Digital Protective Relays

L&T

Larsen & Toubro Limited offers a wide


range of Microprocessor based State-of-the-art
Digital Protective Relays suitable for
LV, MV and HV power distribution systems.
These Relays are manufactured at
L&T’s Mysore works equipped with
modern infrastructure and employing
latest manufacturing and testing equipments.
L&T’s range also include Relays for
special applications manufactured by
Microelettrica Scientifica, Italy.
The applications include Feeder Management,
Load Sharing, Load Shedding, Synchronising,
Grid Islanding etc.

L&T also manufactures a range of


Electronic Single Phase Energy Meters,
Mysore Works Three Phase Energy Meters and
Trivector Meters at the Mysore Works..

Training Centres
The L&T Switchgear Training Centres at
Pune, Lucknow & Coonoor are the only
facilities of their kind in India. The Centres
have state-of-the-art training facilities,
well-equipped workshop & testing systems.

Training programmes on Protective Relaying


and related subjects are being regularly
conducted at above training centres.

Kindly contact the nearest Training Centre


for further details.

Lucknow Pune Coonoor


Plot No. C/6-7 T-156/157, MIDC, Bhosari, Ooty-Coonoor Main Road
Sarojini Nagar Industrial Area Pune 411 026 Needle Industries P.O. Ketti,
Lucknow 226 008 Tel. : 020-7120037, 7120653 Niligiris 643 243 (T.N.)
Tel. : 0522-437591, 437728 Fax : 020-7122993, 7121221 Tel. : 0423-517158
Fax : 0522-437592 e-mail : stc-pune@lntebg.com Fax : 0423-517107
e-mail : stc-lucknow@lntebg.com e-mail: stc-coonoor@lntebg.com
Contents

Pages

Time - Current Characteristics 3

Over Current relays - MC31A, MC61A, MC61C 4-5

Current Sensing relays - MC12A, ME12A, SC14S 6-7

Neutral Displacement relay - MND11


Reverse Power Relay - MRP11 8-9
Voltage relay - MV12

Secondary relays - TCS01, PTF03 10-11

Power Factor Control relay - PFC8, PFC14, PFR8 12-13

Motor Protection relay - MM30, MM30W, MPR300 14-15

Generator Protection relays - IM3GV, MG30, MD32G 16-17

Synchronising relays - SPM21, SCM21. 18-19


Load Sharing Relay - RRS

Voltage Vector shift / Voltage / Frequency relays - UFD34, UM30A 20-21


Directional Over Current relay - DM33

Transformer Protection relays - MD32T, IM30T, UM30SV 22-23

Auto Reclosing Relay - IM30DRE 24-25


Control & Supervision relays - MW33, MU30.

Feeder protection - MC20R, MC30, RPM8 26-27


Capacitor protection relay - IM 30C

1
Corelation between ANSI/IEEE device Function number and Relays

Device Function L&T MS


No. Name Relays Relays

21 Under impedance relay / Distance relay --


25 Synchronising and or Synchro-check relay SPM21
SCM21
26 Over or under temperature protection and control relay --
27 AC under voltage relay MV12 UM30 / UM30SV
UFD34
32 Power directional relay MRP11 MG30
37 Under current or underpower relay MM30
MW33
38 Bearings over temperature relay --
40 Field control (loss of field) relay MG30
45 DC over voltage relay –
46-(61) Reverse phase or phase balance current relay IM30T
MM30
47 Phase-sequence or single-phasing voltage relay UM30
49 Machine or transformer thermal relay IM30T
IM3GV
MM30
50 Instantaneous over current (or rate-of-rise) relay ME12 --
MC12A --
MC61C --
MC61A --
50/27 Voltage restrained over current relay IM3GV
50BF Breaker - failure over current relay --
50N Instanteneous earth fault over current relay MC12A --
MC61A --
MC61C --
51 AC time over current relay MC12A --
MC61A --
MC31A --
MC61C --
51N-(51G) Ground fault time over current relay MC12A --
MC61A --
MC31A --
MC61C --
58 Rectifier failure relay (rotating diodes) --
59 AC over voltage relay MV12 UM30 / UM30SV
-- UFD34 / UM30SV
59/81 Overexcitation relay V/Hz -- UM30 / UM30SV
-- UM30A / UM30SV
60 Voltage balance relay UM30
64 Ground detector (insulation to ground failure of machine or other apparatus) MG30
64S Machine stator ground fault detector relay -- MG30
64R Machine rotor ground fault detector relay -- UBO / CR
67 AC directional over current relay -- DM33
67N-(67G) Directional ground fault over current relay -- DM33
74 Alarm relay -- --
76 DC over current relay -- --
78 Phase angle measuring or out of-step protection relay -- --
-- IM30G
79 Reclosing relay -- IM30DR
80 DC Under voltage relay -- --
81 Frequency relay -- UM30 / UM30SV
-- UFD34
86 Lock-out relay -- --
87 Differential protective relay -- MD32G
-- MD32T
87N-(87G) Ground fault differential protective relay SC14S --
90 Regulating device to adjust a quantity -- --
91 DC directional voltage relay -- --
92 DC directional voltage and current relay -- --
95 Automatic active or reactive load sharing relay – RRS
Vector Surge Protection Relay UM30-SV

