Power Supplies Battery 18 Ah/Security grade 2
Instruction manual PSV 1215-18
DESCRIPTION MAIN FEATURES
PSV 1215-18 is an up-to date power supply unit with bat- • EN 50131-6:2008 compliant, security grade 2
tery backup compliant with EN regulations for social and • Type A, with backup battery
security alarm systems. Unit provides all features required • Nominal output voltage: 13.8 V DC
by EN 50131-6:2008, security grade 2 and many others • Total current capacity: 1.5 A
available in grade 3 only. • ViP (Voltage-in-Parallel) feature increasing reliability
Distinctive and unique feature of PSV 1215-18 is invented and capacity of power supply systems – any number of
by Alarmtech ViP mode – Voltage-in-Parallel. Power sup- power supplies with ViP feature can be connected (+)
ply units with ViP feature can be connected in parallel both and (-) in parallel to same bus without need for addi-
(+) and (-) on one common power bus without a need of tional synchronization
additional synchronization. Connected units will share • Programmed to work with 18 Ah batteries
load on a bus. ViP feature can be used to build distributed • Short circuit and overload protection
and redundant power systems. It can be also used to com- • Lack of mains detection
pensate voltage drops on a bus by placing power supply • Low output voltage detection
units in distant bus sections. • Broken fuse detection and identification
Power conversion is based on high frequency SMPS regu- • Detection of power unit failure
lator providing high conversion efficiency. Low losses in- • Over-voltage protection
side unit preserve batteries from overheating shortening • Detection of different battery faults
battery life time. Computerized battery recharging circuit • Deep discharge protection of battery
works in constant current – limited voltage mode – the • Remote and local battery testing
most advanced and the best mode to provide the longest • Tamper security provided (case opening detection)
possible battery life time. • Built-in real time diagnostic system with fault visualisa-
Power unit is equipped with built-in diagnostic system de- tion and localisation by LED on PCB
tecting and signalling mains failure, different battery fail- APPLICATIONS
ures including end-of-life warning, output faults like low
voltage or broken fuse. • Intruder alarm systems
• Social alarm systems
• Access control systems
BLOCK N PE L
DIAGRAM
230 VAC
EMC filter
Fuse
Isolation
transformer
Rectifier
Over
ViP load sharing
Energy storage DC/DC SMPS ViP converter Voltage
circuitry
Protection
KICK -
START
Alar mt ech
Output fuse
F 2= 5A
Battery fuse
Mains fuse 3.15 A quick
0.2 A slow 17 ... 19VAC EPS APS OU T SAB SAB -RBD* -BAT+ -12 V+
- +
PSV 1215-18 power supply installation and start-up pro- • The socket outlet delivering 230 VAC shall be installed
cedure: near the power supply unit and shall be easily accessi-
• Fix unit in destination place using 4 fixing holes ble
• Place sealed lead acid battery 12 V/18 Ah in battery • Make sure that cable delivering 230 VAC to power sup-
chamber ply is disconnected from mains
• Make connection between left battery (-) and battery • Connect 230 VAC cable to 230 VAC input in power sup-
connector using black battery cable ply unit – make sure that PE cable is connected to PE
• Make connection between right battery (+) and bat- input
tery connector using red battery cable • Switch on mains delivering energy to power supply -
• Make appropriate connections between power output PSV 1215-18 unit will start automatically delivering
and power receivers power to the load and monitoring state of PS
• Make required connections between signalling outputs
of PSV 1215-18 unit and cooperating units (outputs
EPS, APS, OUT, SAB, input –RBT*)
Power Supply 24 VDC Power Supply 24 VDC Power Supply 24 VDC Power Supply 24 VDC
OUTPUT SPECIFICATION
Type of Power Supply acc. to EN 50131-6:2008: type A
Security grade acc. to EN 50131-6:2008: grade 2
Nominal output voltage: 13.8 V
Minimal output voltage in battery mode: 10.0 V (in APS mode)
Total maximal current (load and battery recharging): 1.5 A
Total rated output current: 1.2 A
Quiescent current internally consumed in PS: 0.03 A
Maximal output ripple RMS voltage: <5% of nominal output voltage
Output fuse: 2 A, 5x20 mm type F
BATTERY
Battery type: 12 V, 18 Ah battery
Battery recharging method: constant current – limited voltage
Maximal battery recharging current: 0.25 A
Time to recharge 18 Ah batteries to 80%: 58 h max (< 72 h)
Battery voltage triggering APS fault: 11 V
Battery voltage triggering DDP circuit: 10 V
Output voltage triggering OUTPUT fault: 9V
Battery fuse: 3.15 A, 5x20 mm type F
MONITORING OUTPUTS
EPS – loss of mains APS – battery pack low voltage, battery failure
OUT – output voltage low, power unit failure SAB – case tampering
Electrical characteristics of monitoring outputs: - Potential free semiconductor relay
for EPS, APS, OUT fault signalling
- Micro-switch for case tampering signaling
Logical characteristics of monitoring signals: Closed state – monitored condition not present
Open state – monitored condition present
ENVIRONMENT
Environmental Class acc. to EN 50130-5:1998: Class I
Operating temperature and humidity range: +5º C…+40º C, RH to 90%, no condensation
WEIGHT AND DIMENSIONS
Weight without battery: approx. 1.5 kg
Weight with battery (18Ah): approx. 7 kg
Dimensions: 230 x 300 x 100 mm (W x H x D)
Compliance: