Manual
GenSets
967-0121
2-91
Printed in U.S.A.
Table of Contents
SECTION TITLE PAGE
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Front Cover
1 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How to Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3 CONTROL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Voltage Reconnection with Optional Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Generator Set Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Fuel Tank and Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Injection Pump Adapter Assembly (DJE only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Oil Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Balancing Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Switchboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Reconnectible Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Optional Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Remote Start-Stop Switch (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
5 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Pre-Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Pre-Heating and Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Automatic Starting and Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Applying Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Exhaust System Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Break-In Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Exercising Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Engine Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
High/Low Operating Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Dust and Dirt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Out-of-Service Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Returning the Set to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
6 ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Centrifugal Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Governor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Charge Rate Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Valve Clearance Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
i
SECTION TITLE PAGE
7 GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Periodic Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Fuel Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Governor Linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Crankcase Breather Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Crankcase Breather . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Cooling System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Fuel Pump Sediment Bowl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Air Cleaners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Contractor Model Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Optional Oil Bath Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Oil Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Oil Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
8 PERIODIC MAINTENANCE SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
ii
Safety Precautions
Before operating the generator set, read the Operator’s • Do not wear loose clothing or jewelry in the vicinity of mov-
Manual and become familiar with it and the equipment. Safe ing parts, or while working on electrical equipment. Loose
and efficient operation can be achieved only if the equip- clothing and jewelry can become caught in moving parts.
ment is properly operated and maintained. Many accidents Jewelry can short out electrical contacts and cause shock
are caused by failure to follow fundamental rules and precau- or burning.
tions.
• If adjustment must be made while the unit is running, use
The following symbols, found throughout this manual, alert you extreme caution around hot manifolds, moving parts, etc.
to potentially dangerous conditions to the operator, service per-
sonnel, or the equipment. ELECTRICAL SHOCK CAN CAUSE SEVERE PER-
SONAL INJURY OR DEATH
This symbol warns of immediate haz- • Remove electric power before removing protective shields
ards which will result in severe personal injury or or touching electrical equipment. Use rubber insulative
death. mats placed on dry wood platforms over floors that are
metal or concrete when around electrical equipment. Do
This symbol refers to a hazard or unsafe not wear damp clothing (particularly wet shoes) or allow
practice which can result in severe personal injury or skin surface to be damp when handling electrical equip-
death. ment.
• Use extreme caution when working on electrical compo-
This symbol refers to a hazard or unsafe nents. High voltages can cause injury or death. DO NOT
practice which can result in personal injury or prod- tamper with interlocks.
uct or property damage. • Follow all applicable state and local electrical codes. Have
all electrical installations performed by a qualified licensed
FUEL AND FUMES ARE FLAMMABLE. Fire and explosion electrician. Tag open switches to avoid accidental closure.
can result from improper practices.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO
• DO NOT fill fuel tanks while engine is running, unless ANY BUILDING ELECTRICAL SYSTEM. Hazardous
tanks are outside the engine compartment. Fuel contact voltages can flow from the generator set into the utility line.
with hot engine or exhaust is a potential fire hazard. This creates a potential for electrocution or property dam-
age. Connect only through an approved isolation switch or
• DO NOT permit any flame, cigarette, pilot light, spark, or an approved paralleling device.
other ignition source near the generator set or fuel tank.
GENERAL SAFETY PRECAUTIONS
• Fuel lines must be adequately secured and free of leaks.
Fuel connection at the engine should be made with an ap- • Coolants under pressure have a higher boiling point than
proved flexible line. Do not use copper piping on flexible water. DO NOT open a radiator or heat exchanger pres-
lines as copper will become brittle if continuously vibrated sure cap while the engine is running. Allow the generator
or repeatedly bent. set to cool and bleed the system pressure first.
• Be sure all fuel supplies have a positive shutoff valve. • Benzene and lead, found in some gasoline, have been
• Do not smoke while servicing lead acid batteries. Lead identified by some state and federal agencies as causing
cancer or reproductive toxicity. When checking, draining
acid batteries emit a highly explosive hydrogen gas that
or adding gasoline, take care not to ingest, breathe the
can be ignited by electrical arcing or by smoking.
fumes, or contact gasoline.
EXHAUST GASES ARE DEADLY
• Used engine oils have been identified by some state or
• Provide an adequate exhaust system to properly expel federal agencies as causing cancer or reproductive toxic-
discharged gases. Visually and audibly inspect the ex- ity. When checking or changing engine oil, take care not to
haust daily for leaks per the maintenance schedule. En- ingest, breathe the fumes, or contact used oil.
sure that exhaust manifolds are secured and not warped.
Do not use exhaust gases to heat a compartment.
• Provide appropriate fire extinguishers and install them in
convenient locations. Consult the local fire department for
• Be sure the unit is well ventilated. the correct type of extinguisher to use. Do not use foam on
electrical fires. Use extinguishers rated ABC by NFPA.
MOVING PARTS CAN CAUSE SEVERE PERSONAL
• Make sure that rags are not left on or near the engine.
INJURY OR DEATH
• Remove all unnecessary grease and oil from the unit. Ac-
• Keep your hands, clothing, and jewelry away from moving cumulated grease and oil can cause overheating and en-
parts. gine damage which present a potential fire hazard.
• Before starting work on the generator set, disconnect • Keep the generator set and the surrounding area clean
starting batteries, negative (-) cable first. This will prevent and free from obstructions. Remove any debris from the
accidental starting. set and keep the floor clean and dry.
• Make sure that fasteners on the generator set are secure. • Do not work on this equipment when mentally or physically
Tighten supports and clamps, keep guards in position over fatigued, or after consuming any alcohol or drug that
fans, drive belts, etc. makes the operation of equipment unsafe.
LS-9
Section 1. General Information
This manual contains information on operating, main- 1-800-888-ONAN (this automated service uses touch-
taining, and adjusting the Onan® DJB and DJE genera- tone phones only). By entering your area code and the
tor sets. Study and follow these instructions carefully. A first three digits of your local telephone number, you will
well-planned service and maintenance program will help receive the name and telephone number of the distribu-
provide longer unit life and better performance. tor nearest you.