2
Product Design Standards

Reference standards
IEC 60255, IEC 61000,
IS3231, IS8686

Dielectric test : IS 3231 / IEC 60255-5


Impulse test: : IS 8686 / IEC 60255- 5
HF disturbance test: : IS 8686 / IEC 60255-22-1
Electrostatic discharge test : IEC 61000-4-2
Electrical fast transient : IEC 61000-4-4
Radiated electro magnetic field test : IEC 61000-4-3
Surge immunity : IEC 61000-4-5
Ring wave test: : IEC 61000-4-12
Voltage dips & interruption test : IEC 61000-4-11
Power frequency magnetic test : IEC 61000-4-8

Time - Current Characteristics (At TMS = 1)

1,000

100
Trip Time (Sec.)

10

1 B
C

01
1 10 20

Multiple of set current (Is)

For Trip time at TMS other than 1 A : Normal Inverse 3.0 Sec.
Trip time = (Trip time at TMS = 1) x TMS OR B : Normal Inverse 1.3 Sec.
50msec whichever is more C : Very Inverse
D : Extreme Inverse

3
Over Current Relays
Wiring Diagrams

MC31A
R Y B R Y B
1 1

2 2 MICRO
CONTROLLER R1 N0
9
3 3
MC31A 10
4 4
NC
R2
13 13 PROTECTION 11
5 5
F50(Is) 12
6 6 R3
F51(0s) 17
15 15

16 16 18

7 7 R4
27
8 8 R Y B E
28
21
22 R5
PROG. 29
25 ERROR
L/+ 30
In = 1A; 5A ˜
0n = 1A; 5A N/- 26

MC61A

R Y B R Y B
1 1

2 2 MICRO
CONTROLLER R1 N0
9
3 3
MC61A 10
4 4
PROTECTION R2 NC
13 13 11
5 5
F50(Is) 12
6 6 R3
F51(Os)
17
15 15
F50(Ihs)
16 16 18
F51(Ohs)
7 R4
7
27
8 8
R Y B E
28
21
R5
22
PROG 29
25 ERROR
L/+
In = 1A; 5A 30
0n = 1A; 5A 26
N/-

MC61C
R Y B R Y B
1 1 R1
9

2 2 MICRO
CONTROLLER 10 NO
R2
3 3 11

4
MC61C 12
4 NC
PROTECTION R3
13 13 17
BKR
5 5 18 OPEN
F50(Is)
R4
6 6 F51(Os) 27 BKR

15 15 F50(Ihs) 28 CLOSE
F51(Ohs) R5
16 16
29
7 7
30
8 D1
8 19 L/R
R Y B E
D2
20 BI*
21 D3
31
22
C 32
PROG
25 ERROR
In = 1A ; 5A L/+ S-
0n = 1A ; 5A ˜
S+
N/- 26
9 PIN MALE

4
Over Current Relays
Three Phase Over Current &
Earth fault Relays

• Display of currents, settings,


Trip data & Trip history for analysis
& trouble shooting

• Built in self supervision & self


testing feature to ensure continuous

158mm
reliability

• Separate Indication for power ON &


Programming mode or relay fault

• Separate fault indication


m
4m m
• In MC61C - Communication with 20 4m
22
Computer & breaker control through
RS 485 Port
121mm
• Four user programmable output
relays

