Vous êtes sur la page 1sur 16

Time Current Curves TD012030EN Effective September 2017

Series G R-Frame
800-2500A, 240-690V

Contents
Description Page
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Digitrip 310+ Electronic Trip Unit types RGH, RGC


Long Delay Response and Short Delay with Flat Response and Override
(LSI, LSIG, ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01210020E . . . . . . . . 5
Long Delay Response and Short Delay with I2T Response Curve and Override (LS, LSG) TC01210021E . . . . . . . . 6
Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . TC01210022E . . . . . . . 7
Maintentance Mode / Instantaneous Setting 1600A / 2000A (ALSI, ALSIG) . . . . . . . . . . . TC01210024E . . . . . . . 8
Maintentance Mode / Instantaneous Setting 2500A (ALSI, ALSIG) . . . . . . . . . . . . . . . . . . TC01210023E . . . . . . . 9

Digitrip RMS 310 Electronic Trip Unit types


Typical Instantaneous Time-Phase Current Characteristic Curve Based on In . . . . . . . . . . . SC-5629-93 . . . . . . . . 10
Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In . . . . SC-5630-93 . . . . . . . . 11
Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In . . . . . . . . . SC-5631-93 . . . . . . . 12

Note:
The following curves meet the requirements of UL, CSA, IEC, CCC and CE.
The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history.

Time Current Curves are engineering reference document for application and coordination purposes only.
Time Current Curves TD012030EN
AD012020EN Series G
Effective September
October 2013
2015 L-Frame
R-Frame

Notee: Unless noted below, all curves remain unchanged from their prior revision .

Revision Curve Number Page Date


Instantaneous curve adjusted TC01210020E 5 9 - 2015

  to meet tolerances. TC01210021E 6

ZSI times added to short delay curves. 5 9 - 2015

 SIOPEG@eaton.com 6

Override curve tolerances adjusted to 5,6 9 - 2017


match numerical percentages for 310+

2 eaton www.eaton.com
EATON
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015

Catalog Number Selection


This information is presented only as an aid to understanding catalog numbers.
It is not to be used to build catalog numbers for circuit breakers or trip units.

Table 1. RG Circuit Breaker/Frame

RG H 3 250 39 ZG E C

Frame Rating
RG Blank = 80% rated
C = 100% rated (except 2500A)
Amperes
Performance
160 = 1600 Trip Unit
600 480 415 240 Terminations
200 = 2000 33 = 310+ Electronic LS
H 50 65 70 125 250 = 2500 32 = 310+ Electronic LSI M = Metric tapped line/load
C 65 100 100 200 35 = 310+ Electronic LSG conductors
Poles 35B22 = 310+ Electronic LS(A), GFA, no trip E = Imperial tapped line/load
3 = Three 36 = 310+ Electronic LSIG conductors
4 = Four 36B22 = 310+ Electronic LSI(A), GFA, no trip
38 = 310+ Electronic ALSI Feature
with Maintenance Mode
39 = 310+ Electronic ALSIG Blank = No feature
with Maintenance Mode B20 = High load alarm
39B22 = 310+ Electronic ALSI(A) B21 = Ground fault
with Maintenance Mode and GFA, no trip ZG = Zone selective interlocking

EATON www.eaton.com 3
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame


LS LSI ALSI (With Maintenance Mode)

CAUSE OF TRIP
L
Ir Rating Ir Rating Ir Rating RESET
S
Chart Chart Chart
I

B C B C B C
A D I TEST / ALARM A D I TEST / ALARM A D I TEST / ALARM
r r r
E ∑ E ∑ E ∑
F F F
H G H G H G
4 7 4 7 4 7
2 10 t (s) 2 10 t (s) 2 10 t (s)
r r r
12 LONG STATUS 12 LONG STATUS 12 LONG STATUS
Engaged Engaged Engaged
15 15 15
24 20 24 20 24 20
3 4 3 4 3 4
2 5 I sd (xIr) Remove
2 5 I sd (xIr) 2 5 I sd (xIr)
6 6 Remove Remove
SHORT SHORT 6 SHORT
9 7 9 7 9 7
8 8 8

Inst. 50
t sd (ms) t sd (ms)
120 SHORT 120 SHORT

300 300 Remote MM

I i (xIn)
INST
7 8
6 Max
4
2.5
Maintenance Mode

NP 6635C07 H26 NP 6635C07 H25 NP 6635C07 H24

LSG LSIG ALSIG (With Maintenance Mode)

CAUSE OF TRIP CAUSE OF TRIP CAUSE OF TRIP

L L L
Ir Rating RESET
Ir Rating RESET
Ir Rating RESET
S S S
Chart Chart Chart
I I

