REMODELACION FACHADA DEL C.C.

REAL PLAZA PRIMAVERA 14500-17-QA-REP-001


QUALITY Rev. 1
Date: 14/08/2018
LIQUID PENETRANT TEST RECORD
Page: 1/1
Doc N°:
Contractor: RUAG CONSTRUCCION Project Location: REAL PLAZA PT-RUAG-013
Client: InterPropertiers Peru Discipline: MECHANICAL Date: 3/16/2019
Drawing: E - 03 System: N/A
Acceptance AWS D1.1 - 2015 , Clause 6.10 Parte C
Inspected material: ASTM A36
Requirements: TYPE II
Penetrant:
Type: Visible Application mode:
Brand: Cantesco Immersion
Lot N°: 18054 Pulverization X
Post-Emulsifiable, lipophilic Brush X
Post-Emulsifiable, hidrophilic
Washable with H2O
Removable with solvent X
Emulsified: Developer:
Type: Visible Type: Visible
Brand: Magnaflux Brand: Magnaflux
Lot N°: 18022 Lot N°: 18078
Time: Application mode: Pulverization
Application mode: Revealed time (min) 10 min
Previous cleaning: mechanical cleaning Interpretation time (min): 10 min
Temperature in the surface (°C): 20 Lighting: > 1000 lux
Drying: Cloth Final cleaning: Removable with solvent

Made by: Efrain Perez Ventura Date: 3/16/2019 Signature:_____________________

Welding Thickness Defect


Item Joint Welder Code Diameter Result Observations
Process (mm) Type Dimension
Evaluated with Acceptance
01 FLT-J01 GMAW YMV300119 --- 2,5 PA POINTS NC Requirements

Evaluated with Acceptance


02 FLT-J02 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


03 FLT-J03 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

FLT-J01

FLT-J02
FLT-J03

LEGEND: C: ACCEPTABLE NC: REJECT SO: UNDERCUT OTR: OTHER


PG: CLUSTER POROSITY PA: PIPING POROSITY CI: IRREGULAR CORD
FC: INSUFFICIENT LEG SIZE FG: INSUFFICIENT THROAT FF: INCOMPLETE FUSION

Approved by:

CONSTRUCTION RUAG QUALITY CLIENT

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: 3/16/2019 Date:


REMODELACION FACHADA DEL C.C. REAL PLAZA PRIMAVERA 14500-17-QA-REP-001
QUALITY Rev. 1
Date: 14/08/2018
LIQUID PENETRANT TEST RECORD
Page: 1/1
Doc N°:
Contractor: RUAG CONSTRUCCION Project Location: REAL PLAZA PT-RUAG-014
Client: InterPropertiers Peru Discipline: MECHANICAL Date: 3/16/2019
Drawing: E - 03 System: N/A
Acceptance AWS D1.1 - 2015 , Clause 6.10 Parte C
Inspected material: ASTM A36
Requirements: TYPE II
Penetrant:
Type: Visible Application mode:
Brand: Cantesco Immersion
Lot N°: 18054 Pulverization X
Post-Emulsifiable, lipophilic Brush X
Post-Emulsifiable, hidrophilic
Washable with H2O
Removable with solvent X
Emulsified: Developer:
Type: Visible Type: Visible
Brand: Magnaflux Brand: Magnaflux
Lot N°: 18022 Lot N°: 18078
Time: Application mode: Pulverization
Application mode: Revealed time (min) 10 min
Previous cleaning: mechanical cleaning Interpretation time (min): 10 min
Temperature in the surface (°C): 20 Lighting: > 1000 lux
Drying: Cloth Final cleaning: Removable with solvent

Made by: Efrain Perez Ventura Date: 3/16/2019 Signature:_____________________

Welding Thickness Defect


Item Joint Welder Code Diameter Result Observations
Process (mm) Type Dimension
Evaluated with Acceptance
01 FLT-J04 GMAW YMV300119 --- 2,5 FF POINTS NC Requirements

Evaluated with Acceptance


02 FLT-J05 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


03 FLT-J06 GMAW YMV300119 --- 2,5 FF POINTS NC Requirements

Evaluated with Acceptance


04 FLT-J07 GMAW YMV300119 --- 2,5 FF POINTS BC Requirements

FLT-J04

FLT-J05

FLT-J07

FLT-J06

LEGEND: C: ACCEPTABLE NC: REJECT SO: UNDERCUT OTR: OTHER


PG: CLUSTER POROSITY PA: PIPING POROSITY CI: IRREGULAR CORD
FC: INSUFFICIENT LEG SIZE FG: INSUFFICIENT THROAT FF: INCOMPLETE FUSION

Approved by:

CONSTRUCTION RUAG QUALITY CLIENT

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: 3/16/2019 Date:


