Académique Documents
Professionnel Documents
Culture Documents
Paper
This work focuses on the measurement and analysis of the electric field for live working in a 1000-kV substation. Also, it
compares the electric field and the shielding efficiency requirement of a 1000-kV substation with 1000-kV transmission lines.
The electric field at the ground potential of the substation was measured using a microelectromechanical system (MEMS)-based
device. However, for safety reasons and to acquire rigorous data, finite element method (FEM) was applied to calculate the
electric field at equipotential. Two cases of entry into equipotential were considered: one in which the worker moves along
tension insulators to live conductors, and another where the worker is lifted to an energized bus bar on an insulated elevating
platform. Our results indicate that the electric field values on the worker in the 1000-kV substation and transmission lines are
about the same at ground potential, while at equipotential, the substation’s maximum electric field is 25.2% higher outside the
conductive clothing and 47.4% higher outside the metallic mask as compared to the 1000-kV transmission lines. Based on these
results, for live working in a 1000-kV substation, we recommend the use of conductive clothing with 60-dB shielding efficiency,
which is similar to that used in live working on a 1000-kV transmission line, but the metallic mask should have 25-dB shielding
efficiency, which is 5 dB higher than that used for the transmission line. © 2018 Institute of Electrical Engineers of Japan.
Published by John Wiley & Sons, Inc.
Keywords: 1000-kV substation; electric field measurement; finite element analysis; live working; shielding efficiency
1. Introduction Worse still, the live line worker will have a tingling feeling when
he is floating on a strong AC field. These uncomfortable feelings
Recently, 1000 kV transmission lines and substations are built
will affect normal operations and can even cause accidents.
to meet the growing power demand in China. Reducing the outage
Thus, a high-voltage live line worker should essentially wear
time and improving the power system reliability are of prime conductive clothing to reduce the adverse effects caused by the
importance. Therefore, live working for repair and maintenance
AC electric field [5]. The international guidelines IEEE Standard
in the ultrahigh voltage (UHV) power grid is getting more and C95.6-2002 [6] and the International Commission on Non-Ionizing
more attention because of its effectiveness as well as technical and Radiation Protection (ICNIRP) [7] give reference safety levels
economic benefits. The “hot stick” and the “bare hand” are two of 5 and 10 kV/m for general public and occupational exposure,
main techniques of live working [1]. Of these, the latter method has respectively. The International Council on Large Electric Systems
been widely adopted for live working on high-voltage transmission (CIGRE) points out that 15 kV/m is also an acceptable safety
lines. level for occupational exposure [8]. Based on these guidelines,
The presence of the worker in an energized power system the Chinese National Standard GB 6568–2008 [9] specifies that
considerably distorts the electric field due to accumulated surface the electric field inside the conductive clothing should be less than
charges on his body [2]. Thus the field strength on various parts 15 kV/m, and for the exposed body parts, such as the worker’s face,
of the worker’s body will be different. The first study on electric it should be less than 240 kV/m. With the increased voltage levels
field measurement on a live line worker’s body was conducted of power transmission, the electric field is also being investigated
on 138 and 345 kV lines, and the electric field recognition level for HV and UHV power systems while taking the human body
of the human body was determined as 240 kV/m (6 kV/in) [3,4]. into consideration [10–14]. The ongoing construction of 1000 kV
In this case, the worker feels like a gentle breeze blowing on his UHV projects in China has initiated research on the subject of live
skin, which is due to the action of the electric field on the hairs working technology and working personnel’s safety requirements
of the skin. If the electric field exceeds 240 kV/m, the live line for 1000 kV power networks [15–20]. In our earlier work, we
worker will hear a buzzing sound. This kind of noise is due to developed a conductive clothing to be used for live working on
the mechanical vibration on the eardrum caused by the AC field. 1000-kV transmission lines and tested its electrical performance
[17]. Furthermore, the electrical field on the worker’s body was
a Correspondence to: Linong Wang. E-mail: wangln@whu.edu.cn measured both at ground potential and at equipotential [17–19].