G G G

B C B C B C
A D I TEST / ALARM A D I TEST / ALARM A D I TEST / ALARM
r r r
E ∑ E ∑ E ∑
F F F
H G H G H G
4 7 4 7 4 7
2 10 t (s) 2 10 t (s) 2 10 t (s)
r r r
12 LONG STATUS 12 LONG STATUS 12 LONG STATUS
Engaged Engaged Engaged
15 15 15
24 20 24 20 24 20
3 4 3 4 3 4
2 5 I sd (xIr) Remove
2 5 I sd (xIr) 2 5 I sd (xIr)
6 Remove 6 Remove
SHORT 6 SHORT SHORT
9 7 9 7 9 7
8 8 8
.4 .6 .4 .6 .4 .6
.2 .8 I (x 1000A) .2 .8 I (x 1000A) .2 .8 I (x 1000A)
g g g
1.0 GND 1.0 1.0 GND
GND
1.2 1.2 1.2

*
Inst.
*
K L K L
tg (ms) J M t / t (ms)
sd g
J M t / t (ms)
sd g
120 GND N SHORT / GND N SHORT / GND
R O R O Remote MM
300 Q P Q P

* Settings t g (ms)
Inst. 120 300 * Settings t g (ms)
Inst. 120 300
I i (xIn)

7
INST
8
50 J K L
t sd Inst.
120
J
M N
K L
O
t sd 120 M N O 6 Max
(ms) (ms)
300 P Q R 300 P Q R 4
2.5
Maintenance Mode

NP 6635C07 H23 NP 6635C07 H21


NP 6635C07 H22

*1600A/2000A Faceplates shown, 2500A Faceplates may differ

Figure 1. Digitrip 310+ Faceplates

4 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015


Circuit Breaker Time/Current Curves (Phase Current)


Series G R-Frame Circuit Breakers
Current in Multiples of (Ir)
Long Delay Response and Short Delay with Flat Response and Override
0.5 0.7 1 2 3 4 5 7 10 12 20 30
10000 Catalog Types: RGH, RGC circuit breakers, three- and four-pole
2 HOURS

9000
8000 Trip Unit Types: 32 (LSI), 36 (LSIG), 38 (ALSI), 39 (ALSIG)
7000
6000
Available Sensors Rated Amperes
5000
1.15 (Ir) / (In) 1600A 2000A 2500A
1 HOUR

4000
A 800A 1000A 1600A
3000 B 900A 1200A 1700A
C 1000A 1400A 1800A
2000 D 1100A 1600A 2000A
E 1200A 1700A 2100A
F 1400A 1800A 2200A
G 1500A 1900A 2400A
1000 H 1600A 2000A 2500A
900
800
700 Notes:
Maximum Total
600
Clearing Time 1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating for
500
ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
400 trip.

300 2. Application frequency is 50/60 Hz.

3. There is a memory effect that can act to shorten the long delay. If the breaker trips on a long delay
200 overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload
will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory. .
Available Long Delay Time
100
2, 4, 7, 10 ,12, 15, 20, 24 sec 4. The right portion of the curve is determined by the interrupting rating. of the circuit breaker.
90
80 Shown @ 6 x Ir +0/–30%
1 MINUTE

70 5. The left portion of the curve is shown as a multiple of the Long Delay Setting.
60 (Long Delay Pickup = 115% of Ir ). Range is 110–120%.
50
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
40 and the interruption of the current.

7. The short delay pickup has nine settings/positions;


.
30
1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9
2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6
20 24

.
TIME IN SECONDS

8. For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
breaker at 17,500A. Instantaneous tolerance is ± 20%.
15
Minimum Total 9. Maximum clearing time when using zone selective interlocking is 62ms.
10
9
Clearing Time
8
7
6
.
7
LSI LSIG ALSI (With Maintenance Mode) ALSIG (With Maintenance Mode)

CAUSE OF TRIP CAUSE OF TRIP CAUSE OF TRIP


L L L

Ir Rating Ir Rating Ir Rating Ir Rating

.
5 Chart
S
RESET

Chart
S
RESET

Chart
S
RESET

Chart I I I

4 G G

4
3
B C B C B C
B C A D I TEST / ALARM TEST / ALARM A D I TEST / ALARM
A D I TEST / ALARM r A D I r
r E ∑ r
E ∑ E ∑
E ∑
F F F
F H G H G H G
H G

.
4 7 4 7
4 7 2 10 t (s) 4 7 2 10 t (s)
2 10 t (s) r 2 10 t (s) r
r 12 LONG STATUS r STATUS
STATUS Engaged 12 LONG STATUS 12 LONG Engaged
12 LONG Engaged Engaged
15 15
15 24 20 15 24 20
24 20 24 20
3 4 3 4
2 5 I sd (xIr) 3 4

2
3 4 2 5 I sd (xIr)
2 5 I sd (xIr) 6 Remove 2 5 I sd (xIr) Remove Remove
Remove SHORT 6 6 SHORT
6 SHORT SHORT
9 7 9 7
9 7 8 9 7
8 8
8
.4 .6 .4 .6
.2 .8 I (x 1000A) .2 .8 I (x 1000A)
g

