Vous êtes sur la page 1sur 73

Operation Manual

BD Comfort Light Control


Code No. 99-97-2449
Edition: 01/2017 GB
Table of contents Page I

1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2 Program version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

3 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.1 Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 Block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.1 Power supply and CAN bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Nano controller 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2.2 Description of connections and jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2.3 Connection assignment Nano controller 103. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2.4 Light-emitting diodes (LEDs) / Nano controller 103 . . . . . . . . . . . . . . . . . . . . . 11
4.3 Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3.1 Power module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3.2 Analogue in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.3 Smart Light Controller SLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

5 User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26


5.1 Start screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.2 Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.2.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.2.1.1 Number of light groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.1.2 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.1.3 Screen saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.1.4 Day dependency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2.1.5 Number of day times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2.1.6 Interpolating scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2.1.7 Changing the password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.2.1.8 System Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.2.1.9 System time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.2.1.10 Controller parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.2.2 Light groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2.2.1 Number of indoor sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.2.2 Number of outdoor sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.2.3 Number of light channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2.2.4 Configuration light channels 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2.2.5 Configuration relay channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.2.6 Program number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.2.7 Move-in date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.2.8 Configuration indoor sensor 1-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page II Table of contents

5.2.2.9 Configuration outdoor sensor 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40


5.2.2.10 Sensor difference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
5.2.3 User scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
5.2.3.1 Difference standard scene - user scene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
5.2.3.2 Configuration user scene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
5.2.4 Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
5.2.4.1 Program overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
5.2.4.2 Setting the change of day . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
5.2.4.3 Creating a scene in a program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
5.2.4.4 Kind of scene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
5.2.4.5 Selection of user scene . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
5.2.4.6 Start mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
5.2.4.7 Stop mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
5.2.4.8 Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
5.2.4.9 Colour mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
5.2.4.10 Colour temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
5.2.4.11 Active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
5.2.5 Time switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
5.2.6 Control light. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
5.2.6.1 Configuration input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
5.2.6.2 Light level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
5.2.6.3 Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
5.2.6.4 Pressing time building site light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
5.2.6.5 Light groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
5.2.7 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
5.2.7.1 IO cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
5.2.7.2 Data backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
5.2.7.3 Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
5.2.7.4 Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
5.2.8 Energy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66

6 Error codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68

7 Brief instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
General Page 1

1 General
The BD Comfort Light Control consists of a Nano controller 103 with touch screen, the
three Nano I/O module PCBs "Smart Light Controller SLC", "Analog In" and a "Power
module" as well as a power supply. The control is adjusted via the touch screen.
Important information:
– Read the manual thoroughly before using the control
– Pay attention to damage
– Always ensure that there is no voltage on the device when changing or adjusting
hardware
– Check connections and completeness before commissioning:
• 4 screws, 4 dowels and a cable gland as an accessory;
• a total of 6 jumpers on the power module and 1 jumper on the "Analog In"
module;
• PE line is connected to the Nano controller 103;
• ribbon cable is connected to the Nano controller 103 and the "Smart Light
Controller SLC";
• 24 V, 5 V and GND of the power supply unit are connected to the power
module.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 2 Program version

2 Program version
The product described in this operation manual is computer-based and most of its
functions are carried out by means of software.
This operation manual corresponds to:
User interface V2.2.0
Firmware version of the modules V2.1.3
Released in February 2017

Product- and documentation changes:


BIG DUTCHMAN reserves the right to modify this document or the product described
herein without prior notice. BIG DUTCHMAN is not responsible for informing you about
a product or operation manual update. If in doubt, please contact BIG DUTCHMAN.
Last date of change appears on the front page.
NOTE
• BIG DUTCHMAN reserves all rights. The reproduction of this operation manual or
parts thereof is not permitted without prior written consent by BIG DUTCHMAN.
• BIG DUTCHMAN has spared no effort to provide this operation manual as correctly
as possible. If you come across any mistakes or inaccuracies, BIG DUTCHMAN
would be grateful for receiving a respective note.
• The contents of this operation manual may be altered without prior notice.
• Regardless of the above mentioned, BIG DUTCHMAN disclaims liability for any
type of mistake in this operation manual or the consequences thereof.
 Copyright 2017 by BIG DUTCHMAN

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Introduction Page 3

3 Introduction

3.1 Use

The BD Comfort Light Control is used for the automatic control of all types of light
sources. Thanks to the 8 analogue outputs and 4 relays, both ECG-DIM devices and
contactors can be controlled and switched. 4 digital and 8 analogue inputs are available
for checking sensors and probes. The control can be expanded with the module PCBs
of the "Nano I/O" based on CAN bus. Alternatively, there is the option of dimming the
light sources connected to the current sinks directly on the SLC if this has previously
been switched on the board.

3.2 Block diagram

The circuit diagram in figure 3-1 shows the internal design of the BD Comfort Light
Control. Internally, all Nano I/O modules are connected for communication via CAN bus
and 5 V/24 V DC. In addition, 24 V DC are provided for the voltage supply of the
externally connected sensors and light sources via each module.

Figure 3-1: Block diagram of the internal structure

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 4 Introduction

Table 3-1: Legend to figure 3-1

Number Description
1 5 V/24 V power supply
2 Nano controller 103
3 Touch screen
4 Nano I/O, Analogue In
5 Nano I/O, Smart Light Controller
6 Power module
7 Ribbon cable

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 5

4 Installation

4.1 Power supply and CAN bus

All external cables are routed into the housing by means of cable glands that are
screwed to the underside of the housing. The power supply requires a voltage of 100-
240 V AC on the primary side. For this purpose, the cable for the voltage supply is
attached to the contacts L, N and PE on the power supply unit. It is important that PE
also remains connected to the Nano controller 103 (in the cover). If further modules are
used for the control, the CAN bus cable must be connected to the corresponding
connections on the Power module.
The supply voltage and the CAN bus signal for the Nano controller 103 are routed via
the 14-pole ribbon cable.

