SATELLITE FIRE STATION AT MIC

ELECTRICAL PANEL BOARD SCHEDULE


FOR BINDING
|

MLB015

NOTES: CONTRACTOR CONTRACT NO. GC17108800

TITLE
MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
SATELLITE FIRE STATION AT MIC, MLB015
1 ISSUED FOR APPROVAL May-19 AH AH PM
ELECTRICAL PANEL BOARD SCHEDULE
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
#N/A

REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 001 of 009 2
INDEX

SHEET NO. PANEL NAME TAG NO. LOCATION LOAD DESCRIPTION

GROUND FLOOR
3 DB-01 497-30-DB-0001 LIGHTING
LOW VOLTAGE ROOM (B1-GR-19)
GROUND FLOOR SMALL POWER
4 DB-02 497-30-DB-0002
LOW VOLTAGE ROOM (B1-GR-19) AND HVAC
GROUND FLOOR SMALL POWER
5 DB-03 497-30-DB-0003
LOW VOLTAGE ROOM (B1-GR-19) AND MISCELLANEOUS
GROUND FLOOR
6 DB-04 497-30-DB-0004 UPS
UPS ROOM (B1-GR-17)
SUBSTATION LIGHTING AND SMALL
7 DB-05 497-30-DB-0005
MV ROOM(B2-GR-01) POWER
SUBSTATION LIGHTING, SMALL POWER
8 DB-06 497-30-DB-0006
LV ROOM (B2-GR-03) AND HVAC
LIGHTING AND SMALL
9 DB-07 497-30-DB-0007 FIRE PUMP ROOM (B3-GR-01)
POWER
FOR BINDING
|

NOTES: CONTRACTOR CONTRACT NO. GC17108800

TITLE
REFERENCE DOCUMENTS:
MESAIEED INDUSTRIAL CITY
MLB015-9-EB-0001,2,3 SATELLITE FIRE STATION - ELECTRICAL SINGLE LINE DIAGRAM 2 RE-ISSUED FOR APPROVAL Jul-19 AH AH AH PM
SATELLITE FIRE STATION AT MIC, MLB015
MLB015-9-E17-0002 SATELLITE FIRE STATION - POWER SYSTEM STUDY 1 ISSUED FOR APPROVAL May-19 AH AH AH PM
MLB015-9-E34-0002 SATELLITE FIRE STATION - ELECTRICAL UTILITY DATA ELECTRICAL PANEL BOARD SCHEDULE
MLB015-9-E12-0004 SATELLITE FIRE STATION - CABLE SIZING CALCULATIONS 0 ISSUED FOR COMMENTS Jan-19 AH AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.

REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 002 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
LOAD DESCRIPTION LOAD DESCRIPTION

PROTN
TN

PROTN
TN
SE

SE
LE
CABLE

LE
CABLE
S
POLES

POLES
S
WIRESS

WIRESS
CU/LS

CU/LS
S
AMPS

S
AMPS
PHAS

PHAS
ELCB

ELCB
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B
3 Nos LTG. (F3E) & 01 Nos. EXIT AT GENERATOR ROOM (B1-GR-20), 02 Nos LTG. (F3E) & 01
QB1 R 10 DP MCB - 3x2.5mm² Nos. EXIT AT LOW VOLTAGE ROOM (B1-GR-19), 02 Nos LTG. (F3E) AT TER. ROOM (B1-GR-18), 616 QB25 R 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
03 Nos LTG. (F3E) AT UPS ROOM (B1-GR-17)
02 Nos LTG. (F3) AT GENERATOR ROOM (B1-GR-20), 02 Nos LTG. (F3) AT LOW VOLTAGE
1 ROOM (B1-GR-19), 02 Nos LTG. (F3) AT TER. ROOM (B1-GR-18), 03 Nos LTG. (F3) AT UPS ROOM 9
QB2 Y 10 DP MCB - 3x2.5mm² 540 QB26 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
(B1-GR-17)
05 Nos LTG. (C1E) & 02 Nos. EXIT AT CORRIDOR (B1-GR-03) , 03 Nos LTG. (C1E) & 03 Nos. EXIT
QB3 B 10 DP MCB - 3x2.5mm² 199 QB27 B 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
AT AIR LOCK (B1-GR-02).

