Vous êtes sur la page 1sur 15

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

01/10

To lassic Atmosphere Series C

F113-12RFP (Globe) F1113-12RFP (Angle)


Installed upstream of Reduced Pressure Zone Backflow Preventer. Normally Open Valve - Closes when discharge from RPZ Relief Valve is sensed or by engaging Solenoid Manual Operator. Limit Switch provides local visual and remote electrical indication of valve closure. Valve must be manually reset. Pressure gauge (provided) indicates valve reset for automatic service Anti-Scale Coated Main Valve Stem for added protection. Fail Safe operation - Valve closes upon Main Valve or Pilot Diaphragm failure.

To Floor Drain JB113 L

5
2 X
X

FS99

Standard Components
1 - Main Valve (Single Chamber) 2 - 3-Way Solenoid 3 - Manual Reset Ball Valve Port 1 - Valve Cover Port 2 - Pressure Port 3 - Atmosphere 4 - JB113 Junction Box 5 - FS99 Flow Sensor 6 - Pressure Gauge L - Limit Switch X - Isolation Cocks FC - Flo-Clean Strainer

X FC 1
FLOW
CLOSES VALVE OPENS VALVE

Operations
The Watts Flood Protection Shutdown Valve system prevents catastrophic property damage that can occur due to Relief Valve discharge and/or a blocked or overwhelmed floor drain during normal relief valve operation. Typical conditions which can cause continuous relief valve discharge are:
Fouled First Check Seat due to dirt, debris or rocks Failed First Check Spring Clogged or blocked Relief Valve Sensing Line Relief Valve Diaphragm failure

ing the Solenoid Pilot. The Solenoid Pilot is equipped with a Manual Operator which simulates power when manually engaged. The valve mounted JB113 Junction Box is equipped with an adjustable time delay to avoid valve closure due to intermittent or nuisance relief valve discharge. The Limit Switch provides local visual and remote electrical indication of valve closure. The valve remains closed and cannot re-open if flow stops or electrical service is interrupted, and must be manually reset after the RPZ is diagnosed and/or repaired. The valve comes complete with the valve mounted JB113 Junction Box with adjustable time delay, pre-wired Solenoid Valve, Manual Reset with Pressure Gauge, Limit Switch and FS99 Flow Sensor (field installed). Fail-safe operation is assured by closing valve upon Main Valve or Pilot Diaphragm failure and a specially coated Main Valve Stem for added protection.

The Watts 113-12RFP Flood Protection Shutdown Valve is a normally open valve designed to be installed upstream of a Reduced Pressure Zone (RPZ) Backflow Prevention device. It is normally open and closes driptight when continuous relief valve discharge through the drain pipe is sensed by the FS99 Flow Sensor, energiz12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Materials
Body & Cover: Ductile Iron ASTM A536 Coating: NSF Listed Fusion Bonded Epoxy Lined and Coated 316 Stainless Steel Buna-N (standard) EPDM (optional) Viton (optional) Stainless Steel
D

F113-12RFP (Globe) F1113-12RFP (Angle)


Globe
L M

Angle

Trim:

K H I J

Elastomers: Stem, Nut & Spring:

A B C

E F G

Operating Pressure
Threaded = 400 psi 150 Flanged = 250 psi 300 Flanged = 400 psi

Operating Temperature
Buna-N: 160F Maximum EPDM: 300F Maximum Viton: 250F Maximum

Pilot System
Solenoid Brass NEMA 4 General Purpose 110-VAC

Tubing & Fittings


Copper / Brass (Standard) Stainless Steel (Optional)