2 1.0 g
GND 1.0 GND
1.2 1.2

Available Short * *
K L K L
Inst. J M t / t (ms) 50
sd g J M t / t (ms)
t sd (ms) N SHORT / GND t sd (ms) sd g
120 SHORT N SHORT / GND
120 SHORT R O
Q P R O Remote MM

2
Remote MM

Delay Pickup
300 Q P
300

4 * Settings t g (ms)
Inst. 120 300
I i (xIn)
INST * Settings t g (ms)
Inst. 120 300
I i (xIn)
INST
t sd Inst. J K L J K L 7 8

Settings
7 8 50
120 M N O t sd 120 M N O 6 Max

1
(ms) 6 Max
300 P Q R (ms)
4 300 P Q R 4
2.5 2.5

0.9 Maintenance Mode Maintenance Mode

0.8 ISD x Ir ± 5% 3
6 NP 6635C07 H22
NP 6635C07 H24 NP 6635C07 H21

(See Note 7)
NP 6635C07 H25

0.7
0.6
5 9
0.5 0.5
300 ms *1600A/2000A Faceplates shown, 2500A Faceplates may differ
8
0.4 (P,Q,R) 0.4 TIME IN SECONDS
Instantaneous
0.3 Override (See Note 8)
0.3

0.2 0.2

7
Override curve should start
120 ms from 21000A (17500 with
0.1 (M,N,O) +20 % tolerance applied)
0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
Inst. 0.05
(J,K,L)
0.04 0.04
Application Determines
0.03 End of
0.03Curve

0.02 0.02

17500A

0.01 0.01
0.5 0.7 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100

Current in Multiples of (Ir) Current in 1000A Increments

Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

Figure 2. Digitrip 310+ Long Delay Response and Short Delay with Flat Response and Override Curve (LSI, LSIG, ALSI, ALSIG) -
Curve Number TC01210020E, September 2017
EATON www.eaton.com 5
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame


Circuit Breaker Time/Current Curves (Phase Current)


Series G R-Frame Circuit Breakers
Current in Multiples of (Ir) Long Delay Response and Short Delay with I2T Response Curve and Override
Catalog Types: RGH, RGC circuit breakers, three- and four-pole
0.5 0.7 1 2 3 4 5 7 10 12 20 30
10000 Trip Unit Types: 33 (LS), 35 (LSG)
1 HOUR 2 HOURS

9000
8000
7000 Available Sensors Rated Amperes
6000 (Ir) / (In) 1600A 2000A 2500A
5000
1.15 A 800A 1000A 1600A
4000
B 900A 1200A 1700A
3000 C 1000A 1400A 1800A
D 1100A 1600A 2000A
E 1200A 1700A 2100A
2000
F 1400A 1800A 2200A
G 1500A 1900A 2400A
H 1600A 2000A 2500A
1000 Notes:
900
800
700 1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere derating for
Maximum Total ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an over-temperature protection
600
Clearing Time trip.
500

400 2. Application frequency is 50/60 Hz.

300 3. There is a memory effect that can act to shorten the long delay. If the breaker trips on a long delay
overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload
will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is
200
inverse to the amount of time that has elapsed since the previous overload. Approximately five
minutes is required between overloads to completely reset memory.
Available Long Delay Time
2, 4, 7, 10, 12, 15, 20, 24 sec 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
100 Shown at 6 x Ir +0 / –30% 5. The left portion of the curve is shown as a multiple of the Long Delay Setting.
90
1 MINUTE

80 (Long Delay Pickup = 115% of Ir ). Range is 110–120%.


70
60 6. Total clearing times shown include the response times of the trip unit, the breaker opening,
50 and the interruption of the current.
40 7. The short delay pickup has nine settings/positions; 1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9
2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6

.
30
8. For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the
breaker at 17,500A. Instantaneous tolerance is ± 20%.
20 24

.
TIME IN SECONDS

9. Short delay I2T band has a tolerance of ±15%.

Minimum Total
15 10. Breakpoint back to FLAT response occurs at 8 x Ir for upper line of the I2T curve.
10
Clearing Time 11. Maximum clearing time when using zone selective interlocking is 62ms.
.
9
8
7
6 7 LS LSG

.
5

4 CAUSE OF TRIP
L
Ir Rating Ir Rating RESET
4 Chart Chart
S

3
G

2
3 . A
B C

H G
D I

F
r
E ∑
TEST / ALARM A
B C

H G
D I

F
r
E ∑
TEST / ALARM

2 2
4 7
10 t (s)
r
2
4 7
10 t (s)
r
12 LONG STATUS
12 LONG STATUS Engaged
Engaged
15 15
24 20 24 20
3 4 3 4
2 5 I sd (xIr) 2 5 I sd (xIr)
2 6 SHORT
Remove 6 SHORT
Remove