QB4 R 10 DP MCB - 3x2.5mm² COVE LIGHT AT AIR LOCK (B1-GR-02). 100 QB28 R 10 DP MCB 30 mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
05 Nos LTG. (C1E) & 01 Nos. EXIT AT CORRIDOR (B1-GR-03) , 06 Nos LTG. (C1E) & 02 Nos. EXIT
QB5 Y 10 DP MCB - 3x2.5mm² AT AIR LOCK (B1-GR-02). 257 QB29 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
2 10
01 Nos LTG. (F1E) AT RADIO ROOM (B1-GR-08), 02 Nos LTG. (F1E) AT SUPERVISOR OFFICE (B1-
QB6 B 10 DP MCB - 3x2.5mm² GR-09), 03 Nos LTG. (C1E) AT DINNING AREA (B1-GR-04), 03 Nos LTG. (C2E) & 01 Nos. EXIT AT 326 QB30 B 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
PANTRY (B1-GR-07)
06 Nos LTG. (C1) AT DINNING AREA (B1-GR-04), 02 Nos LTG. (C2) & 02 Nos LTG. (W1) AT
QB7 R 10 DP MCB - 3x2.5mm² 203 QB31 R 10 DP MCB 30mA - SPARE
PANTRY (B1-GR-07)
01 Nos LTG. (F3) AT BMS ROOM (B1-GR-11), 03 Nos LTG. (F1) AT LECTURE ROOM (B1-GR-10),
QB8 Y 10 DP MCB - 3x2.5mm² 522 QB32 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
3 02 Nos LTG. (F1) AT RADIO ROOM (B1-GR-08), 02 Nos LTG. (F1) AT SUPERVISOR OFFICE (B1- 11
01 Nos LTG. (C2E) AT ABLUTION (B1-GR-05), 06 Nos LTG. (C1E) & 01 Nos. EXIT AT PRAYER 2Cx2.5 mm2
QB9 B 10 DP MCB 30mA 3x2.5mm² ROOM (B1-GR-06), 09 Nos. LTG. (C2E) & 01 Nos. EXIT AT WASH & WC (B1-GR-14), 03 Nos. LTG. 501 QB33 B 10 DP MCB - CU/XLPE/GSWA/LSZH + 03 Nos. LTG (F4) AT BATTERY ROOM (B1-GR-16). 216
(C2E) AT LOCKERS AREA (B1-GR-15), 02 Nos LTG. (F3E) AT FIRE KIT STORAGE (B1-GR-13). 1C x2.5 mm2 CU/PVC/ECC
01 Nos LTG. (C2) AT ABLUTION (B1-GR-05), 06 Nos LTG. (C1) AT PRAYER ROOM (B1-GR-06), 07
QB10 R 10 DP MCB 30mA 3x2.5mm² Nos. LTG. (C2) & 02 Nos LTG. (W1) AT WASH & WC (B1-GR-14), 03 Nos. LTG. (C2) AT LOCKERS 485 QB34 R 10 DP MCB 30mA - SPARE
AREA (B1-GR-15), 02 Nos LTG. (F3) AT FIRE KIT STORAGE (B1-GR-13).
4 12
QB11 Y 10 DP MCB - 3x2.5mm² COVE LIGHT AT PRAYER ROOM (B1-GR-06). 100 QB35 Y 10 DP MCB 30mA - SPARE

QB12 B 10 DP MCB 30mA 3x2.5mm² 04 Nos LTG. (F3) AT FUEL TANK ROOM 240 QB36 B 10 DP MCB 30mA - SPARE

QB13 R 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 QB37 R 10 DP MCB 30mA - SPARE

5 QB14 Y 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 13 QB38 Y 10 DP MCB - - SPARE

QB15 B 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 QB39 B 10 DP MCB - - SPARE

QB16 R 10 DP MCB - 3x2.5mm² 10 Nos LTG. (F5E) & 03 Nos. EXIT AT FIRE APPLIANCES BAY (B1-GR-21). 1039 QB40 R 10 DP MCB - - SPARE

6 QB17 Y 10 DP MCB - 3x2.5mm² 08 Nos LTG. (E1) & 01 Nos EXIT AT FIRE APPLIANCES BAY (B1-GR-21). 62 14 QB41 Y 10 DP MCB - - SPARE