Model MC31A MC61A MC61C


Description 3 Phase O/C + E/F 3 Phase O/C + E/F + Highset 3 Phase O/C + E/F + Highset
Communication and breaker control
Device Code 51 RYBN 50/51 RYBN 50/51 RYBN
Design Numerical Relay Numerical Relay Numerical Relay
Functions Available Lowset O/C -Is Lowset O/C -Is Lowset O/C -Is
Lowset E/F -Os Highset O/C -Ihs Highset O/C -Ihs
Lowset E/F -Os Lowset E/F -Os
Highset E/F -Ohs Highset E/F -Ohs
Settings O/C Is = 20-200% Step 5% O/C Is = 20-200% Step 5% O/C Is = 20-200% Step 5%
E/F Os = 5-80% Step 5% E/F Os = 5-80% Step 5% E/F Os = 5-80% Step 5%
Time Characteristics available - HS O/C = (0.2 to 40) x In step of - HS O/C = (0.2 to 40) x In step of -
NI, VI, EI, or Definite Time 0.2 In or disable 0.2 In or disable
TMS 0.1 - 1.6 Step 0.05 HS E/F = (0.1 to 20) x On step of - HS E/F = (0.1 to 20) x On step of -
0.1 On or disable 0.1 On or disable
Time Characteristics available - Time Characteristics available -
NI, VI, EI, or Definite Time NI, VI, EI, or Definite Time
TMS : 0.1 - 1.6 Step 0.05 TMS : 0.1 - 1.6 Step 0.05

Other Features Site selectable Trip time Char. Site selectable Trip time Char. HS delay:0.1-2 Sec step 0.01 -
Sec. or Inst.
Highset can be disabled RS 485 Communication
Display of Currents, Trip count Display of Currents, Trip count Breaker control
Self supervision feature Self supervision feature Auto doubling of highset, -
(Relay co-ordination)
Burden on CT £ 0.25 VA on CT/Phase £ 0.25 VA on CT/Phase £ 0.25 VA on CT/Phase
Burden on PT Not applicable Not applicable Not applicable
Operating temp 0 0C to 600C 00C to 600C 00C to 600C
Weight < 2kg < 2kg < 2kg
Burden on Auxiliary supply £ 10 VA £ 10 VA £ 10 VA
Output Contact 1 N/O Contact for self suprvn 1 N/O Contact for self suprvn 1 N/O Contact for self suprvn
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cut Out 113 x 142 113 x 142 113 x 142
O R D E R I N G I N F O R M AT I O N
Auxiliary supply Type 1 20-110V AC / DC or 20-110V AC / DC or 20-110V AC / DC or
Type 2 88-264V AC / DC 88-264V AC / DC 88-264V AC / DC
CT rating 1 AMP or 5 AMP 1 AMP or 5 AMP 1 AMP or 5 AMP
(site selectable) (site selectable) (not site selectable)
Output Contacts 4NO or 2NO + 2NC 4NO or 2NO + 2NC 4 NO

5
Over Current Relays
Wiring Diagrams

MC12A / ME12A

1 COM

2 +VE/PH.
Aux. Supply
R1
3 -VE/N
μP. Control
Ckt.
F50/50N COM
10
F51/51N

11

12

MC12A / Me12

SETTING RANGE (Is)


In AUX SUPPLY MC12A ME12
1A 24 - 110V AC/DC (10-40)% In (1-16)% In
5A 95 - 240V AC/DC (20-80)% In
(50-200)% In

SC14S

11
2
10

9 ˜ Control R
1

Ckt. 3

7
+ 5
Test (24V) DC-DC Test
Voltage 6
Convrt.
8
4
12

SC14S

In CT OPERATED RELAY SETTING RANGE (Is)


1A NO AUXILIARY SUPPLY (10-40)% IN
5A REQUIRED (20-80)% IN

6
Current Sensing Relays
Single Phase Over current / Earth fault Relay
Sensitive E/F Relay / Instantaneous Current Relay

• Easy setting through front panel


DIP Switches

• Indication for
Power ON and trip status

158mm
• Test feature - helps maintenance

• Compact, light weight helps in


reducing panel size & thickness.

22 mm
m
4
4m
20
71mm

Model MC12A ME12A SC14S


Description 1 Ph O/C or E/F 1 Ph Sensitive E/F Instantaneous current relay

Device Code 50/51 or 50N/51N 50N/51N 87N/64R


Design Microcontroller Based Microcontroller Based Static
Functions Available Lowset O/C -Is Lowset S E/F -Is
Highset O/C -Ihs Highset S E/F -Ihs.
Lowset E/F -Os
Highset E/F -Is