* School of Electrical Engineering, Wuhan University, Wuhan 430072, The measurement results showed that the maximum electric field
China on the worker’s body when performing live working on 1000-kV
** American University of Sharjah, Sharjah 26666, United Arab Emirates transmission lines was nearly twice that on 500-kV transmission
*** China Electric Power Research Institute, Wuhan 430074, China lines and about 1.5 times that on 750-kV transmission lines
© 2018 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
Y. FANG ET AL.
Torso Location1
elliptic cylinder
30 Location2
50
Location4
Location5 Framework
E-field (kV/m)
Location4 0
78.13
156.3
234.4
312.5
390.6
Location3 468.8
546.9
Bus bar 625.0
703.1
781.3
859.4
937.5
1016
Location2 1094
1172
1250
1328
Post 1406
1484
insulator 1562
1641
1719
1797
Location1 1875
1953
2031
2109
2188
2266
2344
2422
Working 2500
platform
Fig. 12. Case II: Electric field distribution on the worker’s body
at location 3
E-field (kV/m)
0
84.3
168.8
Fig. 11. Case II: Worker’s locations for electric field calculation 253.1
337.5
421.9
506.3
590.6
Table IV. Case II: Worker’s electric field strength (kV/m) 675.0
759.4
calculations 843.8
928.1
1012
Body part Loc.1 Loc.2 Loc.3 Loc.4 1097
1181
1266
Top of head 243 533 1629 1351 1350
1434
Face 86–186 240–453 521–1499 450–1171 1519
Fingertip 128 176 261 270 1603
1688
Chest 14–71 59–234 65–456 270–541 1772
1856
Feet 314 613 1824 2523 1941
2025
Enhancement factor 15.62 16.01 17.80 19.54 2109
2194
2278
2362
2447
2531
At location 3, the worker’s head is 0.5 m away from the bus bar. 2616
2700
At location 4, his hands touch the bus bar, i.e., he has reached the
line voltage level. Fig. 13. Case II: Electric field distribution on the worker’s body
The simulation model developed for this case comprised of at location 4
frameworks, bundle conductors, drop conductors, bus bars, post
insulators, capacitor voltage transformer (CVT), grading rings, and from 314 to 1824 kV/m, an increase of 4.8 times during this
gas-insulated switchgear (GIS). The insulated platform was also movement.
taken into account in this modeling. In this case, the worker was 3. The electric field of the worker’s body reaches its max-
assumed as a floating object at locations 1−3, and the worker’s imum value of 2523 kV/m at location 4. However, the
potential was set as the phase voltage at location 4. Table IV shows electric field at the worker’s head is lower in this situa-
the computed results of electric field, and Figs 12 and 13 present tion than that at location 3 due to the shielding effect of
the electric field distribution at locations 3 and 4, respectively. The the bus bar.
following observations about the electric field distribution can be 4. During the process of entering equipotential by the insulated
extracted from Table IV and Figs 12 and 13. platform, the electric field enhancement factor increases
from 15.62 to 19.54, an increase of about 25.1%.
1. The electric field on the worker’s body varies at different
locations during the process of approaching the energized In Case I, the electric field distribution changes greatly with
bus bar. As the distance from the bus bar decreases, the the variation of worker’s posture. The largest electric field occurs
electric field on worker’s body keeps on increasing. The at his feet at location 1, while the peak value appears at his
maximum electric field always occurs at the worker’s feet. fingertips at location 5. In Case II, although the electric field
2. The worker is at floating potential at locations 1−3, and the increases with decreasing distance from bus bar, the electric field
electric field on his body is within the range 14–1824 kV/m. distribution changes a little before the worker touches the bus bar.
The electric field values at the worker’s head and feet are When the worker stays at the bus-bar voltage level, the electric
much larger than at other body parts. When approaching field at the head top and face in Case II is 84.6% and 97.6%,
the bus bar (from location 1 to location 3), the electric field respectively, which are lower than those in Case I. However, the
at worker’s head top changes from 243 to 1629 kV/m, an electric field at the worker’s feet in Case II is about 5.6 times
increase of 5.7 times. The electric field at his feet increases that in Case I.
1000
Shielding efficiency, which is the ratio of electric field reduction, In addition, the largest enhancement factor at equipotential
is an important index of conductive clothing and can be defined level indicates that worker’s posture also has a major impact on
as follows [30]: the electric field enhancement. Although our specified shielding
efficiency will keep the worker safe, we recommend that the
Uref
SE dB = 20log10 (2) worker should watch his posture and he should be educated about
U
the posture effects on the electric field distortion. We recommend
where SE dB is the shielding efficiency, U ref represents the that the worker should not stretch his arms out and should keep
reference voltage without conductive clothing, and U is the voltage himself inside bundle conductors as much as possible to minimize
measured at the same spot with conductive clothing. the electric field distortion while standing on the conductors. When
IEC 60895–2002 [30] and GB/T 6568-2008 [8] stipulate that the worker performs operation on the energized bus bar, the electric
the shielding efficiency of conductive clothing must be higher than field at the face is much lower than the case in which the worker
40 dB up to the voltage level of 800 kV. In an electrostatic field, is standing on the conductors. Thus for bus bar live working, the
the voltage and electric field have a linear relationship, thus the worker should pay more attention to his feet because the highest
obtained electric field can be used to calculate SE dB . Based on electric field occurs at his feet. Therefore, the conductive socks
the numerical results, the maximum electric field on the worker’s must be perfectly connected to the trousers of conductive clothing
body at equipotential is 2876 kV/m. The conductive clothing with in order to guarantee the shielding effect.
