Altistart48 Troubleshooting
Page 2/4

Information

Name : Hafiz Muhammad Faisal


First name :
Company : Engro
Customer :

Project: Altistart48 Troubleshooting 06/29/2019 10:05:41 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/4

Discrimination diagram
Discrimination status :

Project: Altistart48 Troubleshooting 06/29/2019 10:05:41 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/4

Range Masterpact NW Compact NSX EasyPact EZC

Designation/Fuse NW20H1 NSX400N EZCV250N


technology
Rating (A) 2000 A 400 A 250 A

Trip unit Micrologic 5.0 A Micrologic 2.3 TM Fixed

Trip unit rating 2000 A 400 A 250 A

Trip class

Long delay settings

Ir 800 A 400 A 250 A

Tr 0.5 s 16 s NA

Short delay settings

Isd 1200 A 4000 A 2500 A

Tsd 0s 0.02 s NA

Instantaneous
tripping
Ii 4000 A 4800 A NA

Discrimination Discrimination Discrimination


Upstream
Status limit: 840A limit: 840A

Project: Altistart48 Troubleshooting 06/29/2019 10:05:41 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.

Vous aimerez peut-être aussi