Settings O/C Is = 50-200% Step 10% OR S E/F = 1-16% step 1% Is = 10-40% step 5%
E/F Is = 10-40% Step 2% OR HS S E/F = (2-16) xls OR 20-80% step 10%
E/F Is = 20-80% Step 4% in steps of 2 ls
HS O/C = (2-16) xls step 2 Is
HS E/F = (2-16) xls step 2 Is
Time Characteristics available- Time Characteristics available- Time Characteristics available-
Nl, VI, EI, or Definite Time NI, VI, EI or Definite Time 3 Instantaneous (25ms) OR
3 ranges of def Time (1, 10,100) ranges of def Time (1, 10, 100) time delayed 100ms / 200ms
TMS : 0.1 - 1.6 Step 0.1 TMS : 0.1 - 1.6 Step 0.1 Self Powered
Other Features Site selectable Trip time Char. Site selectable Trip time Char. Relay testing possible by ext.24V -
Supply
Highset can be disabled Highset can be disabled Flag indication / LED indication
Harmonic rejection
Burden on CT £ 0.25 VA on CT £ 0.25 VA on CT £ 6VA
Burden on PT Not applicable Not applicable Not Applicable
Operating temp 00C - 600C 00C to 600C 00C to 600C
Weight < 1.5kg < 1.5kg < 1.5kg
Burden on Auxiliary supply £ 5.5 VA £ 5.5 VA Not Applicable
Output Contacts 2 C/O Contacts (S/R) 2 C/O Contacts (S/R) 2 C/O Contacts (S/R)
Construction Draw out Draw out Draw out
Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224 71 x 158 x 224
Panel Cutout 62 x 142 62 x 142 62 x 142

O R D E R I N G I N F O R M AT I O N

Auxiliary supply Type 1 20-110V AC / DC or 20-110V AC / DC or Not Applicable


Type 2 88-264V AC / DC 88-264V AC / DC
CT rating 1 AMP or 5 AMP 1 AMP or 5 AMP 1 AMP or 5 AMP

Range Setting 10-40% OR 20-80% OR 50-200% 10-40% OR 20-80%


Site Selectable

7
MND11, MRP11, MV12
Wiring Diagrams

MND11

1
6

R1
2 7

R Y B 3 L /+ 5
μP.
Aux. Supply Control
4 N /- Ckt. 9
F64 R2
11

12
10

MND11
PT VOLTAGE : 110V AC

MRP11

1
4

R Y B 2 + VE / PH. 5
Aux. Supply
3 R1
– VE / N μP.
Control
11
Ckt. 7
F32

8
12

6
9

10 MRP11

Vn In AUX SUPPLY
110 V AC 1A 24–110 V AC/DC
415 V AC 5A 95–240 V AC/DC

MV12

1
5

2 4
R1
3 +VE/PH. μP.Control 6
Aux. Supply Ckt.
4 F27
-VE/N F59 8
11
9
12
7

MV12

8
Neutral Displacement Relay
Reverse Power Relay
Under Voltage OR
Over Voltage Relay

• Easy setting through front panel


DIP Switches

• LED indication for


Power ON and trip status

158mm
• Test feature - helps maintenance

• Compact, light weight helps in


reducing panel size & thickness.

22 mm
m
4
4m
20
71mm

Model MND11 MRP11 MV12


Description Neutral Displacement Reverse Power 1 Ph U/V OR O/V

Device Code 59 Vo 32 27 OR 59
Design Microcontroller Based Microcontroller Based Microcontroller Based
Functions Available Voltage relay for E/F Protection Reverse Power Level Lowset U/V - Vs
of generator earthed thro’ Highset U/V - Vhs OR
neutral earthing transformer Lowset O/V - Vs
Highset O/V - Vhs
Settings Fault voltage Vs - PT input Vn 110V, 240V, 415V AC U/V Vs = 95-20% step 5%
2% - 32% of Vn step 2% CT input In 1 A / 5 A U/V Vhs = 90-20% step 10%
Alarm voltage Vis - Pick up level 1% - 15% O/V Vs = 105-180% step 5%
2% - 32% of Vn step 2% Min. setting 0.5% O/V Vhs = 110-180% step 10%
Time Characteristics available- TMS 0 to 1.5 step 0.1 Time Characteristics available-
Inverse time or Definite time Definite time characteristics Inverse time or Definite time
TMS : 0.1 - 1.6 Step 0.1 TMS : 0.1 - 1.6 Step 0.1

