Vous êtes sur la page 1sur 51

CHAPTER 3

POWER QUALITY AND DYNAMIC VOLTAGE RESTORER (DVR)

3.1 INTRODUCTION TO POWER QUALITY

Power quality has become major concern to both electric utilities

and customers. In many countries, the effects of lack of power quality

have been resulting in wastage of several billions of dollars every year.

This is due to carelessness of most industries in not upgrading their

plants which result in very high cost due to loss of products, loss of

production time, clean up and recalibration of the process. The use of

complexity and sensitivity of new technologies in electric equipments is

one of the major causes of power quality problems such as voltage

disturbances on the supply network. Power electronic equipments are

more sensitive to voltage disturbances and leads to large growth of

voltage disturbances. It is difficult to detect the sources leading to

power quality problems. Factors for the causes of most power quality

problems are beyond the control of utilities and can never be totally

eliminated. Some of the sources of power quality problems in order of

frequency of occurrence are:

1. User loads

2. User electrical system and grounding

3. Weather related such as lightening, wind and rain

4. Utility distribution system

5. Utility transmission system


6. utility generation system

Power quality review is a complex subject and involves aspects such

as power system, equipment modeling, power quality event mitigation

and optimization and data analysis. The basic knowledge of the

different power system disturbances is important in order to determine

the events and causes of equipment failure as well as to apply

mitigation measures more effectively. Power system disturbances are

dominated by voltage quality and harmonics.

3.2 Voltage Quality

The control and design are the two constraints of DVR which are

affected by voltage quality. The DVR performance depends on the

voltage quality at the location DVR is inserted. Voltage quality includes

sags, swells, interruptions and harmonics.

3.2.1 Voltage sags

Voltage sags are in many references stated as the most important

and costly power quality problems and, because of high risk of tripping

devices and a relative frequent occurrence. Voltage sags have been

treated in many papers for instance. Voltage sags are categorized as

symmetrical and unsymmetrical.

3.2.1.1) Symmetrical voltage sags

Voltage sags are usually caused b short –circuit current into fault

and a simplified model is illustrated in fig 3.2. Magnitude and phase of

the voltage sag at the point of common coupling (PCC) are determined

by the fault and supply impedances, using the following eqn.3.1:


Zfault
Vsag =E (3.1)
Zfault +Zsupply

By the impedance considerations the reduced magnitude and in

some cases a phase jump can be estimated. Fig 3.2 illustrates the used

definitions of the voltage at the PCC with Vsag as the voltage during the

sag and Φsag is the phase jump at PCC. Simple symmetrical voltage sag

can be characterized by the following three parameters

 Voltage during sag (Vsag)

 Sag duration (tsag)

 Phase jump (Фsag)

Zf
Fault
E Zs

Supply Load
PCC
Fig 3.1: Simplified ciruit for voltage sag calculation

Vpresag

Vmissing
Фsag
Vsag

Fig 3.2: Vector diagram of various voltages during sag

The definition of voltage sag with phasors can be stated as:

Vsag = Vpresag -Vmissing (3.2)


As per the definition, the voltage sag is the voltage at PCC during

the voltage sag and can be calculated as pre-sag voltage (often the rated

voltage) subtracted the missing voltage. In order to have full

compensating, the DVR must inject the missing voltage. If the voltage

sag is severe, Vsag is low and shallow voltage sag is characterized as

high Vsag value.

3.2.1.2) Non-symmetrical voltage sags

Usually the large portion of the voltage sag will be non-symmetrical

in nature. These non-symmetrical natures have a considerable impact

on the design and control of DVR and voltage sag distribution could

justify the design of the DVR for non-symmetrical voltage sags and

therefore focus performance evaluation on the compensation of non-

symmetrical sags.

The voltage sags are caused by different kinds of faults in the grid.

The faults can be categorized as:

1. Three-phase faults

2. Three-phase faults with ground connection

3. Two-phase faults

4. Two-phase faults with ground connection

5. Single-phase faults

In direct or effective grounded systems (3-5) can lead to non-

symmetrical voltage sag and in isolated or high impedance grounded

system (3-4) can lead to non-symmetrical voltage sag. The propagation

through transformers and grounding used at each voltage level is

essential for the propagation of the voltage sags associated with faults.
Non-symmetrical voltage sags very often include a phase shift of two

phases and depending on the circumstances, the voltage phasors come

closer or more separate. The phase-shift, which is very different from

the phase jump from symmetrical voltage sag, must be detected and

compensated by the DVR to restore the load voltages. The magnitude to

be injected by the dynamic voltage restorer is important, because the

DVR has a finite voltage rating and it sets a limit for the type of non-

symmetrical sags, which can be compensated. For some DVR topologies

the line voltage values are of greater interest. The positive sequence

component is also useful for evaluating the expected power drain for

non-symmetrical voltage sag, because for symmetrical load currents, on

the injection of positive sequence results in a power drain for the DVR

storage.

3.2.2 Voltage Interruptions

Voltage interruptions are usually caused by different types of faults

e.g. malfunction of protection equipment or lightening. Sometimes,

without redundancy, fault often leads to long interruption, which

requires manual intervention. Short interruptions are often caused by

automatic reclosing after fault. Short interruptions below three minutes

are normally considered a voltage quality problem. Interruptions are a

severe power quality problem. Occurrence of voltage interruptions is

very rare because of redundancy and high maintenance of the grid

especially in wide range of industrial countries. A correlation can be

found between interruptions and voltage sags. Taking measures to

decrease the number of interruptions may increase the number of


voltage sags. For instance by having a meshed distribution system

(high redundancy) the number of interruptions goes down, but the

voltage sags can occur more frequently and be more severe.

