Evergreen Chiller Performance Outputs

Project Name: Grand Hyatt 04/22/2008


Sales Office: Carrier, Mumbai 01:21 PM

Tag Name: 23XRV 350TR

Chiller Weights
Chiller Model ............................ 23XRV4042NRVAA9-- Total Rigging Weight .......................................... 19161 lb
Starter / VFD .............. VFD - Unit Mounted (w/ filter) Total Operating Weight ...................................... 21098 lb
Refrigerant Type ............................................... R-134a Refrigerant Weight ................................................. 750 lb
Cooler Condenser
Size .......................................................................... 40 Size .......................................................................... 42
Waterbox Type ..................... Nozzle-in-Head, 150 psi Waterbox Type ..................... Nozzle-in-Head, 150 psi
Passes ....................................................................... 2 Passes ....................................................................... 2
Tubing ............... Super E2 (SUPE2), .025 in, Copper Tubing ............. Spike Fin III (SPK3), .025 in, Copper
Fluid Type ................................................ Fresh Water Fluid Type ................................................ Fresh Water
Fouling Factor (hr-sqft-F)/BTU ....................... 0.00025 Fouling Factor (hr-sqft-F)/BTU ....................... 0.00100
Compressor Motor
Size ............................................................................ R Size ............................................................................ V
Economizer ............................................................. No Line Voltage/Hertz ......................................... 400-3-50
Flow Controls
Flasc Orifice ............................................................. 23

Output Type Full Load Part Load Part Load Part Load
Percent Load 100.00 75.00 50.00 25.00
Chiller Capacity 350 Tons 263 Tons 175 Tons 88 Tons
Chiller Input kW 216 kW 114 kW 53 kW 31 kW
Chiller Input Power 0.618 kW/Ton 0.435 kW/Ton 0.301 kW/Ton 0.360 kW/Ton
NPLV 0.356 kW/Ton N/A N/A N/A
Cooler
Entering Temp. 53.60 F 51.34 F 49.09 F 46.85 F
Leaving Temp. 44.60 F 44.60 F 44.60 F 44.60 F
Flow Rate 932.3 gpm 932.3 gpm 932.3 gpm 932.3 gpm
Pressure Drop 16.6 ft wg 16.7 ft wg 16.7 ft wg 16.8 ft wg
Condenser
Leaving Temp. 96.80 F 82.47 F 68.32 F 66.68 F
Entering Temp. 89.60 F 77.30 F 65.00 F 65.00 F
Flow Rate 1376.1 gpm 1376.1 gpm 1376.1 gpm 1376.1 gpm
Pressure Drop 17.1 ft wg 17.5 ft wg 18.1 ft wg 18.1 ft wg
Motor
Motor Rated Load Amps 398 311 248 220
Motor OLTA 430
Chiller Rated Line Amps 327 177 86 57
Chiller Inrush Amps 327
Max Fuse/CB Amps 700
Min Circuit Ampacity 409

Messages:

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is based on ARI
( 1)
Standard 550/590-2003.

Evergreen Chiller Builder v4.37 Page 1 of 1