Dimensions
A B C D E F G H I J K L PORT SIZE 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1 1 M PORT SIZE 1/8 1/8 1/4 3/8 3/8 3/8 1/2 1/2 1 SHIPPING WEIGHTS* 15 15 35 65 95 190 320 650 940 VALVE GLOBE GLOBE GLOBE COVER TO ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE PORT SIZE THRD. 150# 300# CENTER THRD. 150# 300# THRD. 150# 300# SIZE 1-1/4 1-1/2 2 2-1/2 3 4 6 8 10 7-1/4 7-1/4 9-3/8 11 10-1/2 8-1/2 9-3/8 11 12 15 20 25-3/8 29-3/4 9 10 11-5/8 13-1/4 15-5/8 21 26-3/8 31-1/8 3-1/2 3-1/2 4-15/16 7 7 8-5/8 11-3/4 15-3/4 18-3/4 3-1/4 3-1/4 4 5-1/2 5-1/4 4 4 5-1/2 5-3/4 6-3/4 8-1/2 11 14-7/8 4-1/4 5-13/16 6-1/8 7-1/8 8-7/8 11-1/2 15-5/8 1-7/8 1-7/8 4 4 5-1/4 4 4 4 5-3/4 6-3/4 8-1/2 11 14-7/8 4-1/4 4-5/16 6-1/8 7-1/8 8-7/8 11-1/2 15-5/8 1/4 1/4 1/2 1/2 1/2 1/2 1/2 1/2 1

For larger sizes consult factory

Valve Cover Chamber Capacity


Valve Size (in) fl.oz. U.S. Gal 1-1/4 4 1-1/2 4 2 4 2-1/2 10 3 10 4 22 6 70 8 1-1/4 10 2-1/2

Valve Travel
Valve Size (in) Travel (in) 1-1/4 3/8 1-1/2 3/8 2 1/2 2-1/2 5/8 3 3/4 4 1 6 1-1/2 8 2 10 2-1/2

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Flow Data
Valve Size - Inches Maximum Continuous Flow Rate Gpm (Water) Maximum Intermittent Flow Rate Gpm (Water) CV Factor GPM (Globe) CV Factor GPM (Angle) 1-1/4 93 115 29 39 1-1/2 125 158 34 53 2 208 260 55 66 2-1/2 300 370 75 99 3 460 570 125 170

F113-12RFP (Globe) F1113-12RFP (Angle)

4 800 1000 220 280

6 1800 2300 460 650

8 3100 3900 775 1100

10 4900 6000 1200 1600

Maximum continuous flow based on velocity of 20 ft. per second. Maximum intermittent flow based on velocity of 25 ft. per second. The Cv Factor of a value is the flow rate in US GPM at 60 F that will cause a 1 psi drop in pressure. The factors stated are based upon a fully open valve. Cv factor can be used in the following equations to determine Flow (Q) and Pressure Drop ( P): Q (Flow) = Cv P P (Pressure Drop) = (Q/CV)2

1 1/4 1 1/2 2 1 1/4 1 1/2 2 1/2 2 2 1/2 3

100 50

Pressure Difference psi

10 5

10

50

100

500

1000

5000 10000 20000

10 8

10

Headloss

Angle Globe

100000

Flow Rate - Gallons per minute (Water)

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Main Valve

F113-12RFP (Globe) F1113-12RFP (Angle)

1 2 3 4 5 6 7 8 9

10
11 12 13 14 15 16 17

ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

DESCRIPTION Cover Cover Bearing Shaft / Stem Stud Cover Nut Diaphragm* Body Quad Seal* Seat Ring Spring Stem Nut Diaphragm Washer Spacer Quad Seal Retainer O-Ring* Quad Seal Plate Seat Gasket*

MATERIAL ASTM A536 65-45-12 Epoxy Coated Ductile Iron SAE 841 Bronze ASTM A276 304 Stainless Steel ASTM A570 Gr.33 Zinc Plated Steel ASTM A570 Gr.33 Zinc Plated Steel Buna-N (Nitrile) ASTM A536 65-45-12 Epoxy Coated Ductile Iron Buna-N (Nitrile) ASTM A743 CF8M (316) Stainless Steel (8 and Smaller) ASTM B62 Bronze (10 and Larger) ASTM A276 302 Stainless Steel ASTM A276 304 Stainless Steel ASTM A536 65-45-12 Epoxy Coated Ductile Iron ASTM A276 304 Stainless Steel ASTM A536 65-45-12 Epoxy Coated Ductile Iron Buna-N (Nitrile) ASTM A743 CF8M (316) Stainless Steel (8 and Smaller) ASTM B62 Bronze (10 and Larger) Buna-N (Nitrile)
* Contained in Main Valve Repair Kit

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
JB113 Junction Box 6.00

F113-12RFP (Globe) F1113-12RFP (Angle)

Power
Relay with Red LED Indicator
15 10 5 20 25

UP

SEC

30

8.00

LNG 1 2 3 4 5 6
Solenoid ( by factory)