3.2.3 Voltage Harmonics

Harmonics are treated as non fundamental voltage signals often

appear at all levels in the electrical system. With reference to DVR, the

harmonic content of the voltage before and after the DVR operation has

major interest. Before the DVR, background distortion level (during no-

load conditions) can be measured and the level of distortion may

influence the control of the DVR. The DVR can inject some harmonics

in addition to background harmonics gives the resulting load voltage

harmonics. This resulting load voltage distortion is an important

evaluation parameter of the DVR performance. Sources to the distortion

of the load voltages vary and the three main sources are:

 Background voltage harmonics: Background harmonics can

easily be transferred to the load voltage side. During voltage

injection harmonics from background distortion can be amplified

or damped in the DVR control system. A supply voltage with high

harmonic content can complicate the synchronization to the

supply and interface with the DVR control.

 Harmonics injected by the DVR: The THD of the injected series

voltage depends on the DVR hardware (converter topology,

switching frequency, modulation method, modulation index and

filtering). Non-linear effects in the converter can even be a pure

fundamental reference voltage injects harmonics, caused by non-


linear effects in the DVR such as dead time, transistor and diode

voltage drop.

 Non-linear load currents: A non-linear load currents distorts the

load voltage, which depends on the strength of the grid, the

inserted DVR and the resulting impedance seen by load. This will

include impedance in the DVR and the grid.

The voltage distortion Vsag can be calculated by a summation of

harmonic components, according to:


2
Vsag   Vh (3.3)
h2

And the total harmonic distortion (THD) in percent can be calculated

by:

Vsag
VTHD% = 100% (3.4)
V1

The DVR has the potential of improving the load voltage with

respect to harmonic distortion, which means both compensate for

background harmonics and to compensate for the distorted load voltage

caused by a distorted load current. This type of control is often termed

as harmonic blocking control or series harmonic filtering.

3.2.4 Non-symmetrical voltages

In a three phase system the degree of symmetry is very important

for a large group of three-phase loads. For a DVR non-symmetry

implies hardware and control to be able to detect and correct the


unbalanced supply and load voltages. The degree of symmetry is main

performance criteria, which can be used to evaluate the DVR.

In the analysis of three-phase systems the decomposition to

symmetrical components is useful. Equation 3.5 shows the

transformation from phase phasor values to symmetrical components.

Vd  1 a a   Va 
2
V  = 1 1 a 2 a  V  (3.5)
 q 3  b
   Vc 
 Vo  1 1 1

The degree of symmetry is often evaluated as the negative sequence

component divided by the positive sequence component. According to:

Vq
Vnon-symmetric % = 100% (3.6)
Vd

It is important to distinguish the non-symmetry from the four different

sources:

 Background non-symmetry: Caused by other loads and can be a

relative permanent condition, which can interface with the DVR

control and make the load voltages non-symmetrical.

 Non-symmetrical loads: A high non-symmetrical load can,

because of the voltage drop across the DVR and the supply, lead

to non-symmetrical load voltages.

 Non symmetrical voltage sag: Short duration non-symmetry

caused by a non symmetrical fault incident in the grid.

 Non-symmetry generated by the DVR: A DVR inserted to remove

symmetrical and non-symmetrical voltage sags, but in some


cases the DVR may increase the non-symmetry by voltage

injection or by the voltage drop caused by non-symmetrical load

currents.

3.3 Series Voltage Controller [Dynamic Voltage Restorer, (DVR)]

The series controllers for control of the fundamental voltage are

termed as a series connected PWM regulator in, a static series regulator

in and, but mostly the devices are termed dynamic voltage restorers. If

the device only injects reactive power the device can be termed as series

var compensators.

Taking the same simplified model of supply and load, but now with a

series controller inserted to support the load. A 0.5 pu voltage sag can

by a series device be restored by a 0.5 pu DVR and only 0.5pu of the

energy absorbed by the load has to be supplied by the DVR. The supply

continues to be connected and no resynchronization is necessary as it

is the case with a shunt connected converter.

Fig 3.3: Circuit diagram of a system with series controller,


The series voltage controller is connected in series with the

protected load as shown in figure 3.3. Usually the connection is made

via a transformer, but configurations with direct connection via power

electronics also exist. The resulting voltage at the load bus bar equals

the sum of the grid voltage and the injected voltage from the DVR. The

converter generates the reactive power needed while the active power is

taken from the energy storage. The energy storage can be different

depending on the needs of compensating. The DVR often has

limitations on the depth and duration of the voltage sag that it can

compensate. Therefore right sized has to be used in order to achieve the

desired protection. Options available for energy storage during voltage

sags are conventional capacitors for very short durations but deep,

batteries for longer but less severe magnitude drops and super

capacitors in between. There are also other combinations and

configurations possible.

There are configurations, which can work without any energy

storage, and they inject a lagging voltage with the load current. There

are also different approaches on what to inject to obtain the most

powerful solution. The main advantage with this method is that a single

DVR can be installed to protect the whole plant (a few MVA) as well as

single loads. Because of the fast switches, usually IGBT’s, voltage

compensation can be achieved in less than half a cycle. Disadvantages

are that it is relatively expensive and it only mitigates voltage sags from

outside the site. The cost of a DVR mainly depends on the power rating

and the energy storage capacity.


Fig.3.4: Configuration for a DVR.

3.3.1 Principle of DVR


Dynamic voltage restorer (DVR) protects the load from voltage

disturbances. DVR maintains the load voltage at a predetermined level

during any source voltage abnormal conditions such as voltage

sags/swells or distortion. The working principle of the DVR can be

explained through the fig 3.4. Under normal operating conditions, let

the three phase voltage phasors Va1, Vb1 and Vc1. During abnormal

conditions, the phase voltage vectors may be altered to Va2, Vb2 and

Vc2. DVR does not supply any real power in the steady state. This

implies that the phase angle difference between DVR voltage phasor

and current phasor must be 900 in the steady state.

