E10 - 1 2011 International Conference on Electrical Engineering and Informatics

17-19 July 2011, Bandung, Indonesia

Testing and Diagnostics of Power Transformer in


PT. Indonesia Power
Kamojang Geothermal Power Plant Unit 1
Agus Purwadi #1, Nana Heryana#2, Dadan Nurafiat#3, Cahyono Sosetyo*4, Agus Setiana*5, Arief Mustaqim*6
#
School of Electrical Engineering and Informatics, Institute of Technology Bandung
Jalan Ganesha 10, Bandung 40132, Indonesia
1
apurwadi57@gmail.com
*
PT. Indonesia Power, Kamojang Geothermal Power Plant
Jalan Raya Kamojang Garut 44101, Indonesia

Abstract— This paper presents testing and diagnostics of 40 To obtained information of equipment’s conditions, several
MVA, 150/11.8 kV,Ynd5 main transformer and 4 MVA, 11.8/6.3 tests should be conducted.
kV auxiliary transformer on PT. Indonesia Power Kamojang Current maintenance scenario of electrical maintenance is
Geothermal Power Plan unit 1, that have been in operations for condition based maintenance or preventive maintenance.
more than 25 years, since 1982. Although the main and auxiliary Testing data is stored as a database of electrical condition.
power transformer installed have been fulfilled their design life, Combined information between historical data and testing
the concept of simple replacement of power transformer in the data will give the trend of electrical equipment’s condition.
system considering it as weak or potential source of trouble is no
The trend will give characteristic of equipment deterioration.
more valid in the present scenario of financial constraint. Today
the paradigm has changed and many efforts are being directed to Proper information about equipment condition is useful to
explore new approach/techniques of testing, monitoring, determine appropriate correcting and maintenance action
diagnosis, life assessment and condition evaluation and should be done.
possibility of extending the life of existing power transformer. Transformer is an essential part in power transmission and
In this effort of extending the life of existing power distribution. It serves as interface between power generation
transformer, testing and diagnostics of power transformer equipment and transmission system, between transmission
conditions become very important step whether it is possible to system and distribution system, and between distribution
extend certain time of useful life beyond design life and save system and load. Transformer failure will result in great loss
investment on new power transformer. This paper mainly asses
in electrical system. Hence, a well establish maintenance
the life condition of total insulation system of power transformer
due to failure of insulation material considered to be major should be conducted.
factor in power transformer, Testing and diagnostics done on
main and auxiliary power transformer based on Transformer II. TRANSFORMER TESTING
Turn Ratio (TTR) test, Winding Resistance (Rdc) test, Insulation Several tests that are conducted for power transformer are
Resistance (IR)Test, Tan delta test, Dissolve Gas Analysis (DGA) as follow:
test and Dielectric Response Analysis (Dirana) test. This kind of
tests gives in depth information regarding power transformer A. Transformer Turn Ratio Test
conditions and abnormalities. The test results show that the oil Transformer turn ratio test is conducted to obtain
and paper insulation of both power transformers were very wet
information about voltage ratio of transformer. An unusual
and need immediate purification. Condition of winding
resistance on main power transformer also showed very
deviation value from the rating indicates that there is problem
significant increase value (300%) compare to the previous in the winding.
commissioning data that mean also increasing load losses
significantly.
B. Winding Resistance (Rdc) Test
Winding resistance test is conducted to obtain resistance
Keywords— Testing, diagnostics, power transformer, life value of transformer winding. Rdc test information can be
assessment, kamojang geothermal power plant used to determine whether the winding is balance or not

I. INTRODUCTION C. Insulation Resistance (IR)Test


Electrical equipment will undergo deterioration as soon as Insulation resistance test is conducted to obtain resistance
the equipment is installed. This deterioration should be value of insulation system in power transformer. Deterioration
checked or it will cause electrical failures and malfunctions. value of insulation resistance indicates contamination
existence in insulation.

978-1-4577-0752-0/11/$26.00 ©2011 IEEE


D. Tan Delta Test TABLE I
TTR TEST RESULT (MAIN TRANSFORMER)
Tan delta test is conducted to obtain information about
dielectric losses in electrical insulation system. Insulation is Phase Maximum deviation from nominal (%)
very much like a simple capacitor. In an ideal insulation it A 0.51
only has a capacitive part. Tan delta test measure the resistive B 0.46
component of insulation. System high tan delta value will has
C 0.48
a high losses. It indicates that there is a problem in the
insulation.
E. Dissolved Gas Analysis (DGA) Test
Dissolved gas test is conducted to obtain information about
dissolved gas components in transformer oil. Combinations
and quantities of gas components in oil-immersed power
transformer can lead to malfunction of transformer or worse,
failure of the transformer.
F. Dielectric Response Analysis (Dirana) Test
Dielectric Response Analysis is conducted to obtain
information about moisture content in electrical insulation.
The test is similar to tan delta test but conducted in wide
frequency range.
(a)
III. TEST RESULTS
A. Main Transformer

(b)

Fig.1 (a) Main Transformer Under Test

(c)

Fig.2 LV Winding resistance test result (Main Transformer) Fig.3 Testing equipment (a) CPC 100 (b) DIRANA Tester
(c) IR Tester
TABLE III
SHORT CIRCUIT TEST RESULT (MAIN TRANSFORMER)

Factory Test with W-Meter 3-Phase Measurement

SN Pk [kW] f [Hz] Tap UHV ULV [kV] uk [%] Uk [V]