4.2 Nano controller 103

The Nano controller 103 is the control unit for the nano I/O series and can be connected
to a touch screen. The controller is equipped with four relays, four digital and one
analogue inputs, two CAN bus connections and one USB and Ethernet interface. The
controller communicates with other module PCBs of the nano I/O series through CAN
bus, connected by a ribbon cable.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 6 Installation

4.2.1 Technical data

Technical data
Code no. 91-02-6026
Dimensions (W x L x H) 83 mm x 130 mm x 26 mm
Supply voltage range 24 VDC +/- 20 %
Current consumption Typical: 0.18 A
Maximum: 0.30 A
Inputs 1 analogue input: 0-10 V or 0-20 mA (to be set
with jumpers)
4 digital inputs: can be galvanically isolated
from the power supply (to be set with jumpers)
Outputs 4 relays
10 A at 125 V AC, 5 A at 30 V DC / 250 V AC
Ambient temperature 0 - 50 ?
Weight 0.350 kg

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 7

4.2.2 Description of connections and jumpers

1 Jumper - galvanic isolation


Jumper OFF: no galvanic isolation
Jumper ON: digital signals are galvanically isolated
2 Connection power supply and digital inputs
+24 V / GND and 4 digital inputs
3 USB ports
Purpose depends on application
4 Connection power supply and CAN bus
Power supply +24 V/GND and CAN bus 0/internal (max. length of the ribbon
cable: 2 m)
5 Jumper – termination CAN bus 0 (internal)
OFF: terminating resistor is turned off
ON: terminating resistor is turned on

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 8 Installation

6 Connection CAN bus 0:


Connection for CAN bus 0 (internal)
7 Jumper – termination CAN bus 1 (external)
OFF: terminating resistor is turned off
ON: terminating resistor is turned on
8 Connection CAN bus 1 - galvanically isolated
Connection for CAN bus 1 (external)
9 Connection analogue input
0-10 V / 0-20 mA with power supply
10 Jumper - analogue input
Jumper ON: 0-20 mA
Jumper OFF: 0-10 V
11 Connection relay
Connection for relay
12 Jumper – Real Time Clock (RTC)
ON: internal RTC active
OFF: external RTC active
13 Connection RS 232
For development purposes
14 Connection touch screen
Connection of the touch screen
15 Connection application programming interface JTAG
Connection of the JTAG API
16 Jumper boot loader
To program the controller via USB, set jumpers and restart the controller.
17 Push-button
Reserved for service purposes
18 Ethernet interface
Not equipped in standard version
19 MicroSD slot
Purpose depends on application

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 9

4.2.3 Connection assignment Nano controller 103

1 Connection +24 V/GND and 4 digital inputs


+24 V = power supply +24 V DC
GND = power supply 0 V
GND digital = 0 V digital input
Digital input 1
Digital input 2
GND digital = 0 V digital input
Digital input 3
Digital input 4

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 10 Installation

2 Connection power supply and CAN bus


Ribbon cable 2 x 7 cores
If the Nano controller-103 is connected to the power supply plus the CAN bus
via the flat-ribbon cable, this replaces the connection of the voltage supply to
connection "1" and the CAN bus to "3".
3 Connection terminal CAN bus 0 (internal)
1: CAN Low
2: CAN High
3: CAN Shield
4: CAN Ground

4 Connection terminal CAN bus 1 (external)


1: CAN Low
2: CAN High
3: CAN Shield
4: CAN Ground

5 Analogue input (0-10 V / 0-20 mA) with power supply


1: GND
2: Analogue input (0-10 V / 0-20 mA)
3: +24 V power supply

6 Relay connection terminals

C 1-4: COM connection terminal relay 1-4


S 1-4: Make-contact connection terminal relay 1-4

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 11

4.2.4 Light-emitting diodes (LEDs) / Nano controller 103

No. Description Colou Description


r
1 LED power supply green On: Power supply OK
2 Error LED red On: Error occurred
Status LED green Flashing: Processor operating / OK
3 LED power suppler USB green On: Power supply at USB port OK
port
4 Digital input LED 1 green On: digital input active
Digital input LED 2 green On: digital input active
Digital input LED 3 green On: digital input active
Digital input LED 4 green On: digital input active

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 12 Installation

4.3 Modules

The following chapter describes the modules installed as standard. Modules of the
same type (maximum 8 in the controller) must have different module numbers. The
module number results from the increase of the offset of the CAN ID by one and is set
by means of jumpers (see table 4-1). In addition, care must be taken to terminate the
last card in the control (CAN bus termination). Please find further information in the
chapters for the individual modules.

Table 4-1: Jumper settings of the module numbers

Jumpers

Offset of CAN 0 1 2 3 4 5 6 7
ID
Module 1 2 3 4 5 6 7 8
number

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 13

4.3.1 Power module

The power module is used to supply components of


a Nano I/O module series with 24 V and 5 V DC in
an easy manner. The module can be installed
where a galvanically isolated CAN bus via the
intelligent CAN bus coupler is not required. It
connects the internal CAN bus directly with the
outside.
Th power module can only be operated with the 
99-30-3914 dual power supply 5/24 V 35 W 2.2 A
110-240 V AC 50/60 Hz NW SNT RD-35B.
Otherwise, the 5 V logic voltage is not available.

