eu/energyefficiency/sites/energyefficiency/files/files/COC_DC/2016/2016_b
est_practice_guidelines_v7.1.2.pdf

- Data Center Master List of Energy Efficiency Actions:

https://datacenters.lbl.gov/resources/data-center-master-list-energy

- ITU-T L.1300 Best Practices for Green Data Centres

https://www.itu.int/rec/T-REC-L.1300-201406-I/en

- ITU-T L.1310 Energy Efficiency Metrics and Measurement Methods for Telecommunication
Equipment

https://www.itu.int/rec/T-REC-L.1310-201211-S

- Mission Critical Facilities, Data Centers, Technology Spaces and Electronic Equipment ASHRAE
Technical Committee 9.9: https://tc0909.ashraetcs.org/

- ASHRAE TC9.9 Proposed Clarification to ASHRAE Thermal Guidelines

https://tc0909.ashraetcs.org/documents/Clarification%20to%20ASHRAE%20Thermal%20Guideli
nes.pdf

- ASHRAE TC9.9 Data Center Networking Equipment – Issues and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE%20Networking%20Thermal%20Guidelines.pdf

- ASHRAE TC9.9 Data Center Power Equipment Thermal Guidelines and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_TC0909_Power_White_Paper_22_June_2016
_REVISED.pdf

- ASHRAE TC9.9 IT Equipment Thermal Management and Controls

https://tc0909.ashraetcs.org/documents/ASHRAE%202012%20IT%20Equipment%20Thermal%2
0Management%20and%20Controls_V1.0.pdf

- ASHRAE TC9.9 Data Center Storage Equipment – Thermal Guidelines, Issues, and Best
Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_Storage_White_Paper_2015.pdf

- The Green Grid: Recommendations for Measuring and Reporting Overall Data Center Efficiency
Version 2 – Measuring PUE for Data Centers

http://www.thegreengrid.org/~/media/WhitePapers/Data%20Center%20Metrics%20Task%20Forc
e%20Recommendations%20V2%205-17-2011.ashx?lang=en

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


28
ANEXO FIGURAS – Figura 1

Partes interesadas

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


29
ANEXO FIGURAS – Figura 2

Áreas de actuación – Marco CEEDA

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


30
ANEXO FIGURAS – Figura 3

CEEDA – Adopción internacional

http://www.ceedacert.lat/cpds-certificados

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


31
ANEXO FIGURAS – Figura 4

Auditoría energética

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


32
ANEXO FIGURAS – Figura 5

Órganos de coordinación

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


33
ANEXO FIGURAS – Figura 6

Proyecto de mejora

https://www.ashrae.org/resources--publications/bookstore/datacom-series

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


34
ANEXO FIGURAS – Figura 7

Fundamentos

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


35
ANEXO FIGURAS – Figura 8

Cooling – Sellado de aberturas

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


36
ANEXO FIGURAS – Figura 9

Cooling – Pasillo caliente/frío

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


37
ANEXO FIGURAS – Figura 10

Cooling – Relación de caudales

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


38
ANEXO FIGURAS – Figura 11

Cooling – Diseños “Non-Shadowed”

”The Efficient Datacenter Improving Datacenter Efficiency Through Intel Technologies and High Ambient
Temperature Operation”

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


39
ANEXO FIGURAS – Figura 12

Cooling – Compactación TI

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


40
ANEXO FIGURAS – Figura 13

Cooling - Mantenimientos

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


41
ANEXO FIGURAS – Figura 14

Cooling/TI - Relación de operación de equipos en alta temperatura

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


42
ANEXO FIGURAS – Figura 15

TI – Servidores no utilizados

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


43
ANEXO FIGURAS – Figura 16

Equipamiento TI – Gestión del dato

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


44
ANEXO FIGURAS – Figura 17

Medición – Puntos de referencia PUE

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


45
ANEXO FIGURAS – Figura 18

Tendencias – Evolución progresiva en las mejoras

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


46
Caso Práctico 1: Auditoría en Fundamentos en EE - CEEDA
Bronze

Ejercicio Práctico 1:
Auditoría en Fundamentos en EE - CEEDA Bronze
El siguiente video introducido por el instructor muestra la mejora progresiva en unas
instalaciones para reducir consumos eléctricos evitables.

En base a las indicaciones de la exposición que se irán indicando en el video, indique al final
del video las medidas adoptadas atendiendo a las siguientes categorías:

- Monitorización

- Cooling

- Power

- Equipos IT y electromecánicos (configuraciones internas)

Continuación:

Realice un ejercicio de comparación de las medidas indicadas en el vídeo y registradas en el


ejercicio anterior para determinar, en base a la tabla de buenas prácticas de CEEDA
Enterprise - Bronze, el nivel de cumplimiento en cada una de ellas.

Si existiera alguna práctica del esquema no mencionada en el video indicar «Pendiente de


verificar».

Por el contrario, aquellas buenas prácticas mencionadas que no tengan referencias en el


esquema CEEDA Enterprise – Bronze (p. ej. medidas relacionadas con aspectos de power)
serán acciones relacionadas con niveles Silver/ Gold superiores que se comentarán más
adelante.

Utilice la tabla indicada al inicio del apartado “Soluciones” a modo de lista de verificación o
checklist

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


47
Caso Práctico 2: Ineficiencias en la gestión del aire

Ejercicio Práctico 2:
Ineficiencias en la gestión del aire
Los problemas típicos en la gestión del aire se resumen en tres situaciones diferenciadas:

- Bypass: aire enfriado que retorna sin pasar a través de ningún equipo TIC

- Recirculación: el equipo de TI no obtiene suficiente aire frío y admite


cualquier aire disponible (del pasillo caliente o residual de la sala)

- Presión negativa: la velocidad del aire enfriado que circula por un ducto o
piso elevado es alta y succiona aire de retorno o residual de sala por aberturas
innecesarias o por separaciones de elementos dañados o mal ajustados

Con el uso de la siguiente herramienta y aplicando valores de temperatura registrados en sus


propias salas técnicas localice el grado de eficiencia en la gestión del aire que está aplicando:

http://www.dc-oi.com/apdataentry-esp.php

Issue 1.0 EEBP – Sesión Técnica 3 - Training Workbook


48
Energy Efficiency Best Practices (EEBP)

Sesión Técnica 4:

Eficiencia Energética – Altitude

Training Workbook
Every effort has been made to ensure that the information contained in this document is true and correct
at the time of going to press. However, the technology, systems, products, processes, specifications
and content in general described in this document are subject to continuous development and
DCProfessional is entitled to change them at any time and to expand on them. DCProfessional cannot
accept liability for any loss or damage of any nature whatsoever arising or resulting from the use of or
reliance on information or particulars in this document.

All names and other data used in examples are fictitious.

The information contained in this document is of a general nature.

No part of this document may be reproduced by any means, other than with the express written
permission of the copyright holder.

© Copyright 2016 by DCProfessional Development

All rights reserved. No part of this manual may be used, reproduced, or transmitted in any form or by any
means, electronic mechanical, including photocopying, recording, or by any information storage and
retrieval system, without the prior agreement and written permission of the publisher, except for the
inclusion of brief quotations in a review.

The contents of this manual are subject to ongoing revision without notice due to continuing
developments in standards, regulations, methodology, design, and manufacturing.

This manual forms part of the DCProfessional Development curriculum, and is presented without
warranty of any kind, including but not limited to implied warranties, for the manual’s quality or fitness for
any particular purpose. DC Professional Development shall not be liable to the purchaser or any other
entity with respect to any liability, loss or damage caused directly or indirectly by this manual.

All brand names and trademarks are the property of their respective owners.
DCProfessional Development
28 Scrutiny Street
London EC2A 4RP
United Kingdom

www.dc-professional.com

ACKNOWLEDGEMENTS

DCProfessional Development is indebted to the following organizations and individuals for their
invaluable support in the preparation of this manual:

Organizations: DCD Group, DCD Focus Magazine, DCD Intelligence,

Individuals: Agustín López Neira (Training Project Developer & Content Producer Manager).

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 2


Relación de contenidos

Relación de contenidos .............................................................................................................. 3

Objetivos .................................................................................................................................... 6

Altitude – Practicas avanzadas ................................................................................................... 6

Introducción ................................................................................................................................ 7

Evolución.................................................................................................................................... 8

Actuales Protagonistas/Referencias ........................................................................................... 9

Necesidades actuales .............................................................................................................. 10

Soluciones ................................................................................................................................ 11
Cooling ............................................................................................................................ 12
Diseño - contención de aire caliente o frío ......................................................... 12
Proporcionar el espacio adecuado en las puertas de los rack ......................... 13
Segregación de equipamiento ............................................................................. 13
Separación en distintas zonas ambientales ....................................................... 14
Revisión de los settings CRAC/CRAH ................................................................ 15
Aplicación de condiciones ambientales expandidas en la admisión del equipamiento
TI (sólo salas de telecomunicaciones) ............................................................... 16
Revisión y aumento de las temperaturas del agua enfriada (control de las válvulas
electrónicas de expansión > EEVs termostáticas > TEV) .................................. 17
Ventiladores de velocidad variable ..................................................................... 18

Power 19
Despliegue de UPS modulares ............................................................................ 19
UPS de alta eficiencia .......................................................................................... 19
Uso de modos operativos eficientes en las UPS ............................................... 20
IT 21
Hardware IT - Power ............................................................................................. 21
Activar las funcionalidades de gestión eléctrica ............................................... 22
Hardware conforme con Energy Star.................................................................. 22
Hardware que facilite los informes de temperatura y energía .......................... 23
Selección de equipamiento conveniente para entornos DC - dirección de los flujos de
aire ........................................................................................................................ 24
Despliegue de tecnologías grid y virtualización ................................................ 24
Métricas y monitorización ............................................................................................. 25
Medición de los consumos de agua ................................................................... 25

Tendencias.............................................................................................................................. 26

Referencias / Saber más .......................................................................................................... 27

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 3


ANEXO FIGURAS – Figura 1 ................................................................................................... 28
Mejora controlada ............................................................................................................ 28

ANEXO FIGURAS – Figura 2 ................................................................................................... 29


Áreas de actuación – Marco CEEDA ............................................................................... 29

ANEXO FIGURAS – Figura 3 ................................................................................................... 30


CEEDA – Intermedio “Silver” ........................................................................................... 30

ANEXO FIGURAS – Figura 4 ................................................................................................... 31


Contención ...................................................................................................................... 31

ANEXO FIGURAS – Figura 5 ................................................................................................... 32


Puertas ............................................................................................................................ 32

ANEXO FIGURAS – Figura 6 ................................................................................................... 33


Separación ambiental ...................................................................................................... 33

ANEXO FIGURAS – Figura 7 ................................................................................................... 34


Settings: Ejemplo típico CRAC/CRAH «fighting» ............................................................. 34

ANEXO FIGURAS – Figura 8 ................................................................................................... 35


Condiciones ambientales expandidas .............................................................................. 35

ANEXO FIGURAS – Figura 9 ................................................................................................... 36


VSD: Ventiladores de Velocidad Variable ........................................................................ 36

ANEXO FIGURAS – Figura 10 ................................................................................................. 37


UPS 37

ANEXO FIGURAS – Figura 11 ................................................................................................. 38


Hardware y funcionalidades ............................................................................................. 38

ANEXO FIGURAS – Figura 12 ................................................................................................. 39


Tecnologías Grid y Virtualización ..................................................................................... 39

ANEXO FIGURAS – Figura 13 ................................................................................................. 40


Medición WUE ................................................................................................................. 40

ANEXO FIGURAS – Figura 14 ................................................................................................. 41


Tendencias – Evolución progresiva en las mejoras.......................................................... 41

Caso Práctico 1: Cadena de la energía eléctrica en el Data Center ......................................... 42

Caso Práctico 2: Cálculo en ineficiencias por ventiladores (fans) ............................................. 43

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 4


Uso apropiado del Workbook
Este workbook ha sido diseñado para un uso conjunto en las sesiones presenciales, casos de estudio y
workshops de este módulo, de modo que los asistentes puedan adquirir conocimientos de aplicación
práctica en un entorno de la industria de los Data Center.