QB18 B 10 DP MCB - 3x2.5mm² 10 Nos LTG. (F5) AT FIRE APPLIANCES BAY (B1-GR-21). 1015 QB42 B 10 DP MCB - - SPARE
FOR BINDING

QB19 R 10 DP MCB - 3x2.5mm² 07 Nos LTG. (E1) AT FIRE APPLIANCES BAY (B1-GR-21). 47 - R - - - - - SPACE
|

7 QB20 Y 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (W4) FOR FAÇADE LIGHTING. 252 15 - Y - - - - - SPACE

QB21 B 10 DP MCB 30mA 3x2.5mm² 07 Nos LTG. (W4) FOR FAÇADE LIGHTING. 294 - B - - - - - SPACE

QB22 R 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT ROOF (B1-RF-01). 360 - R - - - - - SPACE

8 QB23 Y 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT ROOF (B1-RF-01). 360 16 - Y - - - - - SPACE

QB24 B 10 DP MCB - 3x2.5mm² 06 Nos LTG. (S) AT LECTURE ROOM (B1-GR-10). 42 - B - - - - - SPACE

SUB TOTAL 3626 2868 3392 SUB TOTAL 1000 1500 1216

TOTAL (KW) 9.9 TOTAL (KW) 3.7

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 4626 4368 4608 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT CONDUCTORS 50 16 WAY
FAULT LEVEL : ** kA Total Connected Load = 13.6 KW Hz ** kA
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 9.5 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHITNG PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-01 REFERENCE DRAWINGS: MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0001 MLB015-9-EB-0002-01 415V SINGLE LINE DIAGRAM, LV SWBD-02 FED FROM LV SWBD-02 (Feeder No.1)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB015-9-ED-0003 GROUND FLOOR - POWER LAYOUT
CABLE ENTRIES: INCOMING : BELOW 5. OUTDOOR LIGHTING SHALL BE CONTROLLED VIA PHOTO ELECTRIC- LOCATION MLB015-9-ED-0004 ROOF FLOOR - POWER LAYOUT
OUTGOING : ABOVE CELL WITH OVERRIDE SWITCH . GROUND FLOOR MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED LOW VOLTAGE ROOM (B1-GR-19)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800


SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-01)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER


REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 003 of 009 2
MCB TAG

MCB TAG
LOAD (W) LOAD (W)

SZH

SZH
TN

TN
SE

ES

LE

SE

ES

LE
LOAD DESCRIPTION LOAD DESCRIPTION

WIRESS

WIRESS
CU/LS

CU/LS
AMPS
S

S
AMPS
PROT

PROT
PHAS

POLE

PHAS

POLE
CABL

CABL
ELCB
B

ELCB
B
WAY

WAY
SIZE

SIZE
NO.