DVR injects the required compensating voltage through

transformer. The transformer is connected in series to the load. DVR

operates only during the abnormal conditions and remains idle during

normal operating conditions. During operation, DVR has a capability to

supply and absorb active and reactive power. Dynamic voltage restorer

corrects the load voltage by supplying reactive power generated

internally on the occasion of small fault. DVR develops active power


when it is required to balance larger faults. It requires dc energy device

to develop the active power. Usually, dc capacitor banks are used as

the dc energy storage device. Most often caused voltage disturbances

are voltage sags as they can cause load tripping. Dynamic voltage

restorer (DVR) is a series controller connected in series to the load. DVR

injects voltage in series to the load through the injection transformer

and voltage source converter. The injecting transformer injects the

required voltage vector (magnitude and angle) which adds to the source

voltage to restore the load voltage to pre-abnormal condition. The

components of DVR are:

a) Energy Storage: usually batteries are used to provide the required

energy for compensation of load voltage during abnormal conditions. In

online monitoring and conditioning systems, required energy for

compensation is drawn from supply line feeder through a rectifier and a

capacitor. In low power applications, photovoltaic cells can also provide

energy.

b) Inverter circuit: Since the loads in distribution system operate with

ac power supply, inverter is required to invert the dc power from the

energy storage into ac power. Usually for normal three phase supply,

three phase voltage source inverter is used. Three phase VSI cannot

control the output voltage instead only transform the dc signal to

corresponding ac with same magnitude. Hence requires large energy

storage for high voltage injection. Moreover, voltage source inverter

output waveform shape is step waveform (treated as highly harmonic


content waveform) and hence requires a filter at the output of the

inverter to modify the step output into sinusoidal.

c) Series injection transformers: Three single phase injection

transformers are used to inject the voltage at the load end. Usually 1:1

ratio is used, but if required step up transformer can also be used. The

injection transformers are provided with suitable MVA rating, the

primary winding voltage and current ratings, short circuit impedance

values.

d) Filter Unit: Since the semiconductor devices exhibit non-linear

characteristics resulting in distorted waveforms associated with high

frequency harmonics at the inverter output. Hence to minimize the

harmonics, a harmonic filtering unit is required. In turn the filtering

unit can cause voltage drop and phase shift in the fundamental

component of the inverter output. To overcome this problem, multilevel

topology can be used in voltage source inverter which has double

impact in reducing filter size and energy storage requirement

simultaneously.

e) Controller and auxiliary circuits: By-pass switches, breakers and

protection relays are some auxiliaries to the Dynamic Voltage Restorer

(DVR) block. In addition to all these, PWM controller is required to

generate pulses to the inverter in accordance to the abnormality in load

voltage. Most often PI controller is used. When tuning becomes difficult,

PI controller is tuned with proper methodology.

3.3.2 Location of the DVR


The dynamic voltage restorer is close to low voltage customer. Fig

3.5 illustrates a simplified model of the Dynamic Voltage Restorer


V DVR
(DVR).
Zs V conv Iload
Is Rdvr
Xdvr

Vs
Load Vload

Fig 3.5: Simplified model of DVR

In the Fig 3.5, DVR is represented as an ideal voltage source (Vconv)

with an inserted reactive element (XDVR), which mainly represents the

reactive elements in the injection transformers and line filters and an

inserted resistive element (RDVR), which represents the losses in the

DVR. The size of the inserted impedance is closely related to the DVR

voltage rating (VDVR) and the DVR power rating ( S DVR ) .

2
VDVR
X DVR  .VDVR , X (3.7)
S DVR

2
VDVR
RDVR  .VDVR , R (3.8)
S DVR

2
VDVR
Z DVR  .VDVR , Z (3.9)
S DVR

VDVR,Z  VDVR, R  jVDVR , X (3.10)

Type of transformer used, the line filter and losses in the DVR affects

the VDVR ,Z .

A DVR with high injection capability (high VDVR ) and ability only to

protect a small load (low S DVR )has large equivalent DVR impedance
( Z DVR ). A high resistive part increases the energy, which should be

dissipated from the DVR and the costs associated with losses. High

total inserted DVR impedance increases the potential load voltage

fluctuations if the load is non-linear and /or has a fluctuating load

behavior. When DVR is connected to the medium voltage level, it

protects a large consumer or group of consumers. Inserting a large DVR

at the MV-level will only increase the supply impedance for a low

voltage load slightly. Some of the advantages of the high rated DVR at

the medium voltage level are:

 If the distribution system is operated as a three wire system with

isolated or inductor grounded system, injection of positive and

negative sequence system is significant.

 The costs per MVA to protect are expected to be lower if one large

central DVR is located at the medium voltage level instead of

decentralized low voltage units.

Some of the disadvantages of the high rated DVR at the medium voltage

level are:

 Protecting a large load requires a medium voltage DVR otherwise the

losses in the DVR will be too high.

 During ground faults in the medium voltage system the phase to

ground voltages can increase with 31/2, and a higher isolation level

may of the injection transformers must be ensured.

3.3.3 Operation of DVR

The DVR can be operated in three different modes which are

described as
1. Bypass mode: the Dynamic Voltage Restorer (DVR) is bypassed

mechanically or electronically during high load currents and down-

stream short circuits. In this mode the DVR cannot inject a voltage

to improve the voltage quality.

2. Standby mode: The supply voltages are at rated level and the DVR

is ready to compensate for voltage sag. During standby mode the

DVR can have secondary tasks and operation modes.

 Loss less mode: The DVR performs no switching and the

losses in the DVR are minimized to conduction losses.