El curso está estructurado para que el Tutor exponga funcionalidades y ejemplos de casos prácticos con
el apoyo del material del Tutor (proyecciones, videos, simulaciones, técnicas de aprendizaje acelerado).

Siempre que sea posible, los asistentes deben participar de forma activa individual o en grupos
reducidos para desarrollar y completar ejercicios orientados a consolidar su aprendizaje Se ha
dispuesto de un entorno de aprendizaje adecuado para que pueda actuar de modo seguro.

El objetivo del workbook es ser un documento de trabajo orientado al refuerzo de la información


presentada por el Tutor. Cada asistente debe disponer de una copia digital o en papel de este workbook
con antelación al curso de modo que pueda ayudar a la preparación previa del curso, especialmente en
los casos de aquellos asistentes menos familiarizados con algunas temáticas del curso, además de
servir durante y después de la formación como documento de consulta.

No está diseñado en cualquier caso para proporcionar de modo detallado todos los aspectos teóricos ni
fundamentos de una tecnología o aplicación, sino específicamente aquellos especialmente relevantes
para el desarrollo del curso y los objetivos concretos de aprendizaje.

Cualquier consulta, aclaración o incidencia sobre DCProfessional training curses puede dirigirla a:

agustin.lopez@datacenterdynamics.com

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 5


Objetivos
Altitude – Practicas avanzadas
Al finalizar este módulo, será capaz de:

• Identificar las mejores prácticas avanzadas en todas las áreas electromecánicas, TIC y de
monitorización de las instalaciones

• Conocer los fundamentos de las mejores prácticas avanzadas en todas las áreas
electromecánicas, TIC y de monitorización de las instalaciones

• Reconocer las ventajas y posible adaptación en distintos entornos de los data center de las
mejores prácticas avanzadas en todas las áreas electromecánicas, TIC y de monitorización de
las instalaciones

• Identificar las métricas y actividades de monitorización avanzadas que permiten habilitar un


proceso común en el equipo y terceras partes

También dispone de la oportunidad de:

- Compartir sus conocimientos y opiniones

- Exponer casos reales y problemáticas en experiencias vividas o conocidas

- Escuchar atentamente las opiniones del resto de los asistentes

- Aportar comentarios de manera activa, respetando el enfoque del resto de participantes en la


aplicación de soluciones o puntos de vista concretos, incluso cuando sean opuestos a sus
propias valoraciones y entendimiento como base del enriquecimiento del grupo

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 6


Introducción

La aplicación de medidas esenciales permite avanzar en el proceso de mejora hacia la aplicación


controlada de nuevas medidas en la eficiencia, de modo que no se ponga en riesgo la disponibilidad de
los sistemas.

*Figura 1*
La aplicación generalizada de las medidas especificadas en el nivel CEEDA Bronze permite por tanto
avanzar en las medidas correspondientes al nivel CEEDA Enterprise Silver que se desarrollan en esta
sesión.

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 7


Evolución

Para poder avanzar y profundizar en las medidas relacionadas con la eficiencia energética y a se
habrán formalizado y realizado:

- Definición y designación de roles y funciones en la organización

- Aplicación de programas y actividades de formación a todos los responsables y empleados


relevantes con implicación de personal externo subcontratado

- Definición del plan de mejora de la eficiencia con un objetivos establecidos y revisados en base
a un ciclo de vida definido en la organización

- Consideración y aplicación de, al menos, las medidas indicadas en el esquema CEEDA Bronze
en el caso de data center corporativos

- Consideración y aplicación de medidas de eficiencia adicionales procedentes de otras guías o en


base a la propia consideración lógica de la organización y que complementen las medidas
básicas indicadas en el esquema CEEDA Bronze en el caso de data center corporativos y según
sea el caso particular de las instalaciones

A partir de aquí podemos introducirnos en la aplicación al detalle de las medidas de niveles superiores
como CEEDA Silver.

*Figura 2*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 8


Actuales Protagonistas/Referencias

Entre las referencias principales en aspectos de aplicación de mejores prácticas y herramientas para la
industria del data center podemos destacar:

- CEEDA (Certifed Energy Efficient Data Center Award): primer esquema de certificación en la
industria del data center en la consideración de aplicación de las mejores prácticas reconocidas
a nivel internacional para los centros de datos. http://www.ceedacert.com/

- EU CoC (European Union Code of Conduct): creado en respuesta al aumento del consumo de
energía en centros de datos y la necesidad de reducir los impactos en aspectos ambientales,
económicos y energéticos relacionados. Cuenta con más de 120 participantes y 245 promotores
en la aplicación de las buenas prácticas reconocidas por la industria.
http://iet.jrc.ec.europa.eu/energyefficiency/ict-codes-conduct/data-centres-energy-efficiency

- COE (Center of Expertise for Energy Efficiency in Data Centers): Promovido por Lawrence
Berkeley National Laboratory (LBNL) y esponsorizado por U.S. Department of Energy (DOE)
dispone de herramientas y una master list con acciones recomendadas como mejores prácticas
a implementar en los data center. https://datacenters.lbl.gov/

- DOE (US Department of Energy) Better Buildings: con suite de herramientas para la adopción de
líneas base, formación, casos de estudio y programa de reconocimiento a los mayores
ahorradores de energía. http://energy.gov/eere/better-buildings

- EPA (United States Environmental Protection Agency): métricas, clasificación de equipamiento


de red, UPS y servidores y reconocimiento ENERGY STAR; Data center benchmarking.

https://www.energystar.gov/index.cfm?c=prod_development.server_efficiency

- FEMP (US Federal Energy Management Program): talleres, casos de estudio, políticas,
intercambio de información y asistencia técnica. http://energy.gov/eere/femp/energy-efficiency-
data-centers

- The Green Grid: métricas y herramientas de aplicación de modelos de madurez en eficiencia


energética para data centers. http://www.thegreengrid.org/

- Information technology industry council: Políticas de uso de la eficiencia energética en


dispositivos TIC. https://www.itic.org/

- ASHRAE: Estándares de referencia en aspectos ambientales relacionados con el equipamiento


TI y de telecomunicaciones para los data center. https://www.ashrae.org/

- AFCOM: Asociación de profesionales en la industria del data center con capítulos en EEUU,
APAC y Reino Unido. https://www.afcom.com/

- The Telecommunication Standarization Sector (ITU-T): Órgano permanente de la International


Telecommunication Union (ITU) se encarga de estudiar asuntos técnicos, operativos y tarifarios
relacionados con las recomendaciones y normalización de las telecomunicaciones a nivel
mundial.

https://www.itu.int/rec/T-REC-L/recommendation.asp?lang=en&parent=T-REC-L.1300

- SINGAPORE STANDARD SS 564 Series: Singapore Standard for green data centres.
https://www.singaporestandardseshop.sg/product/Package.aspx?ID=5dfe0c1e-eeca-4cd6-9a8d-
5fe9cdc2eac6

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook 9


Necesidades actuales

La aplicación de medidas de eficiencia energética a nivel fundamental tiene en consideración aspectos


básicos iniciales de auditoría e inventariado para iniciar una toma de decisiones en base a una
estrategia más o menos agresiva en función de los elementos en activo.

Adicionalmente, considera la aplicación de estrategias básicas pero esenciales en atención a un diseño


organizado para poder atender a una gestión del aire lógica y aprovechando los espacios libres que
haya dejado el posible equipamiento decomisionado de cara a habilitar la posibilidad de estrategias más
avanzadas.

La monitorización se aborda desde un punto inicial de mínimos y en la que se deberá progresar


atendiendo a la máxima “no se puede gestionar lo que no se puede medir” como principio para la
mejora continua, especialmente atendiendo a evitar riesgos en la operación de los servicios activos.

Otros de los apartados que empiezan a considerarse en este momento es la aplicación de medidas en
dispositivos relacionados con la distribución y almacenamiento de la energía.

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


10
Soluciones

Para establecer un criterio concreto en los planes de mejora energética tomaremos el esquema de
CEEDA “Enterrprise” como referencia y con el objetivo de cubrir un escenario de un data center ya en
operación y, por otra parte, tomar la referencia de los sistemas TI y que en esquemas como CEEDA
Colocation o CEEDA Telco no estarían representados.

La relación de las mejores prácticas indicadas a continuación se corresponden con el nivel CEEDA
Silver para este esquema de data center corporativo y organizados por área funcional para mayor
claridad (*Figura 3*)

Nombre de la mejor práctica Sección Área funcional

Considerar el impacto ambiental que representan los dispositivos Silver 01 Políticas generales
instalados (TI + M & E)

Hardware IT - Power Silver 02 TI: Equipamiento servicios

Activar las funcionalidades de gestión eléctrica Silver 03 TI: Equipamiento servicios

Hardware conforme con Energy Star Silver 04 TI: Equipamiento servicios

Hardware que facilite informes de temperatura y energía Silver 05 TI: Equipamiento servicios

Selección equipamiento conveniente para entornos de data center - Silver 06 TI: Equipamiento servicios
dirección de los flujos de aire

Despliegue de tecnologías grid y virtualización Silver 07 TI: Equipamiento servicios

Diseño - contención de aire caliente o frío Silver 08 Cooling

Proporcionar el espacio adecuado en las puertas de los rack Silver 09 Cooling

Segregación de equipamiento Silver 10 Cooling

Separación en distintas zonas ambientales Silver 11 Cooling

Revisión de los settings CRAC/CRAH Silver 12 Cooling

Aplicación de condiciones ambientales expandidas en la admisión del Silver 13 Cooling


equipamiento TI (sólo telecomunicaciones)

Revisión y aumento de las temperaturas del agua enfriada (control de las Silver 14 Cooling
válvulas electrónicas de expansión > EEVs termostáticas > TEV)

Ventiladores de velocidad variable Silver 15 Cooling

Despliegue de UPS modulares Silver 16 Power

UPS de alta eficiencia Silver 17 Power

Uso de modos operativos eficientes en las UPS Silver 18 Power

Medición de los consumos de agua Silver 19 Generales

Aquellos interesados de modo específico en las buenas prácticas establecidas para los tres niveles
Bronze, Silver, Gold y para el resto de esquemas (Colocation, Design&Operations, Telco) pueden
contactar con personal de DCProfessional y acceder sin coste adicional a las especificaciones
específicas correspondientes.
Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook
11
Cooling

Diseño - contención de aire caliente o frío

Existen una serie de conceptos de diseño cuya intención básica es contener y separar el aire frío
de admisión respecto al aire caliente de retorno en la sala TI.