NO.
R Y B R Y B
4 Nos. OF 13A TWIN SOCKET OUTLET AT LOW VOLTAGE ROOM(B1-GR-19)& 7 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, BMS, ACCESS
QB1 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 800 QB28 R 20 DP MCB - 3x4mm² 700
GENERATOR ROOM\(B1-GR-20) INTERFACE UNIT AND MOTRIZED DAMPER
3 Nos. OF 13A TWIN SOCKET OUTLET AT TER. ROOM(B1-GR-18)& NOVEC 6 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
1 QB2 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 600 10 QB29 Y 20 DP MCB - 3x4mm² 600
ROOM\(B1-GR-23) INTERFACE UNIT AND MOTRIZED DAMPER
5 Nos. OF 13A TWIN SOCKET OUTLET AT PRAYER ROOM(B1-GR-06) & LOCKERS 8 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
QB3 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB30 B 20 DP MCB - 3x4mm² 800
AREA (B1-GR-15) & FIRE KIT STORAGE (B1-GR-13) INTERFACE UNIT AND MOTRIZED DAMPER
8 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
QB4 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT FUEL TANK AREA (B1-GR-22) 400 QB31 R 20 DP MCB - 3x4mm² 800
INTERFACE UNIT, HSSD AND MOTRIZED DAMPER
2 Nos. OF 13A UNSWITCHED SPUR UNIT FOR ACCESS CONTROL PANEL
2 QB5 Y 20 DP MCB 30mA 3x4mm² 13 A POWER SOCKET FOR ELECTRONIC HOT PLATE AT PANTRY (B1-GR-07) 1000 11 QB32 Y 20 DP MCB - 3x4mm² 400
AND DOOR CONTROLLER AT TER ROOM (B1-GR-18)
4 NO. OF 13A UNSWITCHED SPUR UNIT FOR MOTRIZED FIRE DAMPER AT
QB6 B 20 DP MCB 30mA 3x4mm² HAND DRYER AT WASH & WC (B1-GR-14) 1500 QB33 B 20 DP MCB - 3x4mm² 400
FIRE APPLIANCE BAY(B1-GR-21)
5 Nos. OF 13A TWIN SOCKET OUTLET AT LECTURE ROOM (B1-GR-10)& BMS 11 NO. OF 13A UNSWITCHED SPUR UNIT FOR MOTRIZED FIRE DAMPER AT
QB7 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB34 R 20 DP MCB 30mA 3x4mm² 500
ROOM (B1-GR-11) ROOF (B1-RF-01)
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0001)
3 QB8 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET CEILING OUTLET AT LECTURE ROOM (B1-GR-10) 400 12 QB35 Y 20 DP MCB 30mA 3x4mm²
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) - REDUNDANT
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0002)
QB9 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF FLOOR BOX FB-1 AT LECTURE ROOM (B1-GR-10) 800 QB36 B 20 DP MCB 30mA 3x4mm²
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) - REDUNDANT
4 Nos. OF 13A TWIN SOCKET OUTLET AT SUPERVISOR OFFICE (B1-GR-09) &
QB10 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB37 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 4 Nos. OF 13A TWIN SOCKET OUTLET AT FIRE APPLIANCES BAY (B1-GR-15) 800
RADIO ROOM (B1-GR-08)
4 QB11 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 5 Nos. OF 13A TWIN SOCKET OUTLET AT DINING AREA (B1-GR-08) 1000 13 QB38 Y 20 DP MCB 30mA - SPARE

QB12 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT CORRIDOR (B1-GR-03) 600 QB39 B 20 DP MCB 30mA - SPARE

QB13 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 4 Nos. OF 13A TWIN SOCKET OUTLET AT FIRE APPLIANCES BAY (B1-GR-15) 800 QB40 R 20 DP MCB 30mA - SPARE

5 QB14 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 5 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF (B1-RF-01) 1000 14 QB41 Y 20 DP MCB 30mA - SPARE

QB15 B 20 DP MCB 30mA 3x4mm² 13A POWER SOCKET FOR AUDIO VISUAL RACK AT LECTURE ROOM (B1-GR-10) 500 QB42 B 20 DP MCB 30mA - SPARE

QB16 R 20 DP MCB - 3x4mm² 7 Nos. OF VAV 700 QB43 R 32 DP MCB 30mA - SPARE

6 QB17 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0001) AT TER. ROOM (B1-GR-18) 2700 15 QB44 Y 32 DP MCB 30mA - SPARE

QB18 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0002) AT TER. ROOM (B1-GR-18) 2700 QB45 B 32 DP MCB 30mA - SPARE

QB19 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0003) AT LOW VOLTAGE ROOM (B1-GR-19) 2700 QB46 R 32 DP MCB 30mA - SPARE

7 QB20 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0004) AT LOW VOLTAGE ROOM (B1-GR-19) 2700 16 QB47 Y 32 DP MCB 30mA - SPARE

QB21 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0005) AT UPS ROOM (B1-GR-17) 3500 QB48 B 20 DP MCB - - SPARE
FOR BINDING

QB22 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0006) AT BMS ROOM (B1-GR-11) 2700 QB49 R 32 DP MCB - - SPARE

8 QB23 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0007) AT RADIO ROOM (B1-GR-08) 2000 17 QB50 Y 32 DP MCB - - SPARE
|