Technical data
Code no. 91-02-6235
Dimensions (W x L x H) 20 mm x 107.5 mm x 35 mm
Weight 24 g
Ambient temperature 0 - 50 °C

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 14 Installation

1. Connector for additional I/O PCBs load


2. Connectors for additional PCB logic
3. Connection power supply / CAN bus
4. 24 V logic from connection power supply / CAN bus (external)
5. 24 V I/O supply to the left or the right

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 15

Connection power supply / CAN bus


CAN GND
CAN Shield = shield
Can_L = CAN Low
Can_H = CAN High
+5 V = power supply +5 V DC (max. 3 A)
GND = 0 V (GND)
+24 V = power supply +24 V DC (max. 3 A)
24 V logic from connection power supply / CAN bus (external)
If the two jumpers are set to ON, the 24 V logic is supplied by connector no. 3.
If the two jumpers are set to OFF, the 24 V logic must be supplied by connector no. 2.
24 V I/O supply to the left or to the right
All four jumpers set to the left: I/O load supply is fed to the left.
All four jumpers set to the right: I/O load supply is fed to the right.
Two jumpers set to the left, two jumpers set to the right: I/O load supply is fed to the left and the
right.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 16 Installation

Light-emitting diodes (LEDs)

Description of the LEDs


LED 5 V (green) On: 5 V DC supply voltage OK
LED 24 V (green) On: 24 V DC supply voltage OK

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 17

4.3.2 Analogue in

The module PCB "Nano I/O, analogue in" has 8 analogue inputs. These inputs can be
operated in 0 - 10 V or 0 - 20 mA mode. The DIP switches shall be set per input
depending on the requirements. The card can be connected to other PCBs of the
"Nano I/O" series via the lateral connectors.

Technical data
Code no. 91-02-6208
Dimensions (W x L x H) 50 mm x 107.5 mm x 30 mm
Weight 44 g
Ambient temperature 0 - 50 °C
Inputs 8 analogue inputs, 10 bit resolution
0 - 10 V or 0 - 20 mA (to be configured with DIP switches)

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 18 Installation

1. Connectors for additional PCBs


2. Jumper – CAN bus termination
3. ICSP programmer (only for development)
4. Jumper - connectors (CAN-bus address)
5. DIP switch inputs 1 - 8 (0 - 10 V / 0 - 20 mA)
6. + 24 V connection terminals
7. Analogue inputs
8. GND connectors
9. Module connectors (2 x 7 poles); for connection of Viper (optional)

If the card is the last node in the CAN, it must be terminated by using the Term jumper! (Jumpers
set = 120  termination)
Jumper - connector (CAN-bus address)
As supplied, the PCB without connected jumpers has the CAN-bus address 10 (hex). The
jumpers can be used to change the CAN-bus address, if required. Depending on the position
of the jumpers, the addresses 10 to 17 (hex) are possible.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 19

Conversion table decimal to hexadecimal

DIP switch
Depending on the position of the DIP switches, the individual inputs are configured either for 0
- 10 V (OFF) or 0 - 20 mA (ON) mode.
Analogue inputs
The module PCB "Nano I/O, analogue in" has 8 analogue inputs. These inputs can be
configured as 0 - 10 V or 0 - 20 mA inputs. The DIP switches shall be set per input depending
on the requirements.
0-20 mA
DIP switch = ON

0-10 V
DIP switch = OFF

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 20 Installation

Light-emitting diodes (LEDs)

Description
of the LEDs
LED1 Flashing: 
(green) processor is working (CAN
state: pre-operate)
Lit continuously: unit ready
to operate (CAN state:
operate)
LED2 (red) Flashing: error

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 21

4.3.3 Smart Light Controller SLC

The module PCB "Nano I/O, Smart Light Controller SLC" has 8 analogue 0 - 10 V
outputs. All 8 outputs can be controlled via the CAN bus. The first 4 outputs are
connected in parallel and act as current sinks with manual operation. These 4 outputs
increase the performance of the analogue 0 - 10 V control signals, as the analogue
outputs of common (0 - 10 V) control units can only be used at a limited amount to
control the ECG-DIM dimmers. The outputs 1 to 4 can be switched to manual operation
via a switch. The potentiometers 1 to 4 are responsible for the set value in manual
mode. The card can be connected to other PCBs of the "Nano I/O" series via the lateral
connectors.

Technical data
Code no. 91-02-6212
Dimensions (W x L x H) 82 mm x 107.5 mm x 30 mm
Weight 82 g
Ambient temperature 0 - 50 °C
Outputs 8 analogue 0 - 10 V outputs
Additional outputs 1 to 4 as current sink
Max. 200 ECG-DIM devices per output (1 to 4)

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 22 Installation

1. Connectors for additional PCBs


2. Jumper – CAN bus termination
3. Jumper - connectors (CAN-bus address)
4. RS232 port
5. Potentiometer - manual (output 1 - 4)
6. Switch AUTO - MANUAL
7. + 24 V connection terminals
8. Analogue 0 - 10 V outputs
9. GND connectors
10. Connector outputs 1 to 4 (current sink)
11. ICSP programmer (only for development)
12. Module connectors (2 x 7 poles); for connection of Viper (optional)

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 23

If the card is the last node in the CAN, it must be terminated by using the Term jumper! (Jumpers
set = 120  termination)
Jumper - connectors (CAN-bus address)
As supplied, the PCB without connected
jumpers has the CAN-bus address 20
(hex). The jumpers can be used to
change the CAN-bus address, if required.
Depending on the position of the
jumpers, the addresses 20 to 27 (hex)are possible.
Manual rotary switch (outputs 1 to 4)
The outputs 1 to 4 can be switched to manual operation using the switch auto-manual (6). In
the manual mode, the output voltage (10) is set at 0 to 100 % by the potentiometers 1 to 4.

Analogue 0 - 10 V outputs
The module PCB "Nano I/O, analogue out" has 8
analogue 0 - 10 V outputs.