Other Features LED indication for power ON, LED indication Site selectable U/V OR O/V
time characteristics, trip Test feature Site selectable Trip time Char.
Test feature Highset can be disabled
Third harmonics rejection 26db
Burden on PT £ 0.25 VA < 0.25VA £ 0.075 VA on PT
Burden on CT Not Applicable < 0.25VA Not Applicable
Operating temp 00C to 600C 00C to 600C 00C to 600C
Weight < 1.5 kg < 1.5 kg < 1.5 kg
Burden on Auxiliary supply £ 5.5 VA < 8VA £ 5.5 VA
Output Contacts 1 N/O +1C/O Contacts (S/R) 1 N/O+1 C/O 2 C/O Contacts (S/R)
Construction Draw out Draw out Draw out
Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224 71 x 158 x 224
Panel Cutout 62 x 142 62 x 142 62 x 142

O R D E R I N G I N F O R M AT I O N

Auxiliary supply Type 1 20-110V AC / DC 20-110V AC / DC 20-110V AC / DC


Type 2 88-264V AC / DC 88-264V AC / DC 88-264V AC / DC
CT Rating Not Applicable 1AMP OR 5 AMP Not Applicable
PT Rating 110V AC Upto 380V AC 110V/240V/415V (site selectable)

9
Secondary Relays
Wiring Diagrams

TCS 01

L /+ TRIP COIL 1
SUPPLY
(20 - 264V 2
AC / DC 6
TRIP 3 L /+
RELAY Aux. Supply 5
CONTACT
4 N/ - R1
13 7

15 9

BKR. 12 TCS 10
AUX. CKT.
CONT. 11
8

14
TCS 01
TC

Aux. Supply 20-110V AC/DC


88-264V AC/DC
N/ -

PTF 03

2
6
11

5
12
FUSE R1
R LOAD 7
13

FUSE 9
LOAD 14 PTF
Y CKT.
FROM PT
SEC. 110V 10
15
AC PH. -PH.
B LOAD
8
FUSE 16

17
N
PTF 03

10
Secondary Relays
Trip Circuit Supervision Relay
PT Fuse Failure Relay

• Easy setting through front panel


DIP Switches

• Indication for
Power ON and trip status

• Test feature - helps maintenance

158mm
• Compact, light weight - in reducing
panel size & thickness.

• Low power Burden

22 mm
m
4
4m
20
71mm

Model TCS 01 PTF 03


Description Trip Circuit supervision PT Fuse Failure Relay

Device Code 95 ABC 60


Design Static Static

Functions Available Post Close Supervision 3 Phase PT fuse failure


Pre Close Supervision

Rating Not Applicable 110V AC PT


Settings Trip coil supply 110 - 220V AC Not Applicable
OR 24 - 48 - 110 - 220V DC
Operation time 500+/-100mS Operation time £ 7mS
Reset time < 150 mS

Other Features Same Relay for all Rating LED Indication for each phase
Trip supply U/V indication Relay trip status
CB ON/OFF status indication Self powered
High speed operation

Burden on CT Not applicable Not Applicable


Burden on PT Not applicable <0.5 VA per phase on PT
Operating temp 00C to 550C 00C to 550C
Weight < 1.5 kg < 1.5 kg
Burden on Auxiliary £ 10 VA Not Applicable
Output Contacts 2 C/O Contacts (S/R) 2 C/O Contacts (S/R)
Construction Draw out Draw out
Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224
Panel Cutout 62 x 142 62 x 142
O R D E R I N G I N F O R M AT I O N
Auxiliary supply Type 1 20-110V AC / DC or
Type 2 80-264V AC / DC

11
PFC-14, PFC-8, PFR-8
Wiring Diagrams

PFC-8

PFC-8
R1 230VAC
1 13 NC 50Hz
2 R2 14 NC
3 R3 15 NC
4 R4 16

ALARM
5 R5 17
6 R6 18
7 R7 S2 19 BANK #1
8 R8 S1(1A) 20 +
9 NC
S1(5A) 21 +
10 NC 22
415V
11 NC 23
12 E 24
C

BANK #8
R
Y TO
B LOAD
N
NC=NO CONTACT

PFC-14

PFC-14
R1 230VAC
1 13 R12 50Hz
2 R2 14 R13
3 R3 15
R14
4 R4 16
ALARM

5 R5 17
6 R6 18
7 R7 19 BANK #1
S2
8 R8 S1(1A) 20 +
9 R9 S1(5A) 21 +
10 R10 22
415V
11 R11 23
12 E 24
C
BANK #14
R
Y TO
LOAD
B
N

PFR-8
PFR-8
R1 230VAC
1 13 50Hz
2 R2 14
3 R3 15
4 R4 16
ALARM

5 R5 17
6 R6 18
7 R7 S2 19 BANK #1
8 S1(1A) 20
R8 S1(5A)
9 21
10 22
415V
11 23
12 E 24
C

BANK #8
R
Y TO
B LOAD
N

12
Power Factor Control Monitoring Relays
Power Factor Controller Relay (8 & 14 Stages)
Intelligent Power Factor Controller Relay

• On line display of system PF

• Easy setting of power factor C/K ratio


from front panel

144mm
• LED indication for Alarm code,
No. of Banks selected, PF status-
lead / lag / unity,
Auto / Manual mode

• DIP switches selection for


No. of banks / time delay /
bank ratios 0 m
m
11

• Display of system current 144mm


KVAR valves.

