Technical Documents PROFIBUS connector

Stripping the cable (tool example)


• Measure wire length on
Technical template:

Documents
PROFIBUS connector • Insert end of cable and push
Connect & Detect fixing slider as far as it goes
HB157 / vol. 4.02
• Rotate stripping tool
repeatedly around the cable
General Information • Pull off stripper (in closed
The bus connector connects PROFIBUS user knots or complete PROFIBUS net components to the state)
PROFIBUS line.
• Remove cut-off wire/core
Each connector has switchable terminating resistors. Dependent of the type of connector, a insulations remainder
PD/diagnosis socket as well as a controller with 4 LED indicators are additionally integrated.

Features Connecting the PROFIBUS cable


• Cable diagnosis functions via LEDs • Loosen the screw
• Switchable terminating resistors • Lift contact-cover
• Integrated controller for transfer rates up to 12Mbit/s • Insert both wires into the ducts provided
• Metal casing with lose-protected ìsingle-screw-mountingî (watch for the correct line color as below!)
• Fast connection via insulation cutting clamps • Please take care that you do not cause a short
circuit between screen and data lines!
• Close the contact cover
Diagnosis via LEDs
• Tighten screw
Switch PWR TxD Term ERR Description
ON/OFF green green green yellow
x ● x x x Power is OK (+5V ±5%) Please note: the green line must be connected to A, the red line to B!
x ☼ x x x Power is out of +5V ±5%
x ☼ x x ☼ Short-circuit of bus wire possible
Measures in mm: Technical data
x x ○ x x No bus activity of participant 0h 45h 90h Power supply DC 4.75 ... 5.25V
x x ☼ x x Bus activity of participant by end device
x x ● x x Bus activity, RTS (pin 4) of RS485 is not connected Current 10 ... 30mA
OFF x x ○ x Termination is switched off PROFIBUS SubD-male-9pole
OFF x x ☼ x Internal terminating resistor faulty A A
A Plugging cycles jack min. 200
ON x x ● x Termination is activated Cable diameter 8 mm
x x x x ○ No errors detected Casing Zinc-Diecast
OFF x ☼ ○ ● Bus is not terminated Degree of protection IP20
OFF x ○ ○ ● Bus is open B B B C
Temperature range -20hC ... +75hC
Fixing screws / 4-40 UNC/
on: ● off: ○ blinking (5Hz): ☼ not relevant: x
max. tightening torque 0.4Nm
0h 45h 90h Stripping Lengths
Switchable terminating resistors
A 64 61 66 Outside cover/shielding 17mm / 6mm
The switchable terminating resistors are activated by a slide switch, B 34 53 40 Connecting technique Insulation cutting
easily accessible from both sides right and rear. C 15.8 15.8 15.8 clamps
Hereby shutoff of the outgoing bus line is possible. Also for testing Bus cable Type A
purposes the following PROFIBUS components connected via "OUT" (EN50170)
can be switched off without removing the connector. Note!
Please make sure to terminate the last participants on the bus at both Starting with release 5 also highly flexible bus cable may be used:
ends and to connect them to the bus cable via "IN". Lapp Kabel order no.: 2170222, 2170822, 2170322.