Los cambios en el hardware y las herramientas de gestión TI muestran que el flujo de aire y la
temperatura de salida de los dispositivos TI no son constantes y podrían variar rápidamente
debido a la administración de energía y a las herramientas de asignación de las cargas de
trabajo. Esto produce rápidos cambios en los patrones de los flujos de aire en toda la sala
técnica y en las temperaturas de admisión de los equipos TI que no pueden ser fácilmente
predecibles o prevenidas.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Contención del pasillo caliente

 Contención del pasillo frío

 Suministro a rack contenido, retorno a sala,

 Suministro a sala, contención en el aire de retorno del rack (chimeneas en rack)

 Suministro a rack contenido, contención en el aire de retorno a sala (solución típica para
alta densidad en racks que estén refrigerados por aire)

Beneficios

 Mayor nivel de segregación en los aires que permite optimizar la eficiencia y un control
más férreo en la gestión del aire que requiere cada equipamiento

 Opciones de gestionar de manera controlada mayores densidades de carga por rack

 Menor afectación en el resto de sala de situaciones específicas localizadas en ciertos


equipos o racks

*Figura 4*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


12
Proporcionar el espacio adecuado en las puertas de los rack

Cuando sea preciso aplicar ventilación a los equipos TI las puertas sólidas deberían ser
reemplazadas por puertas parcialmente perforadas que garanticen el caudal de aire de
refrigeración adecuado.

La ausencia de perforaciones en las puertas impide el acceso del flujo de aire de refrigeración y
promueve la recirculación dentro un rack cerrado aumentando aún más la temperatura del aire
de admisión de los equipos.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 La aplicación de las recomendaciones establecidas en ISO/IEC 14763-2 con un mínimo


del 66% de zona perforada que podría elevarse a 80% en el caso de las
recomendaciones de otros grupos de expertos

 Puertas apropiadas tanto en el partes frontales como posteriores o superiores en base a


las observaciones de la temperatura del aire de admisión de los equipos

Beneficios

 Evitar que los elementos físicos típicamente de seguridad se conviertan en barreras para
el paso del aire en el caudal que es necesario

 Evitar el colapso de equipos por un recirculación excesiva y recalentamiento del aire de


admisión, más allá de las ineficiencias que producen estas recirculaciones

*Figura 5*
Segregación de equipamiento

Desplegar en distintas áreas los grupos de equipos con requisitos medioambientales


sustancialmente diferentes y/o direcciones de flujo de aire distintas. Cuando los equipos tienen
requisitos ambientales distintos es preferible proporcionar controles ambientales separados.

El objetivo de esta práctica es acotar la influencia negativa en la eficiencia en el data center por
las restricciones en los rangos operativos de ciertos equipos o por un control insuficiente de los
flujos de aire. Esta práctica es aplicable a equipos TI, equipos eléctricos y mecánicos instalados
en los data center.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Salas separadas para los equipos con distintos requisitos ambientales como legados,
junto con la configuración correspondiente de los sistemas de enfriamiento en función de
las necesidades de cada sala

Beneficios

 Evitar restricciones en la aplicación de temperaturas operativas más elevadas a aquella


parte el equipamiento que sí puede funcionar a estar temperaturas.

 Evitar recirculaciones de aires y otros problemas típicos en la gestión del aire y del
espacio en sala que se producen por equipos no estándar

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


13
Separación en distintas zonas ambientales

Se deberían proporcionar áreas separadas cuando el data center alberga tanto equipos
informáticos con un rango operativo ampliado como equipos que requieren un control más
restrictivo de la temperatura o humedad.

Estas áreas deberían disponer de controles medioambientales separados y podrían utilizar


sistemas de refrigeración diferenciados para facilitar la optimización de la eficiencia de
enfriamiento de cada zona.

Algunos ejemplos de equipamiento relacionados con esta práctica que requieren controles
ambientales más estrictos para cumplir con los criterios operativos más amplios típicamente.

 Cintas de almacenamiento

 Equipos que deben cumplir con largos períodos de garantía (+10 años)

 UPS para el mantenimiento de la capacidad de la batería y tiempo de vida

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Salas separadas para los equipos con distintos requisitos ambientales junto con la
configuración correspondiente de los sistemas de enfriamiento en función de las
necesidades de cada sala

Beneficios

El objetivo de esta práctica es evitar la necesidad de establecer la configuración de la planta de


refrigeración del data center en función del equipamiento más restrictivo en términos de rango
operativo y, por lo tanto, comprometer la eficacia de todo el data center

*Figura 6*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


14
Revisión de los settings CRAC/CRAH

Garantizar que las unidades CRAC/CRAH en las zonas ocupadas tengan una apropiada y
consistente configuración de humedad relativa y temperatura y evitar que las unidades funcionen
las unas contra las otras.

Por ejemplo, muchas unidades CRAC/CRAH presentan ahora la opción de interconectar sus
controles y funcionar en equipo si se instalan en la misma zona. Se debería tener cuidado para
entender y evitar cualquier nuevo modo o puntos únicos de fallos potenciales que puedan ser
introducidos.

.Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Reuniones periódicas interna y/o con el fabricante y persona subcontratado de


mantenimiento si fuera oportuno para discutir y aclarar las actividades de revisión del
equipamiento y revisar o modificar según necesidad los modos de funcionamiento
establecidos.

Beneficios

 Evitar los costes adicionales de equipos realizando acciones contradictorias

 Control de las unidades de enfriamiento respecto a las necesidades en cada momento

 Coordinación entre las partes

 Detectar posibles desviaciones de forma prematura y evitar la pérdida de control

 Mantener la observancia de todo el personal interno y externo en las actividades diarias


sabiendo que existen revisiones periódicas de verificación

*Figura 7*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


15
Aplicación de condiciones ambientales expandidas en la admisión del equipamiento TI
(sólo salas de telecomunicaciones)

Cuando sea apropiado y eficaz, se pueden aplicar diseños en los data center para operaciones
en rangos de temperaturas y humedad relativa en los aires de admisión entre los 5ºC y los 40ºC
y el 5% y el 80% de humedad relativa, sin condensación respectivamente y bajo condiciones
excepcional hasta los +45ºC según se describe en ETSI EN 300 019, Class 3.1.

La aplicación de temperaturas de hasta 40ºC o 45ºC permite la eliminación de la refrigeración en


la mayoría de las climatologías permitiendo a los operadores eliminar los costes capitales de
mantenimiento de estos sistemas.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Especificaciones técnicas del equipamiento que puede operar en estos rangos


expandidos

 Equipamiento dentro del tipo establecido en ASHRAE para la Clase 4.

 Espacios con equipamiento típico de telecomunicaciones y que tienen condiciones


ambientales de operación muy distintas y más extensas que el equipamiento TI,
generalmente.

Beneficios

 Reducción de costes en energía y en equipamiento de enfriamiento innecesario


(típicamente en salas telco)

 Separación de ambientes respecto a equipamiento más restringido a nivel ambiental

*Figura 8*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


16
Revisión y aumento de las temperaturas del agua enfriada (control de las válvulas
electrónicas de expansión > EEVs termostáticas > TEV)

Aumentar los puntos de consigna de la temperatura del agua refrigerada para maximizar el uso
de economizadores freecooling y reducir el consumo de energía por parte del compresor.

Cuando se utilicen sistemas DX las temperaturas del evaporador deberían ser revisadas. Las
válvulas de expansión electrónicas (EEVs) permiten un mejor control y mayores temperaturas
del evaporador en comparación con las válvulas de expansión termostática (TEVs).

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Información documentada de las reuniones periódicas con los datos de funcionamiento y


revisión de los registros diarios de temperatura.

 Algunas organizaciones pueden tratar de elevar las temperaturas (alimentación / retorno


y agua fría) y/o humedad en incrementos graduales, en ese caso deberían registrarse en
las reuniones periódicas

Beneficios

 Reducir el esfuerzo energético relacionado con el enfriamiento del agua

 Aprovechamiento mayor de elementos como economizadores en freecooling

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


17
Ventiladores de velocidad variable

Muchas unidades CRAC/CRAH antiguas operan con ventiladores de velocidad fija que
consumen mucha energía y obstaculizan los intentos de controlar la temperatura en la sala
técnica.

Estos ventiladores pueden controlarse ligados a factores como la temperatura del aire de
suministro o el de retorno o la presión en las cámaras/plenum de aire refrigerado.

Debe tenerse en cuenta que las unidades CRAC/CRAH con compresores de velocidad fija
tienen unos requisitos de flujo mínimos que limitan la carga operativa mínima y en consecuencia,
un mínimo en el flujo de aire.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Revisión de los componentes del sistema utilizados, de los manuales de operación y


mantenimiento, los números de modelo de los equipos instalados

 Estudios de coste/beneficio para la sustitución de ventiladores y que puedan observar la


viabilidad de su aplicación prematura respecto al cambio completo del equipamiento en
base a su ciclo de amortización esperado

Beneficios

Los ventiladores de velocidad variable resultan especialmente efectivos si:

 Existe un elevado nivel de redundancia en el sistema de refrigeración

 Se produce un bajo índice de uso de las instalaciones

 Cargas eléctricas muy variables en los elementos de TI

*Figura 9*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


18
Power

Despliegue de UPS modulares

Ahora es posible adquirir sistemas UPS modulares (escalables) con un amplio rango de
capacidades en el suministro de energía.

En el despliegue se preparan las instalaciones físicas, los transformadores y el cableado para


responder a la carga eléctrica diseñada para las instalaciones pero las fuentes típicas de
ineficiencia (como las unidades de conmutación y baterías) se instalan en función de las
necesidades en base a unidades modulares.

Esto reduce sustancialmente tanto el coste de capital como las pérdidas fijas asociadas a estos
sistemas.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 En entornos de baja potencia pueden aplicarse marcos con módulos "plug-in"

 En los entornos más grandes lo más probable es que se trate de unidades completas de
UPS.

Beneficios

 Reducción importante de las pérdidas típicas asociadas a sistemas de UPS

UPS de alta eficiencia

Deberían seleccionarse sistemas UPS de alta eficiencia de cualquier tecnología, incluida la


electrónica o rotativa, para responder a los requisitos de los centros.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Acciones de implantación alineadas con IEC 62040

 Información documentada con las especificaciones técnicas requeridas en la adquisición


de este equipamiento

 Información documentada de las reuniones periódicas con los datos de funcionamiento


respecto a los manuales de operación y mantenimiento

 Revisión de los registros diarios de funcionamiento en comparación con las curvas de


eficiencia especificadas por el fabricante, especialmente durante las pruebas o
situaciones reales de descarga registradas

Beneficios

 Reducción importante de las pérdidas típicas asociadas a sistemas de UPS

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


19
Uso de modos operativos eficientes en las UPS

El UPS debería desplegarse utilizando sus modos operativos más eficientes como el interactivo
de línea. Algunas tecnologías como la rotativa y sistemas de corriente directa (DC) también
pueden mejorar la eficiencia ya que no existe ningún requisito de conversión dual.

