Vous êtes sur la page 1sur 10

IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING

IEEJ Trans 2018


Published online in Wiley Online Library (wileyonlinelibrary.com). DOI:10.1002/tee.22690

Paper

1000-kV UHV Substation Live Working and Safety Recommendations


Yaqi Fang* , Non-member
Habibur Rehman** , Non-member
Bin Xiao*** , Non-member
Tian Wu*** , Non-member
Kai Liu*** , Non-member
Linong Wang*a , Non-member

This work focuses on the measurement and analysis of the electric field for live working in a 1000-kV substation. Also, it
compares the electric field and the shielding efficiency requirement of a 1000-kV substation with 1000-kV transmission lines.
The electric field at the ground potential of the substation was measured using a microelectromechanical system (MEMS)-based
device. However, for safety reasons and to acquire rigorous data, finite element method (FEM) was applied to calculate the
electric field at equipotential. Two cases of entry into equipotential were considered: one in which the worker moves along
tension insulators to live conductors, and another where the worker is lifted to an energized bus bar on an insulated elevating
platform. Our results indicate that the electric field values on the worker in the 1000-kV substation and transmission lines are
about the same at ground potential, while at equipotential, the substation’s maximum electric field is 25.2% higher outside the
conductive clothing and 47.4% higher outside the metallic mask as compared to the 1000-kV transmission lines. Based on these
results, for live working in a 1000-kV substation, we recommend the use of conductive clothing with 60-dB shielding efficiency,
which is similar to that used in live working on a 1000-kV transmission line, but the metallic mask should have 25-dB shielding
efficiency, which is 5 dB higher than that used for the transmission line. © 2018 Institute of Electrical Engineers of Japan.
Published by John Wiley & Sons, Inc.

Keywords: 1000-kV substation; electric field measurement; finite element analysis; live working; shielding efficiency

Received 30 March 2017; Revised 10 December 2017

1. Introduction Worse still, the live line worker will have a tingling feeling when
he is floating on a strong AC field. These uncomfortable feelings
Recently, 1000 kV transmission lines and substations are built
will affect normal operations and can even cause accidents.
to meet the growing power demand in China. Reducing the outage
Thus, a high-voltage live line worker should essentially wear
time and improving the power system reliability are of prime conductive clothing to reduce the adverse effects caused by the
importance. Therefore, live working for repair and maintenance
AC electric field [5]. The international guidelines IEEE Standard
in the ultrahigh voltage (UHV) power grid is getting more and C95.6-2002 [6] and the International Commission on Non-Ionizing
more attention because of its effectiveness as well as technical and Radiation Protection (ICNIRP) [7] give reference safety levels
economic benefits. The “hot stick” and the “bare hand” are two of 5 and 10 kV/m for general public and occupational exposure,
main techniques of live working [1]. Of these, the latter method has respectively. The International Council on Large Electric Systems
been widely adopted for live working on high-voltage transmission (CIGRE) points out that 15 kV/m is also an acceptable safety
lines. level for occupational exposure [8]. Based on these guidelines,
The presence of the worker in an energized power system the Chinese National Standard GB 6568–2008 [9] specifies that
considerably distorts the electric field due to accumulated surface the electric field inside the conductive clothing should be less than
charges on his body [2]. Thus the field strength on various parts 15 kV/m, and for the exposed body parts, such as the worker’s face,
of the worker’s body will be different. The first study on electric it should be less than 240 kV/m. With the increased voltage levels
field measurement on a live line worker’s body was conducted of power transmission, the electric field is also being investigated
on 138 and 345 kV lines, and the electric field recognition level for HV and UHV power systems while taking the human body
of the human body was determined as 240 kV/m (6 kV/in) [3,4]. into consideration [10–14]. The ongoing construction of 1000 kV
In this case, the worker feels like a gentle breeze blowing on his UHV projects in China has initiated research on the subject of live
skin, which is due to the action of the electric field on the hairs working technology and working personnel’s safety requirements
of the skin. If the electric field exceeds 240 kV/m, the live line for 1000 kV power networks [15–20]. In our earlier work, we
worker will hear a buzzing sound. This kind of noise is due to developed a conductive clothing to be used for live working on
the mechanical vibration on the eardrum caused by the AC field. 1000-kV transmission lines and tested its electrical performance
[17]. Furthermore, the electrical field on the worker’s body was
a Correspondence to: Linong Wang. E-mail: wangln@whu.edu.cn measured both at ground potential and at equipotential [17–19].
* School of Electrical Engineering, Wuhan University, Wuhan 430072, The measurement results showed that the maximum electric field
China on the worker’s body when performing live working on 1000-kV
** American University of Sharjah, Sharjah 26666, United Arab Emirates transmission lines was nearly twice that on 500-kV transmission
*** China Electric Power Research Institute, Wuhan 430074, China lines and about 1.5 times that on 750-kV transmission lines

© 2018 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
Y. FANG ET AL.