Connector outputs 1 to 4 (current sink)

The first 4 outputs are connected in parallel. They act as current sink with manual operation and
can be switched to manual mode via a switch (6). The potentiometers 1 to 4 are responsible for
the set value in manual mode. Per output, up to 200 ECG-DIM devices can be connected.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 24 Installation

Light-emitting diodes (LEDs)

Description
of the LEDs
LED1 Flashing: 
(green) processor is working (CAN
state: pre-operate)
Lit continuously: unit ready
to operate (CAN state:
operate)
LED2 (red) Flashing: error

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Installation Page 25

Conversion table decimal to hexadecimal

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 26 User interface

5 User interface
The tree structure in table 5-1 shows the structure of the main navigation. In addition,
the most important characteristics for the use of the software are listed in the table. The
following chapter describes the complete menu navigation, including all possible
settings via the user interface.
Software data:

Table 5-1: Software data

Number of light groups 1-9


Number of user-defined scenes 0-20
Number of steps per user-defined scenes 0-10
Number of daytimes 2-6
Number of programs 0-9
Number of scenes per program per day 0-3
Number of control lights 0-2
Number of time switches 0-9
Number of switching times per time switch per day 0-10

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 27

Figure 5-1: Overview user interface

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 28 User interface

5.1 Start screen

In the start screen (fig. 5-2), all light groups are


displayed. All light groups are numbered and
can be navigated using the arrow keys
( and ). A light intensity of 0 - 100% can
be set via the respective slide in manual
mode. The set date and time are displayed in
the lower bar.

Figure 5-2: Start screen - Overview 1


With the help of the icon (manual mode)
and (automatic mode), it is possible to see
which mode is active for the respective light
group. The mode can also be changed using
these buttons. In automatic mode, the channel
or sensor value is displayed as a bar (as
shown in figure 5-3).

Figure 5-3: Start screen - Overview 2


Use the window icon ( ) to change the
display to the view on the left (figure 5-4). Here
you can switch between the light groups by
means of the navigation arrows. The light
curve current status is displayed in the
automatic mode and the light curve to be run
is shown as a graph (in figure 5-4 no light
curve is active).

Figure 5-4: Start screen - light curve


In the window on the left (fig. 5-5), a light curve
is shown. The vertical red mark represents the
current position in the program light curve.
Use the menu icon ( ) to switch to the main
menu.

Figure 5-5: Start screen - light curve


(active)

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 29

5.2 Menu

In the main menu, switch back to the start


screen by pressing the Home button ( ).
Otherwise, switch to the respective sub
menus via the eight icons shown
(figure 5-6):

Figure 5-6: Menu overview

Overview of the created light curves / light programs. Creation


of light curves and programs is possible.

Setting non-standardized light curves. These can be integrated


in the lighting program.

Overview and configuration of the light groups (assign light


channels, sensors, etc.)

Overview and creation of time switches and time periods. Day


clocks and week clocks are possible.

Configuration of control lights or building site light.

Global settings of the computer (including system time, screen


saver, etc.).

Retrieval of information from hardware and software. Creation


of back-ups and updates of the firmware of the nano disks are
possible.
Setting of energy metering using energy meters with pulse
output. Review possible up to three years.

In the following sub-items the functions and setting options in the sub menus are
explained in detail:

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 30 User interface

5.2.1 Settings

Figure 5-7: Settings - tree structure

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 31

When opening some menus, the


password is always requested first 
(fig. 5-8). This is "0000" on initial
commissioning and is confirmed with
"OK".
The password should then be changed
in this menu.
Figure 5-8: Password input
After entering the password, the "Settings"
menu (fig. 5-9) appears. Use the arrow
keys ( ) and ( ) to navigate within the
menu. To change a setting, tap the entry.
The currently set value or status is
displayed to the right of the respective
entry.

Figure 5-9: Settings - overview:


Functions that are only switched on and
off (such as the screen saver) will change
as soon as you tap the entry. Your change
will be saved immediately. A green
indicator (pos. right) means the function is
activated, a grey indicator (pos. left)
means it is deactivated (fig. 5-10).

Figure 5-10: Settings - example overview

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 32 User interface

5.2.1.1 Number of light groups

The required number of light groups (max. 9)


can be set here (fig. 5-11). A light group can
consist of several light sources, which are
always controlled in the same way. This is taken
into account later in the menu point "Light
groups" and on the start screen. Scroll the list to
change the selected value. To do this, touch the
touch screen and move the finger/pen up or
Figure 5-11: Settings - number of
down. Once the desired value appears in the
light groups
grey bar, save your setting by pressing the
memory icon ( ). To close a menu or discard
the settings, go to the close icon ( ) in the top
right corner.

5.2.1.2 Language

Select here (fig. 5-12) between German,


English and French.

Figure 5-12: Settings - language

5.2.1.3 Screen saver

When the screen saver is activated, the display is switched off one minute after the last
touch. It is switched back on with the next touch.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 33

5.2.1.4 Day dependency

This function allows you to run the lighting programs in up to six different day time
periods. After activation the time periods can be selected in the menu 5.2.4 ”Program”.
If this function is deactivated, the same programs are run every day.
Example: A light group has been assigned to the first program (adjustable in menu
5.2.2 ”Light groups”) and the time between moving in and out is 42 days. This program
is supposed to get a certain light sequence during the first 5 days after moving in. For
the remaining 37 days until moving out, the light group should be controlled differently.
To do this, the day dependency is activated and the number of periods in the "Settings"
menu is selected.
The periods (days 1 - 5 and days 6 - 42) are set in menu 5.2.4 ”Program”. Now all
programs can be set differently for both periods.

5.2.1.5 Number of day times

If the day dependency is activated, you can


select the number of day times (fig. 5-13). In
each period, up to 9 programs with up to 3
scenes can be created. The length of the
individual day time period is set at a later stage
in menu 5.2.4 ”Program”.

