MLB015
TITLE
MESAIEED INDUSTRIAL CITY
2 RE-ISSUED FOR APPROVAL Jul-19 AH AH PM
SATELLITE FIRE STATION AT MIC, MLB015
1 ISSUED FOR APPROVAL May-19 AH AH PM
ELECTRICAL PANEL BOARD SCHEDULE
0 ISSUED FOR COMMENTS Jan-19 AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
#N/A
REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 001 of 009 2
INDEX
GROUND FLOOR
3 DB-01 497-30-DB-0001 LIGHTING
LOW VOLTAGE ROOM (B1-GR-19)
GROUND FLOOR SMALL POWER
4 DB-02 497-30-DB-0002
LOW VOLTAGE ROOM (B1-GR-19) AND HVAC
GROUND FLOOR SMALL POWER
5 DB-03 497-30-DB-0003
LOW VOLTAGE ROOM (B1-GR-19) AND MISCELLANEOUS
GROUND FLOOR
6 DB-04 497-30-DB-0004 UPS
UPS ROOM (B1-GR-17)
SUBSTATION LIGHTING AND SMALL
7 DB-05 497-30-DB-0005
MV ROOM(B2-GR-01) POWER
SUBSTATION LIGHTING, SMALL POWER
8 DB-06 497-30-DB-0006
LV ROOM (B2-GR-03) AND HVAC
LIGHTING AND SMALL
9 DB-07 497-30-DB-0007 FIRE PUMP ROOM (B3-GR-01)
POWER
FOR BINDING
|
TITLE
REFERENCE DOCUMENTS:
MESAIEED INDUSTRIAL CITY
MLB015-9-EB-0001,2,3 SATELLITE FIRE STATION - ELECTRICAL SINGLE LINE DIAGRAM 2 RE-ISSUED FOR APPROVAL Jul-19 AH AH AH PM
SATELLITE FIRE STATION AT MIC, MLB015
MLB015-9-E17-0002 SATELLITE FIRE STATION - POWER SYSTEM STUDY 1 ISSUED FOR APPROVAL May-19 AH AH AH PM
MLB015-9-E34-0002 SATELLITE FIRE STATION - ELECTRICAL UTILITY DATA ELECTRICAL PANEL BOARD SCHEDULE
MLB015-9-E12-0004 SATELLITE FIRE STATION - CABLE SIZING CALCULATIONS 0 ISSUED FOR COMMENTS Jan-19 AH AH AH PM ORIG. DOC. SIZE: A3 THIS IS A DATABASE PRINTOUT AND MUST NOT BE ALTERED MANUALLY REV.
REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 002 of 009 2
TAG
TAG
LOAD (W) LOAD (W)
SZH
SZH
LOAD DESCRIPTION LOAD DESCRIPTION
PROTN
TN
PROTN
TN
SE
SE
LE
CABLE
LE
CABLE
S
POLES
POLES
S
WIRESS
WIRESS
CU/LS
CU/LS
S
AMPS
S
AMPS
PHAS
PHAS
ELCB
ELCB
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
3 Nos LTG. (F3E) & 01 Nos. EXIT AT GENERATOR ROOM (B1-GR-20), 02 Nos LTG. (F3E) & 01
QB1 R 10 DP MCB - 3x2.5mm² Nos. EXIT AT LOW VOLTAGE ROOM (B1-GR-19), 02 Nos LTG. (F3E) AT TER. ROOM (B1-GR-18), 616 QB25 R 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
03 Nos LTG. (F3E) AT UPS ROOM (B1-GR-17)
02 Nos LTG. (F3) AT GENERATOR ROOM (B1-GR-20), 02 Nos LTG. (F3) AT LOW VOLTAGE
1 ROOM (B1-GR-19), 02 Nos LTG. (F3) AT TER. ROOM (B1-GR-18), 03 Nos LTG. (F3) AT UPS ROOM 9
QB2 Y 10 DP MCB - 3x2.5mm² 540 QB26 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
(B1-GR-17)
05 Nos LTG. (C1E) & 02 Nos. EXIT AT CORRIDOR (B1-GR-03) , 03 Nos LTG. (C1E) & 03 Nos. EXIT
QB3 B 10 DP MCB - 3x2.5mm² 199 QB27 B 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
AT AIR LOCK (B1-GR-02).