a shielding efficiency of 40 dB (reduction factor of 100) cannot
meet the Chinese National Standard limit of 15 kV/m electric field
5. Conclusion
inside the conductive clothing. Therefore, conductive clothing with
greater shielding efficiency is needed to maintain the electric field The electric field on a worker for performing live working
intensity within the specified limit. in a 1000-kV substation was measured and calculated. The
The maximum electric field strength of 2876 kV/m can be agreement between measured and calculated values of electric
reduced to the allowable level of 15 kV/m by using conduc- field both for single and double circuit transmission lines proved
tive clothing with a minimum shielding efficiency of 45.7 dB. the accuracy of using FEM-based technique for the electric
Shielding efficiency greater than 45.7 kV/m will be better for field assessment. Therefore, electric field measurements at the
keeping some safety margin. For single and double circuit trans- substation were performed at ground potential while FEM-based
mission lines, the maximum measured electric field reported in substation modeling and simulations were used to evaluate the
Fig. 14 at the fingertips outside the 60-dB conductive clothing electric field while entering the equipotential level.
will be reduced to 2.164 and 2.298 kV/m, respectively. For the Our results showed that there is no significant difference
substation, the 60-dB conductive clothing will reduce the maxi- between the electric field of a 1000-kV substation and that of
mum electric field to 2.876 kV/m, which is well below the spec- transmission lines at ground potential. However, at equipotential
ified limit of 15 kV/m and is also quite close to electric field level, the maximum electric field outside the 60-dB conductive
level being experienced by transmission line workers. Therefore, clothing in the substation is 25.2% higher than that of the
we recommend the use of 60-dB conductive clothing, which transmission lines. Inside the conductive clothing, the maximum
has been already developed for 1000-kV transmission line live electric field is less than 3 kV/m, which is well below the specified
working [17]. limit of 15 kV/m. Therefore, the 60-dB conductive clothing already
Figure 15 displays the details of the calculated electric field for adopted for 1000-kV transmission line live working suffices for
a 1000-kV substation and a 1000-kV double circuit transmission the substation as well. The maximum electric field outside the
line at various points on the worker’s face (outside the mask). The metallic mask in the substation is 47.4% higher than that of
electric field on worker’s face ranges from 1033 to 2314 kV/m transmission lines. Thus, we propose that the metallic mask for live
for the substation while it varies from 785 to 1570 kV/m for the working in the substation should have an additional 5-dB shielding
transmission line. It can be seen that in a substation the electric efficiency as compared to the 20-dB metallic mask already used
field on worker’s face increases more rapidly from his jaw to the for transmission lines. Our 25-dB recommendation will limit the
forehead than in the case of transmission lines. The maximum electric field at the worker’s face to less than 130 kV/m. This is
electric field on the worker’s face in the case of transmission lines the electric field level at which currently a 1000-kV transmission
is twice its minimum value, while for the substation it is 2.24 line worker does not experience any discomfort while performing
times the minimum value. In addition, the maximum electric field live working.
on the worker’s face in the substation is 47.4% higher than that
of the transmission line. According to GB/T 6568-2008 [8], the References
electric field on the exposed body parts, such as the face, should
be less than 240 kV/m. Considering the highest field strength of
(1) Looms JST. Live working on high-voltage lines. Proceedings of
2314 kV/m, the 20-dB metallic mask adopted for transmission
the IEEE. Institute of Electrical and Electronics Engineers 1981;
line will reduce the electric field level to 231.4 kV/m. Although 128(2):89–106.
this level of electric field is below the limit of 240 kV/m, it is (2) Shimizu K, Endo H, Matsumoto G. Visualization of electric fields
significantly higher than the measured electric field inside the around a biological body. IEEE Transactions on Biomedical Engi-
metallic mask for transmission lines. In our earlier experience neering 1988; 35(5):296–302.
of live working on 1000-kV transmission lines, the electric field (3) Kouwenhoven WB, Miller CJ Jr, Barnes HC, Simpson JW, Rorden
measured inside the 20-dB metallic mask was 112–127 kV/m HL, Burgess TJ. Body current in live line working. IEEE Tran. Power
[17,19]. The worker will not have any unpleasant feelings while App. Syst. 1966; PAS-85, 4:403–411.
working on energized conductors at this level of electric field. (4) Miller CJ Jr. The measurement of electric fields in live line working.