4 9 7 9 7
8 8
.4 .6
.2 .8 I (x 1000A)
g
1 1.0
1.2
GND

0.9 Inst.
tg (ms)
0.8 300
120 GND

0.7 5
0.6
9 0.5
0.5
NP 6635C07 H26 NP 6635C07 H23

0.4 7

0.3 *1600A/2000A Faceplates shown, 2500A Faceplates may differ 0.3


6

0.2 0.2
TIME IN SECONDS

Available Short Delay


2
I T Short Delay Pickup Settings Instantaneous
8
(See Note 9) 2–8, 9 x Ir ± 5% Override (See Note 8)
0.1
(See Notes 7 and 10)
0.1
0.09 0.09
0.08
0.07
0.06
. Application Determines
End of Curve
0.08
0.07
0.06
0.05
67 ms 0.05

0.04 0.04

0.03 0.03

See Note 9
0.02 0.02
17500A
Override curve
should start from
the 21000A (17500
0.01 with
0.01 +20%
0.5 0.7 1 2 3 4 5 7 10 12 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100tolerance applied)

Current in Multiples of (Ir) Current in 1000A Increments

I2T Trip Style (LS, LSG)

Figure 3. Digitrip 310+ Long Delay Response and Short delay with I2T Response Curve (LS, LSG) - Curve Number TC01210021E,
September 2017
6 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015


Circuit Breaker Time/Current Curves (Ground Current)


Series G R-Frame Circuit Breakers
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0 Ground Fault Delay Response Curve
10000
9000 Catalog Types: RGH, RGC circuit breakers, three- and four-pole
8000
7000 Trip Unit Types: 35 (LSG), 36 (LSIG), 39 (ALSIG)
6000
5000
LSG LSIG ALSIG (With Maintenance Mode)
4000

CAUSE OF TRIP
3000
CAUSE OF TRIP CAUSE OF TRIP

L L L
Ir Rating RESET
Ir Rating RESET Ir Rating RESET
S S S
Chart Chart Chart
I I

G G G
2000

B C B C B C
A D I TEST / ALARM A D I TEST / ALARM A D I TEST / ALARM
r r r
E ∑ E ∑ E ∑
F F F
H G H G H G
4 7 4 7 4 7
2 10 t (s) 2 10 t (s) 2 10 t (s)
r r r
STATUS 12 LONG STATUS 12 LONG STATUS
12 LONG Engaged Engaged Engaged
15 15 15
24 20 24 20 24 20

1000 3 4 3 4 3 4
2 5 I sd (xIr) 2 5 I sd (xIr) Remove
2 5 I sd (xIr)
Remove 6 SHORT 6 Remove
6 SHORT SHORT
900 9
8
7 9
8
.4 .6
7 9
8
.4 .6
7

.4 .6 .2 .8 I (x 1000A)
800 .2 .8 I (x 1000A)
1.0
g
GND
1.0
1.2
g
GND
.2 .8 I (x 1000A)
1.0
1.2
g
GND
1.2

700 Inst.
tg (ms)
J
K L
*
M t / t (ms)
sd g J
K L
*
M t / t (ms)
sd g
120 GND N SHORT / GND N SHORT / GND

600 300
R
Q P
O R
Q P
O Remote MM

* Settings t g (ms)
Inst. 120 300 * Settings t g (ms) I i (xIn)

500
Inst. 120 300 INST
Inst. J K L 7 8
t sd
120 M N O
50
t sd J K L
(ms) 120 M N O 6 Max
300 P Q R (ms)
300 P Q R 4
2.5

400
Maintenance Mode

NP 6635C07 H22
NP 6635C07 H23 NP 6635C07 H21

300

*1600A/2000A Faceplates shown, 2500A Faceplates may differ


200
SD / GF Delay Settings Table

* t g (ms)
100
90
80
Settings
1 MINUTE

70
60
Inst. 120 300

t sd Inst. J K L
50

40
120 M N O
30
(ms)
300 P Q R
20
TIME IN SE CONDS

Ground Fault Pickup Settings Ground fault delay response notes:


(Tolerance ±10%)
10 1. Curve accuracy applies from –20°C to +55°C ambient. For possible continuous ampere
9 derating for ambient above 40°C, refer to Eaton. Temperatures above +85°C cause an
8
7
over-temperature protection trip.
6 Ig = 1000A for all
2. Application frequency is 50/60 Hz.
5 RG Frames
4 3. Trip units are suitable for functional field testing with test kit cat no: MTST230V.

3 4. For LD Response and SD with Flat Responses curve, see TC01210020E.

5. For LD Responses and SD with I2T Response curve, see TC01210021E.


2
6. For testing information, please contact Eaton.

