Vous êtes sur la page 1sur 28

BRS2216 Outdoor Power System

Telecom Power RBS2216


Outdoor System

1
NTBU
BRS2216 Outdoor Power System

Telecom Power System

AC Input

LOAD (Switch ,ADSL…E.T.C.)


Output DC Distribution Unit
AC Distribution Unit Rectifier # 1

Generator Rectifier # 2
Battery
Rectifier # 3
U.P.S
LVDS
Rectifier # N

Control Supervisory
Unit (CSU)

Telecom Power System


2
1
BRS2216 Outdoor Power System
Contents
ƒ System Overview
¾ Main Feature/Configuration
¾ Outdoor Cabinet Type (1.8M)
¾ Power Distribution configuration (AC,Surge , DC Load , Battery.
¾ Rectifier Power shelf configuration
¾ Rectifier module specification (DP2700)
¾ New Smart CSU controller with LCD Display
¾ System Function Introduction
¾ Delta Remote/Monitor function
¾ -- NRMS monitor software (Mini USB port)
¾ -- Web Server/ SNMP function (Optional)

ƒ Q&A

3
BRS2216 Outdoor Power System
Delta DPS 2700 Series Power System
Main Features:
ƒ AC Input: Optional for three conditions
ƒ 220Vac, Single phase (Already)
ƒ 380Vac, Three phases / Five Wire ( Y Connection)
ƒ System Capacity: -54Vdc / 150A Max.
ƒ IP Protect:Power system Bay: IP54, Equipment Bay: IP55
ƒ DC Distribution: Load Breaker Configurations: Breaker (DIN rail ),
ƒ Battery Breaker: ~125A Breaker, 2 Positions Max.
ƒ LVDB *1 (Standard): 150A on Battery Side
ƒ LVDL *1: 150A on Load Side
ƒ Rectifier: -54Vdc/50A (DPR2700) *3
ƒ Controller: New Smart CSU with LCD
ƒ Relay Output: Total 8 Positions, Customer Definable
ƒ Local/Remote Monitoring and Control – NRMS software
ƒ Local Access: By NRMS via RS232 Interface
ƒ Internet Web Server Function: By Web Server Software/SNMP via RJ45 Interface
(Optional)
ƒ System Dimension (W*D*H): 55.1” x 33.5” x 71.3” inch / 1400 x 850 x 1810mm
ƒ Operating Temperature: 0℃~+55℃(32℉~131℉)

4
BRS2216 Outdoor Power System

New Smart CSU (Relay Board)) CCU (Climate


Control Unit )

New Smart CSU (Main Board))

160W Heat-exchanger

Rectifier ESR-48/56A

19” Rectifier Shelf (SB-05N/HG A ) PDU ( four Configurations)


Battery & Base 5
BRS2216 Outdoor Power System
RBS2216 Outdoor System Drawing

6
BRS2216 Outdoor Power System
Delta Power System Drawing

7
BRS2216 Outdoor Power System
Delta Power System Drawing - Cooling
BHEX

Temp Sensor

Temp Sensor
Airsys HX160-B1
Heat Exchanger
Fan Tray

Fan Speed Control


(Full speed operation)

FL

CSU

Fan ON/OFF Control


Hi Temp Alarm

CCU
Hi Temp Alarm
HEX status Monitoring Architecture of Cooling Control 8
BRS2216 Outdoor Power System
RBS2216 Equipment Bay Configurations
Add markings on base frame for for
AP29
7pcs of 3-hole Cable Gland reserved RBS2216 installation.
(Details show on later page)

10mm

Micro Switch (Front Door)


10U(H) Max. Space for
Transmission Equipment
160 W/K Heat Exchanger

RBS2216

Plinth
4pcs of M10 insert nuts pre-installed in Bracket
For RBS2216 Installation,
Estimated Weight: 140 Kg (With HEX) Pitch: 572mm * 307mm
(Transmission equipment excluded) Load capacity(Tray): 300Kg 9
BRS2216 Outdoor Power System
RBS2216 Power System Bays Configurations

Fan tray mounted on


inside of roof

4U Space for DDF-OVP

Cable gland for DC cables to


equipment bay

Power system
Climate Control Unit
AC termination
External Alarm Terminal
Changeover Switch