Figure 5-13: Settings - Number of


day times

5.2.1.6 Interpolating scenes

If you have activated day time dependency, use this function to adjust the light evenly
to the new time and to the new light intensity of the next set day time.
Example: Two day time periods were set.

Starting day of the day time period Start time Stop time
Day 1: 7:00 a.m. 4:00 p.m.
Day 3: 8:00 a.m. 3:00 p.m.
The start and stop time of the second day is interpolated when the function is activated:

Day 2: 7:30 a.m. 3:30 p.m.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 34 User interface

5.2.1.7 Changing the password

First enter your old password and confirm with "OK". Enter your new password twice in
the next step. Confirm again with "OK" and your password has been changed.

5.2.1.8 System Date

Select the current date here (fig. 5-14). The


internal calendar function always shows the
current date on the start screen.

Figure 5-14: Settings - system date

5.2.1.9 System time

The current time is set in this menu point


(fig. 5-15).

Figure 5-15: Settings - system time

5.2.1.10 Controller parameters

This function is not implemented in version 2.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 35

5.2.2 Light groups

Figure 5-16: Light groups tree structure

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 36 User interface

In the menu 5.2.2 ”Light groups” enter the settings for each light group separately. You
can use the arrows left ( ) and right ( ) to switch between the light groups. The
required number was already set in the menu point 5.2.1.1 ”Number of light groups”. A
light group consists of light sources, which are always controlled the same way.

You can rename the individual light groups. To


do this, go to the pen icon ( ) in the upper right
corner (fig. 5-17).

Figure 5-17: Light groups - overview


group 1

Use the arrow ( ) to remove the previous entry


and use ( ) to switch between upper case and
lower case (fig. 5-18). To write, press the key
with the desired letter until the letter appears on
the text line. The first letter on a key appears
when pressing once, the second letter appears
when pressing twice, and so on (fig. 5-19). If
you want to enter a number, press and hold the
respective key until the number appears. You
Figure 5-18: Name change will get a space by pressing the 0 key once.
Then save your input with the memory icon
( ).

Figure 5-19: Name change -


example

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 37

5.2.2.1 Number of indoor sensors

An indoor sensor is located in the barn and


measures the light intensity there. Up to 16
indoor sensors per light group are supported.
Select the number of connected indoor sensors
here (fig. 5-20).

Figure 5-20: Light groups - number


of indoor sensors

5.2.2.2 Number of outdoor sensors

An outdoor sensor, on the other hand, is located


outside the house and measures the intensity of
the light, so that e.g. curtains can be raised or
lowered additionally. Select the number of
connected outdoor sensors (fig. 5-21). The
maximum supported number per light group is
four.

Figure 5-21: Light groups - number


of outdoor sensors

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 38 User interface

5.2.2.3 Number of light channels

Two light channels can be used per light group.


Light sources with two channels can be
controlled with a colour mode (selectable in the
menu 5.2.4 ”Program”) to produce different
colours and colour temperatures.

Figure 5-22: Light groups - number


of light channels

In the "Zeus" lamp, the first channel controls the warm white and the
second the cold white LEDs.

5.2.2.4 Configuration light channels 1 and 2

As can be seen in figure 5-23 the module


number plus the channel are indicated when
the light channel is set. First enter the channel
to which one of the analogue inputs of the light
group is connected. The module is the "Smart
Light Controller" (4.3.3 ”Smart Light Controller
SLC”). The channels are consecutively
numbered from 1 to 8 on the SLC. Enter the
module number. Since the module number 0 is
Figure 5-23: Light group - not assigned, a module which has the jumper
configuration light setting 0 has the module number 1, in the
channel jumping position 7 it would be the module
number 8, etc. These numbers can also be
seen in menu 5.2.7.1 ”IO cards” .

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 39

5.2.2.5 Configuration relay channel

The setting of a relay channel (fig. 5-24) works


according to the same principle as that of a light
channel. With a relay channel, e.g. switch
contactors can be used to completely separate
the light group from the power supply. The
module number 0 is not assigned here either.
The Nano controller 103 has the module
number 9 and has four relay channels. As soon
Figure 5-24: Light group -
as the set brightness (automatic or manual) is
configuration relay
greater than 0 %, the relay switches.
channel

5.2.2.6 Program number

A program can be assigned to a lighting group


(fig. 5-25). Enter the number of the program to
control the light group. The program is created
later in chapter 5.2.4 ”Program”.

Figure 5-25: Light group -


configuration program
number

5.2.2.7 Move-in date

If you have activated the day dependency in the


settings, set the move-in date here (fig. 5-26).
This day is day 1 in the program sequence.
For more details, see menu 5.2.4 ”Program”.
Since a move-in date can be entered for each
light group, you can use the control for several
houses/compartments.

Figure 5-26: Light groups 


- move-in date

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 40 User interface

5.2.2.8 Configuration indoor sensor 1-16

With this setting you first specify the channel to


which the analogue output of the sensor is
connected (fig. 5-27). These are the "Analog In"
modules. The module number results from the
jumper setting plus one, since the module
number 0 is not assigned. The entry range of
the sensor can be set in the entry "Value range".
Up to 100 lux is measured when a "0" is set, and
up to 1000 lux when a "1" is set. The correction
factor is applied to a voltage drop, e.g. due to
Figure 5-27: Light groups -
configuration indoor the long distance of the sensor to the module, in
sensor order to take exactly this into consideration in
the measured values.

5.2.2.9 Configuration outdoor sensor 1-4

The setting of an outdoor sensor (fig. 5-28) is


performed in the same manner as that of an
indoor sensor. See section 5.2.2.8
”Configuration indoor sensor 1-16”.