1-1
Section 2. Specifications
DJB GENERATOR SETS: 4.5 (50 HZ) AND 6.0 (60 HZ)
DIMENSIONS
Height . . . . 28.94 inches (735 mm) Length . . . 36.69 inches (932 mm)
Width . . . . . 21.75 inches (552 mm) Weight . . . 485 lbs (220 kg)
INSTALLATION REQUIREMENTS
Fuel pump inlet thread size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7/16-24 NPTF
Fuel pump maximum lift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 ft (1.83 m)
Exhaust outlet (pipe tapped) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 inch
Maximum exhaust back pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 inches (686 mm) H2O (6.7 kPa)
Ventilation required . . (60 Hz) . . Engine (Vacu-Flo cooling) . . . . . . . . 560 cfm (15.9 m3/min)
(60 Hz) . . Generator . . . . . . . . . . . . . . . . . . . . . . 160 cfm (4.53 m3/min)
(1800 rpm) Combustion . . . . . . . . . . . . . . . . . . . . 25 cfm (0.7 m3/min)
(50 Hz) . . Engine (Vacu-Flo cooling) . . . . . . . . 467 cfm (13.2 m3/min)
(50 Hz) . . Generator . . . . . . . . . . . . . . . . . . . . . . 133 cfm (3.8 m3/min)
(1500 rpm) Combustion . . . . . . . . . . . . . . . . . . . . 21 cfm (0.6 m3/min)
Battery requirements:
Temperature Quantity Volts BCI Group Cranking Performance Amp.Hr.Capacity
Range Size at 0° F (-17° C) (20 hour rate)
32° F (0° C) and warmer 2 6 1 450 amps 105
0° F (-17° C) and warmer 2 6 2 560 amps 135
-25° F (-32° C) and warmer 2 6 5D 800 amps 190
GENERATOR
Rating (AC output): . . . 4.5 DJB (50 hz) . . . . . . 4.5 kW 6.0 DJB (60 hz) . . . . . . . 6.0 kW
ENGINE
Number of cylinders (vertical in-line) . . . . . . . . . . 2 Displacement . . . . . . . . 60 in3 (984 cc)
Cylinder bore . . . . . . . . 3.25 in. (82.55 mm) Piston stroke . . . . . . . . . 3.625 in. (92.1 mm)
RPM . . . . . . . . . . . . . . . 60 Hz: 1800 rpm 50 Hz: 1500 rpm
Oil capacity . . . . . . . . . 3 U.S. quarts plus 1/2 quart for filter
Fuel consumption
(60 Hz set) (50 Hz set)
Full load . . . . . . . . . . . . 0.64 gph (2.42 L/h) Full load . . 0.53 gph (2.0 L/h)
3/4 load . . . . . . . . . . . . . 0.53 gph (2.01 L/h) 3/4 load . . 0.45 gph (1.70 L/h)
1/2 load . . . . . . . . . . . . . 0.43 gph (1.63 L/h) 1/2 load . . 0.38 gph (1.44 L/h)
1/4 load . . . . . . . . . . . . . 0.33 gph (1.25 L/h) 1/4 load . . 0.27 gph (1.02 L/h)
ADJUSTMENT SPECIFICATIONS
Cylinder head bolt torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 - 46 ft-lb (60 - 62 n•m)
Glow plug torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 15 ft-lb (14 - 20 n•m)
Valve clearances . . . . . Intake: 0.009 in. (0.229 mm) . . . . . . Exhaust: 0.007 in. (0.178 mm)
Centrifugal switch breaker point gap . . . . . . . . . . . . . . . . . . . . . 0.020 inch (0.508 mm)
2-1
DJE GENERATOR SETS: 4.5 (50 HZ) AND 6.0 (60 HZ)
DIMENSIONS
Height . . . . 26.12 inches (663 mm) Length . . . 33.44 inches (849 mm)
Width . . . . . 18.38 inches (467 mm) Weight . . . 485 lbs (220 kg)
INSTALLATION REQUIREMENTS
Fuel pump inlet thread size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7/16-24 NPTF
Fuel pump maximum lift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 ft (1.83 m)
Exhaust outlet (pipe tapped) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 inch
Maximum exhaust back pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 inches (686 mm) H2O (6.7 kPa)
Ventilation required . . (60 Hz) . . Engine (pressure cooling) . . . . . . . . 630 cfm (17.8 m3/min)
(60 Hz) . . Generator . . . . . . . . . . . . . . . . . . . . . . 160 cfm (4.53 m3/min)
(1800 rpm) Combustion . . . . . . . . . . . . . . . . . . . . 29 cfm (0.8 m3/min)
(50 Hz) . . Engine (pressure cooling) . . . . . . . . 525 cfm (14.9 m3/min)
(50 Hz) . . Generator . . . . . . . . . . . . . . . . . . . . . . 133 cfm (3.8 m3/min)
(1500 rpm) Combustion . . . . . . . . . . . . . . . . . . . . 25 cfm (0.7 m3/min)
Battery requirements:
Temperature Quantity Volts BCI Group Cranking Performance Amp.Hr.Capacity
Range Size at 0° F (-17° C) (20 hour rate)
32° F (0° C) and warmer 2 6 1 450 amps 105
0° F (-17° C) and warmer 2 6 2 560 amps 135
-25° F (-32° C) and warmer 2 6 5D 800 amps 190
GENERATOR
Rating (AC output): . . . 4.5 DJE (50 hz) . . . . . . 4.5 kW 6.0 DJE (60 hz) . . . . . . . 6.0 kW
ENGINE
Number of cylinders (vertical in-line) . . . . . . . . . . 2 Displacement . . . . . . . . 70 in3 (1147 cc)
Cylinder bore . . . . . . . . 3.5 in. (89 mm) Piston stroke . . . . . . . . . 3.625 in. (92.1 mm)
RPM . . . . . . . . . . . . . . . 60 Hz: 1800 rpm 50 Hz: 1500 rpm
Oil capacity . . . . . . . . . 3 U.S. quarts plus 1/2 quart for filter
Fuel consumption
(60 Hz set) (50 Hz set)
Full load . . . . . . . . . . . . 0.64 gph (2.42 L/h) Full load . . 0.52 gph (1.97 L/h)
3/4 load . . . . . . . . . . . . . 0.53 gph (2.01 L/h) 3/4 load . . 0.42 gph (1.59 L/h)
1/2 load . . . . . . . . . . . . . 0.43 gph (1.63 L/h) 1/2 load . . 0.35 gph (1.32 L/h)
1/4 load . . . . . . . . . . . . . 0.33 gph (1.25 L/h) 1/4 load . . 0.33 gph (1.25 L/h)
ADJUSTMENT SPECIFICATIONS
Cylinder head bolt torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 - 40 ft-lb (50 - 54 n•m)
Glow plug torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 15 ft-lb (14 - 20 n•m)
Valve clearances . . . . . Intake: 0.010 in. (0.254 mm) . . . . . . Exhaust: 0.007 in. (0.178 mm)
Centrifugal switch breaker point gap . . . . . . . . . . . . . . . . . . . . . 0.020 inch (0.508 mm)
2-2
Section 3. Control Description
CONTROL PANEL COMPONENTS • Exciter Field Circuit Breaker: Protects the exciter
and the alternator if the voltage regulator malfunc-
NOTE: Controls and instruments on the genset vary according to tions.
customer requirement.
• Preheat Switch: Activates the manifold heater and
Standard Features glow plugs for cold engine starting.
• Start-Stop Switch: Starts and stops the genset lo- • Oil Pressure Gauge: Monitors engine lubricating
cally. oil pressure.
• Battery Charge Rate DC Ammeter: Monitors the • Fuse: Protects DC circuit against reversed battery
battery charging current. terminals.
START-STOP KNOCKOUT PLUGS FOR FIELD
SWITCH OPTIONAL CONTROLS BREAKER
PREHEAT
SWITCH
DC FUSE
AMMETER
ES1972C
• AC Voltmeter: Monitors output voltage. • Warning Lights: Red warning lights indicate the
following conditions:
3-1
• Cranking Limiter: Thermally activated device lim- (HATCO) to shut down the engine if engine tem-
its cranking time to 45 - 90 seconds, depending on perature rises above 375° F ± 15° F (190.5° C).
ambient temperature. At the end of the cranking pe-
riod, a red pushbutton pops out, which cannot be re- • AC Control With Meters: The AC control panel has
set until one minute has elapsed. a voltmeter, ammeter, frequency meter, phase se-
lector switch, output voltage adjusting rheostat and
Other Optional Control Features resettable exciter field circuit breaker.