 Harmonic blocking mode and voltage balancing mode:

The DVR improves the load voltage and compensate for

poor background voltage quality. The DVR has to perform

switching and is expected to inject a relatively small

voltage.

 Capacitor emulation mode: The DVR is controlled to

operate as in inserted series capacitor, thereby it can

compensate for large line inductance and for inductance

inserter in conjunction with the DVR.

3. Active mode: Whenever voltage sags are detected, DVR injects the

missing voltage. In this mode DVR should ensure the unchanged

load voltage with minimum energy dissipation for injection due to

high cost of capacitors. The available voltage injection strategies are

pre-sag, phase advance, voltage tolerance and in phase method.

3.3.4 Voltage Injection Methods


Since the dynamic voltage restorer injects the compensating voltage

in order to maintain the load voltage constant, there are certain

limitations in compensating the voltage sags. The factors influencing

the compensation are finite power rating, different load conditions and

different types of voltage sag. Load characteristics dictate the control

strategy of dynamic voltage restorer as some loads are sensitive to

phase angle jump and others are tolerant to phase angle jump. The

injection compensating voltage is categorized as three methods.

1. Pre-sag Compensation: In this method DVR continuously

tracks the supply voltage. The DVR injects the missing voltage

between during sag and pre-sag voltages to the system. During

the compensation, DVR has to compensate both magnitude and

angle. The Fig 3.6 shows the vector representation of pre-sag

conditions. In this method, the injected power cannot be

controlled while load voltage can be restored ideally. Load

conditions and type of fault determines the injected power.


Fig 3.6: Vector diagram of pre-sag compensation

2. In-phase compensation: In this method, injected voltage is

independent of the load current and pre-fault voltage. The

injected voltage is always in-phase with supply voltage. The

added advantage of this method is to minimize the magnitude of

injected voltage for constant load voltage magnitude. The phase

angles of pre-sag and load voltage are different and magnitude of

load voltage is same as pre-fault voltage. The Fig 3.7 represents

the in-phase compensation. During normal conditions, supply

voltage and load voltage are equal with zero phase angle. During

abnormal condition like sag, phase angle jump appears with

reduction of load voltage magnitude. Both the parameters are

compensated by DVR.

Fig 3.7: Vector diagram of in-phase compensation


3. Phase-Advance Compensation: Active power is injected to

sensitive loads continuously in both pre-sag compensation and

In-phase compensation methods. In both methods, DVR

restoration time and performance are confined due to limited

energy storage capacity of dc link which limits the active power

injection. Phase advance methods proves to better compared to

other methods as it associates only reactive power injection

instead of active power. The injected active power is made zero

by injecting compensating voltage perpendicular to load current.

The injected voltage of the phase-advance method is larger than

those of pre-sag or in-phase method. The voltage phase shift in

phase advance method causes voltage waveform discontinuity,

inaccurate zero crossing and load power swing. Hence, phase-

advance compensation should be adjusted to the load that is

tolerant to phase angle jump or transition period should be

taken while the phase angle is moved from pre-fault angle to the

advance angle.
Fig 3.8: Vector diagram of phase advance compensation

3.3.5 DVR LIMITATIONS

Every circuit which has advantages will also have few

disadvantages. A DVR has limited capabilities and the DVR will most

likely to face voltage sag outside the range of full compensation. Some

of the limitations of DVR are:

 Voltage limit: The design is limited in the injection capability to

keep the cost down and to reduce the voltage drop across the

device in standby operation

 Current limit: The DVR has a limitation in current conduction

capability to keep the cost down.

 Power limit: Power is stored in the DC link, but the bulk power

is often converted from supply itself or from a larger DC storage.

An additional converter is often used to maintain a constant DC-

link voltage and rating of the converter can introduce a power

limit to the DVR.


 Energy limit: Energy is used to maintain the load voltage

constant and the storage is normally sized as low as possible in

order to reduce cost. Some sags will deplete the storage fast, and

adequate control can reduce the risk of load tripping caused be

insufficient energy storage.

Other limitations

The voltage injected can with an ideal DVR be done instantly, but

practical DVRs have a finite response-time and other factors may favor

a smooth change from one operating point to another. For the DVR a

slow change to stationary operating point will reduce the risk of in rush

currents and saturation of the transformer. From a load point of view a

fast change of the pre-sag voltage will make the voltage sag unseen. If a

phase change is initiated to minimize the energy storage depletion a

slow change to an adequate stationary operating point may prevent

severe transients and in worst case load tripping. All the limits should

be taken into consideration in the control strategy.

3.3.6 Modeling of DVR

With the Thevinin model of the DVR, the thevinin impedance is the

resultant of fixed resistance, which is equivalent to losses in the DVR

and fixed reactance, which is equivalent to reactive elements of the

DVR. Modeling of DVR includes the voltage handling capability, current

handling capability and size of energy storage. The voltage injection

capability of DVR can be expressed as

VDVR
VDVR %  *100 (3.11)
Vsup ply ,rated
The equipment cost and standby losses limit the voltage injection

capability of the DVR; should be chosen as low as possible. In addition

to voltage rating, current rating also affects the performance of DVR.

The parameters affecting current handling capability of the DVR are

inrush, non-linear loads, down stream short circuits, future increase of

load, standby losses and magnetization of injection transformer. Low

current rating results in overloading of VSC.

VDVR  VL  Z th I L  Vth (3.12)

The load current I L is given by

*
 P  jQL 
IL   L  (3.13)
 VL 

The equation can be rewritten as

V DVR   VL 0  Z th (   )  Vth  (3.14)

Where  ,  and  are the angles of V DVR , Z th and Vth respectively.  is the

load power factor angle and is given by

 QL 
  tan1   (3.15)
 PL 

Assuming the thevinin impedance is very less ( Z th << 1), the voltage

injected by the DVR can be written as

VDVR  VL  Vth  1  K VL , (3.16)

Where K indicates the ratio of source voltage to the load voltage

Vth
K  (3.17)
VL
Apparent power required by the DVR ( SDVR ) is then calculated in terms

of the apparent load power ( S L ).

