Académique Documents
Professionnel Documents
Culture Documents
By:
(Professor)
Amity University
1
DECLARATION
Place: Lucknow
VISHWAM GUPTA
Date:
2
ACKNOWLEDGEMENT
“There are people, who, simply by being what they are, influence, encourage & inspire you
to do things you never thought yourself capable of doing….”
Among these are my teachers, friends & family members to whom I wish to extend my
gratitude on the event of completing my term project file.
Through the columns of this project file, I would like to take the opportunity to thank
Prof. S.T.H.Abidi (Director,ASET) &Brig.U.K.Chopra (Dep. Director, ASET) for
encouraging us in doing the summer training. I would also like to thank Prof.O.P.Singh (HOD,
Department of Electronics and Communication) who gave us valuable suggestions during the
execution of the project.
I would like to thank my external guide Mr. ANCHAL MISHRA (Training Coordinator) and
mentor Dr. GEETIKA SRIVASTAVA who collaborated with me in bringing this project in its
present form. They have been a great source of help & have cleared all our doubts thus being a
great support in every respect.
I would also like to mention the support of my friends & family members for giving me useful
suggestions & contributed a lot to this file without whose endless efforts this work would ever
have been possible. At last I would like to thank all those around me who helped me in any
way to bring the project in its present form.
Any suggestions for the improvement of this project file would be highly accepted.
VISHWAM GUPTA
B.Tech EEE
3
LIST OF FIGURES
FIGURE NO. TITLE OF FIGURE PAGE NO.
1.1 HV and LV transmission side of Khurram Nagar sub-station. 8
9.2.1 Busbar 32
4
LIST OF TABLES
5
CONTENTS
1) INTRODUCTION 8-9
4.1) Working 15
5.2.1) Disadvantages 18
5.3.1) Advantages 19
6) TRANSFORMERS 20-24
6
7) CONDUCTORS 25-27
9.2) Busbar 32
10.1) Relay 35
10.2) Fuse 36
11) CONCLUSION 38
12) REFERENCES 39
7
1) INTRODUCTION
Figure 1.1- High voltage and Low voltage transmission side of Khurram Nagar sub-station.
The sub-station, in which I did my internship, is located near Gudumba Bus station,
Lucknow. The sub-station gets its 132KV supply from the power grids located at
NandKishoreNandan (NKN) sub-station and Chinhut power grid. Here the supply from
Chinhut is used as a primary feed to the sub-station whereas the NKN supply is used for backup.
At first a Lightning Assertor is used in a 3-phase transmission setup in order to protect the grid
from surges due to lightning. After this comes the need to measure the voltage and current in the
transmission lines. For that we use a Capacitor Voltage Transformer and Current
Transformer respectively. Just like an ammeter and a voltmeter, a CT is connected in series
8
with the transmission line whereas a CVT is connected parallel to the transmission line. Since
they both are transformer they must have a transformation ratio. In Khurram Nagar sub-station
the transformation ratio of these to instrument transformers is 400:1 step down.
Now comes the time of implementing some safety features in the transmission line setup.
For that we first use a Line Isolator and then a Bus Isolator. But these alone are not enough, so
we use a Gas Circuit Breaker. These circuit breakers can be operated via control panel in the
operating room.
Two transformers of 40MVA capacity each are installed in Khurram nagar sub-station,
thereby making a total station capacity of 80MVA. A lightning arrestor, current transformer and
some control equipment are used on both sides of the transformers for better monitoring. The
transformers step down the 132KV supply to 33KV supply. Then this 33KV supply is fed to the
nine feeders that are installed in the sub-station. These feeders deliver the power to the following
power houses under the control of LESA:-
UPSIDC
MAHANAGAR
VIKAS NAGAR
SECTOR 25 SARVODAYANAGAR
PGCIL
GSI
ENGINEERING COLLEGE
KALYANPUR
CDRI
There is also a jack bus which is connected to the main bus with the help of a bus
coupler. It is used as a backup feeder when some other feeder is under maintenance. Also there is
another step down transformer installed in the sub-station which is used to supply electricity to
the sub-station.