QB4 R 10 DP MCB - 3x2.5mm² COVE LIGHT AT AIR LOCK (B1-GR-02). 100 QB28 R 10 DP MCB 30 mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
05 Nos LTG. (C1E) & 01 Nos. EXIT AT CORRIDOR (B1-GR-03) , 06 Nos LTG. (C1E) & 02 Nos. EXIT
QB5 Y 10 DP MCB - 3x2.5mm² AT AIR LOCK (B1-GR-02). 257 QB29 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
2 10
01 Nos LTG. (F1E) AT RADIO ROOM (B1-GR-08), 02 Nos LTG. (F1E) AT SUPERVISOR OFFICE (B1-
QB6 B 10 DP MCB - 3x2.5mm² GR-09), 03 Nos LTG. (C1E) AT DINNING AREA (B1-GR-04), 03 Nos LTG. (C2E) & 01 Nos. EXIT AT 326 QB30 B 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
PANTRY (B1-GR-07)
06 Nos LTG. (C1) AT DINNING AREA (B1-GR-04), 02 Nos LTG. (C2) & 02 Nos LTG. (W1) AT
QB7 R 10 DP MCB - 3x2.5mm² 203 QB31 R 10 DP MCB 30mA - SPARE
PANTRY (B1-GR-07)
01 Nos LTG. (F3) AT BMS ROOM (B1-GR-11), 03 Nos LTG. (F1) AT LECTURE ROOM (B1-GR-10),
QB8 Y 10 DP MCB - 3x2.5mm² 522 QB32 Y 10 DP MCB 30mA 3x2.5mm² 01 Nos LIGHTING OUTLET FOR SIGNAGE AT ELEVATION. 500
3 02 Nos LTG. (F1) AT RADIO ROOM (B1-GR-08), 02 Nos LTG. (F1) AT SUPERVISOR OFFICE (B1- 11
01 Nos LTG. (C2E) AT ABLUTION (B1-GR-05), 06 Nos LTG. (C1E) & 01 Nos. EXIT AT PRAYER 2Cx2.5 mm2
QB9 B 10 DP MCB 30mA 3x2.5mm² ROOM (B1-GR-06), 09 Nos. LTG. (C2E) & 01 Nos. EXIT AT WASH & WC (B1-GR-14), 03 Nos. LTG. 501 QB33 B 10 DP MCB - CU/XLPE/GSWA/LSZH + 03 Nos. LTG (F4) AT BATTERY ROOM (B1-GR-16). 216
(C2E) AT LOCKERS AREA (B1-GR-15), 02 Nos LTG. (F3E) AT FIRE KIT STORAGE (B1-GR-13). 1C x2.5 mm2 CU/PVC/ECC
01 Nos LTG. (C2) AT ABLUTION (B1-GR-05), 06 Nos LTG. (C1) AT PRAYER ROOM (B1-GR-06), 07
QB10 R 10 DP MCB 30mA 3x2.5mm² Nos. LTG. (C2) & 02 Nos LTG. (W1) AT WASH & WC (B1-GR-14), 03 Nos. LTG. (C2) AT LOCKERS 485 QB34 R 10 DP MCB 30mA - SPARE
AREA (B1-GR-15), 02 Nos LTG. (F3) AT FIRE KIT STORAGE (B1-GR-13).