SDVR  SL (1  K ) (3.18)

SDVR  VDVR I L * (3.19)

The active and reactive powers can be calculated by separating

apparent load power into its real and imaginary parts

QDVR  SL sin(L )  K sin(s ) (3.20)

PDVR  SL cos(L )  K cos(s ) (3.21)

Where cos(L ) and cos(s ) are the load power factor and source power

factor.

 V cos L    
 
PDVR  PL 1  th  (3.22)

 cos L  

In the equation 3.22, the load voltage is assumed to be 1pu. The

required active power of a DVR depends on the magnitude and the

phase angle jump  of supply voltage as well as the load power factor.

i. Converter Modeling

The main function of the Voltage Source Converter (VSC) is to convert

Dc signal into corresponding step ac signal. The thesis presents a

multilevel topology as VSC. The cascaded H bridge type with isolated

DC source is employed. The fig 3.9 represents the 5 level cascaded H

bridge leg for one phase. Cascaded H-bridge (CHB) multilevel inverter

employs multiple units of H-bridge power cells connected in series to

produce high ac voltage.


Fig 3.9: Configuration of five level H-bridge inverter for one phase

Fig 3.10: configuration of five level CHB inverter

The fig 3.10 represents the configuration of a five level CHB

inverter. If ‘m’ denotes the no. of voltage levels in a CHB inverter, the

no. of H-bridge cells (H) required in each phase is given by

m 1
H  (3.23)
2
For five levels, each phase leg consists of two H-bridge cells fed by

two isolated dc supplies with equal voltage E. The switching sequence

of the switches in each phase is shown in the switching table 3.1.

Table 3.1: Switching sequence of CHB five-level inverter

Inverter switches Voltage


level

T11 T12 T21 T22 T1`1 T121 T211 T221 VAO

1 0 1 0 0 1 0 1 2E

1 1 1 0 0 0 0 1 E

1 0 0 0 0 1 1 1 E

1 0 1 1 0 1 0 0 E

0 0 1 0 1 1 0 1 E

1 1 1 1 0 0 0 0 0

1 1 0 0 0 0 1 1 0

1 0 0 1 0 1 1 0 0

0 1 1 0 1 0 0 1 0

0 0 1 1 1 1 0 0 0

0 0 0 0 1 1 1 1 0

0 1 1 1 1 0 0 0 -E

0 0 0 1 1 1 1 0 -E

0 1 0 0 1 0 1 1 -E

1 1 0 1 0 0 1 0 -E

0 1 0 1 1 0 1 0 -2E

The five voltage levels in a CHB inverter are: 2E, E, 0, -E and -2E.

However, some voltage levels can be produced by more than one

switching state (redundancy); provides great flexibility for switching

pattern design.

a) Phase Shifted Multi-carrier Pulse Width Modulation


Phase Shifted Pulse Width Modulation (PSPWM) is one of the carrier

based modulation schemes or multilevel inverters. In the PSPWM, the

triangular carriers have the same frequency and same amplitude but

phase shifted by an angle. The no. of triangular carriers requires for five

levels inverter is given by

n  (m  1) (3.24)

The phase shift between any two adjacent carrier waves is given by

360
cr  (3.25)
(m  1)

The frequency of the dominant harmonic in the inverter output voltage

determines the inverter switching frequency f sw,inv . For five levels CHB

inverter, the dominant harmonics in phase and line voltages are

distributed around 4m f . The term m f refers to frequency modulation

index (ratio of carrier signal frequency ( f cr ) fundamental signal

frequency ( f m )). The inverter switching frequency is given by

f sw,inv  4m f * f m (3.26)

The inverter requires small filter at the output. A large amount of

transient current flows through the inverter switches when inverters

are requested to generate a significant amount of voltages suddenly in a

step wise manner. This transient voltage can be reduced by over-sizing

of the inverter switches.

ii. AC Filter

Second order LC-type filters are widely used on the AC terminals of

PWM inverters when the output voltages are the main control targets.
The main purpose of the filter is to attenuate the voltage ripple due to

inverter switching. A very large overshoot tends to occur at the filter

capacitor due to inverter switching. The higher order voltage harmonics

that are generated due to PWM switching cannot be attenuated by

controller but by a passive LC filter. The fig 3.11 represents process to

be controlled with filter as a plant. When the filter output voltage is

regulated to inverter output voltage by the controller, load voltage can

be written as

 2f
Vs  Vinv (3.27)
s 2  2d  f s   f2

To meet the design target (Vs = Vinv) as per the eqn. 3.27 at high

frequency ( > f), the inverter output voltage has to be large enough to

compensate the 40db/dec attenuation of the LC filter. Hence,

practically control bandwidth of compensation voltage of dynamic

voltage restorer c, should be limited to c ≤ f.