9
2) TRANSMISSION OF ELECTRICAL ENERGY
Generally, two systems are there that can be used to transmit electrical energy:-
10
Stepping up and stepping down is easy in AC transmission system.
Ease of transforming in AC sub-station than in motor-generator sets of DC system.
Low maintenance.
More economical.
11
3) LIGHTNING ARRESTER
Lightning strikes and surges can become a major problem in electrical power systems and
to deal with that we use lightning arrestors. They protect the conductors, insulators, transformers
and other equipment that are attached to it. Usually a lightning arrester is made up of a high
voltage terminal and a ground terminal. The lightning arrester easily channels to the earth any
lightning surge that travels to it through the transmission line.
In transmission systems, lightning arrestors are made up of porcelain tube. They are high
usually several feet and several inches in diameter. Disks of zinc oxide are generally filled in
them. They are provided with a safety port on the side to dissipate occasional internal explosions
without harming the porcelain cylinder.
12
If we look at figure 2, then we will be able to understand how a lightning arrester works.
Let there be an instrument which is connected to terminal A and terminal E is earthed. In normal
conditions, no current flows through terminal A to terminal E because of the large resistance
between B and C; and C and D. But when lightning strikes, the voltage is very high and even
those large resistances have no effect. So electricity gets channeled to earth without destroying
the instrument.
Figure 3.2- A simple spark gap device which is used to divert lightning strike to ground.
The lightning arresters installed in the sub-station were of ABB. All the arresters were
carefully placed so as to avoid any sort of damage to the sub-station due to lightning strikes and
surges.
Table 3.1- Data sheet of lightning arrester installed in Khurram nagar sub-station.
13
4) ELECTRICAL ISOLATOR
Even though the circuit breakers physically disconnect the current carrying contacts thus
isolating the two lines from each other, but we cannot see that from outside the circuit breaker
and hence it is advisable not to touch the transmission line just by opening the circuit breaker.
For safety purposes, a mechanical isolation technique must be employed so that we can be 100%
sure that there is no current in the transmission line. To achieve that, Electrical Isolators are used.
These are like mechanical switches which are used to completely isolate a part of transmission
circuit so that some maintenance work can be performed.
14
Depending upon the position in power system:
o Bus Side Isolator (isolator directly connected to main bus)
o Line Side Isolator (isolator situated at line side of a feeder)
o Transfer Bus Side Isolator (isolator directly connected to transfer bus)
4.1) WORKING – the first and most important thing to be kept in mind before operating the
isolator is that there are least chances of current flowing in the wire. This is done to avoid arcing.
Therefore an isolator must be opened only after opening the circuit breaker and must be closed
before closing the circuit breaker. The isolator mechanism can be operated both manually by
hand and using a motor that is operated from a distance. Motor system is costly and hence must
be chosen properly, whereas hand operated system is cost effective. Usually hand operated
systems are used for voltages upto 145KV and motorized system are used for higher voltages.
Khurram nagar 132KV sub-station has single break isolators which are used on bus
side, line side as well as on transfer bus side. They all are operated using hand held mechanism.
15
5) CIRCUIT BREAKERS
Circuit breakers are a sort of switching devices that can be activated manually to control
the electrical power system as well as automatically for the protection of the grid. Modern power
systems deal with huge amount of current so the designing of these circuit breakers should be
such that no arc is produced and hence we get safe and loss free functioning.
5.1) WORKING PRINCIPLE - The circuit breaker mainly consists of fixed contacts and
moving contacts. The physical connection between the two current carrying contacts due to the
applied mechanical pressure on the moving contacts, make the “on” state of the circuit breaker.