QB24 B 20 DP MCB - 3x4mm² AIR CURTAIN (497-45-HAF-X0001) AT AIR LOCK (B1-GR-02) 1500 QB51 B 32 DP MCB - - SPARE

QB25 R 20 DP MCB - 3x4mm² AIR CURTAIN (497-45-HAF-X0002) AT AIR LOCK (B1-GR-12) 1500 QB52 R 32 DP MCB - - SPARE

9 QB26 Y 20 DP MCB 30mA 3x4mm² EXHAUST FAN (497-45-HEF-X1003) AT ROOF (B1-RF-01) 400 18 QB53 Y 32 DP MCB - - SPARE

QB27 B 20 DP MCB 30mA 3x4mm² EXHAUST FAN (497-45-HEF-X1003-01) AT ROOF (B1-RF-01) 400 QB54 B 32 DP MCB - - SPARE

SUB TOTAL 11600 11800 12500 SUB TOTAL 2800 1000 1200

TOTAL (KW) 35.9 TOTAL (KW) 5.0

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 14400 12800 13700 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 40.9 KW 50 Hz ** kA 18 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 33.3 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL POWER PANEL 80AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-02 REFERENCE DRAWINGS: MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0002 MLB015-9-EB-0002-01 415V SINGLE LINE DIAGRAM, LV SWBD-02 FED FROM LV SWBD-02 (Feeder No.2)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB015-9-ED-0003 GROUND FLOOR - POWER LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB015-9-ED-0004 ROOF FLOOR - POWER LAYOUT
OUTGOING : ABOVE GROUND FLOOR MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED LOW VOLTAGE ROOM (B1-GR-19)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-02)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER


REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 004 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
LOAD DESCRIPTION LOAD DESCRIPTION

PROTN
TN

PROTN
TN
SE

SE
CABLE
LE

LE
CABLE
S
POLES

POLES
S
WIRESS

WIRESS
CU/LS

CU/LS
S
AMPS

S
AMPS
PHAS

PHAS
ELCB

ELCB
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB1 R 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 R 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH + 4Cx4 mm2 CU/XLPE/GSWA/LSZH +
1 QB2 Y 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 9 QB17 Y 20 TP MCB 30mA ELECTRICAL CENTRAL HEATER (497-31-F-0001) AT ROOF 2300
1C x6 mm2 CU/PVC/ECC 1C x4 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB3 B 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 B 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB4 R 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 R 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH + 4Cx4 mm2 CU/XLPE/GSWA/LSZH +
2 QB5 Y 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 10 QB18 Y 20 TP MCB 30mA ELECTRICAL CENTRAL HEATER (497-31-F-0002) AT ROOF 2300
1C x6 mm2 CU/PVC/ECC 1C x4 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB6 B 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 B 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB7 R 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 R
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
3 QB8 Y 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 11 QB19 Y 32 TP MCB 30mA - SPARE
1C x6 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
QB9 B 20 DP MCB 30mA FUEL PUMP (497-92-P-0001) AT GENERATOR ROOM (B1-GR-20) 500 B
1C x4 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
QB10 R 20 DP MCB 30mA HOT WATER CIRCULATION PUMP (497-31-P-0001) AT ROOF 500 R
1C x4 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
4 QB11 Y 20 DP MCB 30mA 16A 2P+E EXPLOSION PROOF SOCKET AT BATTERY ROOM 500 12 QB20 Y 20 TP MCB 30mA - SPARE
1C x4 mm2 CU/PVC/ECC
QB12 B 32 DP MCB 30mA - SPARE B

R 1000 R
4Cx6 mm2 CU/XLPE/GSWA/LSZH +
5 QB13 Y 32 TP MCB 30mA 32A,3PH+N+E POWER SOCKET AT GENERATOR ROOM (B1-GR-20) 1000 13 QB21 Y 20 TP MCB 30mA - SPARE
1C x6 mm2 CU/PVC/ECC
B 1000 B

R 1000 QB22 R 32 DP MCB 30mA - SPARE


4Cx6 mm2 CU/XLPE/GSWA/LSZH +
6 QB14 Y 32 TP MCB 30mA 32A,3PH+N+E POWER SOCKET AT FIRE APPLIANCE BAY (B1-GR-21) 1000 14 QB23 Y 20 DP MCB 30mA - SPARE
1C x6 mm2 CU/PVC/ECC
B 1000 QB24 B 20 DP MCB 30mA - SPARE