Model PFC-8 PFC-14 PFC-14


Description Power Factor Controller Power Factor Controller IntelligentPower Factor
Controller
Device Code
Design Microcontroller Based Microcontroller Based Microcontroller Based
Functions Available Automatic PF controller Automatic PF controller Automatic PF controller
Can control upto- Can control upto- 8 stages
8 Capacitor Banks 14 Capacitor Banks
Settings PF : 0.8 Lag - 0.95 Lead PF : 0.8 Lag - 0.95 Lead
Switching time 10-20-40-60 S Switching time 10-20-40-60 s Switching time 5-1200 sec.
Threshold reactive current Threshold reactive current Auto C/K setting
Setting 0.5 - 1 A reactive setting 0.5 - 1 A Reactive Can accept unequal banks
Capacitor Bank Selection- Capacitor Bank Selection- Fault indication
4-5-6-7-8 Banks 4-5-6-7-8-10-12-14 Banks
Other Features Display of PF Measurement Display of PF Measurement Display of PF. V. I. KVAR
Auto / Manual Selection Auto / Manual Selection LED indications for faults
Disconnection of Capacitors Disconnection of Capacitors PF status-lead / lag. Lead -
during over voltage & Power failure during over voltage & Power failure PF alarm
Alarm contact for under / over Alarm contact for under/over
compensation, over voltage, under load compensation,over voltage,under load
1 A / 5 A field selectable 1 A / 5 A field selectable 1 A / 5 A field selectable
Burden on CT 0.3 VA 0.3 VA 0.5 VA
Burden on PT £ 10 VA 10 VA £ 10 VA
Operating temp 00C to 600C 00C to 600C 00C to 600C
Weight < 2kg < 2kg <2kg
Output Contacts 8 N/O 14 N/O 8 N/O

Dim W x H x D in mm 144 x 144 x 100 144 x 144 x 110 144 x 144 x 110
Panel Cutout 138 x 138 138 x 138 138 x 138
O R D E R I N G I N F O R M AT I O N
Auxiliary supply 415V AC 415V AC 110V AC

13
Motor Protection Relay
Wiring Diagrams

MM30

A B C A B C R1 21 (10)
(21)
25 25 DISPLAY 10
11 N.O. N.O.
26 26 MICROP. 22
R2 7
27 27 MM30 9 N.C. N.C.

8
28 28 R3 18
FUNCTION 20
39 39
29 29 19
F37 R1 R4 4
41 41 F46 6
30 30 F49
R2 5
32 F51
32
F51R R5 15
43 43
31
In=5A
31 ˜˜˜ F64
St.No.>
AI.0>
R3

R4
17

16
42 42 Itr 14
In=1A
33 33 PROGR. 3
R5
INT. FAULT 2
44
1
C
PRESA/TAP 31:Ion=5A KEYBOARD S- 34/38
S+ 23
PRESA/TAP 33:Ion=1A L/+ 12 24
˜ ˜=
N/- 13
˜ 9 PIN MALE
IEC 255

MM30-W
A B C A B C A B C
25 25 R1 21 (10)
DISPLAY 10
1/5A
26 26 11
MICROP 22 N.O.
R2 7
MM30-W 9 N.C.
8
FUNZIONI
FUNCTION R3 18 (21)
27 27 27 20
1/5A 19 N.O.
28 28 28 F 37 R1 4
F 46 R4 6
39 39 39 N.C.
F 49
29 29 29 F 51 R2 5
F 51R 15
1/5A F 67N/64 R5
30 30 30 BT 2 50 ST. NO.> 17
41 41 41 Al. O> R4 16
32 32 32 ltr RTD 14
43 43 43 S.C. 3
33 33 33 BT 2 50 R.T. 2
1
PROGR. R5
37(b)
INT. FAULT
TO REX
c 38(a)
In = 1 A s- RELAY
In = 5 A 23
12 KEYBOARD s+ EXPANSION
24
Ion = 1 A Ion = 5 A Un = 100V TASTIERA 9 PIN MALE
13