Incoming Power 120V, 1 PH (Field Terminated)

FS-99 Flow Sensor (Field Terminated)

3/4 Conduit Connections (x 3)


CERTIFIED ELECTRICIAN TO CONNECT MAIN POWER AND FS99 FLOW SENSOR TO JB113 JUNCTION BOX

The valve mounted JB113 Junction Box is a lockable NEMA 4 enclosure equipped with an adjustable time delay, electrical relay and terminal strip. There are three 3/4 inch conduit connections. The valve solenoid is prewired. The valve is normally open and closes drip-tight when continuous relief valve discharge through the drain pipe is sensed by the FS99 Flow Sensor. The valve mounted JB113 Junction Box is equipped with an adjustable time delay to avoid valve closure due to intermittent or nuisance relief valve discharge. The time delay is adjusable from 0-30 seconds. Adjusting the dial clockwise increases the time delay for valve closure. Adjusting the dial counterclockwise decreases the time delay for valve closure.
12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
FS-99 Flow Sensor

F113-12RFP (Globe) F1113-12RFP (Angle)

The FS99 Flow Sensor is field installed in the discharge piping from the RPZ Relief Valve. The FS99 senses water in the discharge piping signaling the JB113 Junction Box to close the valve.

From RPZ Relief Valve (with Air Gap)

To Floor Drain

Sensor Probes installed 1/4 inch above pipe bottom

NOTE TO INSTALLING CONTRACTOR


Client/Contractor to provide installation Tee for Flow Sensor. Install Flow Sensor in RPZ discharge line in HORIZONTAL position as shown. Sensor Probes should be cut to length and installed 1/4 inch above pipe bottom. ENSURE SENSOR PROBES DO NOT CONTACT PIPE BOTTOM OR SIDES. CERTIFIED ELECTRICIAN TO CONNECT MAIN POWER AND FS99 FLOW SENSOR TO JB113 JUNCTION BOX

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series

F113-12RFP (Globe) F1113-12RFP (Angle)


The valve Solenoid is prewired to the JB113 Junction Box and is equipped with a Manual Operator. Turning Manual Operator in (clockwise) approximatly 5-6 turns simulates electricity to the Solenoid. Turning Manual Operator out (counterclockwise) returns the valve to electrical stand-by service. Manual operator must be disengaged for normal valve operation.

Disengaged A
A

Engaged
A

A Male Pipe Thread (in) 1/4 3/8 1/2

A Male Pipe Thread (in) 1/4 3/8 1/2

B C Female Pipe Length Thread (in) Thread (in) 1/8 11/16 1/4 7/8 3/8 7/8

The valve pilot circuit is equipped with a Model 60 Flo-Clean Strainer which is used to filter the fluid passing through the control pilot circuit, and provide protection to pilot circuit speed controls and pilots. It is installed in the inlet body port of the main valve, exposing the strainer element to main line flow. The currents and flow across the screen create a self-scouring effect, cleaning the filter element.

B C Female Pipe Length Thread (in) Thread (in) 1/8 11/16 1/4 7/8 3/8 7/8

The Model 51 Single Limit Switch provides local visual and remote electrical indication of valve position. The adjustable collar is set to contact the trip arm when the main valve is closed. The collar can be positioned on the stem by loosening the set-screw to actuate the switch upon valve closure. The single pole double throw Micro-Switch can be connected to the building monitoring system to indicate valve closure.
Single Pole Double Throw Switch

Normally Closed Common Lug Normally Open

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series

F113-12RFP (Globe) F1113-12RFP (Angle)

3 4 6 7 5

8 9 10 11

12 13 2

14 15

1 2 3 4 5 6 7 8

Limit Switch Bracket Stem Trip collar Set Screw Cap Wiper Ring* O-Ring*

9 10 11 12 13 14 15

Guide O-Ring* Polypak* Locknut Body Pin Coupling

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Installation Control Valve

F113-12RFP (Globe) F1113-12RFP (Angle)

Fully read all technical information provided. Prior to installation flush line to remove debris. Install valve upstream of the RPZ Backflow Assembly. For ease of valve service and electrical connections do not install valve vertically. Install valve horizontally in line (valve cover facing UP), so flow arrow matches flow through the line. Consult factory prior to ordering if installation requirements are other than described. Vertical installation of valves larger than 6 is not recommended and may result in poor valve performance and increased maintenance requirements. Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact control valve. Damage or improper valve seating may occur. Provide adequate clearance for valve servicing and maintenance. Install pressure gauges to monitor valve inlet and outlet pressure. Connect cover discharge control tubing to floor drain. Consult Valve Cover Capacity chart on page 2 to determine volume of cover fluid displaced when valve is operated.

