Vous êtes sur la page 1sur 2

NEXANS TÜRKİYE END.

TİC AŞ
TUZLA FABRİKA/TUZLA PLANT

XLPE/OS/PVC/SWA/PVC
FLAME RETARDANT INSTRUMENTATION CABLE
600/1000 V

Design
Max. Conductor Temperatue : 90°C
1.Conductor 3 2 1

Stranded annealed copper to IEC 60228 (Class 2)


2
Cross section: 2,5 mm (7/0,67 mm)

2.Insulation
Cross Linked Polyethylene (XLPE)
Laying-up: Twisted cores

3.Overall Screen
Polyester (PEPT) Tape
2
Tinned stranded copper 0.50 mm
Aluminum backed polyester foil
Polyester (PEPT) Tape

4.Inner Jacket
PVC
Inner sheath Colour: Black

5.Armour
Galvanized steel wire armour
Polyester (PEPT) Tape (optional)

6.Outer Jacket
FR- PVC
Outer sheath Colour: Black

Core Identification
Core : Black – White

Minimum
Flame Retardant Operating Temp. UV Resistant Bending Radius
IEC 60332-1 -30oC +70oC
10xD
Installation Temp.
-5oC +50oC

Customer- Project Document Type Doc. No. Date. Rev. Page


CABLE DEPOT Technical Specification 2015-06464-TS-02 Oct. 2015 0 1/2
NEXANS TÜRKİYE END.TİC AŞ
TUZLA FABRİKA/TUZLA PLANT

Standards
Generally to IEC 60502-1 (where applicable)

Marking (ink-jet)
NEXANS - - cable definition- No. of pairs& cross-section – flame standard - Voltage rating - +
Month/Year meter marking

Example: NEXANS 185 XLPE/OS/PVC/SWA/PVC 1x2x2,5 mm² IEC 60322-1 600/1000 V


10/2015 0050

Electrical Properties
2
2,5 mm
o
o Max. DC Resistance (Ohm/km) @ 20 C 7,41

o Insulation Resistance 5000 M Ohm x km


o Test Voltage (V) 5 minute 3,500 V ac or 8,400 V dc

Physical Characteristics

Poz. No Cable Type Dia. of Overall Diameter Cable


Pair x Size Cable under Weight
armour

Min. Max. Approx.


mm mm mm kg/km

1 2x2,5 9,2 13,7 15,7 403

Customer- Project Document Type Doc. No. Date. Rev. Page


CABLE DEPOT Technical Specification 2015-06464-TS-02 Oct. 2015 0 2/2