Algunos sistemas de UPS disponen de tecnología que permiten la optimización de la energía en


niveles de carga parcial y deberían tenerse en consideración como más apropiadas.

Esto es particularmente relevante en cualquier sistema UPS alimentando cargas mecánicas p.ej.
fans de CRAC/CRAHs.)

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 La comparación y valoración de las tecnologías debería realizarse en base a la última


información sobre los productos disponibles y sin ningún tipo de prejuicio.

 Manuales de operación y mantenimiento de la tecnología de UPS en uso, especialmente


la identificación de los modos de "eficiencia energética".

 Información documentada con las especificaciones técnicas requeridas en la adquisición


de este equipamiento

 Revisión de los registros diarios de funcionamiento en comparación con las curvas de


eficiencia especificadas por el fabricante, especialmente durante las pruebas o
situaciones reales de descarga registradas

Beneficios

 Reducción importante de las pérdidas típicas asociadas a sistemas de UPS

*Figura 10*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


20
IT
Hardware IT - Power

Incluir el rendimiento en eficiencia energética de los dispositivos de TI como un factor de


decisión de alta prioridad dentro del proceso de licitación.

Esto puede realizarse mediante el uso de métricas estándar de tipo Energy Star o SERT
(www.spec.org/sert) o métricas similares, incluso mediante el despliegue de métricas específicas
del usuario que están estrechamente ligadas al entorno objetivo de instalación y que puede
incluir consideraciones sobre el nivel de servicio o la fiabilidad de los componentes.

El consumo eléctrico del dispositivo se debe considerar en relación al uso esperado o a la carga
de trabajo aplicada, además del cálculo del rendimiento en situaciones de picos de consumo y
en relación a vatios.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Políticas de contratación de equipamiento TI donde la mejor práctica se indique de forma


explícita

 Directrices de contratación en caso de ausencia de un procedimiento formal, con


referencias a Energy Star o equivalentes de modo que cualquier elemento suministrado
deba cumplir por defecto con esta buena práctica.

Beneficios

Esta práctica se centra especialmente en las fuentes de alimentación de los dispositivos TI


adquiridos, entre otros beneficios.

 La compra de equipamiento (servidores, UPS) con certificaciones de eficiencia


energética introduce ahorros de consumo hasta el 54% en servidores «Energy Star».

 Es especialmente útil especialmente en los tiempos en los que los servidores


permanecen ociosos.

 Los equipos tipo Energy Star habitualmente disponen de funcionalidades internas para la
gestión del consumo de la energía.

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


21
Activar las funcionalidades de gestión eléctrica

Modificar formalmente el proceso de despliegue del equipamiento con el objeto de incluir la


activación de las funciones de gestión energética en el hardware TI.

Esto incluye la configuración en BIOS, en el sistema operativo y en los drivers.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Información documentada del procedimiento de instalación de servidores

 Enumeración de las medidas adoptadas o características que se instalarán durante los


procesos de parametrización durante la instalación

Beneficios

 Obtención de ahorros adicionales

 Monitorizar directa de los consumos por equipo y análisis de tendencias, variaciones, etc.

Hardware conforme con Energy Star

Se deben de utilizar las referencias a etiquetados como Energy Star a equipamiento TI como
guía para la selección donde y cuando está disponible para el tipo de equipamiento requerido.
Aquellos operadores capaces de determinar el uso eficiente de la energía en el hardware
mediante la aplicación de análisis más avanzados o eficaces deberían seleccionar el
equipamiento más eficiente para cada escenario.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Prácticas alineadas con las especificaciones actuales para servidores de US EPA´s


ENERGY STAR – Versión 2

 Prácticas alineadas con las especificaciones actuales para sistemas de almacenamiento


para Data Center de US EPA´s ENERGY STAR – Versión 1

 Políticas y prácticas de compra en referencia a especificaciones equivalentes según


región (EU Energy Star)

Beneficios

 Control sobre las especificaciones técnicas que manejan los departamentos técnicos y de
compra del equipamiento

 Alineación con regulaciones actuales o venideras que reclamen procesos de adquisición


y mantenimiento de equipamiento sustentables

 Obtención de ahorros adicionales

 Monitorizar directa de los consumos por equipo y análisis de tendencias, variaciones, etc.

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


22
Hardware que facilite los informes de temperatura y energía

Seleccione equipamiento con capacidades de informes en el consumo eléctrico y temperaturas


de admisión, preferiblemente informando de la energía utilizada a modo de contador además del
indicador de potencia.

Cuando sea posible, se deberían utilizar enfoques estandarizados en la industria para la


presentación de informes como IPMI, DCMI y SMASH.

Ejemplo de implantación

Para ayudar en la implantación de una monitorización de la temperatura y la energía a través de


una amplia gama de centros de datos, todos los dispositivos con una interfaz IP deberían incluir
uno de los siguientes:

 SNMP polling de las temperaturas de admisión y gráfica del consumo de energía. Tenga
en cuenta que los eventos en base a SNMP traps y configuración SNMP no son
requeridos

 IPMI polling de las temperaturas de admisión y gráfica del consumo de energía (sujeto a
la inclusión de las temperaturas de admisión por IPMI 2.0 rev 4)

 Una protocolo de interfaz con las que las plataformas actuales de supervisión de los
operadores puedan recuperar las temperaturas de admisión y obtener datos de
consumos de potencia sin la necesidad de compra de licencias adicionales dependientes
del vendedor del equipamiento.

Beneficios

La intención de esta práctica es proporcionar una supervisión ambiental y de uso de la energía


del data center durante la actividad variable de los equipos.

*Figura 11*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


23
Selección de equipamiento conveniente para entornos DC - dirección de los flujos de aire

Al seleccionar los equipos autónomos o en racks personalizados, la dirección del flujo de aire de
los armarios suministrados debe coincidir con el diseño aplicado en el data center.

Los equipos con flujos de aire distintos a los estándares pueden comprometer la gestión del flujo
de aire en el data center y la capacidad de elevar los puntos de consigna de temperatura.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Habitualmente, la dirección del flujo va desde la parte frontal del equipamiento TI hacia la
parte trasera del mismo o desde la parte frontal del equipamiento TI hacia la parte
superior del rack.

 Concretamente, los equipos deben coincidir con la disposición de pasillo frío/caliente o el


esquema de contención implementado en las instalaciones.

 Es posible paliar este problema segregando esos equipos mediante la aplicación de


prácticas adicionales como la segregación del resto del equipamiento estándar.

 Evitar equipamiento autónomo que habitualmente no admite su adaptación a una


organización adecuada de la gestión del aire en el data center, especialmente cuando la
mayor parte del equipamiento en la sala TI está bien organizada y montada en racks

 Aplicación de deflectores o soluciones similares propias o del fabricante que permitan la


adaptación del equipamiento reorientando la admisión y expulsión de aire en las
direcciones estándar definidas por el diseño de la sala.

Beneficios

 Evitar restricciones en la aplicación de temperaturas operativas más elevadas.

 Evitar recirculaciones de aires y otros problemas típicos en la gestión del aire y del
espacio en sala.

Despliegue de tecnologías grid y virtualización

Se debería establecer un proceso formal de aprobación por parte de la alta dirección para
cualquier servicio nuevo que requiera de hardware dedicado y que no funcione sobre
plataformas de recursos compartidos. Esto aplica a aspectos de los servicios relacionados con
servidores, dispositivos de almacenamiento y de red de telecomunicación.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Proceso definido para el estudio, aprobación y puesta en marcha de nuevos servicios

 Especificaciones técnicas aplicadas en la propuesta y selección de equipos que den


soporte a nuevos servicios.

Beneficios

 Mantener opciones de provisionar los nuevos servicios en plataformas de virtualización.

*Figura 12*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


24
Métricas y monitorización
Medición de los consumos de agua

Se debe registrar el consumo de agua de todas las fuentes. Se debería tratar de utilizar estos
datos para gestionar y reducir el consumo total de agua. Tenga en cuenta que el consumo de
agua no se puede comparar directamente con la eficiencia energética (PUE), salvo que se
comprenda la intensidad energética de la fuente de agua. Por tanto, comparar el consumo de
agua entre los edificios no es útil.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Uso de la guía de medición del agua de The Green Grid – Water Usage Effciency (WUE).

 Información documentada del diseño y especificación que detalla los criterios básicos
para esta práctica.

 Presencia y la instalación de medidores de agua.

Beneficios

 Conocer con precisión los consumos totales de las instalaciones desde el punto inicial de
responsabilidad en el uso

 Discriminar aberraciones introducidas por elementos ajenos a la actividad del data center

 Conocer los costes totales, el patrón de evolución de los consumos de la energía en


detalle a lo largo del tiempo y afectación positiva o negativa en base a las actuaciones de
mejora que se vayan produciendo

 Cálculo preciso del PUE

*Figura 13*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


25
Tendencias
Una vez resuelto el análisis gap inicial, haber trabajado en cubrir y mejorar los aspectos relevantes de
un nivel CEEDA Bronze y ampliado y profundizado con CEEDA Silver, el trabajo se centra típicamente
en cumplir con los niveles establecidos en el siguiente nivel CEEDA Gold dentro del método de madurez
presentado.

Subir el siguiente escalón supone automatizar y ampliar las mediciones de los distintos sistemas e
integrar los datos del modo más directo posible para obtener información vital en el menor tiempo, en
tiempo incluso real cuando sea posible. Las mediciones y automatización son fundamentales para
obtener rendimientos en técnicas de freecooling y ajustar la actividad electromecánica a la cantidad de
carga TI y sus variaciones constantes.

Puede parecer un reto insalvable en algunos casos pero no es ni más ni menos la dirección que marca
la industria no sólo por temas de eficiencias energética, incluso por la propia necesidad en alta
disponibilidad.

Poder abordar estas mejores prácticas lo antes posible, entre otras actuaciones complementarias, pone
en una mejor posición la gestión y adaptación de los data center cuando los requisitos se hacen
obligatorios, ya que en ese momento sólo habrá que focalizar los esfuerzos en los aspectos que falten
por formalizar y no el marco completo de los requerimientos.

Un marco organizado como CEEDA permite además atender de manera integrada diversas normativas
y requerimientos que afecten directa o indirectamente al data center al ser un marco de buenas
prácticas generadas por la propia industria y considerar todas las actividades en las áreas funcionales
relevantes.