The potential energy can be stored in the circuit breaker by different ways:-
This stored potential energy is the main factor in the working of the circuit breaker and it
must be released whenever the signal is given. This causes tremendously fast sliding of the
moving contact. All circuit breaker have operating coils (tripping coils and close coil), whenever
these coils are energized by switching pulse, the plunger inside them gets displaced. This
operating coil plunger is typically attached to the operating mechanism of circuit breaker and the
moving contacts are mechanically connected with this operating mechanism through a gear lever
arrangement. There is a conversion of stored potential energy into kinetic energy, which makes
the moving contact to move. Once the cycle of circuit breaker operation is complete, the total
energy is again stored in the form of potential energy by means of spring charging motor or air
compressor or by any other means.
The circuit breaker has to carry large rated or fault power. While carrying this large
power there is always a risk of dangerously high arcing between the moving and the fixed
contacts during the circuit breaker operation. For safe arc quenching in the circuit breaker, the
dielectric strength between the current carrying contacts should be increased rapidly during every
zero current crossing of the alternating current. The dielectric strength of the media in between
contacts can be increased in numbers of ways:-
16
Now we discuss about the two types of circuit breakers used in the sub-station.
5.2) SF6 CIRCUIT BREAKER – It is a type of circuit breaker in which the current
carrying contacts are immersed in Sulphur Hexafluoride gas. SF6 gas has a high affinity of
absorbing free electrons as its electro-negativity is very high. Moreover, SF6 is an excellent
insulator. The SF6 molecules absorb the free electrons from the arc, and hence form a negative
ion. These negatively charged ions have a very low mobility compared to the free electrons.
Hence there is no arcing as the mobility of the charges is the main reason of movement of current
through the gas. Electron can be attached to SF6 molecule in two different ways:-
𝑆𝐹6 + 𝑒 𝑆𝐹6−
𝑆𝐹6 + 𝑒 → 𝑆𝐹5− + 𝐹
SF6 has a very high dielectric property and not only that, its molecules recombine very
fast after the arcing has stopped. The gas can also transfer heat very efficiently through
convection due to its low viscosity. Considering all these properties of SF6, it becomes 100 times
more effective than air to be used in circuit breakers. Hence they can be used for voltage ranges
from 33KV to 800KV and beyond.
17
5.2.1) Disadvantages –
SF6 is a greenhouse gas and the circuit breaker must be manufactured and handled
carefully in order to prevent its release into the atmosphere.
The design of these types of circuit breakers requires almost five times greater
mechanical energy than oil circuit breakers for their proper functioning.
Table 5.1- Specifications for SF6 circuit breaker used in Khurram Nagar 132KV sub-station
5.3) VACUUM CIRCUIT BREAKERS – In this type of circuit breaker, the arc
quenching is done in vacuum. This setup is generally used for arc quenching in medium voltage
applications. Vacuum interrupter is a vacuum chamber in the breaker where all the operations of
opening and closing of contacts and linked arc quenching takes place. The vacuum pressure
inside the vacuum interrupter is generally maintained at 6-10 bar. The interrupter is basically a
steel arc chamber in the center of symmetrically arranged ceramic insulators.
CuCr is generally used to make vacuum circuit breaker contacts, because these current
carrying contacts are very important for the performance of these circuit breakers. Vacuum
circuit breaker is a developing technology, although it was first introduced in 1960’s. Its size has
been greatly reduced and the contact geometry has evolved from butt contact to spiral shape, cup
shape and axial magnetic field contact. These are one of the most reliable medium voltage
switchgears and require least maintenance.
18
Figure 5.2- Vacuum circuit Breaker
5.3.1) Advantages –
19
6) TRANSFORMERS
The energy is generated in bulk at the power plants situated in remote areas. Here the AC
power so generated by these plants is then transmitted over all parts of the country. The power
should be transmitted at appreciably high voltage to reduce the losses and increase the
transmission efficiency. On contrary, at the consumer end, the power should be transmitted at
low voltages based on the nature of load. Such transformation of AC power from one voltage
level to another is obtained by the use of a device known as transformer.
Generator transformers
Sub-station transformers
Unit Auxiliary transformers
System transformers
Interconnecting transformers
Multi-winding transformers for specific needs
20
Figure 6.1- Power transformer in Khurram nagar sub-station
In Khurram nagar 132KV sub-station, there were two transformers with 40MVA
capacity each. One was from EMCO and the other from PME.