Air Filter Frame mounted 2nd Battery Shelf


on Front Door (Battery excluded in cabinet)

Metal duct to AC
termination
1st Battery Shelf
Bottom cable entries (Battery excluded in cabinet)

Estimated Weight: 127 Kg (With Power system)


(Battery strings, DF-OVP excluded) 10
BRS2216 Outdoor Power System
RBS2216 AC Panel Configurations AP36

Phase 1 (with Genset Socket & Changeover Switch):


Implementation: from first batch

Add AC Socket Changeover Switch

Phase 2 (without Genset Socket & Changeover Switch):


Implementation: TBD (Inventory Concern)

Genset Socket

11
BRS2216 Outdoor Power System
RBS2216 Lights & Sensors

Smoke Sensor DC Light

Humidity Sensor
12
BRS2216 Outdoor Power System
RBS2216 AC Input Terminations

AC main input Terminal Block


For 3 phases and neutral connections

AC Grounding Bus Bar


4pcs of M6 insert nuts

AC cabling from outside wall


3pcs of MG32A 3-hole Cable Gland slot (L150mm * W60mm)
For cable range (OD): 5~10mm through cable glands and metal
wiring ducts to main AC
terminations
13
BRS2216 Outdoor Power System

Main Power AC input Type

1P 220Vac Type 3P 380Vac Start Type

AC MAINS INPUT
1 PHASE 220V 50/60Hz
AC MAINS INPUT
3 PHASE 380V + N 50/60Hz

L N
R S T N

R S T N
R S T N

AC BREAKER 3P
AC BREAKER 3P
SURGE-T AC-T&SURGE-T
SURGE-T AC-T&SURGE-T SURGE-S AC-S&SURGE-S
SURGE-S AC-S&SURGE-S SURGE-R AC-R&SURGE-R

SURGE-R AC-R&SURGE-R

R S T PE

R S T PE N

N SURGE ARRESTER AC-N

SURGE ARRESTER AC-N

14
BRS2216 Outdoor Power System
AP32

RBS2216 AC Cable Entry on Both Sides

AC cables pass through left side


of plinth.

Plate (1pcs):
Pre-install on right side
Design to block unused side

New requirement:
AC cables can pass through right side of plinth.
15
BRS2216 Outdoor Power System
AP24

RBS2216 Roof Installation Improvement

Modify rear cover for roof installation without removing rear covers

Roof

Keep clearance between roof and rear


cover to prevent interference

Rear Cover

(Section View from Right Side)

16
BRS2216 Outdoor Power System 7pcs of side cable
entries reserved
RBS2216 Cable Entries 2pcs of 3-hole Cable Glands
For jumper cable 1/2” (OD 12.5mm)
9pcs of compartment cable
entries reserved
4pcs of MG32A 1-hole Cable 2pcs of 3-hole Cable Glands
For cable range (OD): 15~22mm For jumper cable 1/4” (OD 6.35mm)
(2E1, Alarm cable, 1 power cable
for MW)

4pcs of MG32A 3-hole Cable Glands 3pcs MG32A 3-hole Cable Glands
For cable range (OD):5~10mm
(Ericsson’s cables ) For cable range from (OD 5~10mm)

1pce of MG25A 3-hole Cable Gland


For cable range (OD): 2.6~3.6mm
(Delta internal cable)

4pcs of bottom cable


Genset Socket, 32A
entries reserved 3N~(R, S, T, N, PE)
3pcs MG32A 3-hole Cable Gland
For cable range (OD): 5~10mm
For AC Terminations

1pcs MG25A 1-hole Cable Gland


For cable range (OD): 12~16mm
For DC grounding cable 17
BRS2216 Outdoor Power System
RBS2216 Battery Configurations

Reserved cabling space for


Jumper Cables

2nd Battery Shelf


Max. Space suitable for
CSB TPX122200 * 4pcs

1st Battery Shelf


Max. Space suitable for
CSB TPX122200 * 4pcs

18
BRS2216 Outdoor Power System
Recommended Spare Parts & Part Numbers
 
Model Name
RBS 2216, 1.8M
Spare parts Remark
(Delta P/N)
ESOA150-ABA01
CU-18A A-S
Climate Control Unit
V