[16,17]. Presently, live working through a helicopter on 1000-


kV transmission lines has been investigated, and the shielding
efficiency of the conductive clothing is recommended [20].
Live working has been also adopted in substations to avoid the
huge economic losses caused by power interruptions. However,
live working technology in substations is less mature compared
to that in transmission lines. Previous work on substation’s live
working mainly focused on the minimum approach distance
(MAD) and work procedures, and most of the work was conducted
for voltage levels below 500 kV [21–25]. Until now, research
pertaining to live working in a 1000-kV substation has not
been reported. The electric field environment of a 1000-kV
substation for live working is more complex than that of 1000-
kV transmission lines because of more energized equipment and
complicated conductor arrangements in the substation. Therefore,
workers’ safety and protection must be investigated and ensured
Fig. 1. Substation 1000-kV side for electric field measurements
before conducting live working in a 1000-kV substation.
For the first time, this work investigates the electric field
on a live line worker’s body while performing work in a
1000-kV substation both at the ground and equipotential levels.
Also, it provides recommendations for shielding efficiency of
the conductive clothing and the mask that should be used for
live working in a 1000-kV substation. Section 2 reports the Probe
measurement results and analysis of electric field on the worker’s
body at various locations in an energized UHV substation at
ground potential. Section 3 presents the modeling and simulation
results of equipotential level. Our previous work on 1000-kV single Sensor chip
circuit transmission line [16–18] and the simulations performed
in this paper on the double circuit transmission line showed that
electric field calculation by finite element method (FEM) matches
very well with the actual measurements. Therefore, for safety
reasons and rigorous data acquisition, we use FEM to calculate the Signal processing
electric field on the worker’s body during the process of entering
equipotential. In Section 3, two cases are considered: one is to
Fig. 2. Photo of the electric field measurement device
approach the energized phase conductors by moving across the
tension insulators, and another is to touch the bus bar through
the insulated elevating platform. Section 4 compares the electric High voltage electrode
field of 1000-kV substation with 1000-kV single and double circuit
transmission lines at equipotential level. Our recommendations for
shielding efficiency of conductive clothing and metallic mask for
live working in a 1000-kV substation are also provided in this E DSP module
section. Finally, concluding remarks detailing the findings and
contributions made by this work are presented in Section 5.

Ground electrode Electric field probe


2. Electric Field Measurements at Ground Potential
2.1. Measurement scheme The 1000-kV UHV substa- Optical fiber
tion located at Zhejiang province, China, was selected, and the
electric field measurements were carried out at the 1000-kV side
of this substation, as shown in Fig. 1. A microelectromechanical
systems (MEMS)-based electric field measurement device, shown Fig. 3. Measuring device calibration experiment
in Fig. 2, was used for measuring the electric field at ground poten-
tial. The device consists of a field probe and a signal processing
module. The electric field probe has a diameter of 30 mm and between the two electrodes of 1 m. The probe is placed at the
it includes a sensitive chip. The sensitive chip contains a comb center of the grounded electrode, and the field strength data is
driving electrode, a shield electrode, a sensing electrode, and sup- transmitted to a computer via a optical fiber cable. In the onsite test,
porting beams. The driving electrode forces the shielding electrode the measured data is transmitted to the computer through wireless
to oscillate back and forth. This movement shields the sidewalls signals and analyzed by the computer. Electric field strengths on
of the sensing electrode periodically, thus generating an induced various parts of the worker’s body are measured to determine the
current in the sensing electrode. By demodulating the current sig- electric field level while working at ground potential. Based on
nal, the corresponding electric field strength can be obtained. The our earlier live working experience on 1000-kV transmission lines
device needs calibration [26] before conducting the electric field [17–19], seven typical locations, shown in Fig. 4, were selected
measurements in the substation. Figure 3 shows the calibration for the ground potential measurements. During the test, the worker
test layout of the measurement device in a large, uniform elec- wore a conductive clothing with 60-dB shielding efficiency and
tric field. The uniform electric field is generated by two circular, held the probe to measure the electric field at different body parts.
plane-parallel electrodes with a diameter of 3 m with the distance The electric fields outside the surface of conductive clothing and

2 IEEJ Trans (2018)


SUBSTATION LIVE WORKING AND SAFETY RECOMMENDATIONS

of the substation and the transmission lines. Table I shows that


the electric field inside the conductive clothing on the worker’s
body is negligible at the ground potential. Also, it indicates that
6 7 the electric field on the surface of the conductive clothing varies
at different locations, i.e., the electric field values are higher at
locations 4−7 than at locations 1−3 because the former locations
5 are closer to conductors or bus bars than the latter ones. The
electric field outside the conductive clothing increases to 102%
at the head top, 321% at the fingertip, and 60% at the chest
when the worker moves from location 1 to the steel structure
at location 7. The largest electric field always occurs at the top
of the head. These measurements indicate that, from the safety
perspective, more attention should be given to the electric field at
4 the worker’s head than other body parts. The brim of the cap can
be appropriately enlarged to reduce the electric field impact.