IEEE Tran. Power App. Syst. 1967; PAS-86(4):493–498.
Also, sufficient safety margin is guaranteed without approaching
(5) Hotte PW, Gela G, Mitchell JD, Lyons PF. Electrical performance of
the maximum allowable limit of 240 kV/m. Therefore, for the
conductive suits. IEEE Trans. Power Del. 1997; 12(3):1193–1201.
1000-kV substation, we recommend an additional 5-dB shielding (6) IEEE Standard for Safety Levels with Respect to Human Expo-
efficiency of the metallic mask. The 25-dB shielding efficiency sure to Electromagnetic Fields. 0–3 kHz, IEEE Std C95.6-2002,
mask will lower the electric field on substation worker’s face form 2002.
2314 to 130 kV/m, a level that is similar to the one experienced (7) ICNIRP. Guidelines for limiting exposure to time-varying electric,
by the transmission line worker. magnetic and electromagnetic fields (up to 300GHz), International
Commission on Non-Ionizing Radiation Protection (ICNIRP’s), (25) Xiao B, Liu K, Wu T, Liu T, Peng Y, Lie XL, Su ZM, Tang P.
2010. Experimental research on minimum approach distance and complex
(8) CIGRE Position Statement. Power-frequency electromagnetic fields gaps for live working in substation. Proceedings of 5th International
and health, on behalf of the technical committee. Electra, No. 196, Conference on Electric Utility Deregulation and Restructuring and
2001. Power Technologies (DRPT ), 2015; 1595–1599.
(9) GB Standard. Screening clothes for live working, Chinese Std. GB (26) Shimizu K, Endo H, Matsumoto G. Fundamental study on measure-
6568-2008, 2008. ment of ELF electric field at biological body surfaces. IEEE Trans-
(10) Krajewski W. Numerical assessment of electromagnetic exposure actions on Instrumentation and Measurement 1989; 38(3):779–784.
during live-line works on high-voltage objects. IET Science, Mea- (27) Li J, Peng ZR, Yang X. Potential calculation and grading ring
surement and Technology 2009; 3(1):27–38. design for ceramic insulators in 1000 kV UHV substations. IEEE
(11) Zhuang CJ, Zeng R, Zhang B, Zhu PX, Wang L, He JL. The opti- Transactions on Dielectrics and Electrical Insulation 2012; 19(2):
mization of entering route for live working on 750 kV transmission 723–732.
towers by space electric-field analysis. IEEE Trans. Power Del. 2010; (28) GB Standard. Human dimensions of Chinese adults, Chinese Std.
25(2):987–994. GB10000-88, 1988.
(12) Zemljaric B. Calculation of the connected magnetic and electric (29) Shang LQ, Li M. Simulation study on electric field of UHV
fields around an overhead-line tower for an estimation of their transmission lines with different numbers of sub-conductors. 2016
influence on maintenance personnel. IEEE Trans. Power Del. 2011; IEEE International Conference on High Voltage Engineering and
26(1):467–474. Application (ICHVE ), 2016; 1–4.
(13) Wang LN, Zhang QS, Hu JX, Liu K, Wu T, Wang JH. Research (30) IEC. Live working-conductive clothing for use at nominal voltage up
on complex gap discharge model of live working on EHV and to 800 kV a.c. and ±600 kV d.c. IEC 60895-2002, 2002.
UHV high-voltage transmission lines. Canadian J. Electrical and
Computer. Eng. 2014; 37(1):11–18.
(14) Ghassemi M, Farzaneh M. Effects of tower, phase conductors and Yaqi Fang (Non-member) received the B.E. degree in electri-
shield wires on the electrical field around a tower window during live- cal engineering from Wuhan University of
line work. IEEE Transactions on Dielectrics and Electrical Insulation Technology, Wuhan, China, in 2013. She
2015; 22(6):3413–3420.
is currently pursuing the Ph.D. degree in
(15) Huang DC, Shu YB, Ruan JJ, Hu Y. Ultra high voltage transmission
high-voltage and insulation technology at
in China: developments, current status and future prospects. Proceed-
ings of the IEEE 2009; 97(3):555–583. the School of Electrical Engineering, Wuhan
(16) Hu Y, Liu K, Wu T, Liu T, Xiao B, Tang P, Su ZM. Key University. Her current research interests
technology research and application of live working technology on include electromagnetic field calculation in
EHV/UHV transmission lines in China. Proceedings of International engineering and live working technology.