Table 6.1- Data sheet for power transformer installed in 132kV sub-station.
Company EMCO
Serial Number IS 2026/77
Type of cooling Oil Natural Air Forced (ONAF)
Rated power 40MVA
Rated Voltage at No Load 132/33kV
Rated Line Current 175/699.82A
Guaranteed Max. Temperature Rise 50oC for top oil ; 55oC for winding
Reference Ambient Temperature 50oC
Frequency 50Hz
Core & Winding Mass 41000kg
Tank & Fitting Mass 23700kg
Mass of Oil 18670kg
Total Mass 83370kg
21
Figure 6.2- ONAF cooling type of transformer
Current transformer
Potential transformer
The current transformer is usually used short circuited because the ammeter
resistance is very low. To be on the safe side, if for some reason the ammeter is removed
then the secondary windings must be short circuited with the help of a short circuiting
switch. If not done then in absence of counter ampere turns by the secondary, the
22
unconstrained primary mmf will result in extremely high flux in the transformer core
producing extreme core loss causing super heating of the core. Also, high voltage gets
produced across the secondary terminals. Hence, the secondary terminals of the CT
should not be left open circuited in any circumstances.
Manufacturer BHEL
Highest System Voltage 145KV
Frequency 50Hz
Rated Current Factor per Time 25KA/s
Rated Primary Current 800A
Turn Ratio 400:1
6.2.2) POTENTIAL TRANSFORMER – These types of transformers are used for very
accurate voltage readings from a high voltage circuits. They are step down transformers
with a defined voltage transformation ratio. Their secondary is connected to a low range
voltmeter for voltage measurements. Power rating of these transformers is very high.
Dry type potential transformers are used for upto 5,000V and immersed type for beyond
13,800V. Between 5,000V to 13,800V, both types are available. The power ratings are
usually 40W to 100W. A precautionary tip: the secondary is always completely insulated
and isolated from the primary (high voltage) and is grounded for protection of operators.
23
Figure 6.4- Potential Transformer
Manufacturer BHEL
Rated Voltage Factor per Time 1.5/s
Highest System Voltage 145KV
Primary Voltage 76.21KV
Frequency 50Hz
Class 3 Phase
24
7) CONDUCTORS
Capability of withstanding the specific load currents and short time currents.
Free from corona discharge at the rated voltage.
Economical
Minimum number of joints.
Ability to endure various mechanical forces acting on it due to its situation. These forces
can be weight of self and other conductors, atmospheric forces like wind and rainfall;
short circuit forces et al.
Requires minimum number of support insulators.
Suitable materials for conductor systems are copper and aluminum. Another option can
be steel, but it has its limitations which are poor conductivity and high susceptibility to
corrosion.
In order to achieve the above properties of an ideal conductor, they are categorized into
different types depending on utilization:-
Table 7.1- Ground clearance of overhead transmission lines with respect to voltage they are
carrying.
25
Overhead transmission lines can be a nuisance sometimes. So in order to eliminate that
we have two methods:-
The main use of the transmission lines, whatever their categories are, is to transfer power
from one place to another. While transmitting power it is but obvious that there would be some
voltage drop and power loss. This is because of the resistance, capacitance and inductance of the
conductors used as transmission lines. Therefore, the efficiency of transmission lines can be
calculated as:-
26
𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = × 100%
𝑝𝑜𝑤𝑒𝑟 𝑠𝑒𝑛𝑡
Similarly, the voltage regulation of the transmission lines can be calculated using:-
27
8) ELECTRICAL INSULATOR
Electrical insulators are one the most important part of a power system. They are used to
avoid unnecessary contact of the transmission lines from their supporting structures. This ensures
that the electric current doesn’t flow to earth through the supporting points. Electrical insulators
basically are extremely high resistive paths through which virtually no current can flow. In
power system, the overhead transmission lines are supported by properly grounded towers and
poles. So an insulator must be used between the transmission lines and the poles in order to avoid
the flow of electric current to earth. The material of the insulator must possess certain specific
properties for its effective utilization:-
28
Table 8.1- Properties of Porcelain Insulator
8.2) GLASS INSULATOR – It is one the most popular type of insulator used in power
system. It is made up of annealed tough glass.