CE
MS - SCE 1630 - R0

MPR300

R Y B N

Aux. N/O
Start
N/O

Stop
(N/C)

1 2 3 4 5 6 7 8

NC NO Aux.
Supply
MPR300

M Typical connection diagram


for 'Direct Starting' application

14
Motor Protection Relay
• Motor Protection Relay
• Motor Protection Relay with Voltage input
• Lowcost Motor Protection Relay

• Display of various parameters,


trip count and trip data on 8 digit
alphanumeric display

• Separate LEDs for individual


fault indication

• Four user programmable


output relays

158mm
• Built in self supervision &
self testing feature helps
maintenance

• Easy operation by 5 push buttons


m
4m m
20 24m
• RS 485 Port for 2
serial communication with
“MSCOM” user friendly software 121mm

Model MM30 MM-30W MPR300


Description Motor Protection Motor Protection Motor Protection

Device Code 49, 51LR, 46, 37, 50/51, 64, StNo, Itr 12/14, 27/59, 37, 46, 47, 48 49, 51LR, 64, 46, 37
49, 50/51, 51LR, 55, 64, 66, 68, 81
Design Numeric Numeric Numeric
Functions Available Thermal O/L and Pre-alarm Thermal O/L and Pre-alarm Thermal overload
Locked Rotor Locked Rotor Locked Rotor
Current unbalance, phase reversal, Current unbalance, phase reversal, Earth fault
phase loss phase loss Single phasing
Over Current Over Current No load running
Earth Fault Earth Fault
Repeat and prolonged starts Repeat and prolonged starts
Restart Inhibition Restart Inhibition
No load running No load running
Blocking Function Blocking Function
Under frequency / over frequency
Under voltage / over voltage
Running hours
Low PF
Other Features Auto setting Auto setting up to 88 A
1 A or 5 A site selectable (Default 5 AMP) 1 A or 5 A site selectable (Default 5 AMP) Trip time characteristics -
Selectable motor time constant (1 - 60 min) Selectable motor time constant (1 - 60 min) as per IEC947
Display of parameters Display of parameters
Built in self supervision Built in self supervision
RS485 port RS 485 port No RS 485 port
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A (Non-Communication-
Relay)
Burden on PT Not Applicable Not Applicable Not Applicable
Operating temp 100C to 600C 100C to 600C 00C to 600C
Weight < 2kg < 2kg < 0.5kg.
Burden on Auxiliary 8.5 VA 8.5 VA < 8VA
Output Contacts 4 C/O + 1 C/O for self supervision 4 C/O + 1 C/O for self supervision Back panel monitor
Construction Draw out Draw out 70 x 85 x 106
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 Not applicable
Panel Cutout 113 x 142 113 x 142 Motor rated current
O R D E R I N G I N F O R M AT I O N
Auxiliary supply 20-110V AC / DC or 20-110V AC / DC or 240V AC
88-264V AC / DC 88-264V AC / DC

15
Generator Protection Relays
Wiring Diagrams

IM3G-V
A B C
25 (21)
R1 21
DISPLAY 10
1/5A N.O.
26 11
MICROP. 22
27 R2 7
IM3G-V 9 N.C.
1/5A (10)
28 8
FUNZIONI 18
39 R3
29 FUNCTION 20 N.O.
F27/59 19
1/5A R1
41 R4 4
F32 6 N.C.
30
F40 R2 5
33
F46 R5 15
F49 R3 17
Un
32 16
F50/51V
43 R4 14
Un F81 4
31 3 3
42 PROGR. 2
R5 2
44
INT. FAULT 1
C
KEYBOARD S-
34/38
S+
23
L/+ 12 TASTIERA 24

L/- 13 9 PIN MALE


IEC 255

In = 5A In = 1A Un = 100V

MG30

25 21 (21 – 22)
DISPLAY R1 10
1/5A
N.O. N.C.
26 MICROP. 11
22 (10 – 11)
1/5A MG30 7
R2
27 9 N.O. N.C.
FUNZIONI
1/5A
FUNCTION 8
28 R3 18
20
G 39 1>,Z<,Uo>
29 19
12>,T> R1 R4 4
1/5A 6
Zc<,O> R2 5
30
R5 15
41 U,f 17
1/5A

31 W<, Ir> 16
R3
42
1/5A IC, 60FL 14 14
32 R4
43 B.I./B.F. 3 3
2 2
33 1

1/5A PROGR. 37(b)