Correspondingly, the capacitor current and load current can be

calculated as

I cap  sC f Vc (3.28)

V V f 2

I load  inv  inv . (3.29)


Z load Rload s  s  2d f s   f2 
2

The filter ratio is determined by

Lf Rload
 (3.30)
Cf 2d
In the case of pure resistive loads, the filter ratio may be taken as

Lf Rload
to maintain the inverter output current under the rated
Cf d

peak value in a transient state. For highly inductive loads, the filter

ratio can be set to

Lf
Z load .e d (3.31)
Cf

The main steps to be considered for filter design are:

 Filter cut off frequency referring to the inverter switching

frequency

1 
f   sw (3.32)
Lf Cf 10

 Filter ratio referring to the rated load impedance and the control-

damping coefficient

Lf Z load
 (3.33)
Cf d

iii. DC energy storage

The DC energy storage supplies real power to the system during the

operation of DVR. A large DC capacitor needs to be connected in the

DVR to ensure constant input supply to inverter. The DC capacitor in

between the energy storage and inverter serves as the buffer to the

DVR, generating and absorbing power during voltage sag condition. The

size of the capacitor depends on the required active power to be injected


through DC storage capacity. However, the rating of the capacitor can

be calculated by

2( Pactive )Tsag
C (3.34)
Vdc2

Tsag refers to duration of sag and Pactive refers to the active power to be

injected by the DVR.

iv. Injection Transformer

The injection transformer function is to inject the missing voltage to

the line. Usually transformer either steps up or injects the voltage fed

from the out put of the filter before feeding to the line. The transformer

ratio can be defined as:

VDVR
n (3.35)
Vconv

The ratio can be sized to have high utilization of the converter. The

short circuit impedance of a transformer which is the summation of

resistive and reactive elements has a major influence on the short

circuit current. The worst short circuit current can be calculated as

Vsup ply max


I sc  (3.36)
Ztransformer 3

3.4 PROCESS TO BE CONTROLLED

The fig 3.11 represents the part of the DVR referring to main

problem of the research work. In the fig when the DVR is operating, the

load current flows through the transformer secondary. A part of this


load current flow in the transformer primary in the opposite direction to

the filter current.

Fig 3.11: process to be controlled

The negative current reduces the magnitude of filter output voltage;

More DC voltage is required to inject the missing voltage. The negative

current also increases the stress on the inverter switches and PWM

controller. The output voltage of filter can be defined as

1 Ls  R
Vs  Vinv  IL (3.37)
LCs  RCs  1
2
LCs  RCs  1
2

The main function of dynamic voltage restorer is to regulate the

output compensation voltages according to the reference voltages and

to properly reject the disturbances from the load currents. The main

requirement for the voltage regulation and disturbance rejection is to:

Vs
1 (3.38)
Vinv

IL
0 (3.39)
Vs
These equations refer to design targets to be achieved by suitable

control strategies.

3.5 OUTPUT SENSITIVITY FUNCTION

The fig 3.12 represents the closed loop block diagram for process to

be controlled. K and P refer to the plant and the controller. The transfer

function of the LC filter is considered as a plant.

Fig 3.12: Block diagram of process to be controlled

From the fig, the sensitivity functions can be derived to quantify the

system dynamics, robustness and noise rejection property of controller.

The three noises as shown in the fig 3.12 represents control noise Wu ,

output noise Wy and measurement noise Wb . From the fig 3.12, the

sensitivity function can be written as

1
Output to output sensitivity function S yy 
1  KP

 KP
Measure to output sensitivity function S yb 
1  KP

P
Control to output sensitivity function S yy 
1  KP
The gradient of S yy at low frequency determines the dynamic

behavior of the system. The bandwidth of S yb defines the influence of

noise on the output voltage and the closed loop bandwidth. The gain of

S yu verifies the rejection of control perturbations such as PWM related

noises. In addition to the sensitivity functions, module margin can be

determined from the peak magnitude of S yy . The module margin M is

defined as minimum distance of Lyy to the critical locus -1 in the

nyquist plot. The module margin and delay margin quantify the

robustness of the modeling uncertainties. The delay margin is given by





Where  and  represents the phase margin and frequency

corresponding to phase margin. For robust system, the module margin

must be less than 5db and delay margin must be higher than sampling

period.

Fig 3.13: Nyquist plot for Lyy


3.6 CONTROL STRATEGIES

The control strategy is an algorithm to tune the controller

parameters so as to meet desired target. The research work is carried

for four different algorithms for tuning controller parameters. PI

controller, Internal Model Control, RST controller, artificial neural

control is the four different controllers used in the research to test the

performance of DVR.

3.6.1 PID Control

Generally PID controller performs three actions on the given

system. PID contains proportional, integral and derivative actions on

the system. The individual actions on the systems are as follows:

a) Proportional controller

 Accelerates the process response with increase in gain.

 Produces a steady state deviation in the absence of integrator in

the transfer function. This offset decreases with increase in

proportional gain.

b) Integral

 Eliminates the steady state deviation

 Response is sluggish with long oscillations

 Increase of gain makes the system more oscillatory and leads to

instabilities

c) Derivative

 Anticipates future errors

 Introduces a stabilizing effect in the closed loop response.

To meet the design criteria, the plant is considered as LC filter.


1 n2 1.66 *107
G(s)   K  (3.40)
LCs 2  RCs  1 s 2  2n s  n2 s 2  333.33s  1.66 *107

Where K is the system gain, L = 3mH, C = 2μF and R = 1Ω

ωn is the systems natural frequency= 4079rad/sec

 is the systems damping ratio= 0.04.

The poles of the plant are -166.67+4079i.

K p s  KI
Controller C ( s)  (3.41)
s

Characteristic equation of this system is given by

Gch  s3  2n s 2  (n2  K pn2 )s  n2 K I (3.42)

In order to design the controller gain values poles have to be located

based on the required transient parameters (Peak-overshoot, settling

time and Peak time).

  
 d 
 1 2 
Peak time M e  d 
(3.43)

4.6
Settling time Ts  (3.44)
 d nd


Peak time Tp  (3.45)
nd 1   d2

For the desired transient parameters, d and ωd can be obtained.

Since  value in the plant is very less, d cannot be improved to 0.7.