4 12
QB11 Y 10 DP MCB - 3x2.5mm² COVE LIGHT AT PRAYER ROOM (B1-GR-06). 100 QB35 Y 10 DP MCB 30mA - SPARE
QB12 B 10 DP MCB 30mA 3x2.5mm² 04 Nos LTG. (F3) AT FUEL TANK ROOM 240 QB36 B 10 DP MCB 30mA - SPARE
QB13 R 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 QB37 R 10 DP MCB 30mA - SPARE
5 QB14 Y 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 13 QB38 Y 10 DP MCB - - SPARE
QB15 B 10 DP MCB - 3x2.5mm² 05 Nos LTG. (H) AT FIRE APPLIANCES BAY (B1-GR-21). 775 QB39 B 10 DP MCB - - SPARE
QB16 R 10 DP MCB - 3x2.5mm² 10 Nos LTG. (F5E) & 03 Nos. EXIT AT FIRE APPLIANCES BAY (B1-GR-21). 1039 QB40 R 10 DP MCB - - SPARE
6 QB17 Y 10 DP MCB - 3x2.5mm² 08 Nos LTG. (E1) & 01 Nos EXIT AT FIRE APPLIANCES BAY (B1-GR-21). 62 14 QB41 Y 10 DP MCB - - SPARE
QB18 B 10 DP MCB - 3x2.5mm² 10 Nos LTG. (F5) AT FIRE APPLIANCES BAY (B1-GR-21). 1015 QB42 B 10 DP MCB - - SPARE
FOR BINDING
QB19 R 10 DP MCB - 3x2.5mm² 07 Nos LTG. (E1) AT FIRE APPLIANCES BAY (B1-GR-21). 47 - R - - - - - SPACE
|
7 QB20 Y 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (W4) FOR FAÇADE LIGHTING. 252 15 - Y - - - - - SPACE
QB21 B 10 DP MCB 30mA 3x2.5mm² 07 Nos LTG. (W4) FOR FAÇADE LIGHTING. 294 - B - - - - - SPACE
QB22 R 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT ROOF (B1-RF-01). 360 - R - - - - - SPACE
8 QB23 Y 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT ROOF (B1-RF-01). 360 16 - Y - - - - - SPACE
QB24 B 10 DP MCB - 3x2.5mm² 06 Nos LTG. (S) AT LECTURE ROOM (B1-GR-10). 42 - B - - - - - SPACE
SUB TOTAL 3626 2868 3392 SUB TOTAL 1000 1500 1216
MCB TAG
LOAD (W) LOAD (W)
SZH
SZH
TN
TN
SE
ES
LE
SE
ES
LE
LOAD DESCRIPTION LOAD DESCRIPTION
WIRESS
WIRESS
CU/LS
CU/LS
AMPS
S
S
AMPS
PROT
PROT
PHAS
POLE
PHAS
POLE
CABL
CABL
ELCB
B
ELCB
B
WAY
WAY
SIZE
SIZE
NO.
NO.
R Y B R Y B
4 Nos. OF 13A TWIN SOCKET OUTLET AT LOW VOLTAGE ROOM(B1-GR-19)& 7 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, BMS, ACCESS
QB1 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 800 QB28 R 20 DP MCB - 3x4mm² 700
GENERATOR ROOM\(B1-GR-20) INTERFACE UNIT AND MOTRIZED DAMPER
3 Nos. OF 13A TWIN SOCKET OUTLET AT TER. ROOM(B1-GR-18)& NOVEC 6 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
1 QB2 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 600 10 QB29 Y 20 DP MCB - 3x4mm² 600
ROOM\(B1-GR-23) INTERFACE UNIT AND MOTRIZED DAMPER
5 Nos. OF 13A TWIN SOCKET OUTLET AT PRAYER ROOM(B1-GR-06) & LOCKERS 8 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
QB3 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB30 B 20 DP MCB - 3x4mm² 800
AREA (B1-GR-15) & FIRE KIT STORAGE (B1-GR-13) INTERFACE UNIT AND MOTRIZED DAMPER
8 Nos. OF 13A UNSWITCHED SPUR UNIT FOR NOVEC PANEL, ACCESS
QB4 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT FUEL TANK AREA (B1-GR-22) 400 QB31 R 20 DP MCB - 3x4mm² 800
INTERFACE UNIT, HSSD AND MOTRIZED DAMPER
2 Nos. OF 13A UNSWITCHED SPUR UNIT FOR ACCESS CONTROL PANEL
2 QB5 Y 20 DP MCB 30mA 3x4mm² 13 A POWER SOCKET FOR ELECTRONIC HOT PLATE AT PANTRY (B1-GR-07) 1000 11 QB32 Y 20 DP MCB - 3x4mm² 400
AND DOOR CONTROLLER AT TER ROOM (B1-GR-18)
4 NO. OF 13A UNSWITCHED SPUR UNIT FOR MOTRIZED FIRE DAMPER AT