*Figura 14*

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


26
Referencias / Saber más

- CEEDA website: http://www.ceedacert.lat/

- EU Code of Conduct on Data Center Energy Efficiency Best Practice Guidelines:


http://iet.jrc.ec.europa.eu/energyefficiency/sites/energyefficiency/files/files/COC_DC/2016/2016_b
est_practice_guidelines_v7.1.2.pdf

- Data Center Master List of Energy Efficiency Actions:

https://datacenters.lbl.gov/resources/data-center-master-list-energy

- ITU-T L.1300 Best Practices for Green Data Centres

https://www.itu.int/rec/T-REC-L.1300-201406-I/en

- ITU-T L.1310 Energy Efficiency Metrics and Measurement Methods for Telecommunication
Equipment

https://www.itu.int/rec/T-REC-L.1310-201211-S

- Mission Critical Facilities, Data Centers, Technology Spaces and Electronic Equipment ASHRAE
Technical Committee 9.9: https://tc0909.ashraetcs.org/

- ASHRAE TC9.9 Proposed Clarification to ASHRAE Thermal Guidelines

https://tc0909.ashraetcs.org/documents/Clarification%20to%20ASHRAE%20Thermal%20Guideli
nes.pdf

- ASHRAE TC9.9 Data Center Networking Equipment – Issues and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE%20Networking%20Thermal%20Guidelines.pdf

- ASHRAE TC9.9 Data Center Power Equipment Thermal Guidelines and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_TC0909_Power_White_Paper_22_June_2016
_REVISED.pdf

- ASHRAE TC9.9 IT Equipment Thermal Management and Controls

https://tc0909.ashraetcs.org/documents/ASHRAE%202012%20IT%20Equipment%20Thermal%2
0Management%20and%20Controls_V1.0.pdf

- ASHRAE TC9.9 Data Center Storage Equipment – Thermal Guidelines, Issues, and Best
Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_Storage_White_Paper_2015.pdf

- The Green Grid: Recommendations for Measuring and Reporting Overall Data Center Efficiency
Version 2 – Measuring PUE for Data Centers

http://www.thegreengrid.org/~/media/WhitePapers/Data%20Center%20Metrics%20Task%20Forc
e%20Recommendations%20V2%205-17-2011.ashx?lang=en

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


27
ANEXO FIGURAS – Figura 1

Mejora controlada

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


28
ANEXO FIGURAS – Figura 2

Áreas de actuación – Marco CEEDA

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


29
ANEXO FIGURAS – Figura 3

CEEDA – Intermedio “Silver”

http://www.ceedacert.lat/cpds-certificados

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


30
ANEXO FIGURAS – Figura 4

Contención

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


31
ANEXO FIGURAS – Figura 5

Puertas

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


32
ANEXO FIGURAS – Figura 6

Separación ambiental

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


33
ANEXO FIGURAS – Figura 7

Settings: Ejemplo típico CRAC/CRAH «fighting»

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


34
ANEXO FIGURAS – Figura 8

Condiciones ambientales expandidas

Intel IT New Mexico Proof of Concept

Energy Star: Data Center Energy Efficiency Opportunities

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


35
ANEXO FIGURAS – Figura 9

VSD: Ventiladores de Velocidad Variable

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


36
ANEXO FIGURAS – Figura 10

UPS

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


37
ANEXO FIGURAS – Figura 11

Hardware y funcionalidades

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


38
ANEXO FIGURAS – Figura 12

Tecnologías Grid y Virtualización

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


39
ANEXO FIGURAS – Figura 13

Medición WUE

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


40
ANEXO FIGURAS – Figura 14

Tendencias – Evolución progresiva en las mejoras

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


41
Caso Práctico 1: Cadena de la energía eléctrica en el Data Center

Caso Práctico 1: Cadena de la energía eléctrica en el Data


Center

Trate de evaluar los ahorros potenciales en acciones de eficiencia energética en la cadena de


alimentación eléctrica de un data center, incluyendo la iluminación.

Para desarrollar este ejercicio necesitará:

- Información de configuración básica y de eficiencia de los componentes del sistema


eléctricos tales como transformadores, generadores, sistema de alimentación
ininterrumpida (UPS), unidad de distribución de energía (PDU), dispositivos e
iluminación.

- El uso de energía de los sistemas eléctricos

- Herramienta de cálculo en la que introducir los datos


(https://datacenters.lbl.gov/sites/all/files/dcpro_eat.xls)

En base a las preguntas y resultados de la herramienta comentar los resultados finales


obtenidos con el resto de los asistentes

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


42
Caso Práctico 2: Cálculo en ineficiencias por ventiladores (fans)

Caso Práctico 2: Cálculo en ineficiencias por ventiladores (fans)

El concepto fundamental en los ahorros con dispositivos VFD es que la velocidad y el flujo
sean más o menos proporcionales pero el consumo de energía es el cubo.

Si un motor está girando a toda velocidad cualquier reducción en la velocidad aplicará una
reducción en la energía en relación al cubo. Esto quiere decir:

- Una reducción de la velocidad del motor del 100% al 90% la reducción del 10%
implicará un 27% de ahorro en los costes (cubo de 90% = 0.9 x 0.9 x 0.9 = 0.729),
exactamente un 72,9% de la energía inicial en uso.

En base al ejemplo, calcule la reducción de costes al régimen de:

- 75%

- 50%

- 25%

Indique a continuación cuál es el porcentaje de ahorro más significativo.

Issue 1.0 EEBP – Sesión Técnica 4 - Training Workbook


43
Energy Efficiency Best Practices (EEBP)

Sesión Técnica 5:

Eficiencia Energética – Summit

Training Workbook
Every effort has been made to ensure that the information contained in this document is true and correct
at the time of going to press. However, the technology, systems, products, processes, specifications
and content in general described in this document are subject to continuous development and
DCProfessional is entitled to change them at any time and to expand on them. DCProfessional cannot
accept liability for any loss or damage of any nature whatsoever arising or resulting from the use of or
reliance on information or particulars in this document.

All names and other data used in examples are fictitious.

The information contained in this document is of a general nature.

No part of this document may be reproduced by any means, other than with the express written
permission of the copyright holder.

© Copyright 2016 by DCProfessional Development

All rights reserved. No part of this manual may be used, reproduced, or transmitted in any form or by any
means, electronic mechanical, including photocopying, recording, or by any information storage and
retrieval system, without the prior agreement and written permission of the publisher, except for the
inclusion of brief quotations in a review.

The contents of this manual are subject to ongoing revision without notice due to continuing
developments in standards, regulations, methodology, design, and manufacturing.

This manual forms part of the DCProfessional Development curriculum, and is presented without
warranty of any kind, including but not limited to implied warranties, for the manual’s quality or fitness for
any particular purpose. DC Professional Development shall not be liable to the purchaser or any other
entity with respect to any liability, loss or damage caused directly or indirectly by this manual.

All brand names and trademarks are the property of their respective owners.
DCProfessional Development
28 Scrutton Street
London EC2A 4RP
United Kingdom

www.dc-professional.com

ACKNOWLEDGEMENTS

DCProfessional Development is indebted to the following organisations and individuals for their
invaluable support in the preparation of this manual:

Organisations: DCD Group, DCD Focus Magazine, DCD Intelligence,

Individuals: Agustín López Neira (Training Project Developer & Content Producer Manager).

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 2


Relación de contenidos

Relación de contenidos .............................................................................................................. 3

Objetivos .................................................................................................................................... 6

Summit – Practicas de alto nivel ................................................................................................. 6

Introducción ................................................................................................................................ 7

Evolución.................................................................................................................................... 8

Actuales Protagonistas/Referencias ........................................................................................... 9

Necesidades actuales .............................................................................................................. 10

Soluciones ................................................................................................................................ 11
Cooling ............................................................................................................................ 12
Instalación escalable o modular y uso de equipos de refrigeración ................ 12
Freecooling ........................................................................................................... 13
Chillers de alto COP de rendimiento ................................................................... 14
Temperaturas operativas de los sistemas de enfriamiento .............................. 14
Operación eficiente con cargas parciales .......................................................... 15
Dispositivos de frecuencia variable en compresores, bombas y ventiladores 16
Métricas y monitorización ............................................................................................. 17
Lecturas diarias automatizadas (uso de energía y mediciones ambientales, E&M, TI)
............................................................................................................................... 17
Informes documentados ...................................................................................... 18
Consola de informes energéticos y ambientales ............................................... 19

Tendencias.............................................................................................................................. 20
Análisis del ciclo de vida ............................................................................................... 20
Tecnologías alternativas para la generación eléctrica ................................................ 20
Selección / desarrollo de software eficiente ................................................................ 20
Facilitar el uso de economizadores .............................................................................. 20
Refrigeración líquida directa en equipamiento TI........................................................ 21
Reutilización del calor residual..................................................................................... 21
Reutilización del calor residual asistida por bomba de agua ..................................... 21
Métricas e informes sobre la energía reutilizada ......................................................... 21
Emplazamientos cercanos a fuentes de freecooling................................................... 21
Emplazamientos compartidos con fuentes de generación ......................................... 22
Consola de informes medioambiental, E&M y TI integrada ........................................ 22
Uso de los Servidores / componentes de red / almacenamiento ............................... 22

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 3


Referencias / Saber más .......................................................................................................... 23

ANEXO FIGURAS – Figura 1 ................................................................................................... 24


Áreas de actuación – Marco CEEDA ............................................................................... 24

ANEXO FIGURAS – Figura 2 ................................................................................................... 25


CEEDA – Alto nível “Gold” ............................................................................................... 25

ANEXO FIGURAS – Figura 3 ................................................................................................... 26


Instalación escalable o modular y uso de equipos de refrigeración .................................. 26

ANEXO FIGURAS – Figura 4 ................................................................................................... 27


Freecooling por aire - Directo ........................................................................................... 27

ANEXO FIGURAS – Figura 5 ................................................................................................... 28


Freecooling indirecto por aire ........................................................................................... 28

ANEXO FIGURAS – Figura 6 ................................................................................................... 29


Freecooling evaporativo ................................................................................................... 29

ANEXO FIGURAS – Figura 7 ................................................................................................... 30


Freecooling con agua ...................................................................................................... 30

ANEXO FIGURAS – Figura 8 ................................................................................................... 31


Freecooling – Tendencias ................................................................................................ 31

ANEXO FIGURAS – Figura 9 ................................................................................................... 32


Operación eficiente con cargas parciales ......................................................................... 32

ANEXO FIGURAS – Figura 10 ................................................................................................. 33


Monitorización.................................................................................................................. 33

ANEXO FIGURAS – Figura 11 ................................................................................................. 34


Refrigeración líquida directa en equipamiento TI ............................................................. 34

ANEXO FIGURAS – Figura 12 ................................................................................................. 35


Reutilización del calor residual......................................................................................... 35

ANEXO FIGURAS – Figura 13 ................................................................................................. 36


Emplazamientos cercanos a fuentes de freecooling ........................................................ 36

ANEXO FIGURAS – Figura 14 ................................................................................................. 37


Uso de los Servidores / componentes de red / almacenamiento ...................................... 37

Caso Práctico 1: Aplicación de herramientas de GAP análisis ................................................. 37

Caso Práctico 2: Informes de auditoría en eficiencia energética ............................................... 39

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 4


Uso apropiado del Workbook
Este workbook ha sido diseñado para un uso conjunto en las sesiones presenciales, casos de estudio y
workshops de este módulo, de modo que los asistentes puedan adquirir conocimientos de aplicación
práctica en un entorno de la industria de los Data Center.

El curso está estructurado para que el Tutor exponga funcionalidades y ejemplos de casos prácticos con
el apoyo del material del Tutor (proyecciones, videos, simulaciones, técnicas de aprendizaje acelerado).