FS99 Flow Sensor Install FS99 Flow Sensor HORIZONTALLY in RPZ Relief Valve discharge line for proper operation. Do not install vertically. Consult factory if flow sensor other than FS99 is used. Client / Contractor to provide 2 FNPT installation Tee for Flow Sensor. Sensor Probes must be field cut to length and installed 1/4 above pipe bottom for proper operation Insure sensor probes do not contact installation Tee bottom or sidewalls. Line Voltage to FS99 Flow Sensor is 10 volts maximum. Electrical Connections Certified Electrician to connect JB113 Junction Box and FS99 Flow Sensor according to factory schematic to appropriate power source and terminal strip locations. Line Voltage to FS99 Flow Sensor is 10 volts. Power supply to JB113 Junction Box is 120 VAC 60HZ Single Phase. Connect Limit Switch (if equipped) to remote alarm or auxiliary connection as required by project specifications. Pre-set Time Delay to 15 seconds. Insure Solenoid is disengaged by turning Manual Operator counterclockwise (out / left).

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Start-Up

F113-12RFP (Globe) F1113-12RFP (Angle)

Proper Automatic Control Valve startup requires bringing the valve into service in a controlled manner. All adjustments to control pilots and speed controls should be made slowly, allowing the valve to respond and the system to stabilize. NOTE: Control Valves should be setup in a dynamic (flowing) condition for proper startup. Provisions for flow must be made to insure proper settings. 1. Refer to valve schematic. Disengage Solenoid by turning Manual Operator counterclockwise (out). Locate and open Manual Reset Ball Valve. Open upstream and downstream isolation valves to allow controlled filling of the Valve and Backflow Assembly. Open all Isolation Ball Valves. 2. Inlet pressure will open the valve fully. Close Manual Reset Ball Valve. 3. Engage Solenoid by turning (red) Manual Operator clockwise (in) to simulate electrical shutdown signal. Inlet pressure will be indicated on Pressure Gauge and valve will begin to close. Due to low / no flow condition, valve closure may be slower than normal operation. When valve is fully closed adjust Limit Switch trip arm and trip collar to actuate Limit Switch. 4. Disengage Solenoid by returning Manual Operator out (counterclockwise) and open Manual Reset Ball Valve. Pilot System Pressure Gauge will drop to zero. Valve will open fully and is ready for electrical activation. Allow for cover volume to discharge to floor drain. Refer to chart on Page 2 for Cover Chamber Volume. Close Manual Reset Ball Valve. 5. Open JB113 Junction Box. Apply power and observe the clear Electric Relay Control. 6. Pour adequate amount of water into RPZ Relief Valve Air Gap until the RED LED indicator light on the Electrical Relay illuminates / flashes. This indicates the FS99 Flow Sensor is properly installed and is sensing water in the discharge piping. 7. Trap water in discharge piping and observe RED LED on Electrical Relay. Solenoid will energize when duration of Adjust Time Delay elapses. Valve will go closed and must be manually reset. Adjust Time Delay to Customer / Project specifications. To manually reset valve refer to Step 4. 8. For final test simulate actual RPZ Relief Valve discharge and observe floor drain for excessive pooling or flooding. Re-adjust time delay and valve speed controls as needed to achieve desired valve closure time.