QB6 B 20 DP MCB 30mA 3x4mm² HAND DRYER AT WASH & WC (B1-GR-14) 1500 QB33 B 20 DP MCB - 3x4mm² 400
FIRE APPLIANCE BAY(B1-GR-21)
5 Nos. OF 13A TWIN SOCKET OUTLET AT LECTURE ROOM (B1-GR-10)& BMS 11 NO. OF 13A UNSWITCHED SPUR UNIT FOR MOTRIZED FIRE DAMPER AT
QB7 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB34 R 20 DP MCB 30mA 3x4mm² 500
ROOM (B1-GR-11) ROOF (B1-RF-01)
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0001)
3 QB8 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET CEILING OUTLET AT LECTURE ROOM (B1-GR-10) 400 12 QB35 Y 20 DP MCB 30mA 3x4mm²
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) - REDUNDANT
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0002)
QB9 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF FLOOR BOX FB-1 AT LECTURE ROOM (B1-GR-10) 800 QB36 B 20 DP MCB 30mA 3x4mm²
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) - REDUNDANT
4 Nos. OF 13A TWIN SOCKET OUTLET AT SUPERVISOR OFFICE (B1-GR-09) &
QB10 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 1000 QB37 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 4 Nos. OF 13A TWIN SOCKET OUTLET AT FIRE APPLIANCES BAY (B1-GR-15) 800
RADIO ROOM (B1-GR-08)
4 QB11 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 5 Nos. OF 13A TWIN SOCKET OUTLET AT DINING AREA (B1-GR-08) 1000 13 QB38 Y 20 DP MCB 30mA - SPARE
QB12 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT CORRIDOR (B1-GR-03) 600 QB39 B 20 DP MCB 30mA - SPARE
QB13 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 4 Nos. OF 13A TWIN SOCKET OUTLET AT FIRE APPLIANCES BAY (B1-GR-15) 800 QB40 R 20 DP MCB 30mA - SPARE
5 QB14 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 5 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF (B1-RF-01) 1000 14 QB41 Y 20 DP MCB 30mA - SPARE
QB15 B 20 DP MCB 30mA 3x4mm² 13A POWER SOCKET FOR AUDIO VISUAL RACK AT LECTURE ROOM (B1-GR-10) 500 QB42 B 20 DP MCB 30mA - SPARE
QB16 R 20 DP MCB - 3x4mm² 7 Nos. OF VAV 700 QB43 R 32 DP MCB 30mA - SPARE
6 QB17 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0001) AT TER. ROOM (B1-GR-18) 2700 15 QB44 Y 32 DP MCB 30mA - SPARE
QB18 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0002) AT TER. ROOM (B1-GR-18) 2700 QB45 B 32 DP MCB 30mA - SPARE
QB19 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0003) AT LOW VOLTAGE ROOM (B1-GR-19) 2700 QB46 R 32 DP MCB 30mA - SPARE
7 QB20 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0004) AT LOW VOLTAGE ROOM (B1-GR-19) 2700 16 QB47 Y 32 DP MCB 30mA - SPARE
QB21 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0005) AT UPS ROOM (B1-GR-17) 3500 QB48 B 20 DP MCB - - SPARE
FOR BINDING
QB22 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0006) AT BMS ROOM (B1-GR-11) 2700 QB49 R 32 DP MCB - - SPARE
8 QB23 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0007) AT RADIO ROOM (B1-GR-08) 2000 17 QB50 Y 32 DP MCB - - SPARE
|
QB24 B 20 DP MCB - 3x4mm² AIR CURTAIN (497-45-HAF-X0001) AT AIR LOCK (B1-GR-02) 1500 QB51 B 32 DP MCB - - SPARE
QB25 R 20 DP MCB - 3x4mm² AIR CURTAIN (497-45-HAF-X0002) AT AIR LOCK (B1-GR-12) 1500 QB52 R 32 DP MCB - - SPARE
9 QB26 Y 20 DP MCB 30mA 3x4mm² EXHAUST FAN (497-45-HEF-X1003) AT ROOF (B1-RF-01) 400 18 QB53 Y 32 DP MCB - - SPARE