Hence, it is selected based on the value of desired frequency. With the

obtained values, the closed loop characteristic equation with desired

damping ration and frequency can be written as


Gchd   s  a  s 2  2d d s  d2  (3.46)

Pole ‘a’ is selected so as to make the order of desired characteristic

equation and order of controller characteristic equation same. Usually

pole ‘a’ is a high frequency pole that allows the desired poles to

dominate the closed loop system response while allowing the desired

characteristic equation to have correct number of poles. The equation

can reduced to

Gchd  s3  (2d nd  a)s 2  (nd


2
 2d nd a)s  and
2
(3.47)

By comparing the eqns. 3.42 & 3.47, Kp and KI can be obtained

The simulink diagram for the step response of the closed loop system is

shown in the fig 3.14

Fig 3.14: Simulink diagram for step response of closed loop system
12

10

8
Amplitude

0
0 2 4 6 8 10
Time (secs)

Fig 3.15: Output response of PI controller without disturbance.

From the fig 3.15, it is evident that first desired condition is met

with the controller. The simulink diagram closed loop system with

disturbance is given by

Fig 3.16: Simulink diagram of closed loop system with disturbance


20

15

10
Amplitude

-5

-10
0 2 4 6 8 10
Time (secs)

Fig 3.17: Step response with disturbance

It is very clear that with PID controller, the disturbance still exists

at the time of injection which is not desirable. Hence, PID controller

does not give good performance for DVR application.

The bode plot of the closed loop system is shown in fig 3.18. The

performance parameters for the robustness are:

Gain margin (GM): 5.74dB

Phase Margin (PM): 170deg and 2.29deg.


Bode Diagram
20

0
Magnitude (dB)
-20

-40

-60

-80
0

-45
Phase (deg)

-90

-135

-180

-225
0 1 2 3 4 5
10 10 10 10 10 10
Frequency (rad/sec)

Fig 3.18: Closed loop bode plot with PI control

Bode Diagram
20

0
Magnitude (dB)

-20

-40

-60
180

135
Phase (deg)

90

45

-45
0 1 2 3 4 5
10 10 10 10 10 10
Frequency (rad/sec)

Fig 3.19: Output sensitivity plot

The output sensitivity function with PI control can be defined as


1
Go  (3.48)
1  KP

K refers to PI controller transfer function and P refers to the plant

transfer function. The corresponding output sensitivity function is

shown in the fig 3.19. The peak gain of the output sensitivity function

should be less than 5db. In the fig, the peak gain is 19db, which is

clearly greater than the specified. This peak gain indicates that PI

controller does not have disturbance rejection capability.

3.7 SYSTEM DESCRIPTION

In the proposed work, System is composed of generating system,

transmission system and distribution system to show the complete

power system network. Generating system is a three phase source with

13KV, 50Hz. Generating system is fed to two transmission lines

through 3-winding transformers connected in star/delta/delta with a

voltage rating of 13/115/15KV. Such transmission lines feeds two

distribution networks through two transformers connected in

delta/star with voltage rating of 15/11KV. In the test system voltage

sag is created by creating a symmetrical three phase line fault in

distribution system with a fault resistance of 0.66Ω. This fault results

in 20% voltage sag at the utility end. Voltage interruption is created by

creating a three phase line fault with fault resistance of 0.001Ω. The

duration of voltage sag and interruption is 0.3s i.e. between 0.5secs to

0.8secs.

Different case studies are proposed in this thesis. First case study

includes performance analysis of dynamic voltage restorer feeding to RL


load mitigating voltage sag. Second case study includes performance

analysis of dynamic voltage restorer feeding to a rectifier load mitigating

voltage sag. Third case study includes performance analysis of dynamic

voltage restorer feeding to RL load mitigating voltage interruption.

Fourth case study includes performance analysis of dynamic voltage

restorer feeding to rectifier load mitigating voltage interruption.

Fig 3.20: Simulink diagram of the test system


1

Va(V) 0

-1
0 0.2 0.4 0.6 0.8 1
1
Vb(V)

-1
0 0.2 0.4 0.6 0.8 1
1
Vc(V)

-1
0 0.2 0.4 0.6 0.8 1
Time
Fig 3.21: Voltage sag with a fault resistance of 0.66Ω
1

0.9

0.8

0.7
Magnitude (pu)

0.6

0.5

0.4

0.3

0.2

0.1

0
0 0.2 0.4 0.6 0.8 1
Time
Fig 3.22: Load voltage magnitude in pu
1

Va(V) 0

-1
0 0.2 0.4 0.6 0.8 1 1.2 1.4
1
Vb(V)

-1
0 0.2 0.4 0.6 0.8 1 1.2 1.4
1
Vc(V)

-1
0 0.2 0.4 0.6 0.8 1 1.2 1.4
Time

Fig 3.23: Voltage interruption with fault resistance of 0.001ohms

0.9

0.8

0.7
Magnitude (pu)

0.6

0.5

0.4

0.3

0.2

0.1

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Time

Fig 3.24: Load voltage magnitude in pu


3.8 SIMULATION RESULTS

Table 3.2: Test parameters

Parameters Values

Supply voltage 11kV

Filter Capacitance Cf 20µF

Filter inductance Lf 3mH

Filter resistance Rf 1

Proportional gain Kp 0.4142

Integral gain Ki 188.85

Load power factor 45deg lagging

Case 1: Voltage sag mitigation with PI control based DVR

Case 1 illustrates the operation of DVR for the mitigation of voltage

at the utility end with RL load. The PI controller is used for generating

reference signal for the PWM controller which in turn produces the

firing pulses for the multilevel inverter. The fig 3.25 depicts the load

voltage with DVR in operation between 0.5 to 0.8secs. As seen from the

figure, DVR is able to maintain load voltage at 98%. The injected

voltage from the DVR is free from harmonics. The response of a DVR for

the voltage sag is less than 4ms.