1 1.2x Ig
0.9
0.8 0.8x Ig
0.7
0.2x Ig 0.4x Ig 0.6x Ig
0.6
0.5 1.0x Ig

0.4

300 ms
0.3
(L, O, R)

0.2

120 ms
0.1
(K, N, Q)
0.09
0.08
0.07
0.06
Inst.
0.05 (J, M, P)
0.04

0.03

0.02

0.01
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0

Ground Current in Multiples of Ig x 1000

Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) Curve Number TC01210022E, June 2012

EATON www.eaton.com 7
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame


Series G R-Frame Trip Unit Nameplates


Digitrip 310+ Circuit Breaker Time/Current Curves
Maintenance Mode/Instantaneous
Setting (1600A/2000A) ALSI (With Maintenance Mode) ALSIG (With Maintenance Mode)

Notes:
CAUSE OF TRIP CAUSE OF TRIP

L L
1. The Maintenance Mode feature must be ENABLED for these Ir Rating RESET
Ir Rating S
RESET
S
curves to apply. The LED indicator is blue when in Maintenance Chart Chart
I
Mode.
I

2. The end of the curve is determined by the interrupting rating of the


circuit breaker. B C B C
A D I TEST / ALARM A D I TEST / ALARM
r r
E ∑ E ∑

3. Total clearing times shown include the response times of the trip F F
H G H G
4 7 4 7

unit, the breaker opening, and the interruption of the current. 2 10 t (s)
r
12 LONG STATUS
Engaged
2 10 t (s)
r
12 LONG STATUS
Engaged
15 15
24 20 24 20
3 4 3 4

4. Available pickup settings ( x In) (tolerance is ±15%) 2 5


6
I sd (xIr)
SHORT
Remove
2 5
6
I sd (xIr)
SHORT
Remove

1600A Frame: 2.5, 4, 6, 7, 8, 8, 11 9 7 9 7


8 8
.4 .6

2000A Frame: 2.5, 4, 6, 7, 8, 8, 9 .2 .8 I (x 1000A)


1.0
g
GND
1.2

5. These curves are comprehensive for the complete family of


50
t sd (ms)
120 SHORT
J
K L
*
M t / t (ms)
sd g
N SHORT / GND

Series G R-Frame electronic breakers, including all frame sizes,


R O Remote MM
300 Remote MM Q P

ratings, and constructions. The total clearing times shown are I i (xIn)
INST * Settings t g (ms)
Inst. 120 300
I i (xIn)
INST

conservative and consider the maximum response times of the trip 7 8 50 J K L 7 8


6 Max
t sd 120 M N O 6 Max
(ms)
4 300 P Q R 4
unit, the circuit breaker opening, and the interruption of the current 2.5
Maintenance Mode
2.5
Maintenance Mode

in worst case conditions such as: maximum rated voltages,


single-phase interruption, and minimum power factor. Faster NP 6635C07 H24 NP 6635C07 H21

clearing times are possible depending on the specific system


conditions. *1600A/2000A Faceplates shown, 2500A Faceplates may differ

Contact Eaton for additional information.

Maintenance Mode Trip Instantaneous Mode Trip


10 10
9 9
8 8
7 7
6 Maintenance Mode Instantaneous Mode Pickup 6
5
Pickup tolerance (+/- 15%) Tolerance (+/- 15%) 5

4 4

3 3

2 2

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 2.5 4.0 6.0
Max. for 0.6
8.0
0.5 2000A 0.5

0.4
Frame 0.4
TIME IN SECONDS

TIME IN SECONDS

0.3 0.3
Max. for
1600A
0.2 7.0 9.0
Frame 0.2

11.0

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 Application Application 0.06
0.05 Determines Determines 0.05
End of Curve End of Curve
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
0.9
0.6

1
0.5

0.7
0.8

10
5
6

50
20
2

30

40
10
3

100
7

Current in Multiples of Rating (In)

Figure 5. Maintenance Mode/Instantaneous Setting 1600A/2000A (ALSI, ALSIG) - Curve Number TC01210024E, September 2015

8 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015


Series G R-Frame Trip Unit Nameplates


Digitrip 310+ Circuit Breaker Time/Current Curves
Maintenance Mode/Instantaneous Setting (2500A)
ALSI (With Maintenance Mode) ALSIG (With Maintenance Mode)

Notes:
CAUSE OF TRIP CAUSE OF TRIP

L L
1. The Maintenance Mode feature must be ENABLED for these Ir Rating RESET
Ir Rating S
RESET
S
curves to apply. The LED indicator is blue when in Chart Chart
I
Maintenance Mode.
I