• Low Oil Pressure Shutdown: The engine is • AC Control - Housed Sets: The AC control panel
equipped with a low oil pressure cutoff switch has a voltmeter, an ammeter for each line, a circuit
(LOPCO) to shut down the engine if oil pressure breaker for each line, a frequency meter and a run-
drops below 14 psi (97 kPa) ± 2 psi. ning time meter.
CONTROL
PANEL
TRANSFER
PUMP
OIL
VACU-FLO
FILL
AIR SCROLL
PRIMARY
FUEL FILTER
SECONDARY
FUEL FILTER
INJECTION
PUMP
O8L
FILTER
OIL
G1246
DRAIN
3-2
FIELD AIR CLEANER
PREHEAT BREAKER
SWITCH
CONTROL GOVERNOR SENSITIVITY
PANEL ADJUSTMENTS
START-STOP
SWITCH
FUSE
OIL FILL
TUBE
COOLING
AIR IN
AC
GENERATOR
OIL
PRESSURE
GAUGE
OIL
OIL FILTER
FUEL
DRAIN
FILTERS
G1246-1
FUSE START
SWITCH
RUN-STOP
SWITCH
CRANKING LIMITER
RESET BUTTON
PREHEAT
SWITCH
240 VAC 20 AMP
TWISTLOCK RECEPTACLE
(2)
20 AMP LINE
BREAKERS
3-3
Section 4. Installation
INSTALLATION REQUIREMENTS The left side of the set, where generator air is discharged,
requires 3 inches (76 mm) clearance from the wall, so the
Generator set installations must conform to local building set can rock on its mounts. There should be at least 24
codes, fire ordinances, and other local, state and federal inches (610 mm) clearance around all other sides for
regulations. service access.
Installation requirements include:
1/16" LOCK
(1.59 mm) WASHER
FLAT
WASHER
SNUBBER
GENERATOR
OR OIL BASE
MOUNTING
FOOT
CUSHION
MOUNTING SPACER
BUSHING
FLAT
WASHER
CS1370-1
MOUNTING 11-1/2"
SUPPORTS FOR FRONT
VACU-FLO UNIT (292 MM)
13.00 IN.
(330 CM.)
(4) 7/16 INCH
7.88 IN. (11 MM BOLTS)
4.25 IN. (220 4.25 IN.
(108 CM.) (108
CM.) CM.)
M1198
4-2
doesn’t exceed 120° F (49° C) when running at full rated Because an exhaust system is subjected to detrimental
load. conditions such as extreme heat, infrequent operation,
and light operating loads, inspect the exhaust system fre-
Onan thermostatically controlled shutters can be used to
quently to be sure that it remains fume-tight.
aid warm-up after starting and keep cold air out during
shutdown. When the discharged air reaches 120° F (49°
C), shutters begin to open; at 140° F (62° C), the shutters Inhalation of exhaust gas presents the
completely open. hazard of severe personal injury or death. Exhaust
gas can easily leak from a faulty manifold. Do not
Generator set overheating can result in use exhaust manifold heat to warm a room or com-
engine damage. To avoid this, never operate the partment.
generator set with any of the cooling system compo-
nents removed. An approved thimble must be used (Figure 4-5) to pass
exhaust pipes through walls or partitions. Build this thim-
EXHAUST ble according to code (see National Fire Protection Asso-
Pipe exhaust gases outside the enclosure. The exhaust ciation bulletin, Volume 4, section 211 on “Standards for
outlet fits a 1-1/2 inch pipe. Locate the exhaust outlet as Chimneys, Fireplaces, and Vents”).
far as possible from the air inlet, to keep gases from reen-
tering the enclosure. Use seamless flexible tubing to As the exhaust pipe length and number of bends in-
connect the engine exhaust to a rigid pipe extension, if creases, a larger pipe is required, to reduce excessive
used, to prevent transmission of vibration. exhaust restriction and back pressure.
4-3
METER AUTOMATIC
TRANSFER
SWITCH
INCOMING TO LOAD
SERVICE
THIMBLE
MUFFLER
MAIN FUSE
AND SWITCH
LARGE RADIUS
ELBOW DUCT TO REMOVE
HEATED ENGINE AIR
FLEXIBLE
SECTION
CONDENSATION
TRAP
AIR IN
CANVAS
FLEXIBLE SECTION
FUEL LINE
CONCRETE
BASE
BATTERIES
FUEL
RETURN
LINE
TO FUEL TANK
G1100
4-4
LOUVERS
NEAR CEILING
INCOMING
SERVICE
THIMBLE MUFFLER
TO LOAD
MAIN FUSE
AND SWITCH
FLEXIBLE
SECTION
DUCT TO REMOVE
HEATED ENGINE AIR
CANVAS
SECTION AUTOMATIC
LOUVERS
FLEXIBLE
FUEL LINE
CONCRETE
BASE
BATTERIES
FUEL
RETURN
LINE TO FUEL TANK
M1880C
4-5
SINGLE THIMBLE DIAMETER
12 INCHES (305 mm)
LARGER THAN EXHAUST LINE
HOLES IN END
(228.60 mm)
INNER SLEEVE
9" 9"
DRAIN CONDENSATION
TRAP PERIODICALLY
EXS1175
FUEL TANK AND LINES Use an approved flexible fuel line next to the engine. Die-
sel engines require a fuel supply line and a separate fuel
Fuel tanks risk explosion and fire, return line. Install the fuel supply line from the supply
which can cause severe personal injury or death. tank to the inverted flare male elbow mounted in the inlet
Because fuel leaks create fire hazards, always use of the fuel pump. The pump is threaded 7/16-24 NPTF
flexible tubing between the engine and the fuel sup- (American Standard Internal Tapered Pipe Thread).
ply, to avoid leaks due to vibration and/or fuel line
failure. Do not allow the fuel line to contact rough, Install fuel return line from the 7/16-24 size opening in the
sharp or hot surfaces. overflow fitting located on injection pump (where nozzle
fuel return line is also connected) to the top of the fuel
Connect the fuel line to the fuel pump inlet as shown in supply tank. Shield the line with fire-retardant material if
Figure 4-6 for either the DJB or DJE generator set. it passes through a combustible wall or partition.
NOZZLE
NOZZLE
CONNECT FUEL
RETURN LINE HERE
RETURN
(FLEXIBLE LINE) RETURN
LINES CONNECT FUEL
(SHADED) RETURN LINE HERE LINES
PUMP (SHADED)
(FLEXIBLE LINE)
PUMP
FS1851C
4-6
Always use flexible tubing between en- 2. If the tank is installed above the fuel pump inlet level
gine and the fuel supply to avoid line failure due to without a supply line shutoff valve, a ruptured pump
vibration. diaphragm could cause oil dilution, fuel loss, and
fuel leakage to the crankcase.
Never use galvanized or copper fuel
lines, fittings or fuel tanks with diesel fuel systems. 3. If the maximum fuel lift must be exceeded on any in-
Condensation in the tank and lines combines with stallation, consult Onan Application Manual T-030
the sulfur in diesel fuel to produce sulfuric acid. The for information on installing a day tank and an elec-
molecular structure of the copper or galvanized lines tric solenoid shutoff valve.
or tanks reacts with the acid and contaminates the
fuel. 4. Use an electric or manual shutoff valve if the mini-
mum fuel level in the tank is higher than the pump
Carefully clean all fuel system components before put- inlet, to provide positive fuel shutoff when the en-
ting the set into operation. Any dirt or contamination may gine is stopped. This valve also prevents loss of fuel
cause major damage to the fuel injection system. from possible leaks between the tank and the fuel
pump.