Easy condensation of moisture on the glass surface causes a much easier deposition of
dust on that wet surface. This provides a path to the leakage current of the system.
Glass cannot be cast into irregular shapes for higher voltage applications.
29
8.3) POLYMER INSULATOR – These types of insulators have two parts: a rod shaped
core made of glass fiber reinforced epoxy resin and weather sheds made with silicone rubber or
EPDM (Ethylene Propylene Diene Monomer). Here the weather sheds cover the rod shaped core.
It is also called composite insulator because of its two part structure. The weather sheds
safeguard the rod shaped core from outside environment.
Due to unwanted air gaps between rod shaped core and weather sheds, moisture may
enter the insulator causing electrical failure.
Mechanical failure of the core of insulator may occur due to over crimping of end
fittings.
30
9) MISCELLANEOUS EQUIPMENT
Whenever we need to couple the main bus with any other bus or two busses so that there
is no interruption in the power supply, a bus coupler is used. A bus coupler can be used without
arcing. A setup of isolators and circuit breakers is used for coupling.
Bus coupler can be used to couple every generator and feeder with the main bus or with
the spar bus. If we have to repair or analyze a feeder or any other instrument then we can do that
by putting it on the spar bus, thus ensuring that the main bus supply is not disturbed.
31
9.2) BUSBAR
If we talk about transmission system, the primary work that the busbar does is to transmit
electricity from one part to another without much loss.
There are various busbar arrangements used in a transmission system. The main three being:
Single busbar system
Single busbar system with section alisation
Duplicate busbar system
Large substations carry huge amount of power and they cannot afford fault or maintenance
work to hinder the power supply. It can prove to be a very costly affair. Hence, to avoid that, a
duplicate busbar arrangement system is used. The system is very easy to understand and consists
of two busbars. One busbar is the main bus while the other one is the transfer bus or the spare
bus. They are connected by a bus coupler which is a combination of circuit breaker and isolators.
32
9.3) CAPACITOR BANK
One of the most important parts of an electrical power system is a capacitor bank. The
active power, the power required to run all the electrical appliances, is mainly used to run
inductive loads. It is measured in Watts, usually in Kilos and Megawatts for power systems. The
inductive load may include transformers, motors (Synchronous and inductive both), tube lights,
CFLs, electric furnaces et al. they increase the overall inductance of the power system, thereby
increasing the current lag. This causes decrease in the power factor of the system. Lower the
power factor causes increase in demand of supply power in order to maintain same active power
in the system. And finally more power (current) means more losses. Moreover high power factor
results in bad voltage regulation.
Thus to avoid all these problems, current lag must be decreased so that power factor of
the system may be improved. This is ensured by using a capacitor that nullifies the inductive
effect. This is generally achieved by using a static capacitor in series or shunt with the electrical
power system. For better maintenance and effectiveness, a group of capacitor units are used.
They are preferred over using a single capacitor unit per phase. This setup of a number of
capacitors is known as CAPACITOR BANK.
There are two types of capacitor banks (based on their connections in the power system):-
Shunt Capacitor
Series Capacitor
33
The most commonly used capacitor bank connection is shunt connection. They are
usually connected in grounded star connection because of some advantages:-
34
10) PROTECTIVE GEAR
10.1) RELAY
Sometimes, sooner or later, a failure will definitely occur somewhere in a power system.
Its might be because of human negligence or obsolete instruments. But a better system is where a
failure is speedily detected and tackled with proper measures. Immediate disconnection of the
faulty part of the system prevents further damage to it as well as to other parts of the system. In
high voltage circuitry, relays are installed to provide automatic and reliable switchgear
functioning. These relays are used to identify the problem and convey it to the control panel.