2. The end of the curve is determined by the interrupting rating of the


circuit breaker. B C B C
A D I TEST / ALARM A D I TEST / ALARM
r r
E ∑ E ∑

3. Total clearing times shown include the response times of the trip F F
H G H G
4 7 4 7

unit, the breaker opening, and the interruption of the current. 2 10 t (s)
r
12 LONG STATUS
Engaged
2 10 t (s)
r
12 LONG STATUS
Engaged
15 15
24 20 24 20
3 4 3 4

4. Available pickup settings ( x In) (tolerance is ±15%) 2.5, 4, 6, 6, 6, 7. 2 5


6
I sd (xIr)
SHORT
Remove
2 5
6
I sd (xIr)
SHORT
Remove

9 7 9 7
8 8
.4 .6

5. These curves are comprehensive for the complete family of .2 .8 I (x 1000A)


1.0
g
GND

Series G R-Frame electronic breakers, including all frame sizes,


1.2

ratings, and constructions. The total clearing times shown are


50
t sd (ms)
120 SHORT
J
K L
*
M t / t (ms)
sd g
N SHORT / GND

conservative and consider the maximum response times of the trip


R O Remote MM
300 Remote MM Q P

unit, the circuit breaker opening, and the interruption of the current I i (xIn)
INST * Settings t g (ms)
Inst. 120 300
I i (xIn)
INST

in worst case conditions such as: maximum rated voltages, single- 7 8 50 J K L 7 8


6 Max
t sd 120 M N O 6 Max
(ms)
4 300 P Q R 4
phase interruption, and minimum power factor. Faster clearing 2.5
Maintenance Mode
2.5
Maintenance Mode

times are possible depending on the specic system conditions.


NP 6635C07 H24 NP 6635C07 H21

Contact Eaton for additional information.


*1600A/2000A Faceplates shown, 2500A Faceplates may differ

Maintenance Mode Trip Instantaneous Mode Trip


10 10
9 9
8 8
7 7
6 Maintenance Mode Instantaneous Mode Pickup 6
5 Pickup tolerance (+/- 15%) Tolerance (+/- 15%) 5

4 4

3 3

2 2

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 2.5 4.0 6.0 0.6
0.5 0.5

0.4 0.4
TIME IN SECONDS

TIME IN SECONDS

0.3 0.3

0.2 7.0 0.2

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 Application Application 0.06
0.05 Determines Determines 0.05
End of Curve End of Curve
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
1

10
0.9
1
0.6
0.5

0.7
0.8

5
6

50
20

40
2

30
10
3

100
7

Current in Multiples of Rating (In)

Figure 6. Maintenance Mode/Instantaneous Setting 2500A (ALSI, ALSIG) Curve Number TC01210023E, September 2015

EATON www.eaton.com 9
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame

AB DE-ION Circuit Breakers

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units
Typical Instantaneous Time-Phase Current Characteristic Curve Based on In

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000
Circuit Breaker Time/Current Curves (Phase Current)
2 HOURS

Series C® R-Frame Circuit Breakers


5,000 Equipped With Type Digitrip RMS 310 Trip Units
Typical Trip Unit Nameplate
1 HOUR


Westinghouse
Digital
Protection
3,000
For use with Trip Unit Catalog Numbers
1600A Max. 2000A Max. 2500A Max.
Cell No.

Digitrip RMS 310


2,000
RES1600LS RES2000LS RES2500LS
Standard Fixed RES1600LSG RES2000LSG RES2500LSG NP6635C68H07 Made in U.S.A.

Rating Plug
Digitrip RMS 310 Rating Plug

RES1600LS RES2000LS RES2500LS For Use in R Circuit Breaker Only


Engaged Cat._ _
In

Remove

Short Delay
1,000 Pickup
In

500
NP6645C79H01

Frame Available Rating Plugs


Rating Ampere Type Catalog Short Delay
Amperes Rating (In) Number Pickup Range
300
(Max.) Amperes
1600 1600 Fixed 16RES16T 3200-12800
200 1400 Fixed 16RES14T 2800-11200
Maximum Total 1250 Fixed 16RES125T 2500-10000
Clearing Time 1200 Fixed 16RES12T 2400-9600
1000 Fixed 16RES10T 2000-8000
800 Fixed 16RES08T 1600-6400
Minimum Total 800, 1000, 1200, 1600 Adj. A16RES16T1 1600-12800
100
Clearing Time 800, 1000, 1250, 1600 Adj. A16RES16T2 1600-12800

2000 2000 Fixed 20RES20T 4000-16000


1 MINUTE

1600 Fixed 20RES16T 3200-12800


1400 Fixed 20RES14T 2800-11200
50 1250 Fixed 20RES125T 2500-10000
1200 Fixed 20RES12T 2400-9600
1000 Fixed 20RES10T 2000-8000
1000, 1200, 1600, 2000 Adj. A20RES20T1 2000-16000
30 1000, 1250, 1600, 2000 Adj. A20RES20T2 2000-16000
2X