3. Electric Field Modeling and Simulations


for Entering Equipotential
3 2 1
The electric field near live conductors is much stronger than that
Fig. 4. Worker’s locations for electric field measurements at near grounded structures. Therefore, considering the risk of onsite
ground potential implementation, the electric fields on the worker while approaching
live conductors and bus bars were calculated using the FEM-based
software ANSYS. Also, through computer simulations, rigorous
Table I. Electric field strength (kV/m) on the worker at ground
electric field data could be collected at multiple points for different
potential
scenarios. We have validated the accuracy of our simulation
On the surface of conductive clothing results by demonstrating the agreement between our previously
Inside
measured and simulated results of electric field for 1000-kV single
Top of conductive
Location head Fingertip Chest clothing circuit transmission lines [17,18]. In this paper, we also performed
computer simulations for 1000-kV double circuit transmission
Loc.1 114 24 75 0.3 lines and compared the measured and calculated values of the
Loc.2 107 27 70 0.2 electric field to further validate the numerical techniques. Some
Loc.3 117 19 83 0.2 others have also found the FEM method useful and accurate for
Loc.4 196 51 92 0.5 assessing the electric field at the UHV level [20,27].
Loc.5 195 63 112 0.6 Two cases of approaching live conductors are considered. In
Loc.6 216 69 104 0.5 Case I, presented in Figs 6 and 7, the worker approaches live
Loc.7 184 80 90 0.5
conductors through tension insulators. In Case II, detailed in Figs
10 and 11, the worker approaches the bus bar through an insulated
elevating platform. Substation and human body descriptions are
inside it were measured at these seven different test points at the given in Section 3.1, while detailed modeling and calculation
ground potential. for Case I and Case II are included in Sections 3.2 and 3.3,
respectively. A workstation equipped with 16 × 3.07 GHz Intel
2.2. Measurement results and analysis The 60-dB Xeon processors and 64 GB RAM was used to ensure smooth
conductive clothing and the 20-dB metallic mask have been simulation calculations.
recommended for live working on 1000-kV transmission lines [17].
We choose the same as a reference to evaluate their efficacy for live 3.1. Human body and substation description Con-
working in the 1000-kV substation. Table I shows the measured sidering the complexity of the human body, a simplified model of
electric field on the worker’s body at ground potential. According the worker’s body was used according to the statistical data from
to GB/T 6568–2008 [8], the electric field inside the worker’s the Chinese National Standard GB 10000-88 [28]. The worker was
conductive clothing should be less than 15 kV/m while that on assumed to wear a full set of conductive clothing, which includes
exposed parts of the body should be less than 240 kV/m. Table I a mask, suit, gloves, socks, and shoes. The shape of the worker’s
shows that the electric field on the surface of conductive clothing body is more regular when the worker wears conductive cloth-
ranges from 19 to 216 kV/m and the electric field inside conductive ing, thus simplifying the worker’s body. The worker’s head was
clothing varies between 0.2 and 0.6 kV/m. These values of electric assumed spherical, and the body was modeled as an elliptic cylin-
field are well below the limits set by GB/T 6568–2008. Our der. His arms and legs were simulated as cylinders. In order to
previous work on live working on 1000-kV transmission line [17] reduce the electric field distortion caused by the edge effect, the
found the electric field to be 42–265 kV/m outside conductive cylinders of the human body model were smoothed. Table II shows
clothing and 0.4–0.8 kV/m inside conductive clothing at ground the geometry and size of the worker’s body, and Fig. 5 shows the
potential. When the worker stands right below the conductors detailed parameters of human body model.
at location 1, the electric field at the worker’s head and chest The 1000-kV substation framework is adopted with the lower
in the 1000-kV substation is 114 and 75 kV/m, respectively, frame of 38 m (height) and 61 m (width) and the upper frame
which is slightly different from those of the transmission line of 55 m (height) and 54 m (width). Four-bundle conductors with
(106.4 kV/m at the top of the head and 74.2 kV/m at chest) 71 mm diameter and 600 mm bundle spacing are used as connec-
[17]. For other locations, there is a small difference between tions between porcelain insulator strings. The tension II-string has
the electric field range of the worker in the 1000-kV substation 61 insulators (170 mm in unit spacing and 330 mm in diameter),
and the transmission lines due to the different tower structures and the suspension V-string has 59 insulators (160 mm in unit

3 IEEJ Trans (2018)


Y. FANG ET AL.

Table II. Geometry and size of the worker’s body used in


simulations

Body part Geometry Size of geometry (cm) Framework

Head Sphere Radius = 11


Arms Cylinder Radius = 6, Length = 60
Torso Elliptic cylinder Major axis = 50, Minor
axis = 30, Length = 70
Legs Cylinder Radius = 8, Length = 80

Jumper Insulator string


Bundle conductor
Head
11
sphere
Edge chamfer

60 6 Fig. 6. Case I: Simulation model for entering equipotential through


Arms
the tension insulators
cylinde
70

Torso Location1
elliptic cylinder
30 Location2
50
Location4

Legs Insulator string


cylinder 80 Location3

Location5 Framework

Fig. 7. Case I: Worker’s locations for electric field calculation


8

3.2. Case I: Worker moves along tension insulators


Fig. 5. Parameters of the human body model to live conductor Figures 6 and 7 show the case of entering
equipotential while the worker moves along the 10-m-long tension
spacing and 320 mm in diameter). The height and diameter of bus insulators to the live conductor. In this case, some typical locations
bars are 17.65 m and 250 mm, respectively. Post insulators are shown in Fig. 7 were taken into consideration for calculating
used to support the bus bars, and the height of their grounded and analyzing the electric field. The worker’s initial position
metallic supports is 7.4 m. In the substation model, the conduc- at the framework is defined as location 1 (which is similar
tors and bus bars were formed by hexahedral elements through to location 7 in Fig. 4). He starts crouching on the insulators
swap meshing, and the other equipment was meshed with tetra- and reaches the location 2, which is 1 m form the framework,
hedral elements through free meshing to reduce the number of while at location 3 he is 1 m away from the live conductor. At
elements and improve computational efficiency. In this work, elec- location 4, the worker is standing on the insulators, 0.5 m away
trostatic field analysis was applied. If one phase voltage reaches from the conductor, with his arms close to the body. Finally,
the positive peak value U m , the voltages of other two phases are the worker enters the live conductor and stands on the bundle
−U m /2. Earlier research [27] has found that when U m is applied conductor, which is defined as location 5. We assume that the
to the middle phase, the electric field distribution is more uneven worker is stretching his arms to consider the worst scenario at this
compared to the other two side phases in a 1000-kV substation. location.
Therefore, considering the most critical The model developed for this case included frameworks, bundle
√ situation,
√ the maximum
nominal system voltage U m = 1100 × 2/ 3 = 898.146 kV was conductors, jumpers, insulator strings, grading rings, and fittings.
applied to the middle phase, and the voltage applied on other two Some of the components such as post insulators were neglected
phases was −U m /2 = −449.073 kV. The potential of outer bound- in this model because they have very little effect on the results.
aries and the ground plane was assumed to be zero. The potential The worker wearing conductive clothing can be regarded as an
of the frameworks and grounded metallic supports was also set to equipotential object when computing the external electric field of
zero according to real conditions. the worker’s body. The potential of the worker was set to zero at
The presence of the human body disturbs the electric field location 1. For locations 2−4, the worker was treated as a floating
around him. This disturbance in the electric field can be defined object. The phase voltage was applied to the worker at location
by an enhancement factor [11], which is the ratio of the electric 5. Table III displays the numerical results of electric field, and
field with and without the worker, and can be defined as follows: Figs 8 and 9 show the electric field distribution for locations 3
and 5, respectively, in a visual and intuitive way. The following
Em
Enhancement factor = (1) observations can be made from these simulation results:
E0
where E m is the maximum computed electric field with the worker, 1. The electric field on the worker’s body varies with the
and E 0 is the initial electric field without the worker. working location. While approaching the live conductor, the