Conference on Power System Technology (POWERCON ), 2014;
2299–2309. Habibur Rehman (Non-member) received the B.Sc. degree from
(17) Liu K, Wang LN, Hu Y, Shao GW, Liu T, Hu JX, Xiao B. Research the University of Engineering and Tech-
of safety protection for live working on 1000 kV AC ultrahigh voltage nology Lahore, Pakistan, in 1990, and the
transmission line. Proceedings of Asia-Pacific Power and Energy M.S. and Ph.D. degrees from the Ohio State
Engineering Conference (APPEEC ), 2010; 1–5 University, Columbus, Ohio, in 1995 and
(18) Hu Y, Wang LN, Liu K, Liu T, Hu JX, Xiao B. On site application 2001, respectively, all in electrical engineer-
test of live working of UHV AC transmission line. High Voltage Eng.
ing. Presently, he is an Associate Professor
2009; 35(9):2053–2058.
with the Department of Electrical Engineer-
(19) Hu Y, Liu K, Wang LN, Shao GW, Liu T, Hu JX, Xiao B, Zheng
CG, Xu Y. Experimental research on live working on 1000 kV double ing, the American University of Sharjah. He
circuit AC transmission lines on the same tower. High Voltage Eng. has worked on the installation, testing, and commissioning of a
2010; 36(11):2668–2673. 500-kV substation. His research interests include power systems,
(20) Liao C, Ruan J, Liu C, Du Z, Wen W, Zhou T. Helicopter live-line power electronics, adjustable-speed drives, and alternative energy
work on 1000 kV UHV transmission lines. IEEE Trans. Power Del. vehicles.
2016; 31(3):982–989.
(21) Roux M. Innovations in live line maintenance for high voltage Bin Xiao (Non-member) received the M.E. degree in electri-
substations (63 kV) at EDF (Electricite de France). Proceed- cal engineering from Xi’an University of
ings of 6th International Conference on Transmission and Distri- Science and Technology, Xi’an, China, in
bution Construction and Live Line Maintenance (ESMO), 1993; 2007. He is currently with the China Elec-
169–184. tric Power Research Institute. His research
(22) Assad LAX, Rosa JE. Improvement in the 500 kV substations using
interests include transmission line operation
barehand methods without outage of power flow in Brazil’s north-
and maintenance technology and live work-
south interconnection. 10th International Conference on Transmission
and Distribution Construction, Operation and Live-Line Maintenance ing technology.
(ESMO), 2003; 111–117.
Tian Wu (Non-member) received the B.E. degree from the
(23) Alexandru S, Oltean M, Sevastre I, Brabete L. Live replacement
of 400 kV busbar insulators in Brasov substation. Proceedings of China Three Gorges University, Yichang,
12th International Conference on Transmission and Distribution China, in 2006, and the Ph.D. degree in
Construction, Operation and Live-Line Maintenance (ESMO), 2011; high-voltage and insulation technology from
1–7. Wuhan University, Wuhan, China, in 2012.
(24) Shunmugam S, Lumpur K. Live maintenance in high voltage He is currently with the China Electric
substations: Malaysia’s experience. Proceedings of 11th Inter- Power Research Institute. His research inter-
national Conference on Live Maintenance (ICOLIM ), 2014; ests include external insulation in power sys-
1–4. tems and live working technology.
Kai Liu (Non-member) received the B.E. degree in electri- Linong Wang (Non-member) received the B.E. degree in electrical
cal engineering in 2001, and the M.E. and engineering from Xi’an Jiaotong University,
Ph.D. degrees in high-voltage and insulation Xi’an, China, in 1998, and the M.E. and
technology in 2004 and 2012, respectively, Ph.D. degrees in high-voltage and insulation
from Wuhan University, Wuhan, China. technology from Wuhan University (WU),
He is currently with the China Electric Wuhan, China, in 2006 and 2011, respec-
Power Research Institute. His research inter- tively. He is currently a Professor with the
ests include transmission line operation and School of Electrical Engineering, WU. His
maintenance technology and live working research interests include transmission line
technology. operation and maintenance technology, live working technology,
and electrical engineering materials.