Whenever a fault occurs, there are possibilities that any one or a combination of all of
these electrical quantities change (voltage, current, frequency or phase angle). Whenever there is
a short circuit in the transmission line, there is an enormous current flow through it. Therefore, a
large amount of current also flows from the relay causing its contacts to close. This action closes
the trip circuit of the circuit breaker forcing it into a open state. Hence, the faulty part of the
system gets isolated from rest of the power system. This way relays are used as protective
instruments, safeguarding the power system. The relays work mainly on two operating
principles:-
35
10.1.1) TYPES OF RELAYS USED IN CONTROL PANEL OF SUB-STATION –
Differential Relay – It is a type of relay that operates when the vector difference of two
or more electrical quantities exceed a fixed value. When the differential quantity becomes
equal to or greater than the pickup value, the relay will be activated and the circuit
breaker opens causing the isolation of faulty section.
Over-current Relay – It is the type of relay that functions when the current in the circuit
exceeds the fixed value. They are only attached to alternating current circuits and hence
can be operated for fault detection in both the directions. It operates when phase to phase
fault occurs. The starting source is the current in the electrical circuit supplied from the
current transformer to the relay.
Directional Relay – This relay operates when there is an earth fault, i.e. if any one of the
phase touches the earth due to any fault. It is so designed that it attains its operating
moment of force by interacting with the magnetic field of the voltage and current source
it protects. The direction of the moment of force is dependent on the current relative to
the voltage.
Tripping Relay – It is the type of relay that is used in combination with the main relay.
Whenever a fault occurs, the main relay signals the tripping relay to isolate the faulty part
of the power system.
Auxiliary Relay – It is used to indicate the fault in the power system by glowing a bulb
to warn the employees of the fault.
10.2) FUSE
A fuse is a type of protective device that consists of a short piece of wire or thin strip of
metal with low melting point. It is designed such that whenever high current flows through it for
large amount of time, then the wire melts. The fuse is connected in series with the electrical
circuit so that it can physically disconnect the circuit in case of excessive current flow, which
otherwise would damage the electrical circuit. The fuse wire melts due to overheating. If used
efficiently, a fuse wire can be used for both detection and interruption of fault.
36
Fuses can be work as alternative to circuit breakers. Hence in a power system, they are
used where the cost of buying a circuit breaker is too much to bear. They are used in power
systems for upto a voltage of 115KV, to defend instrument transformers.
37
11) CONCLUSION
The practical training that I got from Electricity Training Institute of Uttar Pradesh Power
Corporation Limited, made me learn many thing about the Transmission System deployed for
transmission of electricity from power plants to power houses.
The sub-station allotted to me was Khurram Nagar 132KV in Lucknow. It was a great
experience and I learnt a lot there. The sub-station has of two 40MVA transformers which
determine the capacity of the sub-station. I have also learnt about the various circuit breakers,
busbars, lightning arresters, isolators, and insulators, various types of relays, fuses and bus
coupler.
The hands on experience I had, like repairing burnt cooling fans of transformer and using
temporary measures to ensure supply et al, were all very interesting. The most important thing
that I learnt was that sometimes, especially during summers, it becomes really necessary for the
staff at sub-station to do load shedding because of the over consumption of electricity by us.
Thus, doing my practical training at the 132kV sub-station had been a great experience
and very helpful.
38
12) REFERENCES
http://www.uppcl.org/about_us.html
http://www.meidensha.co.jp/epages/tech/tech-01.html
http://www.universalengineersindia.com/mehru.htm
http://www.electrical4u.com/voltage-transformer-or-potential-transformer-theory/
http://powermin.nic.in/ministry_of_power/miscellaneous/pages/33KV,%205MVAR%20
Capacitor%20Bank.htm
http://upptcl.org/
http://en.wikipedia.org/wiki/Lightning_arrester
http://www.electrical4u.com/
http://en.wikipedia.org/wiki/Busbar
39