4 IEEJ Trans (2018)


SUBSTATION LIVE WORKING AND SAFETY RECOMMENDATIONS

Table III. Case I: Worker’s electric field strength (kV/m) calculations

Body part Loc.1 Loc.2 Loc.3 Loc.4 Loc.5


Top of head 176 196 982 1308 2494
Face 44–106 79–138 303–756 551–1170 1033–2314
Fingertip 106 609 2040 206 2876
Chest 56–93 20–59 76–378 138–413 382–652
Feet 194 393 1587 2062 385
Enhancement factor 8.29 9.22 10.91 11.98 12.39

E-field (kV/m) 3. When crouching on the insulator string (locations 2 and


0
78.10 3), the worker’s potential floats. The electric field on the
156.3
234.4 worker’s body is within 20–2040 kV/m, and the largest
312.5
390.6 electric field occurs at the worker’s fingertips.
468.8 4. When standing on the insulators (location 4), the worker
546.9
625.0 is at space potential relative to the energized conductor,
703.1
781.3
859.4
and the electric field on the worker’s body is about
937.5 200–2060 kV/m and the largest electric field appears at
1016
1094 his feet as a result of the potential difference between the
1172
1250 worker and the insulators.
1328
1406 5. When the worker stands on the live conductor (location
1484
1562 5), i.e., the worker is at line voltage, the electric field on
1641
1719 the body parts outside the bundle conductor (i.e., head and
1797 hands) is relatively high. The electric field at the fingertips
1875
1953 is 2876 kV/m, and it also exceeds 2400 kV/m at the head
2031
2109
2188
top. However, the electric field on the body parts inside the
2266 bundle conductors (e.g., the chest) is much lower (about
2344
2422 380–650 kV/m) because of the shielding effect.
2500
6. The electric field enhancement factor was calculated using
Fig. 8. Case I: Electric field distribution on the worker’s body at the simulated electric field with the human body and the
location 3 simulated electric field at these five locations without the
human body. During the process of entering equipotential,
the enhancement factor increases with decreasing distance
E-field (kV/m)
0 between the worker and the live conductor. The electric
113.3
203.9 field enhancement factor increases from 8.29 to 12.39,
294.5
385.2 which is an increase of 49.5%.
475.8
566.4
657.0
747.7 3.3. Case II: Worker moves through insulated ele-
838.3
928.9 vating platform to bus bar In this case, we studied the
1042
1133 worker’s electric field while approaching the bus bar through an
1223
1314 insulated elevating platform, as shown in Fig. 10. Figure 11 shows
1405 the various positions at which the electric field was analyzed dur-
1495
1586
1677
ing this process. Initially, the worker stands on the platform at
1767
1858
the height of the grounded structure at location 1. The platform
1971 then moves to location 2, which is 5 m away from the bus bar.
2062
2152
2243
2334
2424
2515
2605
2696
2787
2900
Drop conductor
Bus bar
Fig. 9. Case I: Electric field distribution on the worker’s body at
location 5

electric field on the worker’s body keeps increasing from


location 1 to location 5 and reaches a maximum value when GIS
the worker reaches at the line voltage at location 5.
2. The electric field on the worker’s body at ground potential
CVT
while standing on the steel structure (location 1) is less
than 194 kV/m, and the electric field values at worker’s Post insulator
head and feet are larger than on other body parts. These
results of location 1 are consistent with the measured values
of electric field at location 7 in Fig. 4, thus proving the Fig. 10. Case II: Simulation model for entering equipotential
accuracy of the simulation results as well. through the elevating platform

5 IEEJ Trans (2018)


Y. FANG ET AL.

E-field (kV/m)
Location4 0
78.13
156.3
234.4
312.5
390.6
Location3 468.8
546.9
Bus bar 625.0
703.1
781.3
859.4
937.5
1016
Location2 1094
1172
1250
1328
Post 1406
1484
insulator 1562
1641
1719
1797
Location1 1875
1953
2031
2109
2188
2266
2344
2422
Working 2500

platform
Fig. 12. Case II: Electric field distribution on the worker’s body
at location 3