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

Classic Series
Specifications

F113-12RFP (Globe) F1113-12RFP (Angle)

The Flood Protection Shutdown Valve shall be a normally open Diaphragm Valve installed upstream of the Reduced Pressure Zone Backflow Assembly, and automatically close if the RPZ relief valve begins to discharge. A Time Delay supplied in the JB113 Junction Box shall prevent the valve from closing on intermittent discharges from the RPZ relief valve. If continuous Relief Valve discharge occurs, the FS99 Flow Sensor installed horizontally in the RPZ Relief Valve discharge piping shall send a signal to the JB113 Junction Box energizing Solenoid to close the main valve. Once closed the Flood Protection Shutdown Valve must be manually reset. The JB113 Junction Box shall be valve mounted with the Solenoid pre-wired. The FS99 Flow Sensor shall be provided with the valve package and shall be field installed in a horizontal position in the RPZ Relief Valve discharge piping. Vertical installation of the Flow Sensor shall not be acceptable. The valve shall be equipped with a Limit Switch to provide local visual and remote electrical indication of valve closure. The Reduced Pressure Zone Backflow Assembly, Flood Protection Shutdown Valve, JB113 Junction Box and FS99 Flow Sensor shall be provided by the same manufacturer and be covered by a single warranty policy. The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve. Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there shall be no pistons operating the main valve or any pilot controls. The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall be Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover, shall be lined and coated with an NSF 61 Certified Epoxy Coating applied by the electrostatic heat fusion process. All main valve throttling components (valve seat and disc guide) shall be Stainless Steel. The valve body and cover must be machined with a 360-degree locating lip to assure proper alignment. The disc and diaphragm assembly shall contain a Buna-N synthetic rubber Quad Seal that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies utilizing bolts or cap screws for component retention will not be permitted. Direction of flow through the valve shall be the over-the-disc design, causing the valve to close upon diaphragm failure. The exposed portion of the Quad Seal shall contact the valve seat and seal drip-tight. The disc and diaphragm assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided valves will not be permitted. The main valve stem shall be Xylan coated to avoid the effects of mineral or hard water build-up. The main valve spring shall be the manufacturers heavy or extra heavy spring design. All necessary repairs shall be made from the top of the valve while the body remains in line. The Pilot Control System shall contain a Flo-Clean Strainer, NEMA 4, 120 VAC 60HZ 3-Way Solenoid with Manual Operator, Manual Reset Ball Valve, Pressure Gauge, Single Limit Switch, JB113 Junction Box and Isolation Ball Valves on all body connections. The JB113 Junction Box shall be valve mounted and the FS99 Flow Sensor shall be field installed. The valve shall be Watts Model 113-12RFP (globe) or 1113-12RFP (angle) Flood Protection Shutdown Valve.

12541 Gulf Freeway

Houston, Texas 77034 (Ph) 713.943.0688 (Fx) 713.944.9445 www.watts.com

ES-RVD

For Health Hazard Applications


Job Name Job Location Engineer Approval Contractor Approval

Contractors P.O. No. Representative

Series 009, 909, 919, 957 and 994


Reduced Pressure Zone Assemblies
Relief Valve Discharge Rates
14

lpm gpm 152 40 133 35 114 30 95 25 76 20 57 15 38 10 19 5 0 0

", 38", 12" 009QT

Rate of Flow

0 0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi .7 1.4 2.0 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8.3 9.0 9.7 10.3 11.0 11.7 12.4 bar

Pressure
lpm gpm 266 70 228 60 190 50 152 40 114 30 76 20 38 10 0 0
34

" 009M3QT

0 0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi .7 1.4 2.0 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8.3 9.0 9.7 10.3 11.0 11.7 12.4 bar

Note: These curves represent catastrophic or worst case discharge rates. These curves were developed by pressurizing the outlet of the backflow preventer with the second check valves internals removed from the body.

Rate of Flow

Pressure
lpm gpm 228 60 190 152 114 76 38 0 50 40 30 20 10 0 0 0 10 69 20 138 30 207 40 276 50 345 60 414 70 483 80 552 90 621 100 psi 690 kPa

1" 009M2QT

Rate of Flow

Pressure
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

lpm gpm 532 140 456 120 380 100 304 80 228 60 152 40 76 20 0 0

114" 009M2QT

Rate of Flow

0 10 0 .7

20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8.3 9.0 9.7 10.3 11.0 11.7 12.4 bar

Pressure

lpm gpm 513 35 456 120 399 105 342 90 285 75 228 60 171 45 114 30 57 15 0 0

112" 009M2QT

Rate of Flow

0 10 0 .7

20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8.3 9.0 9.7 10.3 11.0 11.7 12.4 bar

Pressure
lpm gpm 836 220 760 200 684 180 608 160 532 140 456 120 380 100 304 80 228 60 152 40 76 20 0 0