Siempre que sea posible, los asistentes deben participar de forma activa individual o en grupos
reducidos para desarrollar y completar ejercicios orientados a consolidar su aprendizaje Se ha
dispuesto de un entorno de aprendizaje adecuado para que pueda actuar de modo seguro.

El objetivo del workbook es ser un documento de trabajo orientado al refuerzo de la información


presentada por el Tutor. Cada asistente debe disponer de una copia digital o en papel de este workbook
con antelación al curso de modo que pueda ayudar a la preparación previa del curso, especialmente en
los casos de aquellos asistentes menos familiarizados con algunas temáticas del curso, además de
servir durante y después de la formación como documento de consulta.

No está diseñado en cualquier caso para proporcionar de modo detallado todos los aspectos teóricos ni
fundamentos de una tecnología o aplicación, sino específicamente aquellos especialmente relevantes
para el desarrollo del curso y los objetivos concretos de aprendizaje.

Cualquier consulta, aclaración o incidencia sobre DCProfessional training courses puede dirigirla a:

agustin.lopez@datacenterdynamics.com

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 5


Objetivos
Summit – Practicas de alto nivel
Al finalizar este módulo, será capaz de:

• Identificar las mejores prácticas de alto nivel en todas las áreas electromecánicas, TIC y de
monitorización de las instalaciones

• Conocer los fundamentos de las mejores prácticas de alto nivel en todas las áreas
electromecánicas, TIC y de monitorización de las instalaciones

• Reconocer las ventajas y posible adaptación en distintos entornos de los data center de las
mejores prácticas de alto nivel en todas las áreas electromecánicas, TIC y de monitorización de
las instalaciones

• Identificar las métricas y actividades de monitorización de alto nivel que permiten habilitar un
proceso común en el equipo y terceras partes

También dispone de la oportunidad de:

- Compartir sus conocimientos y opiniones

- Exponer casos reales y problemáticas en experiencias vividas o conocidas

- Escuchar atentamente las opiniones del resto de los asistentes

- Aportar comentarios de manera activa, respetando el enfoque del resto de participantes en la


aplicación de soluciones o puntos de vista concretos, incluso cuando sean opuestos a sus
propias valoraciones y entendimiento como base del enriquecimiento del grupo

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 6


Introducción

La aplicación de medidas avanzadas permite avanzar en el proceso de mejora hacia la aplicación


controlada de nuevas medidas de alto nivel eficiencia siempre sin poner en riesgo la disponibilidad de
los sistemas.

La aplicación generalizada de las medidas especificadas en el nivel CEEDA Silver permite por tanto
avanzar en las medidas correspondientes al nivel CEEDA Enterprise Gold que se desarrollan en esta
sesión.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 7


Evolución

Para poder avanzar y profundizar en las medidas relacionadas con la eficiencia energética ya se habrán
formalizado y realizado:

- Definición y designación de roles y funciones en la organización

- Aplicación de programas y actividades de formación a todos los responsables y empleados


relevantes con implicación de personal externo subcontratado

- Definición del plan de mejora de la eficiencia con un objetivos establecidos y revisados en base
a un ciclo de vida definido en la organización

- Consideración y aplicación de, al menos, las medidas indicadas en el esquema CEEDA Bronze y
Silver en el caso de data center corporativos

- Consideración y aplicación de medidas de eficiencia adicionales procedentes de otras guías o en


base a la propia consideración lógica de la organización y que complementen las medidas
básicas indicadas en el esquema CEEDA Bronze y Silver en el caso de data center corporativos
y según sea el caso particular de las instalaciones

A partir de aquí podemos introducirnos en la aplicación al detalle de las medidas del nivel superior como
CEEDA Gold.

*Figura 1*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 8


Actuales Protagonistas/Referencias

Entre las referencias principales en aspectos de aplicación de mejores prácticas y herramientas para la
industria del data center podemos destacar:

- CEEDA (Certifed Energy Efficient Data Center Award): primer esquema de certificación en la
industria del data center en la consideración de aplicación de las mejores prácticas reconocidas
a nivel internacional para los centros de datos. http://www.ceedacert.com/

- EU CoC (European Union Code of Conduct): creado en respuesta al aumento del consumo de
energía en centros de datos y la necesidad de reducir los impactos en aspectos ambientales,
económicos y energéticos relacionados. Cuenta con más de 120 participantes y 245 promotores
en la aplicación de las buenas prácticas reconocidas por la industria.
http://iet.jrc.ec.europa.eu/energyefficiency/ict-codes-conduct/data-centres-energy-efficiency

- COE (Center of Expertise for Energy Efficiency in Data Centers): Promovido por Lawrence
Berkeley National Laboratory (LBNL) y esponsorizado por U.S. Department of Energy (DOE)
dispone de herramientas y una master list con acciones recomendadas como mejores prácticas
a implementar en los data center. https://datacenters.lbl.gov/

- DOE (US Department of Energy) Better Buildings: con suite de herramientas para la adopción de
líneas base, formación, casos de estudio y programa de reconocimiento a los mayores
ahorradores de energía. http://energy.gov/eere/better-buildings

- EPA (United States Environmental Protection Agency): métricas, clasificación de equipamiento


de red, UPS y servidores y reconocimiento ENERGY STAR; Data center benchmarking.

https://www.energystar.gov/index.cfm?c=prod_development.server_efficiency

- FEMP (US Federal Energy Management Program): talleres, casos de estudio, políticas,
intercambio de información y asistencia técnica. http://energy.gov/eere/femp/energy-efficiency-
data-centers

- The Green Grid: métricas y herramientas de aplicación de modelos de madurez en eficiencia


energética para data centers. http://www.thegreengrid.org/

- Information technology industry council: Políticas de uso de la eficiencia energética en


dispositivos TIC. https://www.itic.org/

- ASHRAE: Estándares de referencia en aspectos ambientales relacionados con el equipamiento


TI y de telecomunicaciones para los data center. https://www.ashrae.org/

- AFCOM: Asociación de profesionales en la industria del data center con capítulos en EEUU,
APAC y Reino Unido. https://www.afcom.com/

- The Telecommunication Standarization Sector (ITU-T): Órgano permanente de la International


Telecommunication Union (ITU) se encarga de estudiar asuntos técnicos, operativos y tarifarios
relacionados con las recomendaciones y normalización de las telecomunicaciones a nivel
mundial.

https://www.itu.int/rec/T-REC-L/recommendation.asp?lang=en&parent=T-REC-L.1300

- SINGAPORE STANDARD SS 564 Series: Singapore Standard for green data centres.
https://www.singaporestandardseshop.sg/product/Package.aspx?ID=5dfe0c1e-eeca-4cd6-9a8d-
5fe9cdc2eac6

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook 9


Necesidades actuales

La aplicación de medidas de eficiencia energética a nivel fundamental tiene en consideración aspectos


básicos iniciales de auditoría e inventariado para iniciar una toma de decisiones en base a una
estrategia más o menos agresiva en función de los elementos en activo.

Adicionalmente, considera la aplicación de estrategias básicas pero esenciales en atención a un diseño


organizado para poder atender a una gestión del aire lógica y aprovechando los espacios libres que
haya dejado el posible equipamiento decomisionado de cara a habilitar la posibilidad de estrategias más
avanzadas.

La monitorización se aborda desde un punto inicial de mínimos y en la que se deberá progresar


atendiendo a la máxima “no se puede gestionar lo que no se puede medir” como principio para la
mejora continua, especialmente atendiendo a evitar riesgos en la operación de los servicios activos.

Otros de los apartados que tomados en consideración en este momento sería la aplicación de medidas
en dispositivos relacionados con la distribución y almacenamiento de la energía, una gestión ambiental
exhaustiva con la aplicación de cerramientos y segregación de activos en atención a sus necesidades
reales y rangos operativos que los caracterizan, especialmente en el caso de la tecnología dedicada a
las telecomunicaciones.

Este es el punto de partida necesario para abordar acciones de alto nivel relacionadas con:

- Aplicación de estrategias modulares

- Uso sustentable de la energía

- Ajustar el consumo en relación a la resiliencia de las instalaciones

- Desarrollo e implantación de técnicas de alto rendimiento en sistemas de enfriamiento y


aprovechamiento de situaciones favorables externas para reducir el funcionamiento de los
sistemas mecánicos

- Ampliación del uso de dispositivos de frecuencia variable a componentes de todo tipo como
bombas, compresores y todo tipo de ventiladores en relación a la adaptación de los sistemas
electromecánicos al funcionamiento de las cargas parciales variables

En situaciones de diseño y construcción de nuevas instalaciones, incluso en rehabilitaciones, hay


oportunidad de considerar las mejores prácticas de todos los niveles de manera amplia e integrada. En
el caso de instalaciones ya en operación es más habitual comenzar por el camino típico de adopción de
medidas progresiva comenzando por niveles Bronze para consolidar nuevos niveles en base a
situaciones positivas en coste/beneficio atendiendo a posibles ventanas de mantenimiento programadas
y al propio ciclo de renovación del equipamiento lo que supone, todo ello, una estrategia a medio -largo
plazo para las medidas establecidas en los niveles Silver y Gold.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


10
Soluciones

Para establecer un criterio concreto en los planes de mejora energética tomaremos el esquema de
CEEDA “Enterrprise” como referencia y con el objetivo de cubrir un escenario de un data center ya en
operación y, por otra parte, tomar la referencia de los sistemas TI y que en esquemas como CEEDA
Colocation o CEEDA Telco no estarían representados. La relación de las mejores prácticas indicadas a
continuación se corresponden con el nivel CEEDA Gold para este esquema de data center corporativo y
organizados por área funcional para mayor claridad (*Figura 2*).

Nombre de la mejor práctica Sección Área funcional

Rangos medioambientales de operación en equipamiento Gold 01 Políticas generales


mecánico y eléctrico

Modelos de facturación de los servicios Gold 02 Políticas generales

Gestión medioambiental Gold 03 Políticas generales

Gestión energética Gold 04 Políticas generales

Gestión de activos Gold 05 Políticas generales

Uso de energía sustentable Gold 06 Políticas generales

Crear una resiliencia adecuada para los requisitos empresariales Gold 07 Nivel de resiliencia y
aprovisionamiento

Aprovisionamiento Lean de energía y enfriamiento para un Gold 08 Nivel de resiliencia y


máximo de 18 meses en la capacidad del espacio técnico aprovisionamiento

Diseño para maximizar la eficiencia a carga parcial una vez Gold 09 Nivel de resiliencia y
aprovisionada (M&E) aprovisionamiento

Instalación escalable o modular y uso de equipos de refrigeración Gold 10 Cooling

Freecooling Gold 11 Cooling

Chillers de alto COP de rendimiento Gold 12 Cooling

Temperaturas operativas de los sistemas de enfriamiento Gold 13 Cooling

Operación eficiente con cargas parciales Gold 14 Cooling

Dispositivos de frecuencia variable en compresores, bombas y Gold 15 Cooling


ventiladores

Lecturas diarias automatizadas (uso de energía y mediciones Gold 16 Monitoring


ambientales, E&M, TI)

Informes escrito Gold 17 Monitoring

Consola de informes energéticos y ambientales Gold 18 Monitoring

Aquellos interesados de modo específico en las buenas prácticas establecidas para los tres niveles
Bronze, Silver, Gold y para el resto de esquemas (Colocation, Design&Operations, Telco) pueden
contactar con personal de DCProfessional y acceder sin coste adicional a las especificaciones
específicas correspondientes.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


11
Cooling

Instalación escalable o modular y uso de equipos de refrigeración

Debería instalarse una planta de refrigeración de forma modular permitiendo a los operadores
desconectar el equipamiento no requerido. Por tanto, las acciones de activación/desactivación
deberían formar parte de gestión del cambio y revisión de las cargas de refrigeración.