QB27 B 20 DP MCB 30mA 3x4mm² EXHAUST FAN (497-45-HEF-X1003-01) AT ROOF (B1-RF-01) 400 QB54 B 32 DP MCB - - SPARE
SUB TOTAL 11600 11800 12500 SUB TOTAL 2800 1000 1200
TAG
LOAD (W) LOAD (W)
SZH
SZH
LOAD DESCRIPTION LOAD DESCRIPTION
PROTN
TN
PROTN
TN
SE
SE
CABLE
LE
LE
CABLE
S
POLES
POLES
S
WIRESS
WIRESS
CU/LS
CU/LS
S
AMPS
S
AMPS
PHAS
PHAS
ELCB
ELCB
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB1 R 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 R 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH + 4Cx4 mm2 CU/XLPE/GSWA/LSZH +
1 QB2 Y 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 9 QB17 Y 20 TP MCB 30mA ELECTRICAL CENTRAL HEATER (497-31-F-0001) AT ROOF 2300
1C x6 mm2 CU/PVC/ECC 1C x4 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB3 B 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 B 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB4 R 32 DP MCB - ROLLING SHUTTER AT FIRE APPLIANCE BAY (B1-GR-21) 3000 R 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH + 4Cx4 mm2 CU/XLPE/GSWA/LSZH +
2 QB5 Y 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 10 QB18 Y 20 TP MCB 30mA ELECTRICAL CENTRAL HEATER (497-31-F-0002) AT ROOF 2300
1C x6 mm2 CU/PVC/ECC 1C x4 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB6 B 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 B 2300
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
QB7 R 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 R
1C x6 mm2 CU/PVC/ECC
2Cx6 mm2 CU/XLPE/GSWA/LSZH +
3 QB8 Y 32 DP MCB 30mA RETRACTABLE POWER OUTLET AT FIRE APPLIANCE BAY (B1-GR-21) 500 11 QB19 Y 32 TP MCB 30mA - SPARE
1C x6 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
QB9 B 20 DP MCB 30mA FUEL PUMP (497-92-P-0001) AT GENERATOR ROOM (B1-GR-20) 500 B
1C x4 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
QB10 R 20 DP MCB 30mA HOT WATER CIRCULATION PUMP (497-31-P-0001) AT ROOF 500 R
1C x4 mm2 CU/PVC/ECC
2Cx4 mm2 CU/XLPE/GSWA/LSZH +
4 QB11 Y 20 DP MCB 30mA 16A 2P+E EXPLOSION PROOF SOCKET AT BATTERY ROOM 500 12 QB20 Y 20 TP MCB 30mA - SPARE
1C x4 mm2 CU/PVC/ECC
QB12 B 32 DP MCB 30mA - SPARE B
R 1000 R
4Cx6 mm2 CU/XLPE/GSWA/LSZH +
5 QB13 Y 32 TP MCB 30mA 32A,3PH+N+E POWER SOCKET AT GENERATOR ROOM (B1-GR-20) 1000 13 QB21 Y 20 TP MCB 30mA - SPARE
1C x6 mm2 CU/PVC/ECC
B 1000 B
R 2100 - R - - - - - SPACE
4Cx6 mm2 CU/XLPE/GSWA/LSZH +
FOR BINDING
R 500 - R - - - - - SPACE
4Cx4mm2 CU/XLPE/GSWA/LSZH +
8 QB16 Y 20 TP MCB 30mA WATER BOOSTER PUMP (497-24-P-0002) AT ROOF 500 16 - Y - - - - - SPACE
1C x4 mm2 CU/PVC/ECC
B 500 - B - - - - - SPACE
SUB TOTAL 11600 9100 8600 SUB TOTAL 4600 4600 4600
TAG
LOAD (W) LOAD (W)
SZH
SZH
LOAD DESCRIPTION LOAD DESCRIPTION
PROTN
TN
PROTN
TN
SE
SE
CABLE
LE
CABLE
LE
S
POLES
POLES
S
WIRESS
WIRESS
CU/LS
CU/LS
S
AMPS
S
AMPS
PHAS
PHAS
ELCB
ELCB
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
QB1 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT TER. ROOM (B1-GR-04) 400 QB10 R 20 DP MCB 30mA 3x4mm² 16A POWER SOCKET FOR PA/GA RACK AT T.E.R ROOM (B1-GR-04) 1000
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0001)
1 QB2 Y 20 DP MCB 30mA 3x4mm² 200 4 QB11 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT RADIO ROOM (B1-GR-08) 400