Dirt in the system can severely damage
both the injection pump and the injection nozzles.
Dirty fuel is one of the major causes of engine failure. Fuel leaks create the hazard of explo-
Even a tiny particle of dirt in the injection system may sion and fire, which can cause severe personal in-
stop the engine. Because diesel injection systems jury or death. For these reasons, always use flexible
have extremely precise tolerances, make certain that tubing between the engine and the fuel supply, to
fuel is kept clean. avoid leaks due to vibration and/or fuel line failure.
Make certain that the fuel system and the fuel tank lo-
Separate Fuel Tanks cation meet applicable local codes.
The fuel tank top must be lower than the fuel pump level INJECTION PUMP ADAPTER ASSEMBLY
to prevent putting a static head on the fuel pump inlet. If (DJE only)
the fuel tank is shared with another engine, use separate
fuel lines for both engines to avoid starving either one.
A spring and plunger assembly on the side of the pump
adapter (Figure 4-7) on the DJE generator set limits the
The following restrictions apply to separate fuel tank in-
maximum power output of the engine for safe operation
stallation:
and permits maximum fueling during starting.
1. The bottom of the fuel tank must not be more than 6
feet (1.8 m) below the fuel transfer pump inlet, un- Do not change the adjustment of this de-
less an auxiliary electric fuel pump is added. The vice unless absolutely required. The warranty may
maximum lift capacity of the transfer pump is six be voided if the fuel stop is intentionally altered to in-
feet. See the Wiring Diagram for the connection. crease engine power.
ADAPTER
DOWEL PIN
HOLES (2)
4-7
OIL DRAIN stranded load wires near the set, to isolate vibration. Use
the correct size insulated wires for the load rating ap-
Extend the drain to suit the installation. The oil base has plied.
a 1/2-inch pipe size tapped hole.
Connect each load wire to the proper generator output
Do not position the oil drain so that oil lead inside the control box. Insulate the bare ends of the
might drip onto the muffler, any exhaust compo- ungrounded wires. Use the bolt provided on the control
nents, or any other hot parts, causing a fire hazard. box to connect the generator ground lead or earth wire.
Fire presents the hazard of severe personal injury or Install a fused main switch (or circuit breaker) between
death. the generator and the load. If a test run indicates the
wrong rotation of 3-phase motors in the load circuit,
ELECTRICAL CONNECTIONS switch the connections at any two of the generator termi-
nals.
The nameplate on the genset lists its electrical output rat-
ing in watts, volts, and hertz. The wiring diagram, Electrical shock can cause severe per-
shipped with the set, depicts the electrical circuits and sonal injury or death. Check voltage at the nearest
connections for installation. junction box to be sure power has been discon-
nected before disconnecting load wires.
All electrical connections should be made by an electri-
cian or a qualified Onan technician, to meet the local An excessive electrical load can dam-
electrical code requirements. age the generator windings. Divide loads equally be-
tween the output leads to prevent generator damage.
Electrical shock can cause severe per-
sonal injury or death. Do not touch electrical wiring Standby
or components during testing. Disconnect electrical
power by removing starting battery negative (-) cable If the genset is being installed for standby service, add a
before handling electrical wiring or components. manual or automatic double-throw transfer switch to
avoid feeding generator output into the normal power
Load Wires source lines, and to prevent commercial power and gen-
erator output from being connected to the load at the
The control box (junction box) has knockout sections to same time. See the transfer switch installation manual
accommodate load wires. Use flexible conduit and for connection instructions. Also see Figure 4-8.
LINE LOAD GEN
SC1101
4-8
L1
120V
L0 240V
120V
L2
ES1804
FIGURE 4-9. 120/240 VOLT, SINGLE PHASE
For 240 volts, connect one load wire to the L1 connection and 240 volt, 1 phase current and 240 volt, 3 phase cur-
and the second load wire to the L2 connection. Terminal rent (Figure 4-10). In 3-phase operation, connect the
connection L0 is not used for 240 volt service. three load wires to generator terminals L1, L2 and L3 -
one wire to each terminal. In 3-phase operation, the L0
120/240 Volt, 3 Phase, 4 Wire Delta Connected Set:
The 3- phase delta connection is designed to supply 120 terminal is not used.
L1 L1
240V
L2 240V L2
120V
240V
120V
L3 L3
200V
L0
DO NOT USE THIS
CONNECTION FOR
ES1805
ANY 120 VOLT LOADS
For 120/240 volt, 1-phase, 3-wire operation, terminals L1 3 Phase, 4 Wire, Wye-Connected Set: The 3 phase, 4
and L2 are the “hot” terminals. The L0 terminal is the wire connection produces line-to-neutral voltage and
neutral, which can be grounded if required. For 120 volt line-to-line voltage. The line-to-neutral voltage is the
service, connect the black load wire to either the L1 or L2 lower voltage as noted on the unit nameplate, and the
terminal. Connect the neutral (white) wire to the L0 termi- line-to-line voltage is the higher nameplate voltage.
nal. Two 120 volt circuits are available.
Any combination of 1-phase and 3-phase loading may be For 3-phase loads, connect separate load wires to each
used at the same time, if no terminal current exceeds the of the set terminals L1, L2 and L3. Single-phase output of
nameplate rating of the generator. If no 3-phase output is the higher nameplate voltage is obtained between any
used, usable 1-phase output is 2/3 of 3 phase kVA. two 3-phase terminals as shown in Figure 4-11.
L1 L1
208V
L2 208V L2
120V
208V
120V
L3 L3
120V
L0
ES1806
The terminal marked L0 may be grounded if necessary. If using 1-phase and 3-phase current at the same time,
For 1- phase loads, connect the neutral (white) load wire use care to properly balance the 1 phase load, and not to
to the L0 terminal. Connect the black load wire to any one exceed rated line current.
of the other three terminals - L1, L2 or L3. Three separate Figure 4-11 shows load connections for 120/208 voltage.
1- phase circuits are available, with not more than 1/3 the Other voltages are available from either parallel wye or
rated capacity of the set available at any one circuit. series wye, illustrated in Figure 4-12.
4-9
B200
4-10
GROUNDING 2. Connect the generator lead and load wires to be
grounded to the ground stud on the switchboard.
Typical requirements for bonding and grounding are
given in the National Electrical Code, 1990, Article 250. 3. Connect one ungrounded (hot) load wire to the un-
used terminal on each circuit breaker.
Periodic inspection is recommended, especially after
service work has been performed on equipment any- 4. On sets that generate more than one voltage (ex-
where in the electrical system. ample: 120/240), wire the voltmeter to indicate the
higher voltage.