E-field (kV/m)
0
84.3
168.8
Fig. 11. Case II: Worker’s locations for electric field calculation 253.1
337.5
421.9
506.3
590.6
Table IV. Case II: Worker’s electric field strength (kV/m) 675.0
759.4
calculations 843.8
928.1
1012
Body part Loc.1 Loc.2 Loc.3 Loc.4 1097
1181
1266
Top of head 243 533 1629 1351 1350
1434
Face 86–186 240–453 521–1499 450–1171 1519
Fingertip 128 176 261 270 1603
1688
Chest 14–71 59–234 65–456 270–541 1772
1856
Feet 314 613 1824 2523 1941
2025
Enhancement factor 15.62 16.01 17.80 19.54 2109
2194
2278
2362
2447
2531
At location 3, the worker’s head is 0.5 m away from the bus bar. 2616
2700
At location 4, his hands touch the bus bar, i.e., he has reached the
line voltage level. Fig. 13. Case II: Electric field distribution on the worker’s body
The simulation model developed for this case comprised of at location 4
frameworks, bundle conductors, drop conductors, bus bars, post
insulators, capacitor voltage transformer (CVT), grading rings, and from 314 to 1824 kV/m, an increase of 4.8 times during this
gas-insulated switchgear (GIS). The insulated platform was also movement.
taken into account in this modeling. In this case, the worker was 3. The electric field of the worker’s body reaches its max-
assumed as a floating object at locations 1−3, and the worker’s imum value of 2523 kV/m at location 4. However, the
potential was set as the phase voltage at location 4. Table IV shows electric field at the worker’s head is lower in this situa-
the computed results of electric field, and Figs 12 and 13 present tion than that at location 3 due to the shielding effect of
the electric field distribution at locations 3 and 4, respectively. The the bus bar.
following observations about the electric field distribution can be 4. During the process of entering equipotential by the insulated
extracted from Table IV and Figs 12 and 13. platform, the electric field enhancement factor increases
from 15.62 to 19.54, an increase of about 25.1%.
1. The electric field on the worker’s body varies at different
locations during the process of approaching the energized In Case I, the electric field distribution changes greatly with
bus bar. As the distance from the bus bar decreases, the the variation of worker’s posture. The largest electric field occurs
electric field on worker’s body keeps on increasing. The at his feet at location 1, while the peak value appears at his
maximum electric field always occurs at the worker’s feet. fingertips at location 5. In Case II, although the electric field
2. The worker is at floating potential at locations 1−3, and the increases with decreasing distance from bus bar, the electric field
electric field on his body is within the range 14–1824 kV/m. distribution changes a little before the worker touches the bus bar.
The electric field values at the worker’s head and feet are When the worker stays at the bus-bar voltage level, the electric
much larger than at other body parts. When approaching field at the head top and face in Case II is 84.6% and 97.6%,
the bus bar (from location 1 to location 3), the electric field respectively, which are lower than those in Case I. However, the
at worker’s head top changes from 243 to 1629 kV/m, an electric field at the worker’s feet in Case II is about 5.6 times
increase of 5.7 times. The electric field at his feet increases that in Case I.

6 IEEJ Trans (2018)


SUBSTATION LIVE WORKING AND SAFETY RECOMMENDATIONS

Table V. Percentage error between measured and calculated


2400 Double circuit transmission line
results
Subsatation
2200
Percentage error Percentage error
for single for double 2000

Electric field (kV/m)


Body part circuit TL (%) circuit TL (%)
1800
Top of head 5.8 3.9
Face 0.045 2.3 1600
Fingertip 7.1 6.6
1400
Chest 7.4 5.4
Feet — 1.8 1200

1000

1000 kV single circuit(measured)


800
3500
1000 kV single circuit(calculated)
1000 kV double circuit(measured)
–10 –8 –6 –4 –2 0 2 4 6 8 10
3000 1000 kV double circuit(calculated) Distance relative to center of face(cm)
1000 kV substation(calculated)
2500
Fig. 15. Electric field comparison outside the mask for substation
Electric field (kV/m)