1

Va(V) 0

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
1
Vb(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
1
Vc(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time

Fig 3.25: load voltage with PI control

Selected signal: 50.32 cycles. FFT window (in red): 25 cycles


1

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time (s)

Fundamental (50Hz) = 0.9559 , THD= 1.20%


Mag (% of Fundamental)

20

15

10

0
0 2 4 6 8 10
Harmonic order

Fig 3.26: Total harmonic distortion with PI control


Case 2: DVR with rectifier load for mitigation of voltage sag

Case 2 illustrates the rectifier load connected to utility system. The

rectifier load is a non-linear load which distorts the load voltage and

current resulting in voltage and current harmonics. DVR operates

during the period of sag to maintain the load voltage at 98%. The DC

voltage required to mitigate the voltage is sag is . It is clearly seen from

the fig 3.27, that the DVR is injecting harmonic free voltage to the

utility end. The corressponding Total Harmonic Distortion (THD) is

shown in the fig 3.28. The time taken by the DVR to respond to voltage

sag is less than 4ms.

1
Va(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
1
Vb(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
1
Vc(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time

Fig 3.27: Load voltage with PI control with rectifier load


Selected signal: 50.46 cycles. FFT window (in red): 20 cycles
1

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time (s)

Fundamental (50Hz) = 0.9793 , THD= 1.93%


Mag (% of Fundamental)

15

10

0
0 2 4 6 8 10
Harmonic order

Fig 3.28: Total harmonic distortion with PI control

Case 3: Mitigation of voltage interruption with PI control based

DVR

Case 3 depicts the creation and mitigation of voltage interruption at

the uitlity end. Usually in closed loop, DVR can inject only 50% of the

rated load voltage during voltage fluctuations. Here, open loop is used

to make the DVR to inject more than 50% of the rated load voltage.

Case 3 illustrates the capability of a DVR to mitigate voltage

interruption at the utility end with large DC energy stirage facility. The

basic idea is to study the effect of controller on the disturbance

rejection and DC storage capability. The fig 3.29 shows the load voltage

with DVR injecting voltage during the period of voltage interruption.

Since, the DVR has to inject a very large voltage (rated load voltage) a
small delay is observed at the starting of injection. This delay is due to

the time taken by the filter and PWM inverter to develop the voltage.

However, the load voltage is observed to be free from harmonics and

load voltage is maintained at 98% at the utility end. The corressponding

THD of the load voltage is observed to be 3.07% which is below the

value specified as per the standard.

1
Va(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
1
Vb(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
1
Vc(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
Time

Fig 3.29 Load voltage with Controller compensating interruption


Selected signal: 54.56 cycles. FFT window (in red): 25 cycles
1

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time (s)

Fundamental (50Hz) = 0.7139 , THD= 3.07%


Mag (% of Fundamental)

60

40

20

0
0 1 2 3 4 5 6 7 8 9 10
Harmonic order

Fig 3.30: Total harmonic distortion with PI control

Case 4: DVR with rectifier load for mitigation of voltage

interruption

Case 4 describes the utility system connected to rectifier load. The

non linearity nature of the rectifier load distorts the load voltage and

current. This case study depicts the controller capability to reduce the

harmonics and disturbance rejection with non linear load. The DVR is

employed with isolated DC energy storage with open loop control. Since

the DVR has to inject complete rated load voltage it takes some time to

respond which is clearly observed in the fig 3.31 as small delay.

However, the DVR is able to maintain the load voltage at 98%. The

corresponding THD of the load voltage is observed to be 3.17% which is

lesser than the standard.


1

Va(V) 0

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
1
Vb(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
1
Vc(V)

-1
0.4 0.5 0.6 0.7 0.8 0.9 1 1.1
Time

Fig 3.31: load voltage after compensation voltage interruption for rectifier load

Selected signal: 53.94 cycles. FFT window (in red): 25 cycles


1

-1
0.4 0.5 0.6 0.7 0.8 0.9 1
Time (s)

Fundamental (50Hz) = 0.7148 , THD= 3.17%


Mag (% of Fundamental)

60

40

20

0
0 2 4 6 8 10
Harmonic order

Fig 3.32: Total harmonic distortion of load voltage


3.9 SUMMARY

In this chapter power quality issues for a DVR have been treated

and the focus has been on voltage sags, interruptions and the power

electronic controllers for voltage sag mitigation.

 Voltage sags can in many cases be the most severe power quality

problem because they can occur very frequently and lead to a

load tripping. The depth of voltage sag, duration and phase jump

depend on the location of the fault and the protection equipment

used.

 Voltage sag can be caused by faults at all voltage levels. The

voltage sag size and symmetry depend mainly on the type of fault,

grounding principles used at the faulted voltage level and the

transformer connections between the fault and the load of

interest.

 The mitigation of voltage sags can be achieved with power

electronic controllers. The series controller is recognized as a cost

effective solution for voltage sag mitigation.

 The series controller has its limitations in which it can provide

the best performance.

 Voltage injection methods for a series controller illustrate the

voltage disturbance handling capability under certain limitations.

 The multilevel topology for series controller is effective in

reducing the DC energy storage thereby reducing the cost. The

cascade H-Bridge topology with isolated DC source can be

advantageous compared to other topologies.


 The modeling of various parts of the series controller is

described.

 The objective of the research work i.e process to be controlled

needs a good controller inorder to satisfy the desired targets. PI

controller is tuned with pole placement method. The PI controller

response to step disturbance is very poor indicating its weakness

in disturbance rejection.

 The test system includes transmission and two distribution

systems. The voltage sag and interruptions are created by

creating faults with 0.66 and 0.001Ω. Some case studies are

illustrated with RL load and rectifier load mitigating voltage sag

and interruption.

 With pole placement technique, PI controller can provide good

voltage regulation, but cannot reject the disturbance. Hence DC

storage energy required to inject missing voltage is high.

Vous aimerez peut-être aussi