Generator Set Bonding and Equipment
RECONNECTIBLE GENERATORS
Grounding
The factory ships special-order sets with control panels
Bonding is defined in the National Electrical Code, 1990, especially wired for the voltage specified by the cus-
Article 100, as: The permanent joining of metallic parts to tomer. Standard sets without instruments are shipped
form an electrically conductive path which will assure with the T1-T4 or T1-T12 output leads separated in the
electrical continuity to conduct safely any current likely to output box. These single-phase and broad-range gen-
be imposed. erators may be connected to provide any of the output
voltages shown in Figure 4-12. Grounding or earthing
Bonding and equipment grounding procedures should comply with local electrical codes.
must be done correctly for proper system operation
and operator safety. Abnormal system conditions Electrical shock can cause severe per-
may allow ungrounded metallic parts to be ener- sonal injury or death. Never remove the grounding
gized, which could result in severe personal injury or pin from electrical equipment. Incorrect ground or
death. no ground can cause the installation to become elec-
trically “hot”. Equip the installation with adequate
Circuit and System Grounding Ground-Fault Circuit Protection devices to meet the
National Electrical Code (NFPA 70, 551- 7[C]) and to
The design and installation of grounding systems in- provide personal safety.
volves many factors, including multiple transformers,
standby generators, ground fault protection, physical lo- Code 3C or 53C Reconnectible Generators: The sin-
cations of equipment, and conductor type and size. Al- gle-phase, 60- and 50-hertz generators have output
though the consulting engineer and installer are respon- leads T1, T2, T3 and T4 available to make the single
sible for the design and wiring of each particular ground- phase voltage and load connections shown in Figure
ing application, system grounding must conform to na- 4-12 at the installation site.
tional and local codes.
Code 18 or 518 Reconnectible Generators: The
Output Lead Markings three-phase, broad-range, 60 and 50 hertz 12-lead gen-
erators have output leads T1 through T12 available to
Leads on revolving field generators are marked T1, T2, make the single and three phase voltage load connec-
etc. These identifying marks also appear on the wiring tions shown in Figure 4-12.
diagram.
When connecting the output leads, be sure to connect
SWITCHBOARD jumper W10 on the voltage regulator printed circuit board
between terminal V4 (common) and V1, V2, or V3 as
listed on the reconnection diagram.
Electrical shock can cause severe per-
sonal injury or death. Use extreme caution when Code 9x Generators: These special-order three-
working on electrical circuitry. Attach and remove phase, 60 hz, 4-wire generators are rewired at the factory
switchboard leads only when generator set is not op- to provide 347/600 VAC. Output leads T1, T2, T3 and T0
erating. Make certain that the generator set is inop- are available for connection to the load wires. See con-
erative by disconnecting the negative (-) battery ca- nection diagram, Figure 4-12.
ble. Do not touch leads during operation of genera-
tor set. BATTERY CONNECTIONS
A optional wall-mounted switchboard contains amme- The battery is connected for negative (-) ground, Figure
ters, a voltmeter, and circuit breakers. If it is used, the fol- 4-13. Be sure all battery connections are tight.
lowing connections apply:
Battery polarity must agree with the rectifier in the control
1. Connect one ungrounded (hot) generator lead to box. If battery polarity must be changed, reverse the rec-
the unused terminal on each ammeter. tifier connection in the control box.
4-11
Batteries present the hazard of explo-
sion, which can result in severe personal injury. Dis-
connecting battery cables from the battery while the
generator set is cranking or running causes arcing.
For this reason, do not disconnect battery cables
from the battery while the generator set is cranking
or running. To minimize arcing, always disconnect
the negative (-) cable first, and connect it last.
STARTING MOTOR
STARTING MOTOR
SOLENOID
BATTERY NEGATIVE
BATTERY POSITIVE
ES1962
12 V BATTERY
CABLE SIZE
LOOP 4 ft 5 ft 7 ft 9 ft 11 ft 14 ft
1.24 m 1.55 m 2.17 m 2.79 m 3.41 m 4.34 m
Reversed battery polarity can damage intended for a customer-supplied alarm at a remote loca-
or destroy the generator within 3 minutes if stopped, tion, to warn of emergency shutdown. Refer to the Wiring
or within 5 seconds if running. With reversed polar- Diagram for proper alarm connections.
ity, alternator windings will be damaged almost in-
stantly if the battery charging circuit is shorted be-
tween resistor R21 and the B1 end of the charging REMOTE START-STOP SWITCH (Optional)
winding. Make certain that battery polarity is cor-
rect, to avoid damaging or destroying the system. Use 2 wires to connect the SPST remote start-stop
switch to the terminal block marked B+ and to the remote
See the Specifications section of this manual for the 12 in the control box, using the wire sizes listed in Figure
volt battery minimum requirements. Connect battery 4-14.
positive (+) to starter engaging solenoid terminal post,
Figure 4-13. Connect battery negative (-) to a solid
ground connection on the engine. Incorrect connections can damage the
control, the remote switch, and the interconnecting
OPTIONAL ALARM wiring. Ensure that the leads from the remote switch
connect with the corresponding terminals on the
The GND terminal on the remote control terminal block is generator set.
4-12
2
START 1
STOP 3
MOMENTARY
CONTACT
SWITCHES
ES1970C
FIGURE 4-14. REMOTE CONTROL
4-13
Section 5. Operation
Accidental starting of the generator set Limited use of low viscosity oils, such
can cause severe personal injury or death. Make cer- as 10W-30 may be used for easier starting and pro-
tain the generator set is stopped and disconnect the viding sufficient oil flow at ambient temperatures be-
starting battery cables (negative [-] cable first) be- low -5° C (23° F). However, continuous use of low vis-
fore inspecting the generator set. cosity oils can decrease engine life due to wear. Re-
fer to the accompanying chart.
Oil Recommendations If an engine is operated in ambient temperatures consis-
tently below -23° C (-10° F) and there are no provisions to
The use of quality engine lubricating oils combined with keep the engine warm when it is not in operation, use a
appropriate oil drain and filter change intervals are criti- synthetic CE/SF or CD/SF engine oil with adequate low
cal factors in maintaining engine performance and dura- temperature properties such as 5W-20 or 5W-30.
bility.
The use of a synthetic base oil does not
Use SAE 30 oil that meets the American Petroleum Insti- justify extended oil change intervals. Extended oil
tute (API) Classification of CE/SF. CD/SF oil may be change intervals can decrease engine life due to fac-
used in areas where CE/SF oil is not available. CE and tors such as corrosion, deposits and wear.
5-1
In extremely dusty or dirty conditions, oil should be Refer to the Maintenance section of this manual for oil
changed more frequently. When adding oil between change interval and procedures. Always change the oil
changes, use the same brand as already in the engine. filter when changing the oil.
Various brands of oil may not be compatible when mixed.
EXS-1147-1
ALWAYS RETURN
PRIMER LEVER TO
LOWEST POSITION
INJECTION
PUMP RETURN
LINE FITTING
FS1777 FS1854C
DJB FUEL SYSTEM BLEEDING DJE FUEL SYSTEM BLEEDING
Use ASTM 2-D or 1-D fuel, with a minimum Cetane num- NOTE: Fuels with Cetane numbers higher than 45 may be neces-
sary in higher altitudes or in extremely low ambient temperatures,
ber of 45*. Number 2 diesel fuel is usually most economi- to prevent misfires.
cal; however, use ASTM 1-D fuel during the following
conditions: Use fuel with a low sulfur content and a pour point (ability
to filter) of at least 10°F (6°C) below the lowest expected
1. When ambient temperatures are below 32° F (0° C) ambient temperature. Keep fuel clean and protected
5-2
from adverse weather. Leave room for fuel expansion during cranking indicates that no fuel is reaching the
when filling the fuel tank. engine.
Dirt in the system can severely damage 6. In extreme cold (below 32°F or 0°C) it may be nec-
both the injection pump and the injection nozzles. essary to maintain preheating for two minutes after
Because diesel injection systems have extremely the engine starts, to obtain firing or smooth out cylin-
precise tolerances, make certain that fuel is kept ders, especially at no load or light loads.
clean. NOTE: When remotely starting the set, the switch on the set con-
trol must be in its remote position.