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04)
16A INDUSTRIALPOWER SOCKET FOR DATA RACK(JXEQ-0002) 2C x 6 mm2 CU/XLPE/GSWA/LSZ
QB3 B 20 DP MCB 30mA 3x4mm² 2000 QB12 B 32 DP MCB 30mA 110 DC UPS RECTIFIER 1000
AT TECHNICAL EQUIPMENT ROOM (B1-GR-04) +1C x 6 mm2 CU/PVC/ECC
2C x 6 mm2 CU/XLPE/GSWA/LSZ
QB4 R 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB13 R 32 DP MCB 30mA 110 DC UPS RECTIFIER (REDUNDANT)
+1C x 6 mm2 CU/PVC/ECC
2 QB5 Y 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 5 QB14 Y 20 DP MCB 30mA - SPARE
QB6 B 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB15 B 20 DP MCB - - SPARE
QB7 R 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA 100 QB16 R 32 DP MCB 30mA - SPARE
3 QB8 Y 20 DP MCB - 3x4mm² 1 No. OF 13A SPUR UNIT OUTLET FOR OUTDOOR CCTV CAMERA AT SITE 100 6 QB17 Y 32 DP MCB 30mA - SPARE
QB9 B 20 DP MCB - 3x4mm² 1 NO. OF 13A UNSWITCHED SPUR UNIT FOR FACP ATAIR LOCK (B1-GR-02) 200 QB18 B 32 DP MCB - - SPARE
SUB TOTAL 600 400 2300 SUB TOTAL 1000 400 1000
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 1600 800 3300 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|
HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT
CONDUCTORS 50 6 WAY
FAULT LEVEL : ** kA Total Connected Load = 5.7 KW Hz ** kA
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 4.0 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL UPS PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-04 REFERENCE DRAWINGS: MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0004 MLB015-9-EB-0003 UPS - SINGLE LINE DIAGRAM FED FROM UPS
FRAMEWORK REQUIRED : YES CIRCUITS. MLB015-9-ED-0003 GROUND FLOOR - POWER LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB015-9-E17-0002 POWER SYSTEM STUDY
OUTGOING : ABOVE GROUND FLOOR
CABLE GLAND PLATE : UNDRILLED UPS ROOM (B1-GR-17)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED
TAG
LOAD (W) LOAD (W)
SZH
SZH
TN
TN
LE
LE
SE
SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES
POLES
ES
WIRESS
WIRESS
CU/LS
CU/LS
AMPS
S
S
AMPS
PROT
CABL
PROT
CABL
PHAS
PHAS
ELCB
B
ELCB
B
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
3x2.5mm² 05 Nos LTG. (F3E) & 03 Nos. EXIT AT SWITCHGEAR ROOM (B2-GR-01) &
QB1 R 10 DP MCB - 324 R 500
MICC CABLE TRANSFORMER RM (B2-GR-02)
3x2.5mm² 08 Nos LTG. (F3) AT SWITCH GEAR ROOM (B2-GR-01) & TRANSFORMER RM (B2-GR- 4x6mm² +1x6mm²
1 QB2 Y 10 DP MCB - 480 4 QB10 Y 32 TP MCB 30mA 32A,3PH+N+E POWER SOCKET AT TRANSFORMER ROOM (B2-GR-02) 500
MICC CABLE 02) MICC CABLE
4x4mm² +2x2.5mm²
QB3 B 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT TRANSFORMER ROOM (B2-GR-02) 600 B 500
MICC CABLE
4x4mm² +2x2.5mm²
QB4 R 32 DP MCB 30mA 4 Nos. OF 13A TWIN SOCKET OUTLET AT MV SWITCHGEAR ROOM(B2-GR-01) 800 QB11 R 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
2 QB5 Y 20 DP MCB - 2 Nos. OF 13A UNSWITCHED SPUR UNIT FOR HSSD PANEL & NOVEC PANEL 400 5 QB12 Y 32 DP MCB 30mA - SPARE
MICC CABLE
3x4mm²
QB6 B 20 DP MCB - 4 Nos. OF 13A UNSWITCHED SPUR UNIT FOR MOTORIZED DAMPER 200 QB13 B 32 DP MCB - - SPARE
MICC CABLE
QB7 R 10 DP MCB 30mA - SPARE - R - - - - - SPACE
SUB TOTAL 1124 880 800 SUB TOTAL 500 500 500