and double circuit transmission line


2000
electric field on the surface of bundle conductors will increase with
1500 reduced number of subconductors. The maximum electric field on
the surface of an eight-bundle conductor is 2511.5 kV/m. How-
1000 ever, the maximum electric field on the surface of a six-bundle
conductor is up to 2788.1 kV/m. Therefore, the maximum elec-
500 tric field on the surface of the four-bundle conductor, which is
adopted in the 1000-kV substation, is expected to be higher than
0 2788.1 kV/m. When the worker performs equipotential operation
Top of head Face Chest Fingertip Feet on a four-bundle conductor in the substation, the electric field on
Different parts of worker's body
the worker’s body will be higher than that on the eight-bundle
Fig. 14. Electric field intensity comparison between transmission conductor of the transmission lines. Figure 14 shows that, when
lines and substation at equal potential the worker stands on the bundle conductor, the electric field on
worker’s body of a 1000- kV substation is significantly higher
than that of 1000-kV transmission lines. The maximum electric
4. UHV Substation and Transmission Line Electric field measured on worker’s body of a 1000-kV transmission line
Field Comparison and Safety Recommendations is 2298 kV/m (at the fingertips) [19]. For the substation, the max-
4.1. Comparison of the electric field between a 1000- imum electric field on the worker’s body is 2876 kV/m (at the
kV substation and 1000-kV transmission lines In our fingertips), which is 25.2% higher than that of the 1000-kV trans-
earlier work, the electric field on the worker’s body when mission line. For the other body parts, the electric field in the
performing live working on a 1000-kV single circuit transmission substation increases by 30.2% at the worker’s head and by 49.5%
line was measured and calculated [17,18]. Also, the electric at his chest as compared to that of transmission line. These differ-
field at the worker’s body in the case of a 1000-kV double ences can be ascribed to two reasons: (i) the electric field around
circuit transmission line was measured [19]; in this work, we four-bundle conductors is higher than that around eight-bundle
calculate the electric field on the worker’s body due to the double conductors; (ii) four-bundle conductors with a radius of 0.848 m
circuit transmission line. Table V summarizes the percentage provide less shielding effect for the worker than eight-bundle con-
error between the measured and simulated values of the electric ductors with a radius 1.045 m when the worker stands on the
field both for single and double circuit transmission lines. The conductors. It can be also observed from Fig. 14 that the electric
percentage error for the single circuit transmission line ranges field distribution of the 1000-kV substation is consistent with that
from 0.045% to 7.4%, while for the double circuit transmission of the 1000-kV transmission lines. That is, the electric field at the
line it is in the range 1.8−6.6%. These results prove that the body parts with a smaller radius of curvature like head and hands
simulated values of electric field are reasonably accurate and is much larger than at other body parts because the body parts with
thus can be relied upon for assessing the electric field in the a smaller radius are more likely to cause higher electric field.
1000-kV substation where it is not safe to conduct measurements The measured and calculated values of electric field outside the
mask are about the same for the 1000-kV single circuit and double
at multiple points with numerous pieces of energized substation
circuit transmission lines. However, the electric field outside the
equipment. The simulation results in this paper indicate that the
mask is significantly different for the 1000-kV substation and the
electric field in Case II is generally smaller than that in Case
transmission lines, as shown in Fig. 15. The maximum electric
I. Therefore, based on these simulation results and measurement
field of transmission lines at the center of the face is 1145 kV/m,
data from our previous work, a comparison of the worker’s
whereas in the case of the substation, the electric field at the same
electric field (on the surface of conductive clothing and mask)
point outside the mask is 1663 kV/m, which is 45.2% higher than
when standing on the bundle conductor of a 1000-kV substation
that of the transmission lines.
(Case I) and 1000-kV transmission lines is given in Fig. 14. Also,
Case I of standing on the conductor is closer to the transmission
lines scenario. 4.2. Safety recommendations for live working in a
The electric field on the surface of a 1000-kV transmission line 1000-kV substation Conductive clothing is used for live
conductor has been investigated [29] and the results show that working in a UHV power network to reduce the electric field effect.

7 IEEJ Trans (2018)


Y. FANG ET AL.

Shielding efficiency, which is the ratio of electric field reduction, In addition, the largest enhancement factor at equipotential
is an important index of conductive clothing and can be defined level indicates that worker’s posture also has a major impact on
as follows [30]: the electric field enhancement. Although our specified shielding
  efficiency will keep the worker safe, we recommend that the
Uref
SE dB = 20log10 (2) worker should watch his posture and he should be educated about
U
the posture effects on the electric field distortion. We recommend
where SE dB is the shielding efficiency, U ref represents the that the worker should not stretch his arms out and should keep
reference voltage without conductive clothing, and U is the voltage himself inside bundle conductors as much as possible to minimize
measured at the same spot with conductive clothing. the electric field distortion while standing on the conductors. When
IEC 60895–2002 [30] and GB/T 6568-2008 [8] stipulate that the worker performs operation on the energized bus bar, the electric
the shielding efficiency of conductive clothing must be higher than field at the face is much lower than the case in which the worker
40 dB up to the voltage level of 800 kV. In an electrostatic field, is standing on the conductors. Thus for bus bar live working, the