R 2100 - R - - - - - SPACE
4Cx6 mm2 CU/XLPE/GSWA/LSZH +
FOR BINDING

7 QB15 Y 32 TP MCB 30mA WATER COOLER (497-24-E-0001) AT ROOF 2100 15 - Y - - - - - SPACE


1C x6 mm2 CU/PVC/ECC
B 2100 - B - - - - - SPACE
|

R 500 - R - - - - - SPACE
4Cx4mm2 CU/XLPE/GSWA/LSZH +
8 QB16 Y 20 TP MCB 30mA WATER BOOSTER PUMP (497-24-P-0002) AT ROOF 500 16 - Y - - - - - SPACE
1C x4 mm2 CU/PVC/ECC
B 500 - B - - - - - SPACE

SUB TOTAL 11600 9100 8600 SUB TOTAL 4600 4600 4600

TOTAL (KW) 29.3 TOTAL (KW) 13.8

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 16200 13700 13200 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 43.1 KW 50 Hz ** kA 16 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 21.8 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL POWER PANEL 80AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-03 REFERENCE DRAWINGS: MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0003 MLB015-9-EB-0002-01 415V SINGLE LINE DIAGRAM, LV SWBD-02 FED FROM LV SWBD-02 (Feeder No.3)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB015-9-ED-0003 GROUND FLOOR - POWER LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB015-9-ED-0004 ROOF FLOOR - POWER LAYOUT
OUTGOING : ABOVE GROUND FLOOR MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED ELEC. ROOM-1 (B1-GR-38)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE

TP : TRIPLE POLE TITLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-03)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER


REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 005 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
LOAD DESCRIPTION LOAD DESCRIPTION
PROTN
TN

PROTN
TN
SE

SE
CABLE
LE

CABLE
LE
S
POLES

POLES
S
WIRESS

WIRESS
CU/LS

CU/LS
S
AMPS

S
AMPS
PHAS

PHAS
ELCB

ELCB
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B

QB1 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT TER. ROOM (B1-GR-04) 400 QB10 R 20 DP MCB 30mA 3x4mm² 16A POWER SOCKET FOR PA/GA RACK AT T.E.R ROOM (B1-GR-04) 1000
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0001)
1 QB2 Y 20 DP MCB 30mA 3x4mm² 200 4 QB11 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT RADIO ROOM (B1-GR-08) 400
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04)
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0002) 2C x 6 mm2 CU/XLPE/GSWA/LSZ
QB3 B 20 DP MCB 30mA 3x4mm² 2000 QB12 B 32 DP MCB 30mA 110 DC UPS RECTIFIER 1000
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) +1C x 6 mm2 CU/PVC/ECC
2C x 6 mm2 CU/XLPE/GSWA/LSZ
QB4 R 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB13 R 32 DP MCB 30mA 110 DC UPS RECTIFIER (REDUNDANT)
+1C x 6 mm2 CU/PVC/ECC
2 QB5 Y 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 5 QB14 Y 20 DP MCB 30mA - SPARE

QB6 B 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB15 B 20 DP MCB - - SPARE

QB7 R 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB16 R 32 DP MCB 30mA - SPARE

3 QB8 Y 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA AT SITE 100 6 QB17 Y 32 DP MCB 30mA - SPARE

QB9 B 20 DP MCB - 3x4mm² 1 NO. OF 13A UNSWITCHED SPUR UNIT FOR FACP ATAIR LOCK (B1-GR-02) 200 QB18 B 32 DP MCB - - SPARE

SUB TOTAL 600 400 2300 SUB TOTAL 1000 400 1000

TOTAL (KW) 3.3 TOTAL (KW) 2.4

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
FOR BINDING

MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 1600 800 3300 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|

HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT
CONDUCTORS 50 6 WAY
FAULT LEVEL : ** kA Total Connected Load = 5.7 KW Hz ** kA
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 4.0 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL UPS PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-04 REFERENCE DRAWINGS: MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0004 MLB015-9-EB-0003 UPS - SINGLE LINE DIAGRAM FED FROM UPS
FRAMEWORK REQUIRED : YES CIRCUITS. MLB015-9-ED-0003 GROUND FLOOR - POWER LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB015-9-E17-0002 POWER SYSTEM STUDY
OUTGOING : ABOVE GROUND FLOOR
CABLE GLAND PLATE : UNDRILLED UPS ROOM (B1-GR-17)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-04)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER


REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 006 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
TN

TN
LE

LE
SE

SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES

POLES
ES
WIRESS

WIRESS
CU/LS

CU/LS
AMPS
S

S
AMPS
PROT

CABL

PROT

CABL
PHAS

PHAS
ELCB
B

ELCB
B
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B
3x2.5mm² 05 Nos LTG. (F3E) & 03 Nos. EXIT AT SWITCHGEAR ROOM (B2-GR-01) &
QB1 R 10 DP MCB - 324 R 500
MICC CABLE TRANSFORMER RM (B2-GR-02)
3x2.5mm² 08 Nos LTG. (F3) AT SWITCH GEAR ROOM (B2-GR-01) & TRANSFORMER RM (B2-GR- 4x6mm² +1x6mm²
1 QB2 Y 10 DP MCB - 480 4 QB10 Y 32 TP MCB 30mA 32A,3PH+N+E POWER SOCKET AT TRANSFORMER ROOM (B2-GR-02) 500
MICC CABLE 02) MICC CABLE
4x4mm² +2x2.5mm²
QB3 B 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT TRANSFORMER ROOM (B2-GR-02) 600 B 500
MICC CABLE
4x4mm² +2x2.5mm²
QB4 R 32 DP MCB 30mA 4 Nos. OF 13A TWIN SOCKET OUTLET AT MV SWITCHGEAR ROOM(B2-GR-01) 800 QB11 R 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
2 QB5 Y 20 DP MCB - 2 Nos. OF 13A UNSWITCHED SPUR UNIT FOR HSSD PANEL & NOVEC PANEL 400 5 QB12 Y 32 DP MCB 30mA - SPARE
MICC CABLE
3x4mm²
QB6 B 20 DP MCB - 4 Nos. OF 13A UNSWITCHED SPUR UNIT FOR MOTORIZED DAMPER 200 QB13 B 32 DP MCB - - SPARE
MICC CABLE
QB7 R 10 DP MCB 30mA - SPARE - R - - - - - SPACE

3 QB8 Y 10 DP MCB - - SPARE 6 - Y - - - - - SPACE

QB9 B 20 DP MCB 30mA - SPARE - B - - - - - SPACE

SUB TOTAL 1124 880 800 SUB TOTAL 500 500 500

TOTAL (KW) 2.8 TOTAL (KW) 1.5

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
FOR BINDING

MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 1624 1380 1300 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|

CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 4.3 KW 50 Hz ** kA 6 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 3.0 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-05 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0005 MLB014-9-EB-0001-01 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-01 (Feeder No.4)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE SUBSTATION MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED MV ROOM(B2-GR-01)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-05)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 007 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
TN

TN
LE

LE
SE

SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES

POLES
ES
WIRESS

WIRESS
CU/LS

CU/LS
AMPS
S

S
AMPS
PROT

CABL

PROT

CABL
PHAS

PHAS
ELCB
B

ELCB
B
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B
3x2.5mm²
QB1 R 10 DP MCB - 06 Nos LTG. (F3) & 01 Nos. EXIT AT LV ROOM (B2-GR-03). 368 QB10 R 10 DP MCB 30mA - SPARE
MICC CABLE
3x2.5mm²
1 QB2 Y 10 DP MCB 30mA 07 Nos LTG. (F3) WALL MOUNTED FOR SUBSTATION 420 4 QB11 Y 10 DP MCB - - SPARE
MICC CABLE
4x4mm² +2x2.5mm²
QB3 B 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT LV ROOM (B2-GR-03) 600 QB12 B 20 DP MCB 30mA - SPARE
MICC CABLE
4x4mm² +2x2.5mm²
QB4 R 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF 600 QB13 R 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
2 QB5 Y 20 DP MCB - 1 No. OF 13A UNSWITCHED SPUR UNIT FOR FACP 200 5 QB14 Y 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
QB6 B 20 DP MCB - 3 Nos. OF 13A UNSWITCHED SPUR UNIT FOR HSSD PANEL & NOVEC PANEL& BMS 500 QB15 B 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
QB7 R 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0101) AT LV ROOM (B2-GR-03) 2700 QB16 R 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
3 QB8 Y 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0102) AT LV ROOM (B2-GR-03) 2700 6 QB17 Y 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
QB9 B 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0103) AT LV ROOM (B2-GR-03) 2700 QB18 B 32 DP MCB 30mA - SPARE
MICC CABLE
SUB TOTAL 3668 3320 3800 SUB TOTAL 0 0 0

