EE 104 Protective Relaying 3rd Long Exam 2nd Sem AY 2016-2017 05/27/2017 COE Bldg.

Coverage: Protective Relays, Reclosers & Sectionalizers, Relay Coordination


Instruction: Erased answers are considered wrong.

I. Identification. Identify the following.

_______________ 1. Used in power systems to respond either to the rate of rise of gas pressure.
_______________ 2. Detects single phasing, damaging phase voltage unbalance, and reversal of phase rotation of
supply for protection of rotating equipment.
_______________ 3. Prevents any attempt to start a motor with one phase open.
_______________ 4. Detects reverse phase connections of interconnecting circuits, x’mers, or generators.
_______________ 5. Blocks the operation of a voltage controlled current relay when a potential transformer fuse blows.

II. Definition. Define the function(s) of the following protective relay device numbers.

1. 72
2. 76
3. 55
4. 46
5. 50
6. 52T
7. 23M
8. 43L
9. 62
10. 85

III. Relay Coordination. Complete the following table and make a graph of coordination curves.

CT Normal Current Minimum Fault Maximum Fault Pick-up Current Instantaneous


Inputs
Ratio (A) Current (A) Current (A) (A) Current (A)
R1 60 150 600 4000
R2 120 500 1500 25000
R3 200 1000 6000 32500
R4 300 2000 8000 45000

Relay Settings R1 R2 R3 R4
Pick-up Current (Ipu) Settings
Time Settings (D)
Instantaneous Current Settings
Pick-up Current (Actual), A
Instantaneous Current (Actual), A
Maximum Current (Actual), A

Available Settings for the Relays:


Pick-up Current: 1 - 24 A, increment of 0.1 A
Time Delay: 0.05 - 2 sec, increment of 0.01 sec
Instantaneous Current: 1 - 99 A, increment of 3 A

Curve Name A P Q B K
Very Inverse IEC Curve B 13.5 1 1 0 0