2" 009M2QT

Rate of Flow

0 0

10 20 .7 1.4

30 40 2.1 2.8

50 3.5

60 70 80 4.1 4.8 5.5

90 100 110 120 130 140 150 160 170 psi 6.2 6.9 7.6 8.3 9.0 9.7 10.3 11.0 11.7 bar

Pressure

Note: These curves represent catastrophic or worst case discharge rates. These curves were developed by pressurizing the outlet of the backflow preventer with the second check valves internals removed from the body.

lpm gpm 1330 350

212", 3" 009

Rate of Flow

1140 950 760 570 380 190 0

300 250 200 150 100 50 0

0 10 20 30 40 50 60 70 80 90 100 110120 130 140 150 160 170 180 psi 0 .7 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8. 3 9.0 9.6 10.3 11.0 11.7 12.4 bar

Pressure 2

lpm gpm 570 150 475 125

34

", 1" 909

lpm gpm 1520 400 1330 1140 950 760 570 380 190 0 350 300 250 200 150 100 50 0

114", 112", 2" 909

Rate of Flow

380 100 285 190 95 0 75 50 25 0

Rate of Flow

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi 0 .7 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8. 3 9.0 9.6 10.311.0 11.712.4 bar

Pressure

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 psi 0 .7 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8. 3 9.0 9.6 10.3 bar

Pressure

lpm 2090 1900 1710 1520 1330 1140 950 760 570 380 190 0

gpm 550 500 450 400 350 300 250 200 150 100 50 0

212" - 3" 909

Rate of Flow

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 psi 0 .7 1.4 2.1 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.6 8. 3 9.0 9.6 10.3 11.0 11.7 12.4 bar

Pressure

lpm 3420 3040 2660

gpm 900 800 700 600 500 400 300 200 100 0

4", 6", 8", 10" 909

Note: These curves represent catastrophic or worst case discharge rates. These curves were developed by pressurizing the outlet of the backflow preventer with the second check valves internals removed from the body.

Rate of Flow

2280 1900 1520 1140 760 380 0

0 5 0 .3

15 25 35 1.0 1.7 2.4

45 55 65 3.1 3.8 4.5

75 85 95 105 115 125 135 145 psi 5.5 5.9 6.5 7.2 7.9 8.6 9.3 10 bar

Pressure 3

lpm gpm 228 60 190 50 40 30 20 10 0

Capacity w/Second Check Removed


lpm gpm
684 6.8 570 532 456 380 342 304 266 228 190 152 114 76 38 0 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0

1" 919 RV

Backpressure w/Second Check Poppet & Spring Removed

2" 919 QT

Rate of Flow

152 114 76 38 0

Rate of Flow

0 10 20 30 40 50 60 70 80 90 100 110120 130 140150 160 170 180 psi 0 .7 1.4 2.0 2.8 3.5 4.1 4.8 5.5 6.2 6.9 7.8 8.3 9.0 9.710.311.011.712.4 bar

0 0

10 .7

20 30 1.4 2.1

40 2.8

50 3.5

60 4.1

70 4.8

80 5.5

90 6.2

100 110 psi 6.9 7.6 psi

Pressure

Pressure

Rate of Flow

lpm gpm 900 3420 900 3040 2660 2280 1900 1520 1140 760 380 0
800 800 700 700 600 600

212" 10" 994

500 400

500 400 300

300 200 200 100 100 00

0 0 0

40 40 276

80 80 552

120 120 827

160

160 1103

200 200 1379

240 240 1655

280 280 1931

300

psi kPa Note: These curves represent catastrophic or worst case discharge rates. These curves were developed by pressurizing the outlet of the backflow preventer with the second check valves internals removed from the body.

Pressure

lpm gpm 1330 350 1140 300

212" 10" 957

Rate of Flow

950 250 760 200 570 150 380 100 190 0 50 0 0 0 20 138 40 276 60 414 80 psi 552 kPa Typical Flow Rates as sized by floor drain manufacturers gpm 55 112 170 350 lpm 209 426 646 1330 2 3 4 5 Drain Size

Pressure

Wa t e r S a f e t y & F l o w C o n t ro l P ro d u c t s

USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca Watts, 2009

ES-RVD 0904

Vous aimerez peut-être aussi