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 1624 1380 1300 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|
CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 4.3 KW 50 Hz ** kA 6 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 3.0 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-05 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0005 MLB014-9-EB-0001-01 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-01 (Feeder No.4)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE SUBSTATION MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED MV ROOM(B2-GR-01)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED
MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 007 of 009 2
TAG
TAG
LOAD (W) LOAD (W)
SZH
SZH
TN
TN
LE
LE
SE
SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES
POLES
ES
WIRESS
WIRESS
CU/LS
CU/LS
AMPS
S
S
AMPS
PROT
CABL
PROT
CABL
PHAS
PHAS
ELCB
B
ELCB
B
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
3x2.5mm²
QB1 R 10 DP MCB - 06 Nos LTG. (F3) & 01 Nos. EXIT AT LV ROOM (B2-GR-03). 368 QB10 R 10 DP MCB 30mA - SPARE
MICC CABLE
3x2.5mm²
1 QB2 Y 10 DP MCB 30mA 07 Nos LTG. (F3) WALL MOUNTED FOR SUBSTATION 420 4 QB11 Y 10 DP MCB - - SPARE
MICC CABLE
4x4mm² +2x2.5mm²
QB3 B 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT LV ROOM (B2-GR-03) 600 QB12 B 20 DP MCB 30mA - SPARE
MICC CABLE
4x4mm² +2x2.5mm²
QB4 R 32 DP MCB 30mA 3 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF 600 QB13 R 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
2 QB5 Y 20 DP MCB - 1 No. OF 13A UNSWITCHED SPUR UNIT FOR FACP 200 5 QB14 Y 20 DP MCB - - SPARE
MICC CABLE
3x4mm²
QB6 B 20 DP MCB - 3 Nos. OF 13A UNSWITCHED SPUR UNIT FOR HSSD PANEL & NOVEC PANEL& BMS 500 QB15 B 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
QB7 R 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0101) AT LV ROOM (B2-GR-03) 2700 QB16 R 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
3 QB8 Y 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0102) AT LV ROOM (B2-GR-03) 2700 6 QB17 Y 32 DP MCB 30mA - SPARE
MICC CABLE
3x6mm²
QB9 B 32 DP MCB - DX.SPLIT UNIT (497-45-HSU-X0103) AT LV ROOM (B2-GR-03) 2700 QB18 B 32 DP MCB 30mA - SPARE
MICC CABLE
SUB TOTAL 3668 3320 3800 SUB TOTAL 0 0 0
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 3668 3320 3800 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|
CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 10.8 KW 50 Hz ** kA 4 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 9.2 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-06 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0006 MLB015-9-EB-0001-01 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-01 (Feeder No.5)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE SUBSTATION MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED LV ROOM (B2-GR-03)
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED
MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 008 of 009 2
TAG
TAG
LOAD (W) LOAD (W)
SZH
SZH
TN
TN
LE
LE
SE
SE
LOAD DESCRIPTION LOAD DESCRIPTION
POLES
ES
POLES
ES
WIRESS
WIRESS
CU/LS
CU/LS
AMPS
S
S
AMPS
PROT
CABL
PROT
CABL
PHAS
PHAS
ELCB
B
ELCB
B
WAY
WAY
MCB
MCB
SIZE
SIZE
NO.
NO.
