DATA CENTER UNICAUCA

HVAC Load Analysis


for

COMWARE

Prepared By:

COMWARE S.A
Ing. Carlos Medina
B O G O TA

martes, 07 de junio de 2016


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
DATA CENTER UNICAUCA
Bogota, Colombia, 112011 Page 2

Building peaks in August at 5pm.


Bldg Load Ar S %T L S N %
Descriptions ea en ot at en et N
Roof 684 0 0,00 0 7.588 7.588 3,48
Wall 348 0 0,00 0 254 254 0,12
Glass 0 0 0,00 0 0 0 0,00
Floor Slab 0 0 0,00 0 0 0 0,00
Skin Loads 0 0,00 0 7.842 7.842 3,60
Lighting 684 0 0,00 0 2.451 2.451 1,12
Equipment 57.600 0 0,00 0 206.366 206.366 94,62
Pool Latent 0 0 0,00 0 0 0 0,00
People 3 0 0,00 648 787 1.436 0,66
Partition 752 0 0,00 0 0 0 0,00
Cool. Pret. 0 0 0,00 0 0 0 0,00
Heat. Pret. 0 0 0,00 0 0 0 0,00
Cool. Vent. 0 0 0,00 0 0 0 0,00
Heat. Vent. 0 0 0,00 0 0 0 0,00
Cool. Infil. 0 0 0,00 0 0 0 0,00
Heat. Infil. 0 0 0,00 0 0 0 0,00
Draw-Thru Fan 0 0 0,00 0 0 0 0,00
Blow-Thru Fan 0 0 0,00 0 0 0 0,00
Reserve Cap. 0 0 0,00 0 0 0 0,00
Reheat Cap. 0 0 0,00 0 0 0 0,00
Supply Duct 0 0 0,00 0 0 0 0,00
Return Duct 0 0 0,00 0 0 0 0,00
Misc. Supply 0 0 0,00 0 0 0 0,00
Misc. Return 0 0 0,00 0 0 0 0,00
Building Totals 0 0,00 648 217.446 218.094 100,00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0,00 0 0 0 0,00
Infiltration 0 0,00 0 0 0 0,00
Pretreated Air 0 0,00 0 0 0 0,00
Room Loads 0 0,00 648 217.446 218.094 100,00
Plenum Loads 0 0,00 0 0 0 0,00
Fan/Duct/Misc Loads 0 0,00 0 0 0 0,00
Building Totals 0 0,00 648 217.446 218.094 100,00

Total Building Supply Air (based on a 18°TD): 13.587 CFM


Total Building Vent. Air (0,00% of Supply): 0 CFM
Total Conditioned Air Space: 684 Sq.ft
Supply Air Per Unit Area: 19,8634 CFM/Sq.ft
Area Per Cooling Capacity: 37,6 Sq.ft/Ton
Cooling Capacity Per Area: 0,0266 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 18,17 Tons

Y:\ ...\Calculo de Carga Termica Unicauca.CH8


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
DATA CENTER UNICAUCA
Bogota, Colombia, 112011 Page 3

Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.


No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 DATACENTER PISO 3 684 0 217.446 648 None None
5pm August 3 0 13.587 0 0 0
6.731 0,00 19,86 0 0 0
Room Peak Totals: 684 0 217.446 648
Total Rooms: 1 3 0 13.587 0 0 0
Unique Rooms: 1 6.731 0,00 19,86 0 0 0
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
DATA CENTER UNICAUCA
Bogota, Colombia, 112011 Page 4

Air Handler Description: DATACENTER PISO 3 Constant Volume - Proportion


Sensible Heat Ratio: 1,00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 67°DB, 55°WB, 60,65 grains
Indoor Conditions: Clg: 73°DB, 50% RH
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (,808 X 1,08 X 0) = 0 CFM
Winter Vent Outside Air (0,0% of supply) = 0 CFM
Room space sensible gain: 217.446 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 217.446 Btuh
Cooling Supply Air: 217.446 / (,808 X 1,1 X 18) = 13.587 CFM
Summer Vent Outside Air (0,0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 217.446 Btuh
Room space latent gain: 648 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 648 Btuh
Total system sensible and latent gain: 218.094 Btuh

Check Figures
Total Air Handler Supply Air (based on a 18°TD): 13.587 CFM
Total Air Handler Vent. Air (0,00% of Supply): 0 CFM
Total Conditioned Air Space: 684 Sq.ft
Supply Air Per Unit Area: 19,8634 CFM/Sq.ft
Area Per Cooling Capacity: 37,6 Sq.ft/Ton
Cooling Capacity Per Area: 0,0266 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 18,17 Tons
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
DATA CENTER UNICAUCA
Bogota, Colombia, 112011 Page 5

Roof-1-4-No.Clg-L 684 0,50 15,3 0,690 7.227 19,872 13.592


Wall-1-W-D-D 187 1 5,6 0,196 206 5,645 1.055
Wall-2-N-D-D 161 1 1,1 0,196 36 5,645 911
Partition-3-1 751,776 0/0 0,278 0 0,000 0
Lights-Prof=1 684 1,000 2.334
Equipment-Prof=1 57.600 1,000 196.539 0
People-Prof=2 3,0 1,000 750 600
Sub-total 207.092 600 0
Safety factors: +5% +8% +0%
--------- --------- ---------
Total w/ safety factors: 217.446 648 0

Lighting Cooling Loads


Special
Item Quantity Allowance Space Occur- Usage Load
Name Quantity Type Factor Fraction rences Factor (Btuh)
Electrical/mechanical 1,2 watts/sq.ft. 1 1 1 1 2.801
Miscellaneous Lighting -136,8 watts 1 1 1 1 -467
Total 2.334
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
DATA CENTER UNICAUCA
Bogota, Colombia, 112011 Page 6

Building peaks in August at 5pm.

Roof - 3,48%
Wall - 0,12%
Lighting - 1,12%

People - 0,66%
N
e
t

G
a
i
n
B
u 2
i 1
l 8
d .
i 0
n 9
g 4
Btuh
Equipm
- 94,62