Figure 5-28: Light groups -


configuration outdoor
sensor

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 41

5.2.2.10 Sensor difference

If several sensors are used per light group to


measure the light intensity, the maximum
permissible difference of the sensor values can
be set (fig. 5-29). If this difference is exceeded,
the sensors with the largest deviation are not
taken into account, since they could be dirty.
When the sensor difference is maintained, the
mean value of all the values of the sensors is
created.
Figure 5-29: Light groups 
- sensor difference
Example:
Two indoor sensors are connected and the adjusted sensor difference is 20 %.
Case 1:

Sensor Measured light intensity


Sensor 1 25 lux
Sensor 2 27 lux
Since the values of the sensors differ by less than 20 %, the average value (26 lux) is
calculated and assumed as the average light intensity in the house.
Case 2:

Sensor Measured light intensity


Sensor 1 25 lux
Sensor 2 17 lux
In this case, the sensor difference of both values is greater than 20 %. Therefore, the
sensor with the lower value (sensor 2) is not taken into account.

The discussed settings already allow you to control the lamps


manually from on start screen. To use the automatic mode, refer to
the following menu guides.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 42 User interface

5.2.3 User scenes

Figure 5-30: User scenes - creating a user scene

5.2.3.1 Difference standard scene - user scene

Standard scene User scene

Figure 5-31: User scenes - process of the Figure 5-32: User scenes - example user
standard scene scene
Figure 5-31 shows the given process of a In a user scene, the process can be
standard scene. The parameters for a defined by individual steps (maximum 10),
standard scene are set directly in menu as shown in figure 5-32 .
point 5.2.4 ”Program” .

A user scene is required when you need a different process than the
standard one for a scene.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 43

5.2.3.2 Configuration user scene

Up to 12 user scenes can be created (fig. 5-33).


These can be integrated in a program at a later
stage. To modify or create a scene, go to an
entry.

Figure 5-33: User scenes -


overview

The name of the scene can be changed with the


pen icon ( ). In this view (fig. 5-34), the
characteristics of the individual steps as well as
the graphical process of the scene are
displayed. To create or modify a step, tap the
step entry in the list.

Figure 5-34: User scenes -


overview steps

The view in figure 5-35is displayed, in which a


step of the user scene is created. The "Start"
and "End" parameters specify the start and end
values as a percentage. The duration specifies
the time in minutes to be used from the start
value to the end value. Mode 0 is the standard
mode, with only the time taken into account.
Mode 1 and 2 do not yet have a function in this
version.
Figure 5-35: Processing step 1

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 44 User interface

The example from figure 5-36 shows a user


scene consisting of a total of 6 steps in the
overview. Use the arrows to view the data of
each step. In addition, the sequence of the
scene is displayed graphically.

Figure 5-36: User scene - sample


scene 1

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 45

5.2.4 Program

Figure 5-37: Program - tree structure

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 46 User interface

5.2.4.1 Program overview

When the program is started in the main menu, the program overview opens. The
program overview can differ in that it is only possible to navigate between the programs
(independent of the day) or also between day periods (depending on the day). The
setting of the dependency is shown under the menu point 5.2.1 ”Settings”.

Program overview independent of day Program overview dependent on day

Figure 5-38: Program - overview Figure 5-39: Program - overview


independent of day dependent on the day
In the overview in figure 5-38 the set With activated day dependency (fig. 5-39)
programs are displayed graphically. With the start of the day period is displayed by
this setting, the same programs are run means of the calendar icon ( ). In
every day, provided the automatic mode addition during navigation ( ) you can
(to be seen on the start screen) is active. change between the daytime periods. To
create a new scene or modify an existing
one, deactivate the navigation mode
again by pressing the navigation icon
( ).

Each day period therefore has its own overview.

In principle, nine lighting programs can be set, each of which can contain up to three
light scenes (standard or user scenes). In addition, during day-dependent
programming, you can select between six day periods, in which three scenes per
period can be programmed. A day period is always indicated with the starting day of
the period.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 47

5.2.4.2 Setting the change of day

When the daily dependency is activated, the


calendar icon ( ) can be used to set the day
change in the program overview (fig. 5-40).

Figure 5-40: Program - day change

The move-in date is displayed for each light group individually in


menu 5.2.2 ”Light groups” and is defined as day 1.

In this example (fig. 5-41), you can see the


program overview as from day 11. The scenes
set here apply for the period from day 11
onwards.

Figure 5-41: Program


- overview day 11

Using the navigation arrows (left and right), you


can select between the day periods in the
navigation mode and set the day changes
(fig. 5-42).

Figure 5-42: Program - navigation

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 48 User interface

5.2.4.3 Creating a scene in a program

A program is a sequence of up to three scenes per day period (with activated day
dependency). Decide for each scene whether it is to be a standard or a user scene.

Go to the name of the program to select it (fig.


5-43). The pen icon can be used to change the
name of the program.
To add a scene to the program, use the plus
icon ( ).

Figure 5-43: Program - selection


program 1

The window in which the scene can be


configured opens (fig. 5-44). The individual
setting possibilities are explained in the
following sections.

Figure 5-44: Program -


configuration scene

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 49

5.2.4.4 Kind of scene

The first step is to choose between the user and


the standard scene (fig. 5-45). A standard
scene will be set at a later stage under 5.2.4.8
”Parameter”. The previously created user
scenes are selected in the next entry.

Figure 5-45: Program - kind of


scene

5.2.4.5 Selection of user scene

If "user" has been set as the scene type, you


can choose between 12 user scenes in this sub
menu (fig. 5-46).

Figure 5-46: Program - selection


user scene

5.2.4.6 Start mode

You can choose between 4 start modes. The first mode depends on the time, the
modes two and three depend on the temporal or percent values of other scenes. The
fourth start mode depends on a digital input of the light control. For the start mode, it
does not matter whether a standard or a user scene were selected.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 50 User interface

In the first start mode ( ) the start time is


indicated (fig. 5-47). In this case, care must be
taken that no scenes overlap within a program,
which would lead to an error message.