3790335100-S
Controller(NCSU)-LCD Display
V

5505602118-S
Controller(NCSU)-Main Board
V

ESR-48/56A A-S
Rectifier 2700W (DPR2700)
V

3790335000
Temperature Sensor Cable 3M
V

EX-F01 B-S
Fan Tray
V

EX-H01 A-S
Heat Exchanger 22W/K NA
(Delta HEX)
Air Filter G3
3243139500
V

Heat Exchanger
160W/K V
50400000196

19
BRS2216 Outdoor Power System

SMR Shelf 19” H type

SB-05N/HG A DPS 2700 shelf 54V/150A


W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm

20
BRS2216 Outdoor Power System
DP 2000 Series Rectifier

Features and Benefits


ƒ -48V/41.7A, Output; Max. Power 2000W
ƒ Wide Input Voltage Range (90V~300V)
ƒ Power Factor Correction (>0.99)
ƒ Hot-pluggable, All Connectors are at the rear
ƒ Compact Size
≅ 24W/in3 (48V) Power Density
Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)
Light weight:1.64 Kg (4.4lb)
Horizontal(1U)/Vertical(2.8U) Models Available
ƒ High Efficiency: >91% (48V)
ƒ Fan cooling and Easy replaceable fan design
ƒ Operation temp.:-5oC~+65oC
ƒ UL/CUL,TUV/CE Certificated

21
BRS2216 Outdoor Power System
Rectifier - Interface

Pin Number Signal Description

P4 VOP Precharge
P5-P7 VO- DC Output “-”
P8-P10 VO+ DC Output “+”

I/O Connector A1 SGNDO Signal ground


A2 RS485+ RS 485 + communication
Input Signal Output B1 CGND Communication ground
B2 RS485- RS 485 – communication
C1 INH Short pin for well connection
Pin Number Signal Description
C2 IDA ID analog
P1 AC_L AC main, L terminal
D1 IDD ID digital
P2 AC_N AC main, N terminal
D2 IBUS Load Sharing Bus
P3 FG AC main, frame ground
22
BRS2216 Outdoor Power System
New Smart CSU: DPS 2700 Series

LCD Display

Analog
Signal Detection
Configuration, RS-485
Supervision Terminal Interface

RS-485 X 3
With SMR

Web/SNMP Card

Analog RS-485 With


I.D address SMR

Ethernet

54Vdc/50A
With SMR
Configuration,
Supervision 23
(web browser)
BRS2216 Outdoor Power System
Power System Controller – New Smart CSU
ƒ Easy integration with most Delta power systems
ƒ Modular system controller
ƒ User friendly operating interface
Large 128 x 64 pixel LCD Display
Entry of alarm and system parameters from keypad
ƒ High reliable RS-485 communication with Rectifier
ƒ Easy system expansion
Easy extendable custom-design I/O board
ƒ Complete function support
More then 100 system events log
Temperature & Voltage compensation charging
Smart Battery management User Interface
Green Function
ƒ Different possibilities for remote monitoring
1 outside communication port (Mini USB) DB9
Local Access monitoring & Control
Web Server Function (RJ-45) 24
BRS2216 Outdoor Power System
Delta Power System Monitoring & Control
Client User
Internet

Telecom Power Manage


Program
Client User
Client User

Build in HTTP
Web Server

Mini USB Control &


Supervisory
Local Unit

Environment
AC DC Distribution Battery Data
Distribution Rectifiers Management
Acquisition
25
BRS2216 Outdoor Power System

NRMS Monitor software

Mini US
B

Local Access

26
BRS2216 Outdoor Power System

Web Server Function and Feature (Optional)


Features:
Applied in TCP/IP Internet/Intranet Environment
Complete Supervising to Power System
User-friendly Graphic Interface
Dynamic information presentation
Password function
Multi Language Support

Main Screen Microsoft Explorer and Netscape Support

Parameter Setting
Status Configuration
Alarm 27
BRS2216 Outdoor Power System

Q&A

28

Vous aimerez peut-être aussi