Bleeding Fuel System
Preheating the engine longer than one
Bleed air from fuel system as follows: Disconnect the fuel minute in moderate ambient temperatures before
return line (Figure 5-2). Operate the hand priming lever cranking the engine can destroy the manifold heater
on the fuel transfer pump until the fuel flowing from the and glow plugs, because there is no incoming air
fuel return line is free of air bubbles. Then reconnect the flow to cool them. For this reason, do not exceed the
fuel return line. Cranking the engine should expel one minute preheat periods (unless ambient tem-
trapped air from the injection pump. perature is below 0°F), to prevent heater burnout and
conserve the battery.
If the camshaft’s pump lobe is up, crank the engine one
revolution to permit hand priming. When finished, return NOTE: Continuous operation of the preheaters during cranking in
cold weather helps preheat the incoming combustion air, to pre-
priming lever inward (disengaged position) to permit nor- vent misfires as the engine starts running.
mal pump operation.
When the engine reaches operating speed, the centrifu-
PRE-HEATING AND STARTING gal switch and the start-disconnect relay automatically
stop cranking. If the engine fails to start in 45 to 120 sec-
Preheat the engine for 60 seconds when the ambient onds, the cranking limiter trips and stops cranking. If this
temperature is 55°F (13°C) or lower. Preheat the engine occurs, wait one minute before resetting the cranking
for 30 seconds in temperatures above 55°F (13°C). limiter and trying to restart the engine.
NOTE: Depress the preheat switch for one minute, then release it
Do not use ether as a cold weather start- and push the start switch.
ing aid. The heat from the glow plugs or manifold
heater may cause a sudden ignition of the ether va- If the control has an emergency relay reset button, per-
por. This can result in personal injury and damage to form reset only after a shutdown occurs due to low oil
the engine. pressure or high water temperature. Make certain to find
the cause of the failure before restarting the engine.
To preheat the engine:
Overvoltage will destroy the glow plugs
1. Engage the preheat switch for one minute. On con- and air heater in 2 to 3 seconds. If extra power is
tractor models, turn OFF-RUN switch to RUN. needed to start the set, connect an additional 12 volt
battery in parallel to the starting battery. Do not ap-
2. Release the preheat switch and engage the start ply overvoltage to the starting circuit at any time.
switch. On contractor models, continue to hold
PREHEAT switch until engine comes up to speed. STOPPING
On all other models, hold START switch to START
until engine comes up to speed. (This will maintain 1. Push the start-stop switch to the stop position.
heater operation until START switch is disen- 2. If the stop circuit fails, push governor arm down to
gaged.) shut off fuel injection pump.
3. Release the start switch after the engine reaches AUTOMATIC STARTING AND STOPPING
speed.
An optional automatic demand control may be used for
4. Check the oil pressure gauge: it should read at least starting and stopping, but it must provide engine preheat-
20 psi (138 kPa). ing.
NOTE: the pressure-relief valve is not adjustable. The automatic control has a time delay relay to preheat
glow plugs and the manifold heater for about 20 seconds
5. If the engine fails to begin firing after 20 seconds of before cranking occurs. The time delay relay prevents
cranking, return to the preheat procedure of step 1, immediate engagement of the starter in case a load is
then repeat step 2. Absence of blue exhaust smoke reapplied before the engine comes to a complete stop.
5-3
APPLYING LOAD EXERCISING UNIT
Allow the set to warm up before connecting a heavy load. Infrequent use of the generator set can cause it to dete-
Continuous generator overloading may cause high oper- riorate. The following can occur:
ating temperatures that can damage the windings. Keep
the load within the nameplate value for normal operation. • Condensation in the fuel and lubrication system,
Carbon deposits may form on the exhaust system during causing contamination and/or corrosion
operation at light loads; apply full load occasionally be-
fore shutdown to prevent excessive carbon accumula- • Loss of protective oil film on moving engine parts
tions. When possible, connect the load in small incre-
ments, instead of fully loading the genset at once. • Loss of engine fuel prime due to drain-back and/or
evaporation
EXHAUST SYSTEM INSPECTION
• Battery discharge due to internal and external cur-
Make regular inspections of the exhaust system. If you rent leakage
notice a change in the sound or appearance of the ex-
haust system, shut the unit down immediately and have it • Breakdown of generator insulation due to water ab-
inspected by your Onan dealer or distributor. sorption
Hot oil can cause severe personal in- * This applies to a standby genset only. Other units
jury. Do not check the oil level while the generator should be started and loaded by control and load
set is running; wait until the generator set is cool be- application systems normally associated with op-
fore investigating. eration of the unit.
5-4
Improper exercising may cause more DUST AND DIRT
damage than no exercising at all. Significant
amounts of water and raw fuel will remain in the lubri- 1. Keep the generator set and the cooling system
cation oil if the unit is run at a low operating tempera- clean.
ture. Also, operating the engine at no load or at low
temperatures causes carbon buildup and exhaust 2. Service the air cleaner as frequently as necessary.
system fouling. Continued operation in this manner
may cause starting failure and/or engine damage. 3. Change the crankcase oil every 100 operating
Exercising a generator set without exercising its as- hours.
sociated controls and switchgear does not test the
4. Keep oil and fuel in dust-tight containers.
operation of the controls and switchgear. If the con-
trol systems are not fully functional, the system may 5. Keep governor linkage clean.
fail to provide power when required.
HIGH ALTITUDE
After each exercise period, refill the fuel tank and check
the engine for leaks and overall condition. Locate the Maximum power is reduced approximately 4 percent for
cause of any leaks and correct. each 1000 feet (305 m) altitude above sea level, after the
first 1000 feet (305 m).
ENGINE RATINGS
OUT-OF-SERVICE PROTECTION
Ratings apply to altitudes up to 1000 feet (305 m), gen-
sets using standard cooling, normal ambient tempera- The lubricating qualities of diesel fuel should protect a
tures and with No. 2 Diesel fuel. Consult the nearest diesel engine for at least 30 days when the unit is not in
authorized Onan service center for operating character- service. To protect a set that will be out of service for
istics under other conditions. more than 30 days, proceed as follows:
HIGH/LOW OPERATING TEMPERATURES 1. Run the set under at least 50 percent load, until it is
thoroughly warmed up.
The generator set has been designed to operate satis-
factorily in both high (above 100° F) and low (below 0° F) 2. Shut down the engine.
temperatures. Use the oil recommended in the PRE-
START section for the expected temperature conditions. 3. Disconnect the starting batteries and follow stan-
dard battery storage procedures.
High Operating Temperatures
Freezing temperatures may se-
1. See that nothing obstructs air flow to and from the verely damage the starting batteries. When the
set. batteries are in storage, be certain to maintain
their liquid level. Use a trickle charger to main-
2. Keep cooling fins clean. Cylinder air housings tain the correct specific gravity.
should be properly installed and undamaged.
4. Drain the oil from the crankcase while the engine is
Low Operating Temperatures warm. Refill it with clean oil, and attach a tag listing
the type of oil used.
1. Use correct viscosity oil for temperature conditions.
Change oil only when engine is warm. If an unex- 5. Remove the flexible section of the exhaust line.
pected temperature drop causes an emergency, (The exhaust should have a rain cap to prevent the
move the set to a warm location or apply heated air entrance of moisture and dirt. If not, the exhaust can
(never use open flame) externally until oil flows be plugged.)
freely.