El diseño debería estar orientado para maximizar la eficiencia a carga parcial.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Manuales de operación y mantenimiento de los equipos in situ en relación a soluciones


escalables en enfriamiento.

 Sistemas automáticos que entran en baja potencia/baja refrigeración en función de la


carga de TI.

 Estrategias de uso que puedan ser más eficiente en la energía (p.ej. utilizando todas las
unidades de refrigeración a bajas velocidades de ventilación en vez de que mantener
equipos a medio/alto régimen de ventilación con otras unidades totalmente apagadas).

Beneficios

 Ahorros máximos en los costes energéticos de las actividades de soporte a los equipos
TI

*Figura 3*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


12
Freecooling

• Freecooling directo - aire; Se utiliza aire externo para refrigerar las instalaciones. Existen
sistemas de enfriamiento para atender a los grados de humedad y altas temperaturas externas
cuando sea preciso. El aire residual de salida se hace recircular y se mezcla con el aire de
admisión para evitar esfuerzos innecesarios relacionados con la humidificación/dehumectación.

• Freecooling indirecto - aire; El aire recircula dentro de las instalaciones atravesando en un punto
el intercambiador de calor con el aire exterior y eliminar el calor del aire ambiente del data
center.

• Freecoling directo - agua; El agua es enfriada por el aire ambiental exterior a través de un
serpentín de refrigeración. Esto puede lograrse mediante dry-coolers (adiabáticos) o mediante
asistencia de evaporadores con pulverización sobre los dry-coolers (adiabáticos).

• Freecoling indirecto - agua; El agua es enfriada por el aire ambiental exterior a través de un
intercambiador de calor que se utiliza entre la condensadora y los circuitos de agua refrigerada.
Esto puede lograrse mediante torres de refrigeración o dry-coolers (con o sin asistencia
evaporativa con pulverización sobre los dry-coolers o torres de refrigeración).

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Cada una de las prácticas anteriores debe estar en vigor y para abarcar> 80% de las
salas de datos.

 Ruedas de intercambio térmico (Kyoto)

 Informes de funcionamiento con la representación de las horas de funcionamiento y


parámetros asociados

Beneficios

 Aprovechamiento máximo de las condiciones ambientales y especificaciones de


operación del equipamiento para reducir al mínimo el funcionamiento de la planta de
enfriamiento

 Ahorros máximos en los costes energéticos de las actividades de soporte a los equipos
TI

*Figura 4*
*Figura 5*
*Figura 6*
*Figura 7*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


13
Chillers de alto COP de rendimiento

Cuando se requiera instalar una nueva planta de refrigeración se debería priorizar el Coeficiente
de Rendimiento (COP) en los sistemas en el proceso de adquisición y en relación al rango de
funcionamiento estimado.

Las consideraciones de esta práctica atienden a compresores mecánicos y bombas de calor,


además de cualquier dispositivo que utilice energía para elevar la temperatura del calor residual.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 La evidencia incluiría manuales de operación y mantenimiento del equipamiento que


especifiquen el C.O.P de los chillers.

Beneficios

 Menor esfuerzo y consumo de energía en el funcionamiento de componentes típicamente


activos de forma continuada.

Temperaturas operativas de los sistemas de enfriamiento

Evaluar la oportunidad de reducir la temperatura de condensación y aumentar la temperatura de


evaporación, reducir la delta T entre estas temperaturas implica menos trabajo necesario en el
ciclo de refrigeración, mejorando así la eficiencia.

Estas temperaturas dependen de las temperaturas de aire interno necesarias para los equipos TI
y de la calidad de la gestión del aire (véase Configuración de temperatura y humedad).

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Reuniones periódicas interna y/o con el fabricante y persona subcontratado de


mantenimiento si fuera oportuno para discutir y aclarar las actividades de revisión del
equipamiento y revisar o modificar según necesidad los modos de funcionamiento
establecidos.

Beneficios

 Evitar los costes adicionales de equipos realizando acciones ineficientes

 Control de las unidades de enfriamiento respecto a las necesidades en cada momento

 Coordinación entre las partes

 Detectar posibles desviaciones de forma prematura y evitar la pérdida de control

 Mantener la observancia de todo el personal interno y externo en las actividades diarias


sabiendo que existen revisiones periódicas de verificación

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


14
Operación eficiente con cargas parciales

Optimizar las instalaciones para un uso a carga parcial ya que es el estado que experimentarán
durante la mayor parte del tiempo de operación en lugar de carga máxima;

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Chiller secuenciales,

 Uso de torres de refrigeración con carga compartida para una zona de intercambio de
calor más grande

 Aprovechamiento máximo de las áreas de intercambio de calor

 Reducción de la energía consumida en ventiladores

 Reuniones periódicas interna y/o con el fabricante y persona subcontratado de


mantenimiento si fuera oportuno para discutir y aclarar las actividades de revisión del
equipamiento y revisar o modificar según necesidad los modos de funcionamiento
establecidos.

Beneficios

 Máxima adaptación en consideración de todos los sistemas y de los elementos que los
componen

*Figura 8*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


15
Dispositivos de frecuencia variable en compresores, bombas y ventiladores

El uso de dispositivos de frecuencia variable ayuda a reducir el consumo de energía de estos


componentes en condiciones de carga parcial y que es el modo de funcionamiento la mayor
parte del tiempo.

Se debería considerar en el nuevo equipamiento o en el proceso de rehabilitación, la aplicación


de motores de conmutación eléctrica (EC), significativamente más eficientes a nivel energético
que los motores de corriente alterna (AC) tradicionales en una amplia gama de velocidades.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Revisión de los componentes del sistema utilizados

 Manuales de operación y mantenimiento junto a la identificación de los modelos en los


equipos instalados y modo de operación.

 Reuniones periódicas interna y/o con el fabricante y persona subcontratado de


mantenimiento si fuera oportuno para discutir y aclarar las actividades de revisión del
equipamiento y revisar o modificar según necesidad los modos de funcionamiento
establecidos.

.Beneficios

La instalación de variadores de velocidad es fundamental para alcanzar la capacidad de


controlar adecuadamente la velocidad conforme a la demanda. El valor de instalar dispositivos
ajustados manualmente a una velocidad constante o con un control de la configuración reducido
es muy limitado.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


16
Métricas y monitorización
Lecturas diarias automatizadas (uso de energía y mediciones ambientales, E&M, TI)

Las lecturas diarias automatizadas permiten una gestión más efectiva del consumo energético.
Sustituyen a las lecturas manuales periódicas.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Manuales de operación y mantenimiento junto a la identificación de las versiones


instaladas, parametrización y modo de operación.

 Logs y/o consolas de DCIM

 Para un nivel "Gold" se espera que las lecturas sean periódicas y diarias

Beneficios

 Conocer con precisión los consumos a nivel de dispositivos individuales y de sistemas

 Discriminar aberraciones introducidas por elementos ajenos a la actividad del data center

 Conocer patrones de evolución y tendencias de comportamiento en los consumos de la


energía en detalle a lo largo del tiempo y afectación positiva o negativa en base a las
actuaciones de mejora que se vayan produciendo

 Cálculo preciso de las métricas establecidas

*Figura 9*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


17
Informes documentados

Informes periódicos documentados sobre el consumo energético y los rangos medioambientales.

Se debería incluir la determinación de la medida del DCiE o PUE y resto de métricas requeridas
durante el período establecido para los informes.

Este informe puede ser elaborado por un sistema automatizado.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Mantenimiento de un sistema de documentación con registros e informes que incluya


fechas de emisión y números de versión que incluya la trazabilidad de los cambios
aplicados.

 La medición del DCiE o PUE en consideración con las directrices de especificación de las
métricas con rangos de 0 a 3 en el caso del PUE según nivel de granularidad.

 La recolección de datos y cálculos en referencia con The Green Grid o ISO/IEC 30134

Beneficios

 Trazabilidad de la comunicación de los consumos a nivel interno e externo

 Disponer de información histórica que permita recuperar las decisiones y condicionantes


del pasado para poder aplicar acciones de mejora

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


18
Consola de informes energéticos y ambientales

Se debería disponer de una consola con información energética y medioambiental automatizada


que permita al personal eléctrico y mecánico hacer un seguimiento de la eficiencia y el consumo
energético de las instalaciones y mejora de las capacidades.

Se debería incluir la determinación de la medida del DCiE, PUE y resto de métricas requeridas
durante el período de informes.

Sustituye al sistema de informes escritos.

Ejemplo de implantación

Como evidencias típicas de actividad en esta área típicamente se obtienen, entre otras posibles:

 Manuales de operación y mantenimiento junto a la identificación de las versiones


instaladas, parametrización y modo de operación.

 Logs y/o consolas de DCIM

 Para un nivel "Gold" se espera que las lecturas sean periódicas y diarias

Beneficios

 Conocer con precisión los consumos a nivel de dispositivos individuales y de sistemas

 Discriminar aberraciones introducidas por elementos ajenos a la actividad del data center

 Conocer patrones de evolución y tendencias de comportamiento en los consumos de la


energía en detalle a lo largo del tiempo y afectación positiva o negativa en base a las
actuaciones de mejora que se vayan produciendo

 Acceso en tiempo real a información correlacionada de todos las actividades y por todo el
personal según sus funciones

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


19
Tendencias
Una vez resuelto el nivel Gold, aquellos involucrados en instalaciones de última generación o que lleven
más tiempo prestando atención a la eficiencia energética habrán echado en falta medidas adicionales
no indicadas hasta este momento.

Para una presentación organizada y constructiva por acumulación de las mejores prácticas y sus niveles
de interdependencia típicos hemos recurrido al marco CEEDA en sus niveles Bonze, Siver y Gold a
modo de columna vertebral de la eficiencia energética en base a prácticas actuales comúnmente
adoptadas.

Desde esta posición, se pueden adoptar medidas adicionales y más ambiciosas considerando que los
niveles de monitorización especificados en el nivel Gold ya permiten aplicar las medidas con cierta
expectativa de éxito, incluso observar posibles imprevistos en un momento inicial que permita una
marcha atrás controlada sin poner en riesgo la disponibilidad de los servicios.

En cualquier caso CEEDA es un marco dinámico que admite nuevas prácticas según se van
consolidando en data centers operativos pero que avanza a modo de recomendación aquellas prácticas
avanzadas que puedan satisfacer a los más exigentes y que, adicionalmente pueden ser comentadas
con los evaluadores en sus visitas periódicas bianuales en el caso de aquellas instalaciones
certificadas.