2500 2500 Fixed 25RES25T 5000-15000


20 2000 Fixed 25RES20T 4000-12000
1600 Fixed 25RES16T 3200-9600
3X

1250 Fixed 25RES125T➄ 2500-7500


1200 Fixed 25RES12T 2400-7200
1200, 1600, 2000, 2500 Adj. A25RES25T1 24000-15000
10 1250, 1600, 2000, 2500 Adj. A25RES25T2➄ 2500-15000

Interrupting Ratings – 50/60 Hz


RMS Sym. Amperes (kA)
Short Delay Breaker UL/CSA IEC 947-2 (Icu)
4X

5 Type
Pick Up 240V 480V 600V 220-240V 380-415V 500V
Settings RD, CRD 125 065 50 125 065 42
(Tolerance ±10%) RDC, CRDC 200 100 65 200 100 65
3 Utilization Category A
Ics = 0.25 Icu
8X

Uimp = 8 kV
5X

2
Notes
TIME IN SECONDS

Curve accuracy applies from –20°C to +55°C ambient. For possible ampere derating for
ambient above 40°C, refer to Cutler-Hammer.

1 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.
6X

STK2. For field testing using primary injection methods, follow NEMA publication AB-
4-1991.

For 2500A styles, maximum short delay pickup setting = 6X.


.5
For high fault current levels a fixed instantaneous override is provided at 17,500A
(Tolerance ±15%).

.3 The end of the curve is determined by the interrupting rating of the circuit breaker.
7X

See above tabulation.

.2 For ground fault time-current curves see SC-5631-93.

Not UL/CSA Listed.

.1 .1

.05 .05
Fixed Instantaneous
.04
Override
.03 .03

.02
Interrupting
.02
Rating
Determines
End of
Curve
SECONDS

.01 .01

.005

.003

.002

.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000

20,000

30,000

40,000

50,000

100,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

Figure 7. Typical Instantaneous Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5629-93, October 1997

10 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015

AB DE-ION Circuit Breakers

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units
Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000
Circuit Breaker Time/Current Curves (Phase Current) ➃
2 HOURS

Series C® R-Frame Circuit Breakers


5,000
Equipped With Type Digitrip RMS 310 Trip Units
Typical Trip Unit Nameplate
1 HOUR

Westinghouse
Digital
Protection

3,000
For use with Trip Unit Catalog Numbers
Cell No.
1600A Max. 2000A Max. 2500A Max. Digitrip RMS 310

2,000 RES1600LSI RES2000LSI RES2500LSI


Standard Fixed RES1600LSIG RES2000LSIG RES2500LSIG
NP6635C68H07 Made in U.S.A.

Digitrip RMS 310 Rating Plug

Rating Plug RES1600LSI RES2000LSI RES2500LSI For Use in R Circuit Breaker Only
Engaged Cat.
_
In
_

Remove

Short Delay

1,000
Pickup
In

Short Delay
Time
Sec

500 NP6645C79H02

Frame Available Rating Plugs


Rating Ampere Type Catalog Short Delay
Amperes Rating (In) Number Pickup Range
300
(Max.) Amperes
Maximum Total
1600 1600 Fixed 16RS16T 3200-12800
Clearing Time 1400 Fixed 16RS14T 2800-11200
200
1250 Fixed 16RS125T➄ 2500-10000
1200 Fixed 16RS12T 2400-9600
1000 Fixed 16RS10T 2000-8000
800 Fixed 16RS08T 1600-6400
800, 1000, 1200, 1600 Adj. A16RS16T1 1600-12800
100 Minimum Total 800, 1000, 1250, 1600 Adj. A16RS16T2➄ 1600-12800
Clearing Time
2000 2000 Fixed 20RS20T 4000-16000
1600 Fixed 20RS16T 3200-12800
1 MINUTE

1400 Fixed 20RS14T 2800-11200


50 1250 Fixed 20RS125T➄ 2500-10000
1200 Fixed 20RS12T 2400-9600
1000 Fixed 20RS10T 2000-8000
1000, 1200, 1600, 2000 Adj. A20RS20T1 2000-16000
30 1000, 1250, 1600, 2000 Adj. A20RS20T2➄ 2000-16000

2500 2500 Fixed 25RES25T 5000-15000


20 2000 Fixed 25RES20T 4000-12000
1600 Fixed 25RES16T 3200-9600
1250 Fixed 25RES125T➄ 2500-7500
2X

1200 Fixed 25RES12T 2400-7200


1200, 1600, 2000, 2500 Adj. A25RES25T1 24000-15000
10
1250, 1600, 2000, 2500 Adj. A25RES25T2➄ 2500-15000
Interrupting Ratings – 50/60 Hz
RMS Sym. Amperes (kA)
Breaker UL/CSA IEC 947-2 (Icu)
4X

Short Delay Type 240V 480V 600V 220-240V 380-415V 500V


5
Pick Up RD, CRD 125 065 50 125 065 42
Settings RDC, CRDC 200 100 65 200 100 65
(Tolerance Utilization Category A
6X

3 ±10%) Ics = 0.25 Icu


Uimp = 8 kV
Notes
2 ➀ Curve accuracy applies from –20°C to +55°C ambient. For possible ampere derating for
8X

ambient above 40°C, refer to Cutler-Hammer.