6. Service the air cleaner.
2. Use fresh fuel. Protect against moisture condensa-
tion. 7. Remove the glow plugs from the cylinders. Pour 1
ounce (30 ml) of rust inhibitor (or SAE #10 oil) into
3. Keep fuel system clean, and batteries in a well each cylinder. Crank the engine over several times.
charged condition. Reinstall the glow plugs.
4. Partially restrict cool air flow but use care to avoid Do not exceed one ounce oil per
overheating. cylinder. excess oil may fill the combustion
chamber and prevent the engine from cranking,
5. Use additional preheating during cold starts. due to hydraulic lock.
5-5
8. Check the fuel filters for the presence of water, as After the engine has started, excessive blue smoke
shown in the Periodic Maintenance section. will be exhausted until the rust inhibitor or oil has
burned away.
9. Clean the throttle and governor linkage. Protect
them by wrapping with a clean cloth.
10. Clean and wipe the entire unit. Coat parts suscepti-
ble to rust with a light coat of oil or grease.
11. Provide a suitable cover for the entire unit after it
cools down.
RETURNING THE SET TO OPERATION
1. Remove the protective cover from the unit. Wipe off
dust and dirt.
2. Check that fuel lines and injectors are secure and
properly torqued without air or fuel leaks.
3. Check the tag stating the oil type and weight. If it is
not correct, drain oil from the engine, and refill with
the correct oil. Be sure that it is up to “FULL” mark
on dipstick.
4. Remove the material used to plug the exhaust outlet
and reconnect the exhaust line. Check the com-
plete exhaust system for tight connections. Note
the condition of the muffler, exhaust line, etc., and
repair as necessary.
Exhaust gases contain carbon
monoxide, which may cause severe personal in-
jury or death. Before operating the generator
set, make certain the exhaust line is connected
correctly, is fit for operation, and does not leak.
5. Check the entire generator set for fuel or oil leaks.
Correct as required.
6. Check the wiring system for worn wires, loose con-
nections, etc. Repair as required.
7. Install the fully-charged batteries, and connect them
to the generator set. Observe correct polarity. Con-
nect the ground cable last.
Explosive gases are emitted from
batteries when they are being charged. Ignition
of these gases can cause severe personal in-
jury. Do not smoke or allow flame, sparks or arc-
ing equipment in the vicinity while servicing
batteries.
8. Verify that no loads are connected to the generator.
9. Start the engine, and observe the oil pressure
gauge and charge rate ammeter. After start, apply
load to at least 50 percent of rated capacity.
5-6
Section 6. Adjustments
Inadvertently starting the engine may cated on the side of the engine, above the oil filter. The
result in damage to the generator set or serious per- switch opens when the engine stops, and closes when
sonal injury. For this reason, disconnect the batter- engine speed reaches 900 rpm. If necessary, loosen the
ies, negative (-) cable first, before beginning any ad- stationary contact and adjust the point gap to 0.020 inch
justment or maintenance work on the engine, gen- (51 mm). Replace burned or faulty points.
erator, control panel, automatic transfer switch or
associated wiring. High voltage, which can cause severe
personal injury or death, is present at the breaker
CENTRIFUGAL SWITCH point gap. For this reason, disconnect the battery
cable, negative [-] terminal first, before setting the
The start-disconnect centrifugal switch (Figure 6-1) is lo- breaker point gap.
CENTRIFUGAL SWITCH
BREAKER POINTS
SET GAP AT 0.020 INCH
(51 mm)
ES1808
6-1
TURN TO
INCREASE RPM
CHARGE RATE ADJUSTMENT
SPEED
ADJUSTING (Hold spring stud in
NUT position) The adjustable resistor slide tap (Figure 6-3) in the
charging circuit is set to produce a 2 ampere charging
GOVERNOR
SPRING STUD rate. This resistor is found in the generator air outlet. For
(SENSITIVITY
TURN FOR
applications requiring frequent starts, check the battery
ADJUSTMENT)
MINIMUM SPEED specific gravity periodically. If necessary, increase the
DROP, THEN charging rate slightly (move the slide tap up). Adjust this
ADJUST SPEED
CUT slide tap only when the engine is stopped.
GOVERNOR
ARM GOVERNOR
SPRING
GOVERNOR
SENSITIVITY STUD
ADJUSTING
RATCHET DECREASE
SPEED
DECREASE
SENSITIVITY
INCREASE
SPEED
INCREASE
SENSITIVITY FS1778
SPEED
ADJUSTING
NUT
CHARGING RESISTOR
ES1971C
6-2
piston reaches top dead center, the flywheel timing pletely closed.
mark should be aligned with the timing pointer, and
the valve push rods should be stationary. 3. Check cylinder head-bolt torque prior to valve clear-
ance adjustment. Torque values are listed in Sec-
tion 2, Specifications. Adjust valve clearance with
2. Turn the flywheel an additional 10 to 45 degrees the locknut which secures the rocker arm to the cyl-
clockwise (estimated). When the piston is in this po- inder head (see Figure 6-4). Loosen this locknut to
sition, it is in its power stroke, with both valves com- increase clearance: tighten it to reduce clearance.
ADJUST VALVE
ROCKER
CLEARANCE HERE
ARM
VALVE SPRING
RETAINER
VALVE
SPRING
OIL SEAL
INTAKE VALVE
VALVE PUSH ROD
ONLY
VALVE
SEAT
VT1044
4. Using a feeler gauge, check the clearance between gap is established. Valve clearances are listed in
the rocker arm and the valve (see Figure 6-5). In- the Specifications section.
crease or decrease the clearance until the proper
EXHAUST VALVES
PCV VALVE
INTAKE
VALVES
VT1045
6-3
Section 7. General Maintenance
Follow a regular schedule of inspection and servicing, BATTERIES
based on operating hours. Keep an accurate record of
maintenance, service, and operating time. Use the run- Check the condition of the starting batteries at least every
ning time meter (optional) to monitor operating hours. two weeks. Make certain that connections are clean and
Follow the service schedule listed in the Periodic Mainte- tight. A light coating of non-conductive grease will retard
nance Schedule on page 8-1. corrosion at terminals. Add distilled water t o keep the
electrolyte at the proper level above the plates. Check
Many maintenance procedures present the specific gravity; recharge if below 1.260 at 77°F
hazards which can result in severe personal injury or (25°C).
death. Only qualified service personnel with knowl-
edge of fuels, electricity, and machinery hazards Batteries present the hazard of explo-
should perform service procedures. Review the sion, which can result in severe personal injury. Dis-
safety precautions on the inside cover page of this connecting battery cables from the battery while the
manual. generator set is cranking or running causes arcing.
For this reason, do not disconnect battery cables
PERIODIC CHECKS from the battery while the generator set is cranking
or running. To avoid excessive arcing, always dis-
1. Check all fuel and oil lines for possible leakage. connect the negative (-) cable first, and connect it
last.
2. Inspect exhaust lines and mufflers for possible leak-
age and cracks. Discharged batteries are subject to se-
vere damage if exposed to freezing temperatures.
3. Periodically drain moisture from condensation Store all batteries in a fully charged condition, and
traps. maintain their charge during storage.
4. Inspect the cooling system. Be sure the cooling fins
are clean.
FUEL FILTERS
Every 100 hours, open the drains on the bottom of the
5. Inspect electrical wires and connections to see they
fuel filter assembly (Figure 7-1) and allow any water to
are secure and have no fray damage.
escape. The drain plug on the fuel filter can tolerate only
If the generator requires major repair or servicing, contact an a limited amount of torque. Use two wrenches in combi-
authorized Onan service center. nation for breaking the plug loose and for final tightening.