A continuación se indica a modo de resumen las prácticas avanzadas para el mismo esquema de
referencia utilizado en el presente curso, es decir, CEEDA Enterprise:

Análisis del ciclo de vida

Introducir un plan de análisis del ciclo de vida alineado con las directrices locales/regionales
(p.ej. EN 15978) y metodologías estandarizadas internacionales (p.ej. ISO 14040). El objetivo de
esta práctica es reducir la huella global de dióxido de carbono y mejorar la sustentabilidad más
que estar directamente relacionada con aspectos de mejora de la energía.

Tecnologías alternativas para la generación eléctrica

Se debería considerar el suministro de energía desde fuentes de energía alternativa y


sustentable como las pilas de combustible, generación eólica o fotovoltaica y generación de uso
y aplicación local como la biomasa o bio-fuel. De este modo se podría favorecer la reducción de
la huella ambiental del dióxido de carbono pero también son atractivas a nivel económico y
pueden servir de fuente alternativa fiable de suministro eléctrico. El objetivo de esta práctica es
reducir la huella global de dióxido de carbono y mejorar la sustentabilidad más que estar
directamente relacionada con aspectos de mejora de la energía.

Selección / desarrollo de software eficiente

Establecer entre los factores principales de adquisición el rendimiento del software y su consumo
energético. Aunque todavía se están desarrollando herramientas y métodos de previsión y
medición, pueden emplearse aproximaciones como la demanda de potencia (bajo carga) del
hardware necesario para alcanzar los objetivos de rendimiento y disponibilidad. Se trata de una
extensión de la planificación de capacidad y los procesos de comparación existentes.

Facilitar el uso de economizadores

Los diseños deberían de facilitar la aplicación de tanto freecooling como sea posible evitando
posibles consideraciones adversas del propio edificio físico, condiciones climáticas locales o
regulaciones que pudieran ser de aplicación. Se deberían facilitar el uso de economizadores o
sistemas similares que permitan un uso eficaz y económico de los sistemas en el caso de
restricciones del espacio físico.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


20
Refrigeración líquida directa en equipamiento TI

Uso de parcial o total de soluciones de refrigeración líquida en los equipos TI y que sustituyan al
aire como elemento transportador del calor. La eficiencia térmica en estos circuitos es mayor y
permite que la temperatura en el sistema de refrigeración líquida sea más elevada facilitando
adicionalmente el uso de técnicas de freecooling o de reutilización del calor residual.

ASHRAE dispone de guías para el uso de refrigeración líquida en data centers.

*Figura 10*
Reutilización del calor residual

Con frecuencia es posible suministrar directamente el calor residual generado en el data center y
de baja intensidad a espacios industriales u otros destinos tales como espacios de oficinas.
Aunque no resulta en un beneficio propio, sí puede mejorar el consumo de energía en otros
lugares y reducir emisiones al medioambiente.

*Figura 11*
Reutilización del calor residual asistida por bomba de agua

Si no es posible reutilizar directamente el calor residual procedente del data center porque su
temperatura es demasiado baja puede que, de todas formas, siga resultando conveniente en
términos económicos utilizar bombas de calor adicionales para subir esa temperatura hasta un
nivel de uso apropiado que pueda suministrarse a los sistemas de calefacción de las oficinas,
espacios públicos o de otro tipo.

Métricas e informes sobre la energía reutilizada

La oportunidad de reutilizar el calor residual procedente de los data centers tiene referencias en
métricas como Energy Reuse Factor (ERF) y Enery Reuse Effectiveness (ERE) por parte de The
Green Grid y que sirven para informar del aprovechamiento de este calor residual.

Otro tipo de métricas como GEC (Green Energy Coefficient) están en fase de desarrollo y en
espera de una aplicación más extensiva, especialmente en relación a los trabajos desarrollados
mediante la serie de estándares ISO/IEC 30134 y que pueden cambiar las nomenclaturas.

Emplazamientos cercanos a fuentes de freecooling

Ubicar un data center en la proximidades de una fuente potencial de enfriamiento como ríos,
lagos, entre otros es interesante aunque hay que atender a los requisitos regulatorios
medioambientales a nivel local.

*Figura 12*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


21
Emplazamientos compartidos con fuentes de generación

Ubicar el data center próximo a una planta de generación de energía puede reducir las pérdidas
típicas por transmisión de la energía además de proporcionar la oportunidad de operar con
chillers de adsorción aprovechando el calor residual como materia de generación.

Consola de informes medioambiental, E&M y TI integrada

Una consola integrada permite una gestión integrada del uso de la energía y las comparaciones
de las cargas TI con la energía utilizada.

Uso de los Servidores / componentes de red / almacenamiento

La aportación del nivel de uso de cada componente (procesador capacidad de red, capacidad y
rendimiento en almacenamiento) para todo el conjunto o para el grupo de componentes TI
involucrado en un servicio/ubicación particulares.

*Figura 13*

Algunas de las prácticas anteriores pueden resultar de difícil aplicación según sea el caso particular de
cada operador de data center, en cualquier caso representan actividades en las que se está trabajando
actualmente por partes relevantes de la industria de los data center y que son de interés aunque sea a
un nivel de conocimiento y discusión que permita evolucionar su madurez hacia aplicación prácticas.

La aparición de nuevas métricas como el Indicador de Rendimiento (PI) presentada por The Green
Grid que buscan nuevas formas de evaluar y visualizar el rendimiento de la refrigeración en los data
center abordando la disponibilidad, la capacidad y la sostenibilidad al mismo tiempo, ayudan a mantener
las operaciones TI en relación a térmicas seguras y adecuadas, sin perder de vista de la eficiencia.

Este anuncio se une a las métricas ya existentes que no hacen en cualquier caso sino reforzar las
necesidades en la industria de profundizar en las mediciones de los consumos más allá del PUE
aplicando métricas en todo el espectro de operaciones de modo que la imputación de costes asociada a
la prestación del servicio puede ser visualizada el modo más detallado posible de cara a la toma de
decisiones a nivel de negocio.

*Figura 14*

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


22
Referencias / Saber más

- CEEDA website: http://www.ceedacert.lat/

- EU Code of Conduct on Data Center Energy Efficiency Best Practice Guidelines:


http://iet.jrc.ec.europa.eu/energyefficiency/sites/energyefficiency/files/files/COC_DC/2016/2016_b
est_practice_guidelines_v7.1.2.pdf

- Data Center Master List of Energy Efficiency Actions:

https://datacenters.lbl.gov/resources/data-center-master-list-energy

- ITU-T L.1300 Best Practices for Green Data Centres

https://www.itu.int/rec/T-REC-L.1300-201406-I/en

- ITU-T L.1310 Energy Efficiency Metrics and Measurement Methods for Telecommunication
Equipment

https://www.itu.int/rec/T-REC-L.1310-201211-S

- Mission Critical Facilities, Data Centers, Technology Spaces and Electronic Equipment ASHRAE
Technical Committee 9.9: https://tc0909.ashraetcs.org/

- ASHRAE TC9.9 Proposed Clarification to ASHRAE Thermal Guidelines

https://tc0909.ashraetcs.org/documents/Clarification%20to%20ASHRAE%20Thermal%20Guideli
nes.pdf

- ASHRAE TC9.9 Data Center Networking Equipment – Issues and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE%20Networking%20Thermal%20Guidelines.pdf

- ASHRAE TC9.9 Data Center Power Equipment Thermal Guidelines and Best Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_TC0909_Power_White_Paper_22_June_2016
_REVISED.pdf

- ASHRAE TC9.9 IT Equipment Thermal Management and Controls

https://tc0909.ashraetcs.org/documents/ASHRAE%202012%20IT%20Equipment%20Thermal%2
0Management%20and%20Controls_V1.0.pdf

- ASHRAE TC9.9 Data Center Storage Equipment – Thermal Guidelines, Issues, and Best
Practices

https://tc0909.ashraetcs.org/documents/ASHRAE_Storage_White_Paper_2015.pdf

- The Green Grid: Recommendations for Measuring and Reporting Overall Data Center Efficiency
Version 2 – Measuring PUE for Data Centers

http://www.thegreengrid.org/~/media/WhitePapers/Data%20Center%20Metrics%20Task%20Forc
e%20Recommendations%20V2%205-17-2011.ashx?lang=en

- The Performance Indicator: Assessing and Visualizing Data Center Cooling Performance

http://www.thegreengrid.org/events/Performance_Indicator_Webcast_June_2016

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


23
ANEXO FIGURAS – Figura 1

Áreas de actuación – Marco CEEDA

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


24
ANEXO FIGURAS – Figura 2

CEEDA – Alto nível “Gold”

http://www.ceedacert.lat/cpds-certificados

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


25
ANEXO FIGURAS – Figura 3

Instalación escalable o modular y uso de equipos de refrigeración

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


26
ANEXO FIGURAS – Figura 4

Freecooling por aire - Directo

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


27
ANEXO FIGURAS – Figura 5

Freecooling indirecto por aire

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


28
ANEXO FIGURAS – Figura 6

Freecooling evaporativo

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


29
ANEXO FIGURAS – Figura 7

Freecooling con agua

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


30
ANEXO FIGURAS – Figura 8

Freecooling – Tendencias

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


31
ANEXO FIGURAS – Figura 9

Operación eficiente con cargas parciales

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


32
ANEXO FIGURAS – Figura 10

Monitorización

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


33
ANEXO FIGURAS – Figura 11

Refrigeración líquida directa en equipamiento TI

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


34
ANEXO FIGURAS – Figura 12

Reutilización del calor residual

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


35
ANEXO FIGURAS – Figura 13

Emplazamientos cercanos a fuentes de freecooling

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


36
ANEXO FIGURAS – Figura 14

Uso de los Servidores / componentes de red / almacenamiento

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


37
Caso Práctico 1: Aplicación de herramientas de GAP análisis

Caso Práctico 1:
Aplicación de herramientas de GAP análisis

Le solicitan desde una organización la realización de una auditoría que les indique el estado
actual de sus instalaciones en relación a:

- Estado de eficiencia en base a los datos actuales de las instalaciones

- Posibles mejoras en base a las mejores prácticas que podrían aplicar

- El beneficio de consumos y económico potencial que podrían lograr mediante la


aplicación de las posibles mejoras

Los datos concernientes a las instalaciones serán aportadas por el instructor así como la
herramienta a utilizar para poder obtener los resultados requeridos.

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


38
Caso Práctico 2: Informes de auditoría en eficiencia energética

Caso Práctico 2:
Informes de auditoría en eficiencia energética

La confección de informes se suele presentar en relación a unos modelos que cada


organización personaliza y adapta.

Revise el modelo de informe que entrega el instructor y compare los contenidos con los que
habitualmente realiza o recibe en su actividad diaria.

Ponga en común con el resto de asistentes al curso en consideración a las siguientes


preguntas:

- ¿El informe es similar al que dispone su organización?

- ¿Existe información relevante que echa en falta y que debería incorporarse?

- ¿Cómo obtiene actualmente los datos en su caso particular para este tipo de informes
(o para informar desde su área concreta de actividad)?

Issue 1.0 EEBP – Sesión Técnica 5 - Training Workbook


39