[kVA] Position: [kV]
40000 34 50 1 174.4 11.8 8.3 144.8
Three Phase Equivalent Test CPC 100 Measurement

f [Hz] V1 AC [V] I AC [A] Z [Ω] Phi [°] R [Ω] X [Ω] L [mH]


A-N 50 123.714 0.947 62.8226 87.1 3.1803 62.7421 199.71
B-N 50 123.04 0.94 63.1961 87.84 2.3821 63.1511 201.02
C-N 50 122.752 0.944 62.6101 87.83 2.3743 62.5651 199.15
Average Impedance
f [Hz] uk [%] Z [Ω] Phi [°] R [Ω] X [Ω] xk [%] L [mH]
Factory Test 50 8.3 63.1119 89.41 0.6463 63.1086 8.3 200.88
Values:
Measured Values: 50 8.269 62.8751 87.59 2.6455 62.8194 8.262 199.96
Difference to Factory Test [%] -0.38 -0.38 -2.04 309.32 -0.46 -0.46 -0.46

TABLE IIIII
INSULATION TEST (IR) TEST RESULT (MAIN TRANSFORMER) TABLE IVV
DGA TEST RESULT (MAIN TRANSFORMER)
Connection IR (MΩ)
Parameter result Condition
HV - Gnd 785
(ppm) 1 2 3 4
LV - Gnd 530
H2 51 100 101-700 701-1800 >1800
CH4 0 120 121-400 401-1000 >1000
C2H6 2 65 66-100 101-150 >150
C2H4 0 50 51-100 101-200 >200
C2H2 0 35 36-50 51-80 >80
CO 541 350 351-570 571-1400 >1400
CO2 9386 2500 2500-4000 4001-10000 >10000
(TDCG) 592 720 721-1920 1921-4630 >4630

TABLE V
OIL CHARACTERISTIC TEST RESULT (MAIN TRANSFORMER)
Fig.4 tan delta test result (Main Transformer)
Parameter unit result IEC 60422 : 2005
Good Enough Poor
Breakdown
kV / 2,5mm 20,0 > 50 40 < 40
voltage
Moisture
mg / kg 30,0 <5 5 > 10
content
mg KOH /g
Acidity 0,096 < 0,10 0,10 > 0,2
Oil
Sediment % weight N.A. < 0,02

Fig.5 DIRANA test result (Main Transformer)


B. Auxiliary Transformer

Fig.6 Auxiliary Transformer Under Test


Fig.9 DIRANA test result (Aux Transformer)

TABLE VI TABLE VII


TTR TEST RESULT (AUX TRANSFORMER) INSULATION TEST (IR) TEST RESULT (AUX TRANSFORMER)
Phase Maximum deviation from nominal (%)
Connection IR (MΩ)
A 0.37
HV - Gnd 332
B 0.38
C 0.43 LV - Gnd 885

TABLE VIII
DGA TEST RESULT (AUX TRANSFORMER)

Parameter result Condition


(ppm) 1 2 3 4
H2 53 100 101-700 701-1800 >1800
CH4 0 120 121-400 401-1000 >1000
C2H6 0 65 66-100 101-150 >150
C2H4 0 50 51-100 101-200 >200
C2H2 0 35 36-50 51-80 >80
CO 537 350 351-570 571-1400 >1400
Fig.7 LV Winding resistance test result (Aux Transformer) CO2 7030 2500 2500-4000 4001-10000 >10000
(TDCG) 590 720 721-1920 1921-4630 >4630

TABLE IX
OIL CHARACTERISTIC TEST RESULT (AUX TRANSFORMER)
Parameter unit result IEC 60422 : 2005
Good Enough Poor
Breakdown kV /
25,0 > 50 40 < 40
voltage 2,5mm
Moisture
mg / kg 28,6 <5 5 > 10
content
mg
Acidity KOH /g 0,085 < 0,10 0,10 > 0,2
Oil
%
Sediment N.A. < 0,02
weight
Fig.8 tan delta test result (Aux Transformer)
IV. CONCLUSIONS REFERENCES
The test results show that the paper and oil insulation of [1] P. Gill, Electrical Power Equipment Maintenance and Testing, 2nd
edition., CRC Press, Taylor & Francis Group. 2009.
both power transformers were very wet and need immediate
[2] IEEE Std. C57.12.90. IEEE Standard Test Code for Liquid-Immersed
treatment such as purification. Condition of winding Distribution, Power, and Regulating Transformer
resistance of main power transformer based on short circuit [3] IEEE Std. C57.104.2008. IEEE Guide for the Interpretation of Gases
test showed very significant increase value (300%) compare to Generated in Oil-Immersed Transformer
[4] IEEE Std. 62-1995. IEEE Guide for Diagnostics Field Testing of
the previous commissioning data that mean also increasing
Electric Power Apparatus – Part 1: Oil Filled Power Transformer,
load losses significantly. Carbon dioxide content in oil Regulators, and Reactor.
insulation of both power transformers is in dangerous [5] VDE 0530 Part 1, Recommended Practice for the measurement of
condition category according to IEEE Std C57.104.2008. Tan power factor tip-up of electrical machinery stator coil insulation.
delta test result of main power transformer show that average
tan delta increment exceeding VDE 0530. Total insulation
resistance of both power transformers is still in normal
condition range for large and medium power transformer.