Inadvertently starting the engine may Fuel presents the hazard of fire or ex-
result in damage to the generator set or serious per- plosion which can cause severe personal injury or
sonal injury. For this reason, disconnect the batter- death. Do not permit any flame, spark, pilot light,
ies, negative (-) cable first, before beginning any cigarette, arc-producing equipment or other ignition
maintenance work on the engine, generator, control source near the fuel system. Keep an ABC type fire
panel, automatic transfer switch or associated wir- extinguisher nearby.
ing.
CONNECTOR
ELBOW (TO
(FROM FUEL
INJECTION
TRANSFER
PUMP)
PUMP)
PRIMARY SECONDARY
FILTER FILTER
DRAIN DRAIN
FS1113
FIGURE 7-1. DUAL FUEL FILTERS
7-1
Every 600 hours, change the primary fuel filter by remov- GOVERNOR LINKAGE
ing the washer and capscrew on top of the fuel filter body.
Every 3000 hours, change the secondary fuel filter in the Every 100 hours, carefully pull the neoprene governor
same manner as the primary fuel filter. ball joints apart and clean them. Do not lubricate these
joints. See Figure 7-2.
Fuel presents the hazard of fire or ex-
plosion that can cause severe personal injury or
death. Do not work on the fuel system when the gen-
erator set is hot. Clean fuel spills and allow vapor to
evacuate prior to starting the generator set.
FS1114
7-2
CRANKCASE
BREATHER
TUBE
CLEAN
CRANKCASE
BREATHER
PIPE EVERY
500 HOURS
C1014
CRANKCASE BREATHER to release breather cap and valve assembly, Figure 7-4.
Wash cap, valve assembly and baffle in suitable solvent.
After every 200 hours of operation, remove hose clamp, Dry and reinstall.
breather hose, breather cap clamp and insulator halves
BREATHER
HOSE
SCREEN
HOSE CLAMP
SCREEN
RETAINER
O-RING
CLAMP
FILTER
BREATHER OIL
TUBE BAFFLE
ASSEMBLY
LS1206C
7-3
FUEL PUMP SEDIMENT BOWL Every 100 hours, remove the sediment bowl from the fuel
transfer pump and filter body (Figure 7-5). Clean out any
Fuel presents the hazard of fire or ex- water or particulate present in the bowl and filter. When
plosion which can cause severe personal injury or re-installing the sediment bowl, make sure the filter and
death. Do not permit any flame, spark, pilot light, gasket are in place.
cigarette, arc-producing equipment or other ignition
source near the fuel system. Keep an ABC type fire
extinguisher nearby.
FUEL PUMP
AND FILTER
BODY
FILTER
GASKET
BOWL
FS1115
AIR CLEANERS solvent, dip the element in engine oil and squeeze it as
dry as possible.
After every 50 hours of operation, remove and clean the
filter element (Figure 7-6). After washing the element in
ELEMENT
RETAINER
M1770
CONTRACTOR MODEL AIR CLEANER 3. Remove thumbscrew and take out element. Wash
element in detergent and water (use new element
1. Remove pre-cleaner and wash out dirt. Dry and re- after 6 washings). Dry and reinstall.
install.
4. Remove air cleaner baffle from cover, wash out dirt,
2. Loosen clamp and remove end cover. and reinstall in cover.
7-4
DUST CUP
COVER (PRE-CLEANER)
THUMBSCREW
CLAMP
BAFFLE
ELEMENT
FS1853C
7-5
OPTIONAL OIL BATH AIR CLEANER 2. Refill the base to the oil level mark with fresh oil of
the same weight as used in the engine.
1. Loosen the bottom clamp, remove the cleaner base
and clean the part (Figure 7-8).
KEEP OIL AT
THIS LEVEL
M1771
OIL FILTER CHANGE Stop the engine and drain the crankcase oil while the en-
gine is still hot. Place a pan under the drain outlet and
Place the pan under the oil filter and remove the filter by remove the oil drain plug or open the oil drain valve. After
turning it counterclockwise. Clean the filter mounting the oil is completely drained, replace the drain plug or
area. Oil filter gasket with clean oil. To install the new fil- close the drain valve. Refill with oil of the correct API des-
ter, turn the filter on clockwise until the gasket touches ignation and SAE viscosity grade for the temperature
the mounting base, then tighten 1/2 turn. conditions (refer to Operation section).
Hot oil and a hot oil filter may cause se- Hot oil may cause severe burns. Wear
vere burns to the skin. Wear goggles, apron and goggles, apron and rubber gloves, and use extreme
gloves when replacing the oil filter. care when changing the oil.
OIL CHANGE Check the oil level indicator after every 8 hours of opera-
tion, and maintain the oil level at the full mark (Figure
Inadvertently starting the engine may 7-9). The oil should be changed after every 100 hours of
result in damage to the generator set or serious per- operation. Refer to the Specifications section for crank-
sonal injury. For this reason, disconnect the batter- case and filter capacity.
ies, negative (-) cable first, before beginning any
maintenance work on the engine, generator, control Hot oil may cause severe burns by
panel, automatic transfer switch or associated wir- blowing out from the oil fill tube of a running genera-
ing. tor set. Do not check the oil level while the generator
set is operating.
7-6
ALWAYS REPLACE CAP
TIGHTLY OR OIL
LEAKAGE MAY OCCUR
OIL FILL
TUBE
LS1181
7-7
Section 8. Periodic Maintenance
Schedule
Regularly scheduled maintenance means lower operat- Failure to disconnect the generator set
ing costs and longer service life for the generator set. battery could result in damage to equipment or seri-
The following schedule may be used as a guide. How- ous personal injury in the event of inadvertent start-
ever, actual operating conditions should determine the ing. Before beginning any maintenance work on the
maintenance schedule. In exceptionally dusty or dirty engine, generator, control panel, automatic transfer
conditions, certain service periods may have to be re- switch or associated wiring, disconnect the battery,
duced. Check the condition of the crankcase oil, filters, negative (-) cable first.
etc., frequently, until the proper service time periods are
established. Many troubleshooting and mainte-
If any abnormalities in operation, unusual noises from nance procedures present hazards which can result
engine or accessories, loss of power, overheating, etc. in severe personal injury or death. Only qualified
occur, contact the nearest authorized Onan dealer. service personnel with knowledge of fuels, electric-
ity, and machinery hazards should perform service
Exhaust gas presents the hazard of se- procedures. Review safety precautions on inside
vere personal injury or death. Inspect the exhaust cover page before attempting these maintenance
system audibly and visually each day, or each time procedures.
the generator is started (whichever is sooner). With
the generator set running, momentarily open the ac-
cess cover to inspect the muffler. Shut down the
generator set and have any leaks repaired immedi-
ately.
8-1
HOURS OF OPERATION MAINTENANCE TASK
8 • Inspect exhaust system
• Inspect generator set
• Check fuel supply; see Note 1
• Check oil level
1. Water or foreign material in fuel can ruin the injection system. If daily inspection
shows water or excessive dirt in sediment bowl, fuel handling and storing facilities
should be checked and situation corrected. Primary and secondary fuel filters can
be replaced following correction of fuel contamination problem.
3. Tighten head bolts and adjust valve clearance after first 50 hours on new and over-
hauled engines, and then adjust valve clearance each 500 hours thereafter.