TIME IN SECONDS

Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.
➀ STK2. For field testing using primary injection methods, follow NEMA publication AB-
7X

1 4-1991.

➀ For 2500A styles, maximum short delay pickup setting = 6X.


➁ For high fault current levels a fixed instantaneous override is provided at 17,500A
(Tolerance ±15%).
➂ The end of the curve is determined by the interrupting rating of the circuit breaker.
.5 See above tabulation.
3X

5X

➃ For ground fault time-current curves see SC-5631-93.


300 ms ➄ Not UL/CSA Listed.
.3

200 ms
.2

100 ms
.1 .1

.05 .05
Fixed Instantaneous
I .04 Override ➁
.03 .03
Interrupting
.02 .02
Rating
Determines
End of
Curve ➂
SECONDS

.01 .01

.005

.003

.002

.001 .001
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20
10,000

20,000

30,000

40,000

50,000

200,000
100,000

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

CURRENT IN AMPS

Figure 8. Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5630-93,
October 1997
EATON www.eaton.com 11
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame

AB DE-ION Circuit Breakers

Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units
Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In

CURRENT IN AMPERES

1000

2000

3000

4000
100

200

300

400
500
600
700
800
900
50 60 70 80 90
10,000 10,000

2 HOURS
2 HOURS

Circuit Breaker Time/Current Curves (Phase Current) ➀

Series C® R-Frame Circuit Breakers


5,000 Equipped with Type Digitrip RMS 310 Trip Units 5,000

1 HOUR
1 HOUR

for Ground Fault Protection


For use with Trip Unit Catalog Numbers
3,000 1600A Max. 2000A Max. 2500A Max. 3,000
RES1600LSG RES2000LSG RES2500LSG
RES1600LSIG RES2000LSIG RES2500LSIG 2,000
2,000

Westinghouse Westinghouse
Digital Digital
Protection Protection
1,000 1,000

Cell No. Cell No.

Digitrip RMS 310 Digitrip RMS 310


500 500
NP6635C68H07 Made in U.S.A. NP6635C68H07 Made in U.S.A.

Digitrip RMS 310 Rating Plug Digitrip RMS 310 Rating Plug
For Use in R Circuit Breaker Only For Use in R Circuit Breaker Only
300 Cat._ _ Cat.
_ 300
Engaged Engaged
In In_

200 Remove Remove


200
Short Delay Short Delay
Pickup Pickup
Gnd. Fault *Gnd. Fault Pickup Gnd. Fault *Gnd. Fault Pickup
In SETTING CURRENT In SETTING CURRENT
Pickup Pickup
A 200A A 200A
* * Short Delay
100 400A Time 400A 100
600A 600A
800A Sec 800A
1000A 1000A
B 1200A B 1200A

1 MINUTE
1 MINUTE

Gnd. Fault C 1200A Gnd. Fault C 1200A


Time D 1200A Time D 1200A
E E
Sec F Sec F
H H
50 K K 50
Gnd. Gnd.
NP6645C79H05 NP6645C79H06

30 Notes 30
Curve accuracy applies from –20°C to +55°C ambient.

20 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. 20
For field testing using primary injection methods, follow NEMA publication AB-4-1991.

➀ For phase time-current curves see SC-5629-93 and SC-5630-93.

10 10
1000 A.
600 A.

5 5
200 A.

Ground Fault Pickup


3 Settings 3
(Tolerance ±10% Except,
±20% on 200 A. Setting)
2 2
1200 A.
400 A.

800 A.
TIME IN SECONDS

TIME IN SECONDS

1 1

.5 SEC
.5 .5

.3 SEC
.3 .3

.2 .15 SEC .2

.1 .1

.05 .05

.03 .03

.02 .02

.01 .01

.005 .005

.003 .003

.002 .002

.001 .001
50 60 70 80 90
500

700
200

300

400

600

800
900
1000

2000

3000

4000
100

CURRENT IN AMPERES

Figure 9. Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In - Curve Number SC-5631-93, October 1997

12 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015


EATON www.eaton.com 13
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame


14 EATON www.eaton.com
Series G Time Current Curves TD012030EN
R-Frame Effective September 2015


EATON www.eaton.com 15
Time Current Curves TD012030EN Series G
Effective September 2015 R-Frame


Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2017 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD012030EN / TBG 001369 All other trademarks are property
September 2017 of their respective owners.

Vous aimerez peut-être aussi