MODELACIÓN HIDRÁULICA

ESCENARIO 1.- ACTIVACIÓN DE SPK EN CIRCUITO 1


RED PRINCIPAL SISTEMA HIDRÁULICO CONTRA INCENDIOS - GALPÓN SAN MIGUEL
Darcy- Minor Loss Headloss Headloss
Length Diameter D Nominal Velocity Pressure
Label Start Node Stop Node Material Weisbach e Coefficient Flow (L/s) Gradient (Friction)
(Scaled) (m) (mm) (pulg) (m/s) Loss (psi)
(m) (Local) (m/m) (m)
P-0 6.24 PMP-1 R-1 152.40 Steel 0.000030 4.00 -68.00 3.72 0.521 0.44 4.60
P-1 132.45 PMP-1 J-1 186.40 Steel 0.000030 4.80 68.00 2.48 0.037 3.41 7.00
P-3 25.66 J-1 J-3 152.40 Steel 0.000030 1.28 52.00 2.85 0.063 1.09 2.30
P-6 111.58 J-1 J-3 76.00 Steel 0.000030 1.28 7.00 1.49 0.030 3.25 4.80
P-13 148.44 J-2 J-3 152.40 Steel 0.000030 0.80 -26.00 1.44 0.012 1.74 2.60
P-9 45.83 J-3 J-5 152.40 Steel 0.000030 0.80 26.00 1.41 0.013 0.52 0.80
P-7 190.80 J-3 J-4 76.00 Steel 0.000030 0.80 7.00 1.49 0.030 5.56 8.00
P-8 176.60 J-4 J-1 76.00 Steel 0.000030 1.00 -9.00 1.99 0.051 8.85 12.90
P-10 102.42 J-5 J-2 152.4 Steel 0.000030 0.80 26.00 1.41 0.012 1.15 1.80
MODELACIÓN HIDRÁULICA
ESCENARIO 2.- ACTIVACIÓN DE SPK EN CIRCUITO 2
RED PRINCIPAL SISTEMA HIDRÁULICO CONTRA INCENDIOS - GALPÓN SAN MIGUEL
Darcy- Minor Loss Headloss Headloss
Length Diameter D Nominal Velocity Pressure
Label Start Node Stop Node Material Weisbach e Coefficient Flow (L/s) Gradient (Friction)
(Scaled) (m) (mm) (pulg) (m/s) Loss (psi)
(m) (Local) (m/m) (m)
P-0 6.24 PMP-1 R-1 152.40 Steel 0.000030 4.00 -68.00 3.72 0.521 0.44 4.60
P-1 133.89 PMP-1 J-1 186.40 Steel 0.000030 4.80 68.00 2.48 0.037 3.44 7.00
P-3 1.29 J-1 J-3 152.40 Steel 0.000030 1.28 52.00 2.85 0.455 0.05 0.80
P-6 113.51 J-1 J-3 76.00 Steel 0.000030 0.80 7.00 1.48 0.030 3.29 4.80
P-5 109.53 J-2 J-3 152.40 Steel 0.000030 0.80 -28.00 1.55 0.014 1.48 2.20
P-4 156.82 J-3 J-2 152.40 Steel 0.000030 0.80 24.00 1.30 0.010 1.51 2.20
P-7 190.32 J-3 J-4 76.00 Steel 0.000030 0.80 7.00 1.48 0.029 5.51 8.00
P-8 174.21 J-4 J-1 76.00 Steel 0.000030 1.00 -9.00 1.99 0.052 8.78 12.70
PRESIÓN DISPONIBLE
ESCENARIO 1.- ACTIVACIÓN DE SPK EN CIRCUITO 1
RED PRINCIPAL SISTEMA HIDRÁULICO CONTRA INCENDIOS - GALPÓN SAN MIGUEL
Elevation Demand Hydraulic Pressure (m Pressure
ID NODO
(m) (L/s) Grade (m) H2O) (psi)
256 J-1 0.00 0.00 86.40 86.20 123.14
259 J-2 13.00 52.00 82.94 69.80 99.71
261 J-3 13.00 0.00 84.77 71.60 102.29
265 J-6 0.00 0.00 83.00 82.80 118.29
267 J-4 0.00 16.00 77.34 77.20 110.29
271 J-5 13.00 0.00 84.18 71.00 101.43
PRESIÓN DISPONIBLE
ESCENARIO 2.- ACTIVACIÓN DE SPK EN CIRCUITO 2
RED PRINCIPAL SISTEMA HIDRÁULICO CONTRA INCENDIOS - GALPÓN SAN MIGUEL
Elevation Demand Hydraulic Pressure (m Pressure
ID NODO
(m) (L/s) Grade (m) H2O) (psi)
256 J-1 0.00 0.00 82.98 82.80 118.29
259 J-2 13.00 52.00 80.81 67.70 96.71
261 J-3 13.00 0.00 82.39 69.30 99.00
265 J-3 0.00 0.00 79.60 79.40 113.43
267 J-4 0.00 16.00 74.00 73.80 105.43