the voltage and electric field have a linear relationship, thus the worker should pay more attention to his feet because the highest
obtained electric field can be used to calculate SE dB . Based on electric field occurs at his feet. Therefore, the conductive socks
the numerical results, the maximum electric field on the worker’s must be perfectly connected to the trousers of conductive clothing
body at equipotential is 2876 kV/m. The conductive clothing with in order to guarantee the shielding effect.
a shielding efficiency of 40 dB (reduction factor of 100) cannot
meet the Chinese National Standard limit of 15 kV/m electric field
5. Conclusion
inside the conductive clothing. Therefore, conductive clothing with
greater shielding efficiency is needed to maintain the electric field The electric field on a worker for performing live working
intensity within the specified limit. in a 1000-kV substation was measured and calculated. The
The maximum electric field strength of 2876 kV/m can be agreement between measured and calculated values of electric
reduced to the allowable level of 15 kV/m by using conduc- field both for single and double circuit transmission lines proved
tive clothing with a minimum shielding efficiency of 45.7 dB. the accuracy of using FEM-based technique for the electric
Shielding efficiency greater than 45.7 kV/m will be better for field assessment. Therefore, electric field measurements at the
keeping some safety margin. For single and double circuit trans- substation were performed at ground potential while FEM-based
mission lines, the maximum measured electric field reported in substation modeling and simulations were used to evaluate the
Fig. 14 at the fingertips outside the 60-dB conductive clothing electric field while entering the equipotential level.
will be reduced to 2.164 and 2.298 kV/m, respectively. For the Our results showed that there is no significant difference
substation, the 60-dB conductive clothing will reduce the maxi- between the electric field of a 1000-kV substation and that of
mum electric field to 2.876 kV/m, which is well below the spec- transmission lines at ground potential. However, at equipotential
ified limit of 15 kV/m and is also quite close to electric field level, the maximum electric field outside the 60-dB conductive
level being experienced by transmission line workers. Therefore, clothing in the substation is 25.2% higher than that of the
we recommend the use of 60-dB conductive clothing, which transmission lines. Inside the conductive clothing, the maximum
has been already developed for 1000-kV transmission line live electric field is less than 3 kV/m, which is well below the specified
working [17]. limit of 15 kV/m. Therefore, the 60-dB conductive clothing already
Figure 15 displays the details of the calculated electric field for adopted for 1000-kV transmission line live working suffices for
a 1000-kV substation and a 1000-kV double circuit transmission the substation as well. The maximum electric field outside the
line at various points on the worker’s face (outside the mask). The metallic mask in the substation is 47.4% higher than that of
electric field on worker’s face ranges from 1033 to 2314 kV/m transmission lines. Thus, we propose that the metallic mask for live
for the substation while it varies from 785 to 1570 kV/m for the working in the substation should have an additional 5-dB shielding
transmission line. It can be seen that in a substation the electric efficiency as compared to the 20-dB metallic mask already used
field on worker’s face increases more rapidly from his jaw to the for transmission lines. Our 25-dB recommendation will limit the
forehead than in the case of transmission lines. The maximum electric field at the worker’s face to less than 130 kV/m. This is
electric field on the worker’s face in the case of transmission lines the electric field level at which currently a 1000-kV transmission
is twice its minimum value, while for the substation it is 2.24 line worker does not experience any discomfort while performing
times the minimum value. In addition, the maximum electric field live working.
on the worker’s face in the substation is 47.4% higher than that
of the transmission line. According to GB/T 6568-2008 [8], the References
electric field on the exposed body parts, such as the face, should
be less than 240 kV/m. Considering the highest field strength of
(1) Looms JST. Live working on high-voltage lines. Proceedings of
2314 kV/m, the 20-dB metallic mask adopted for transmission
the IEEE. Institute of Electrical and Electronics Engineers 1981;
line will reduce the electric field level to 231.4 kV/m. Although 128(2):89–106.
this level of electric field is below the limit of 240 kV/m, it is (2) Shimizu K, Endo H, Matsumoto G. Visualization of electric fields
significantly higher than the measured electric field inside the around a biological body. IEEE Transactions on Biomedical Engi-
metallic mask for transmission lines. In our earlier experience neering 1988; 35(5):296–302.
of live working on 1000-kV transmission lines, the electric field (3) Kouwenhoven WB, Miller CJ Jr, Barnes HC, Simpson JW, Rorden
measured inside the 20-dB metallic mask was 112–127 kV/m HL, Burgess TJ. Body current in live line working. IEEE Tran. Power
[17,19]. The worker will not have any unpleasant feelings while App. Syst. 1966; PAS-85, 4:403–411.
working on energized conductors at this level of electric field. (4) Miller CJ Jr. The measurement of electric fields in live line working.
IEEE Tran. Power App. Syst. 1967; PAS-86(4):493–498.
Also, sufficient safety margin is guaranteed without approaching
(5) Hotte PW, Gela G, Mitchell JD, Lyons PF. Electrical performance of
the maximum allowable limit of 240 kV/m. Therefore, for the
conductive suits. IEEE Trans. Power Del. 1997; 12(3):1193–1201.
1000-kV substation, we recommend an additional 5-dB shielding (6) IEEE Standard for Safety Levels with Respect to Human Expo-
efficiency of the metallic mask. The 25-dB shielding efficiency sure to Electromagnetic Fields. 0–3 kHz, IEEE Std C95.6-2002,
mask will lower the electric field on substation worker’s face form 2002.
2314 to 130 kV/m, a level that is similar to the one experienced (7) ICNIRP. Guidelines for limiting exposure to time-varying electric,
by the transmission line worker. magnetic and electromagnetic fields (up to 300GHz), International