R Y B R Y B
3x4mm² FIRE
QB1 R 10 DP MCB 30mA 3x2.5mm² 06 Nos LTG. (F3) AT FIRE PUMP ROOM (B3-GR-01). 360 QB10 R 20 DP MCB - EXHAUST FAN (497-45-HEF-X0003) AT FIRE PUMP ROOM (B3-GR-01). 600
RESISTANT CABLE
3x2.5mm² FIRE
1 QB2 Y 10 DP MCB 30mA 03 Nos LTG. (F3E) & 01 Nos. EXIT AT FIRE PUMP ROOM (B3-GR-01). 188 4 QB11 Y 20 DP MCB - 3x4mm² 1 No. OF 13A UNSWITCHED SPUR UNIT FOR MOTORIZED DAMPER 100
RESISTANT CABLE
QB3 B 10 DP MCB 30mA 3x2.5mm² 04 Nos LTG. (F3) AT TANK AREA 240 QB12 B 10 DP MCB 30mA - SPARE
QB4 R 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT AT FIRE PUMP ROOM (B3-GR-01). 600 QB13 R 10 DP MCB - - SPARE
2 QB5 Y 32 DP MCB 30mA 4x4mm² +2x2.5mm² 2 Nos. OF 13A TWIN SOCKET OUTLET AT ROOF 400 5 QB14 Y 20 DP MCB - - SPARE
QB6 B 32 DP MCB 30mA 4x4mm² +2x2.5mm² 3 Nos. OF 13A TWIN SOCKET OUTLET AT TANK AREA 600 QB15 B 20 DP MCB - - SPARE
QB7 R 32 DP MCB - 3x6mm² DX.SPLIT UNIT (4977-45-HSU-X0201) AT FIRE PUMP ROOM (B3-GR-01) 2700 QB16 R 32 DP MCB 30mA - SPARE
3 QB8 Y 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0202) AT FIRE PUMP ROOM (B3-GR-01) 2700 6 QB17 Y 32 DP MCB 30mA - SPARE
QB9 B 32 DP MCB - 3x6mm² DX.SPLIT UNIT (497-45-HSU-X0203) AT FIRE PUMP ROOM (B3-GR-01) 2700 QB18 B 32 DP MCB 30mA - SPARE
MCCB R Y B
Total Load (W)
PADLOCKING FACILITY IN "OFF" POSITION 1. ALL WIRES/CABLES SHALL BE LSZH SHEATH AND COPPER AS PER QP-PVL 4260 3388 3540 415/240 VOLTS 100 AMPS 3 PHASE 4 WIRE
|
CONDUCTORS
FAULT LEVEL : ** kA HOLD :FAULT LEVEL SHALL BE UPDATED BASED ON POWER SYSTEM STUDY REPORT Total Connected Load = 11.2 KW 50 Hz ** kA 4 WAY
SERVICE CONDITION : INDOOR 2. MAXIMUM DEMAND LOAD PER PANEL IS CALCULATED AS PER
KAHRAMAA REGULATIONS
SPECIAL SERVICE CONDITION : N/A DESCRIPTION: Maximum Demand Load (MDL) = 9.6 KW INCOMER:
DEGREE OF PROTECTION : IP-42 MIN 3. ALL CABLES SHALL BE PROVIDED WITH SUITABLE MECHANICAL LIGHTING AND POWER PANEL 40AT/100AF
TYPE OF ENCLOSURE : METAL/FORM 2b PROTECTION PANEL NAME : DB-07 REFERENCE DRAWINGS MCCB-4P
TYPE OF MOUNTING : WALL MOUNTED 4. DISTRIBUTION BOARD SHALL INCLUDE 25% SPARE OUTGOING TAG NO: 497-30-DB-0007 MLB015-9-EB-0001 KEY SINGLE LINE DIAGRAM FED FROM LV SWBD-02 (Feeder No.4)
FRAMEWORK REQUIRED : YES CIRCUITS. MLB014-9-ED-0007 SUBSTATION - LIGHTING LAYOUT
CABLE ENTRIES: INCOMING : BELOW LOCATION MLB014-9-ED-0008 SUBSTATION - POWER LAYOUT
OUTGOING : ABOVE FIRE PUMP ROOM (B3-GR-01) MLB015-9-E17-0002 POWER SYSTEM STUDY
CABLE GLAND PLATE : UNDRILLED
GLAND REQUIRED : YES
GLAND TYPE : AS REQUIRED
MCCB : MOULDED CASE CKT. BREAKER REV. DESCRIPTION DATE BY CHKD APP'D APP'D Doc. No. MLB015-9-E34-0001 Sht. 009 of 009 2