Vous êtes sur la page 1sur 2

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Seismic Design for Special Moment Resisting Frames Based on CBC 2001 - ASD

INPUT DATA & DESIGN SUMMARY


COLUMN SECTION => W14X176
A d tw bf tf Sx Ix rx ry Zx k
51.8 15.2 0.83 15.65 1.31 281 2140 6.43 4.02 320 2.00
BEAM SECTION = > W30X108
A d tw bf tf Sx Ix rx ry Zx k
31.7 29.8 0.55 10.48 0.76 299 4470 11.87 2.15 346 1.56

STRUCTURAL STEEL YIELD STRESS Fy = 50 ksi THE SMRF DESIGN IS ADEQUATE.


THE GRAVITY LOAD (1.2D + 0.5 L) ON THE BEAM wg = 2 klf (Continuity column stiffeners 13/16 x 7
BEAM LENGTH BETWEEN COL. CENTERS l= 28 ft with 1/2" fillet weld to web & CP to flanges.
COLUMN AXIAL LOAD AT SERVICE LEVEL D= 113 kips A doubler plate is required with thickness of 1-1/16 in. )
L= 75 kips
COLUMN AXIAL LOAD AT HORIZ. SEISMIC Eh = 5.5 kips (CBC 30A-1)
SEISMIC COEFFICIENT Ca = 0.44 (CBC Tab. 16A-Q)
IMPORTANCE FACTOR I= 1.15 (CBC Tab. 16A-K)
REDUNDANCY FACTOR r= 1.25

AVERAGE STORY HEIGHT OF ABOVE & BELOW h= 12 ft


REDUCED SECTION DIMENSIONS a= 6 in, [0.5~0.75bf]
b= 24 in, [0.65~0.85db]
c= 2.25 in, [ < 0.25bf]

ANALYSIS r = (4c2 + b2 ) / 8c = 33.1 in


Sh = dc/2 + a + b/2 = 25.6 in

THE BEAM LOCAL BUCKLING LIMITATION (CBC 2213A.7.3)


bf / (2tf ) = 6.89 < 52 / (Fy)0.5 = 7.35 [Satisfactory]
d / tw = 54.73 < 640 / (Fy)0.5 = 90.51 [Satisfactory]

THE BEAM BRACING LIMITATION (CBC 2213A.7.8)


Smax = 96ry = 17.17 ft
Hence, both flanges of beam shall be braced at maximum spacing 17.17 ft.

THE COLUMN LOCAL BUCKLING LIMITATION (CBC 2213A.7.3 & ASD N7, Pg 5-96)
bf / (2tf ) = 5.97 < 7.00 [Satisfactory]

THE ALLOWABLE COLUMN DESIGN LOADS (CBC 1612A.3.1, 2213A.8.2, & 2213A.8.4.1)
Pt = 0.9D - (rEh + 0.5CaID) / 1.4 = 76 kips (Compression)
Pc = D + 0.75[L + (rEh + 0.5CaID) / 1.4] = 188 kips (Compression, Governs)
Pc = D + (rEh + 0.5CaID) / 1.4 = 138 kips (Compression)

THE BEAM - COLUMN RATIO REQUIREMENT (CBC2213A.7.5)


SMpc* / (SMpb* ) = 1.64 > 1.00 [Satisfactory]
( > 1.25 The column flanges need to be laterally supported only at the beam top flange.
Where SMpc* = SZc (Fyc - Pc / Ag ) = 2473 ft-kips CBC 2213A.7.7.1)
SMpb* = S(Mpr + Mv) = 1505 ft-kips
Mv = [2Mpr /(L-2Sh)+wg(L-2Sh)/2] Sh= 272 ft-kips
Mpr = b Fyb zb = 1233 ft-kips
3
zb = Zb - 2c tf (d - tf) = 247 in
b= 1.2 (FEMA Sec. 7.5.2.2)

THE BENDING MOMENT AT THE COLUMN FACE (CBC2213A.4.2)


Mf = Mpr + [2Mpr / (L - 2Sh) + wg(L - 2Sh)/2] (a + b/2)
= 1424 ft-kips < Fyb Zb = 1442 ft-kips [Satisfactory]
(Cont'd)

THE COLUMN DESIGN LOADS (CBC 2213A.5.1)


Pt = 0.85D - W0Eh = 81 kips (Compression)
Pc = D + 0.7L + W0Eh = 181 kips (Compression, Governs)
Where W0 = 2.8 (CBC Tab. 16A-N)

THE COLUMN COMPRESSION CAPACITY (CBC 2213A.4.2 & ASD E2)


Pc,allow = 1.7FaA = 1890.6 kips > Pc [Satisfactory]
Where K = 1.0
Es = 29000 ksi (1-F2/2)Fy / (5/3+3F/8-F3/8) = 21.47 kis, for Cc > (Kl/r)
2
Cc = (2p Es/Fy) 0.5
= 107
Fa = { 12p2Es/[23(Kl/r)2] = N/A kis, for Cc < (Kl/r)
MAX(Klx/rx, Kly/ry) = 67.10 < 200 [Satisfactory]
F = (K l / r) / Cc = 0.63

THE CONTINUITY PLATE REQUIREMENT (FEMA Sec. 3.3.3.1 & CBC 2213A.7.4)
tst = tbf for interior connection, or (tbf /2) for exterior connection = 0.76 in,USE 0.81 in, ( 13/16 in )
bst = 7 in > bfb /3 - twc /2 = 3.08 in, (ASD Sec. K1.8) [Satisfactory]
Ast = [Pbf - Fyc twc(tfb + 5kc)] / Fyst = -7.498 in2, (ASD K1-9) < tst bst [Satisfactory]
Where Pbf = 0.18bfbtfbFyb = 71.6 kips, (CBC 2213A.7.4)

The best fillet weld size (ASD Sec.J2.2b)


> wMIN = 0.25 in
w= 1/2 in
< wMAX = 0.6875 in
[Satisfactory]
The required weld length between A36 continuity plates and column web (FEMA Fig 3-6)
Lw = Pbf / [(2) 1.7 (0.3Fu )(0.707 w)] = 71.6 / [(2) 1.7 (0.3x70)(0.707x1/2)] = 2.14 in
< 2(Lnet) [Satisfactory]
Where Lnet = dc - 2(kc) = 11.2
(Use complete joint penetration groove welds between continuity plates & column flanges.)

THE PANEL ZONE THICKNESS REQUIREMENT (CBC 2213A.7.2)


tReqD = MAX (t1, t2) = 1.59 in
t1 = Vz / (0.55Fycdc) - 3bfctfc2 / (dcdb) = 1.59 in, (CBC 13A-1)
Where Vz = 2(0.8) SMf / (db - tfb/2) - 2(0.8)Mf / h = 738.7 kips
(SEAOC Design Manual, Vol. III, Pg 182)
t2 = (dz + wz ) / 90 = (db -2tst + dc - 2kc) / 90 = 0.44 in

Since twc = 0.55 in < tReqD , a doubler plate is


required with thickness of 1-1/16 in.

Techincal References:
1. ICBO: "2001 California Building Code, Title 24, Part 2, Volume 2", 2002.
2. SEAOC: "Seismic Design Manual - Volume 3", International Code Council, 2000.
3. AISC: "Manual of Steel construction 9th", American Institute of Steel Construction, 1990.

Vous aimerez peut-être aussi