TOTAL (KW) 10.8 TOTAL (KW) 0.0

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
FOR BINDING

MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 3668 3320 3800 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|

CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 10.8 KW 50 Hz ** kA 4 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 9.2 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-06 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0006 MLB015-9-EB-0001-01 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-01 (Feeder No.5)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE SUBSTATION MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED LV ROOM (B2-GR-03)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-06)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 008 of 009 2
TAG

TAG
LOAD (W) LOAD (W)

SZH

SZH
TN

TN
LE

LE
SE

SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES

POLES
ES
WIRESS

WIRESS
CU/LS

CU/LS
AMPS
S

S
AMPS
PROT

CABL

PROT

CABL
PHAS

PHAS
ELCB
B

ELCB
B
WAY

WAY
MCB

MCB
SIZE

SIZE
NO.

NO.
R Y B R Y B
3x4mm² FIRE
QB1 R 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT FIRE PUMP ROOM (B3-GR-01). 360 QB10 R 20 DP MCB - EXHAUST FAN (497-45-HEF-X0003) AT FIRE PUMP ROOM (B3-GR-01). 600
RESISTANT CABLE
3x2.5mm² FIRE
1 QB2 Y 10 DP MCB 30mA 03 Nos LTG. (F3E) & 01 Nos. EXIT AT FIRE PUMP ROOM (B3-GR-01). 188 4 QB11 Y 20 DP MCB - 3x4mm² 1 No. OF 13A UNSWITCHED SPUR UNIT FOR MOTORIZED DAMPER 100
RESISTANT CABLE
QB3 B 10 DP MCB 30mA 3x2.5mm² 04 Nos LTG. (F3) AT TANK AREA 240 QB12 B 10 DP MCB 30mA - SPARE

QB4 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT AT FIRE PUMP ROOM (B3-GR-01). 600 QB13 R 10 DP MCB - - SPARE

2 QB5 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF 400 5 QB14 Y 20 DP MCB - - SPARE

QB6 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT TANK AREA 600 QB15 B 20 DP MCB - - SPARE

QB7 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (4977-45-HSU-X0201) AT FIRE PUMP ROOM (B3-GR-01) 2700 QB16 R 32 DP MCB 30mA - SPARE

3 QB8 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0202) AT FIRE PUMP ROOM (B3-GR-01) 2700 6 QB17 Y 32 DP MCB 30mA - SPARE

QB9 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0203) AT FIRE PUMP ROOM (B3-GR-01) 2700 QB18 B 32 DP MCB 30mA - SPARE

SUB TOTAL 3660 3288 3540 SUB TOTAL 600 100 0

TOTAL (KW) 10.5 TOTAL (KW) 0.7

MANUFACTURER: LOAD DETAILS


SPECIFIC REQUIREMENTS ADDITIONAL REQUIREMENTS DISTRIBUTION BOARD:
FOR BINDING

MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 4260 3388 3540 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|

CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 11.2 KW 50 Hz ** kA 4 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 9.6 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-07 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0007 MLB015-9-EB-0001 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-02 (Feeder No.4)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE FIRE PUMP ROOM (B3-GR-01) MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED

ABBREVIATIONS: CONTRACTOR CONTRACT NO. GC17108800

SP : SINGLE POLE FS : FUSE SWITCH

DP : DOUBLE POLE SF : SWITCH FUSE


TITLE
TP : TRIPLE POLE

TPN : TRIPLE POLE & NEUTRAL


MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
4P : 4 POLE SATELLITE FIRE STATION AT MIC, MLB015
LSZH : LOW SMOKE ZERO HALOGEN 1 ISSUED FOR APPROVAL May-19 AH AH PM
MCB : MINIATURE CIRCUIT BREAKER
ELECTRICAL PANEL BOARD SCHEDULE (DB-07)
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
RCBO : RESIDUAL CURRENT CIRCUIT BREAKER WITH OVER CURRENT PROTECTION
#N/A

MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 009 of 009 2

Vous aimerez peut-être aussi