Figure 5-47: Program - start mode 1

Alternatively, a scene can be selected in the


same or in another program according to which
the current scene is timed ( ). The scene can
be started with a delay, earlier (negative) or
later (positive) than the reference scene 
(fig. 5-48). If both scenes are in the same
program, care must be taken that the set delay
is greater than the duration of the reference
scene since scenes in the same program must
Figure 5-48: Program - start mode 2 not overlap.

The same principle of dependence on other


scenes also applies to the percentage of
brightness ( , fig. 5-49). When the reference
scene reaches the set value, the scene starts.
This dependency only works if the reference
scene is in another program because scenes in
the same program cannot overlap.

Figure 5-49: Program - start mode 3

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 51

In the fourth start mode ( , fig. 5-50) a start


depends on the digital input When the digital
input is activated with an external button, the
scene starts. Since it is not foreseeable when
the button is actuated, a scene with the fourth
start mode can only be used in a program
together with scenes which also use start mode
4.

Figure 5-50: Program - start mode 4

5.2.4.7 Stop mode

This mode can only be set for standard scenes because the duration of a user scene
is determined by the duration of the individual steps. The stop mode setting is the same
as the start mode setting.

5.2.4.8 Parameter

In the "Parameter" entry, the standard scenes are configured if this has been selected
in the "Kind of scene" entry. Use the arrows ( , ), to select the parameters.

The first parameter is the boost time (fig. 5-51).


This is rarely necessary with fluorescent tubes,
since these lamps require a short pulse
beforehand in order to be dimmed uniformly.

Figure 5-51: Program - parameter -


boost time

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 52 User interface

In the selected time, the set maximum light


value is reached (fig. 5-52).

Figure 5-52: Program - parameter -


dim-up time

The maximum level is only given as the


percentage value, not the time, as this results
from the difference between the start and stop
times, the up and down dimming times, and the
minimum hold and down dimming time 
(fig. 5-53).

Figure 5-53: Program - parameter -


maximum level

The dim-down time is the time needed to dim a


light to an adjustable minimum value (fig. 5-54).

Figure 5-54: Program - parameter -


dim-down time

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 53

In the holding time min., an adjustable minimum


value is maintained before the light is dimmed
down to 0 % (fig. 5-55).

Figure 5-55: Program - parameter -


hold time min.

The minimum level must always be less than


the maximum level. This value is dimmed in the
dim-down time (fig. 5-56).

Figure 5-56: Program - parameter -


minimum level

The dim-down time min. always dims down


from the minimum value to 0 %. The time during
which this is to be done can be set here
(fig. 5-57).

Figure 5-57: Program - parameter -


dim-down time min.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 54 User interface

5.2.4.9 Colour mode

The colour mode is only usable with light sources using two channels (e.g. Zeus
lamps).

This setting (fig. 5-58) is taken into account


when the program has been assigned to a light
group with two light channels. A colour mode is
a process in which the colour temperature is
changed by dimming both light channels. This
allows different colour sequences to be created.

Figure 5-58: Program - colour mode

The colour temperature does not affect the set brightness.

In the colour mode "nature", the course of the


sun is simulated (fig. 5-59, orange curve). In
this case, the temperature rises to half the time
and then drops again at the same speed. The
blue curve shows the brightness. The maximum
value is set in the menu point 5.2.4.10 ”Colour
temperature”.
Figure 5-59: Program - colour mode
- nature

This colour mode is used to linearly increase or


decrease the brightness. In addition, the value
of the maximum colour temperature is
maintained for 6 % of the duration (fig. 5-60).

Figure 5-60: Program - colour mode


- trapeze

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 55

Figure 5-61 shows the colour mode "ramp". The


light curve starts with the set colour
temperature. This falls linearly to the minimum
value of 2700 Kelvin in the time of the maximum
brightness.

Figure 5-61: Program - colour mode


- ramp

In the "fixed" mode, both colour temperatures


remain constant at the value 100 % (fig. 5-62).

Figure 5-62: Program - colour mode


- fixed

5.2.4.10 Colour temperature

The maximum colour temperature for the colour


modes is defined in this menu point (fig. 5-63).
This value has no effect on manual operation.

Figure 5-63: Program - colour


temperature

5.2.4.11 Active

Here you can see and change the active state. When deactivated, the scene is not
executed.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 56 User interface

5.2.5 Time switch

Figure 5-64: Time switch - tree structure

A time switch makes it possible to switch relay outputs precisely, either daily or on set
week days. A total of 9 time switches with 10 switching times each per day are
available.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 57

In the overview (fig. 5-65), the set switching


times of the various time switches are displayed
for the respective weekdays.

Figure 5-65: Time switch - overview


Monday

Use the navigation icon ( ) to switch between


the weekdays (left, right) and the time switches
(top, bottom) (fig. 5-66). Before a time switch
can be set, the navigation mode must be
deactivated again with the navigation icon.

Figure 5-66: Time switch -


navigation

To set a time switch, tap the respective name


(highlighted in orange, fig. 5-67). Three
additional icons appear in the lower bar, and the
known pen icon appears in the upper left corner
to change the name.

Figure 5-67: Time switch - selection


clock 1

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 58 User interface

After pressing the output icon ( ), the relay


channel which is to be switched can be
adjusted (fig. 5-68). The Nano controller 103
has the module number 9 and provides 4 relay
channels. The module number 0 is not
assigned here either.

Figure 5-68: Time switch -


configuration relay
channel

To set the properties, go to the clock icon ( ).


Use the calendar icon ( ) to select either day
or week time switch. A "1" in the "Set" icon (on
the left) is used to set a daytime time switch.
The signal can be inverted with ( ). In figure
5-69 , the signal is not inverted, so it switches at
the set switching times.