REMODELACION FACHADA DEL C.C. REAL PLAZA PRIMAVERA 14500-17-QA-REP-001
QUALITY Rev. 1
Date: 14/08/2018
LIQUID PENETRANT TEST RECORD
Page: 1/1
Doc N°:
Contractor: RUAG CONSTRUCCION Project Location: REAL PLAZA PT-RUAG-015
Client: InterPropertiers Peru Discipline: MECHANICAL Date: 3/16/2019
Drawing: E - 03 System: N/A
Acceptance AWS D1.1 - 2015 , Clause 6.10 Parte C
Inspected material: ASTM A36
Requirements: TYPE II
Penetrant:
Type: Visible Application mode:
Brand: Cantesco Immersion
Lot N°: 18054 Pulverization X
Post-Emulsifiable, lipophilic Brush X
Post-Emulsifiable, hidrophilic
Washable with H2O
Removable with solvent X
Emulsified: Developer:
Type: Visible Type: Visible
Brand: Magnaflux Brand: Magnaflux
Lot N°: 18022 Lot N°: 18078
Time: Application mode: Pulverization
Application mode: Revealed time (min) 10 min
Previous cleaning: mechanical cleaning Interpretation time (min): 10 min
Temperature in the surface (°C): 20 Lighting: > 1000 lux
Drying: Cloth Final cleaning: Removable with solvent

Made by: Efrain Perez Ventura Date: 3/16/2019 Signature:_____________________

Welding Thickness Defect


Item Joint Welder Code Diameter Result Observations
Process (mm) Type Dimension
Evaluated with Acceptance
01 FLT-J08 GMAW YMV300119 --- 2,5 --- --- C Requirements

Evaluated with Acceptance


02 FLT-J09 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


03 FLT-J10 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


04 FLT-J11 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


05 FLT-J12 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

FLT-J12

FLT-J11
FLT-J08

FLT-J09

FLT-J010

FLT-J12

LEGEND: C: ACCEPTABLE NC: REJECT SO: UNDERCUT OTR: OTHER


PG: CLUSTER POROSITY PA: PIPING POROSITY CI: IRREGULAR CORD
FC: INSUFFICIENT LEG SIZE FG: INSUFFICIENT THROAT FF: INCOMPLETE FUSION

Approved by:

CONSTRUCTION RUAG QUALITY CLIENT

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: 3/16/2019 Date:


REMODELACION FACHADA DEL C.C. REAL PLAZA PRIMAVERA 14500-17-QA-REP-001
QUALITY Rev. 1
Date: 14/08/2018
LIQUID PENETRANT TEST RECORD
Page: 1/1
Doc N°:
Contractor: RUAG CONSTRUCCION Project Location: REAL PLAZA PT-RUAG-016
Client: InterPropertiers Peru Discipline: MECHANICAL Date: 3/16/2019
Drawing: E - 03 System: N/A
Acceptance AWS D1.1 - 2015 , Clause 6.10 Parte C
Inspected material: ASTM A36
Requirements: TYPE II
Penetrant:
Type: Visible Application mode:
Brand: Cantesco Immersion
Lot N°: 18054 Pulverization X
Post-Emulsifiable, lipophilic Brush X
Post-Emulsifiable, hidrophilic
Washable with H2O
Removable with solvent X
Emulsified: Developer:
Type: Visible Type: Visible
Brand: Magnaflux Brand: Magnaflux
Lot N°: 18022 Lot N°: 18078
Time: Application mode: Pulverization
Application mode: Revealed time (min) 10 min
Previous cleaning: mechanical cleaning Interpretation time (min): 10 min
Temperature in the surface (°C): 20 Lighting: > 1000 lux
Drying: Cloth Final cleaning: Removable with solvent

Made by: Efrain Perez Ventura Date: 3/16/2019 Signature:_____________________

Welding Thickness Defect


Item Joint Welder Code Diameter Result Observations
Process (mm) Type Dimension
Evaluated with Acceptance
01 FLT-J13 GMAW YMV300119 --- 2,5 PA POINTS NC Requirements

Evaluated with Acceptance


02 FLT-J14 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


03 FLT-J15 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

Evaluated with Acceptance


04 FLT-J16 GMAW YMV300119 --- 2,5 SO POINTS C Requirements

FLT-J13

FLT-J16
FLT-J14

LEGEND: C: ACCEPTABLE NC: REJECT SO: UNDERCUT OTR: OTHER


PG: CLUSTER POROSITY PA: PIPING POROSITY CI: IRREGULAR CORD
FC: INSUFFICIENT LEG SIZE FG: INSUFFICIENT THROAT FF: INCOMPLETE FUSION

Approved by:

CONSTRUCTION RUAG QUALITY CLIENT

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: 3/16/2019 Date: