NORTHBRIDGE

2.9MVA 3-15kV Transformer Unit

Transformer Enclosure MV Switchgear Cubicle


The transformers are packaged inside an ISO type container of the
following dimensions:
HV Switchgear
Length: 2991mm The transformer package includes MV switchgear on a
Width: 2438mm frame type ABB SafePlus CV, 15kV, 630A.
Height: 2591mm
Weight ± 9400kG Construction
Manufacturer: ABB
The container is metal clad and is of robust construction and provides Type: SafePlus Type C,V
IP55 protection for the switchgear and control system. The Rated Voltage: 15kV
transformer unit is suitable for permanent or temporary outdoor Nominal Voltage: refer to transformer
installation. The container incorporates forklift pockets, DNV Nominal Frequency: 50Hz / 60Hz
overhead lifting points and twist lock corners. Short Time Current: 21 kA
Maximum Ambient Temperature: + 40°C
Capacity Rated Current: 630A
Protection: IP2x
The unit is rated: 2900KVA, 3phase 50hz/60hz

Enclosures Control Interlock Panel


Folded steel and ISO container type enclosure are both available in
two forms: one designed for fixed installation at permanent outdoor When the control panel is energised, the main transformer cooling
locations, the other transportable for moving from site to site. Both fans will operate and a supply made available to the Battery
types give IP55 and have overhead lifting facilities. Charger.

The control panel has the following function:-


 Start main transformer Cooling Fans
General Arrangement  Supply Battery Charger
 Control MV breaker Trip Relay Circuit
The Transformer Unit is designed to be used for step up or step down  Control LV breaker Shunt Trip Circuit
applications.  Control Main Transformer and door interlock protection
circuits
Each unit consists of the following components:-
These relays and indicator lamps are connected to 24V DC from
 MV Cable Termination Chamber the battery to maintain indication of fault if the main power is
 MV switchgear Cubical disconnected
 Transformer
 LV Circuit Breaker Control Room
 LV Cable Termination Chamber Lighting, and power sockets are located in the Control Room and
 Control Interlock Panel are powered from the auxiliary supply
 Control Room
 28V Battery/Charger Unit The control room also contains:-
 Earth Bar  MV Switchgear Cubicle
 24V Battery Charger Unit
 Control Interlock Panel
 Access to MV Cable Connections
 Rubber Mat
1
Page

NORTHBRIDGE NORTHBRIDGE
Middle East Industrial Services Pte Ltd

United Arab Emirates United Kingdom Singapore


www.northbridge-me.com www.crestchic.co.uk www.northbridge-ap.com

DUSTRIAL SERVICES DUSTRIAL SERVICES


NORTHBRIDGE

2.9MVA 3-15kV Transformer Unit

Transformers

The transformers are housed at each end of the enclosure and


accessed by double doors. The base of the enclosure transformer
section is continuously welded to form a ‘Bund’ in the event of
cooling oil leakage.

Additional cooling is provided by fans mounted in the side of the


enclosure.

Protection device for the transformer and access doors are wired to
the control panel.

Three phase oil-immersed distribution transformer specification:-

Type: CTMU 24 HA 2900


Power / Cooling: 2,500kVA (overload capacity 116%) see Note 1
Number of Phases: 3
Rated Frequency: 50Hz / 60Hz
Primary Voltage: 11000 (5500)+-2x10%/433 (50Hz)
6351(3175)+-2x10%/433 (50Hz)
+20% with 60Hz
Secondary Voltage: 433
Connection: YN(YN)yn0, D(D)yn11
Altitude: < 1,000m
Maximum Ambient + 40°C
Temperature:
Impedance voltage 6%
at rated current:

Note 1: Overload capacity 110% at 2540/433V, 50Hz.


2
Page

NORTHBRIDGE NORTHBRIDGE
Middle East Industrial Services Pte Ltd

United Arab Emirates United Kingdom Singapore


www.northbridge-me.com www.crestchic.co.uk www.northbridge-ap.com