Figure 5-69: Time switch - mode


Example:
In this example, two switching times have been set for a time switch. Fig. 5-70 shows
the inverted and the non-inverted signal.

Figure 5-70: Time switch - inverting

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 59

In the settings shown in figure 5-71 a different


time can be set for each day of the week ( ).
In addition, the signal is inverted here ( ), i.e.
the relay does not switch when the switching
time is set.

Figure 5-71: Time switch - example


mode

Use the switching time icon ( , fig. 5-67) to


open the configuration window of the switching
time (fig. 5-72). The start and end times can be
selected here. To delete the switching time, tap
the delete icon ( ).

Figure 5-72: Time switch - switching


time

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 60 User interface

5.2.6 Control light

Figure 5-73: Control light - tree structure

A control light is switched on manually by means of a button at the digital input with a
specific brightness (light level). When this button is pressed briefly, the light switches
off automatically after a set period of time. If the button is pressed for a certain period
of time, the building site light switches on and does not switch off until the button is
pressed again. Up to two control or building site lights can be configured.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 61

5.2.6.1 Configuration input

A control light is activated via a digital input to


which e.g. a button can be connected. Enter the
module number and the channel (fig. 5-74). The
module number "0" is not assigned here.

Figure 5-74: Control light -


configuration input

5.2.6.2 Light level

The light intensity level indicates the brightness


of the light group for a control or building site
light (fig. 5-75).

Figure 5-75: Control light - light level

5.2.6.3 Duration

The duration of the control light indicates the


time after which it automatically switches off
again (fig. 5-76). The building site light switches
off only after the button has been pressed
again.

Figure 5-76: Control light - duration

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 62 User interface

5.2.6.4 Pressing time building site light

If the button is pressed for at least the set


pressing time (fig. 5-77), the building site light is
activated. This illuminates with the adjusted
light level and must be switched off manually by
means of a button.

Figure 5-77: Control light - Pressing


time "structure light"
(building site light)

5.2.6.5 Light groups

Select the light groups which are to be switched


on for the control or building site light here
(fig. 5-78).

Figure 5-78: Control light - light


groups

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 63

5.2.7 Service

Figure 5-79: Service - tree structure

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 64 User interface

5.2.7.1 IO cards

In the menu point "IO cards" information about the installed modules of the "Nano I/O"
series can be retrieved and the firmware can be updated.

In the overview in figure 5-80 all connected


modules including module number ("[ ]"), 
CAN-ID ("0x") and status can be viewed. The
module number 9 is the Nano controller 103,
which has no CAN ID.

Figure 5-80: Service - IO overview

Tap a module display to see the overview of


inputs and outputs. In this example, figure 5-81
shows the values (in mV) of the outputs of the
SLC. To perform a firmware update, go to the
icon at the bottom left ( ) and specify the
name of the file from the USB flash drive
without file extension.

Figure 5-81: Service - SLC


overview

The firmware update requires absolute caution. There is a risk of data


loss. Therefore this may only be carried out by specialists.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 65

5.2.7.2 Data backup

Data backups can be loaded onto ( ) and


from ( ) USB flash drives. To do this, go to
the corresponding icon (fig. 5-82) and fill in the
name of the file without extension or name it.

Figure 5-82: Service - data backup

When a data backup is loaded from a USB flash drive, all previous settings
are overwritten.

5.2.7.3 Factory settings

After password input, the entire system is in the factory settings.

When the system is reset to factory settings, all scenes and previous
settings are cleared.

5.2.7.4 Info
The installed version number of the software is displayed here.

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 66 User interface

5.2.8 Energy

In the "Energy" menu point, the energy consumption can be recorded and
displayed. For this purpose the light control must first be connected to the
S0 bus of the current meter. The S0 bus is connected to a digital input of
the light control.

On the start screen of the menu point "Energy"


(fig. 5-83), the energy consumed for the current
day is displayed.
Use to switch between the consumption of
the current month, current year and previous
two years, see fig. 5-84 to fig. 5-86.

Figure 5-83: Energy - overview


current day

Figure 5-84: Overview current month Figure 5-85: Overview current year

Figure 5-86: Overview last year Figure 5-87: Overview two years ago

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
User interface Page 67

To configure the energy measurement, set the


pulse number under ( ) on the start screen
(fig. 5-83). The pulse number indicates the
output of the current counter per kWh
(fig. 5-88). This information can be found in the
manufacturer's data for the current meter.

Figure 5-88: Energy - pulses per


kWh

Furthermore, use ( ) on the start screen


(fig. 5-83) to define to which digital input the
current counter is connected (fig. 5-89).

Figure 5-89: Energy - settings


digital input

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Page 68 Error codes

6 Error codes
Error codes are created and displayed on the screen if wrong entries or incorrect
values are detected.
Example:

The following error codes are possible:


1. Unexpected error occurred!
2. Overlap with other scene!
3. Minimum running time cannot be achieved!
4. Dependent scene not valid!
5. Percentages are not achieved!
6. Scene does not exist!

BD Comfort Light Control


Edition: 01/2017 M 2449 GB
Brief instruction Page 69

7 Brief instruction
1. Fix the housing with dowels and screws to the wall
2. Insert the cable glands at the bottom
3. Connect the power supply with 230 V AC as well as lamps, possibly CAN bus,
sensors, buttons, etc. (see 4 ”Installation”)
4. Change jumper settings, if necessary (see 4.3 ”Modules”)
5. Restore system to factory settings (see 5.2.7.3 ”Factory settings”)
6. Change settings on the touch screen (see 5 ”User interface”)

BD Comfort Light Control


Edition: 01/2017 M 2449 GB

Vous aimerez peut-être aussi