8 IEEJ Trans (2018)


SUBSTATION LIVE WORKING AND SAFETY RECOMMENDATIONS

Commission on Non-Ionizing Radiation Protection (ICNIRP’s), (25) Xiao B, Liu K, Wu T, Liu T, Peng Y, Lie XL, Su ZM, Tang P.
2010. Experimental research on minimum approach distance and complex
(8) CIGRE Position Statement. Power-frequency electromagnetic fields gaps for live working in substation. Proceedings of 5th International
and health, on behalf of the technical committee. Electra, No. 196, Conference on Electric Utility Deregulation and Restructuring and
2001. Power Technologies (DRPT ), 2015; 1595–1599.
(9) GB Standard. Screening clothes for live working, Chinese Std. GB (26) Shimizu K, Endo H, Matsumoto G. Fundamental study on measure-
6568-2008, 2008. ment of ELF electric field at biological body surfaces. IEEE Trans-
(10) Krajewski W. Numerical assessment of electromagnetic exposure actions on Instrumentation and Measurement 1989; 38(3):779–784.
during live-line works on high-voltage objects. IET Science, Mea- (27) Li J, Peng ZR, Yang X. Potential calculation and grading ring
surement and Technology 2009; 3(1):27–38. design for ceramic insulators in 1000 kV UHV substations. IEEE
(11) Zhuang CJ, Zeng R, Zhang B, Zhu PX, Wang L, He JL. The opti- Transactions on Dielectrics and Electrical Insulation 2012; 19(2):
mization of entering route for live working on 750 kV transmission 723–732.
towers by space electric-field analysis. IEEE Trans. Power Del. 2010; (28) GB Standard. Human dimensions of Chinese adults, Chinese Std.
25(2):987–994. GB10000-88, 1988.
(12) Zemljaric B. Calculation of the connected magnetic and electric (29) Shang LQ, Li M. Simulation study on electric field of UHV
fields around an overhead-line tower for an estimation of their transmission lines with different numbers of sub-conductors. 2016
influence on maintenance personnel. IEEE Trans. Power Del. 2011; IEEE International Conference on High Voltage Engineering and
26(1):467–474. Application (ICHVE ), 2016; 1–4.
(13) Wang LN, Zhang QS, Hu JX, Liu K, Wu T, Wang JH. Research (30) IEC. Live working-conductive clothing for use at nominal voltage up
on complex gap discharge model of live working on EHV and to 800 kV a.c. and ±600 kV d.c. IEC 60895-2002, 2002.
UHV high-voltage transmission lines. Canadian J. Electrical and
Computer. Eng. 2014; 37(1):11–18.
(14) Ghassemi M, Farzaneh M. Effects of tower, phase conductors and Yaqi Fang (Non-member) received the B.E. degree in electri-
shield wires on the electrical field around a tower window during live- cal engineering from Wuhan University of
line work. IEEE Transactions on Dielectrics and Electrical Insulation Technology, Wuhan, China, in 2013. She
2015; 22(6):3413–3420.
is currently pursuing the Ph.D. degree in
(15) Huang DC, Shu YB, Ruan JJ, Hu Y. Ultra high voltage transmission
high-voltage and insulation technology at
in China: developments, current status and future prospects. Proceed-
ings of the IEEE 2009; 97(3):555–583. the School of Electrical Engineering, Wuhan
(16) Hu Y, Liu K, Wu T, Liu T, Xiao B, Tang P, Su ZM. Key University. Her current research interests
technology research and application of live working technology on include electromagnetic field calculation in
EHV/UHV transmission lines in China. Proceedings of International engineering and live working technology.
Conference on Power System Technology (POWERCON ), 2014;
2299–2309. Habibur Rehman (Non-member) received the B.Sc. degree from
(17) Liu K, Wang LN, Hu Y, Shao GW, Liu T, Hu JX, Xiao B. Research the University of Engineering and Tech-
of safety protection for live working on 1000 kV AC ultrahigh voltage nology Lahore, Pakistan, in 1990, and the
transmission line. Proceedings of Asia-Pacific Power and Energy M.S. and Ph.D. degrees from the Ohio State
Engineering Conference (APPEEC ), 2010; 1–5 University, Columbus, Ohio, in 1995 and
(18) Hu Y, Wang LN, Liu K, Liu T, Hu JX, Xiao B. On site application 2001, respectively, all in electrical engineer-
test of live working of UHV AC transmission line. High Voltage Eng.
ing. Presently, he is an Associate Professor
2009; 35(9):2053–2058.
with the Department of Electrical Engineer-
(19) Hu Y, Liu K, Wang LN, Shao GW, Liu T, Hu JX, Xiao B, Zheng
CG, Xu Y. Experimental research on live working on 1000 kV double ing, the American University of Sharjah. He
circuit AC transmission lines on the same tower. High Voltage Eng. has worked on the installation, testing, and commissioning of a
2010; 36(11):2668–2673. 500-kV substation. His research interests include power systems,
(20) Liao C, Ruan J, Liu C, Du Z, Wen W, Zhou T. Helicopter live-line power electronics, adjustable-speed drives, and alternative energy
work on 1000 kV UHV transmission lines. IEEE Trans. Power Del. vehicles.
2016; 31(3):982–989.
(21) Roux M. Innovations in live line maintenance for high voltage Bin Xiao (Non-member) received the M.E. degree in electri-
substations (63 kV) at EDF (Electricite de France). Proceed- cal engineering from Xi’an University of
ings of 6th International Conference on Transmission and Distri- Science and Technology, Xi’an, China, in
bution Construction and Live Line Maintenance (ESMO), 1993; 2007. He is currently with the China Elec-
169–184. tric Power Research Institute. His research
(22) Assad LAX, Rosa JE. Improvement in the 500 kV substations using
interests include transmission line operation
barehand methods without outage of power flow in Brazil’s north-
and maintenance technology and live work-
south interconnection. 10th International Conference on Transmission
and Distribution Construction, Operation and Live-Line Maintenance ing technology.
(ESMO), 2003; 111–117.
Tian Wu (Non-member) received the B.E. degree from the
(23) Alexandru S, Oltean M, Sevastre I, Brabete L. Live replacement
of 400 kV busbar insulators in Brasov substation. Proceedings of China Three Gorges University, Yichang,
12th International Conference on Transmission and Distribution China, in 2006, and the Ph.D. degree in
Construction, Operation and Live-Line Maintenance (ESMO), 2011; high-voltage and insulation technology from
1–7. Wuhan University, Wuhan, China, in 2012.
(24) Shunmugam S, Lumpur K. Live maintenance in high voltage He is currently with the China Electric
substations: Malaysia’s experience. Proceedings of 11th Inter- Power Research Institute. His research inter-
national Conference on Live Maintenance (ICOLIM ), 2014; ests include external insulation in power sys-
1–4. tems and live working technology.

9 IEEJ Trans (2018)


Y. FANG ET AL.

Kai Liu (Non-member) received the B.E. degree in electri- Linong Wang (Non-member) received the B.E. degree in electrical
cal engineering in 2001, and the M.E. and engineering from Xi’an Jiaotong University,
Ph.D. degrees in high-voltage and insulation Xi’an, China, in 1998, and the M.E. and
technology in 2004 and 2012, respectively, Ph.D. degrees in high-voltage and insulation
from Wuhan University, Wuhan, China. technology from Wuhan University (WU),
He is currently with the China Electric Wuhan, China, in 2006 and 2011, respec-
Power Research Institute. His research inter- tively. He is currently a Professor with the
ests include transmission line operation and School of Electrical Engineering, WU. His
maintenance technology and live working research interests include transmission line
technology. operation and maintenance technology, live working technology,
and electrical engineering materials.

10 IEEJ Trans (2018)

Vous aimerez peut-être aussi