R5
44 INT. FAULT TO REX
C
S–
38(a) RELAY
23 EXPANSION
S+
24
12 KEYB0ARD
TASTIERA 9 PIN MALE
13

CE
MS-SCE 1629-R0 In=1A In=5A Un=100V

MD32-G
A B C
87G + 87N (21)
I1A 25 R1 21
DISPLAY 10
I1B 1/5A N.O.
11
I1C 26 MICROP. 22
1/5A R2 7 N.C.
9
27 MD32-G (10)
8
1/5A
28 R3 18 N.O.
FUNCTION 20
39
G 19 N.C.
F187G R1 R4 4
F287G 6
29 F87N R2
5
1/5A R3 15
I2A R5
30 R4 17
I2B 41 1/5A 16
R = Stabilising resistor
I2C 31 14
Z = Protection surge B3
arrester (if required) 42 PROGR. B2 3
1/5A R5
32 INT. FAULT
B1 2
43
Z 1

˜˜˜
1/5A C 34/38
33 S-
23
R 50-60
KEYBOARD S+
_ 24
L/+ 12
N/- 13 ˜ ˜= 9 PIN MALE
˜
16
Generator Protection Relays
• Multifunction Generator Protection Relays
• Percentage Biased Generator Differential Relay

• Display of various parameters,


trip count & trip data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

• Four user programmable

158mm
output relays

• Built in self supervision &


self testing feature help maintainance

• Easy operation by 5 push buttons


m
4m m
20 24m
• RS 485 Port for 2
serial communication with “MSCOM”
User friendly software
121mm

Model IM3G-V MG30 MD32-G


Description Generator Protection Generator Protection Generator Differential

Device Code 50/51V, 49,46,27,59,81,40,32, 37 21, 24, 27/59, 32, 37, 40, 46, 49, 87, 50/51, 50LBB, 64S/87N
50/27, 50V/51V, 51BF, 60FL, 64S, 68, 81
Design Numeric Numeric Numeric
Functions Available Voltage rest. O/C Highset Voltage rest. O/C Highset Generator Differential
Trip time char. NI, Def time Trip time char. NI, Def time Bias % with dual adjustable -
Thermal Image Thermal Image slope
Lowset Negative sequence Lowset Negative sequence Over Current
Highset Negative sequence Highset Negative sequence Stator E/F
Under voltage, Over voltage Under voltage, Over voltage CB Failure protection
Under frequency, Over frequency Under frequency, Over frequency
Loss of Field, Reverse Power Loss of Field, Reverse Power
Low forward power, Low forward power,
CB Failure protection CB Failure protection
100% E/F
95% E/F
PT fuse failure
Over excitation
Other Features 1 A or 5 A site selectable 1 A or 5 A site selectable 1 A or 5 A site selectable
Display of Parameters Display of Parameters Display of Parameters
Built in Self supervision Built in Self supervision Wave form capture feature
RS485 Port, Blocking Function RS485 Port, Blocking Function Built in Self supervision, -
RS485 Port
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A
Burden on PT 0.04 VA 0.04 VA Not Applicable
Burden on Auxiliary supply 8.5 VA 8.5 VA 8.5 VA
Operating temp 100C to 600C 100C to 600C -100C to 600C
Weight < 2kg < 2kg < 2kg
Output Contacts 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time del
1 C/O for self supervision 1 C/O for self supervision 1 C/O for self supervision
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142
O R D E R I N G I N F O R M AT I O N
Auxiliary supply Type 1 20-110V AC / DC or 20-110V AC / DC or 20-110V AC / DC or
Type 2 88-264V AC / DC 88-264V AC / DC 88-264V AC / DC

17
Wiring Diagrams

SPM21

21
DISPLAY R1 10 52
C
25 11
MICROP. 22
UG 7
26
SPM21 R2 9 F
8
FUNCTION
29 18
R3 20 F
F25SX
UB 19
30 PROGR. R1
INT. FAULT 4
41 R4 6 U
5
F+ R2 15
G1 R5 17
UG U
F- R3 16
SPM21 44
52 14 B.I.
U+ R4 BX BR
3
BR 52 (N.O.)
UB 2
U- R5 SX 1
C
S-
34/38
S+
23
L/+ 12 24
KEYBORD
N/- 13 9 PIN MALE
IEC 255

SCM21
Connection diagram of 1 bus with 1 line

25 R1 21
DISPLAY 10
UL
26 11
MICROP. 22
R2 7
27 SCM21 9

28 8
FUNCTION SX
39 R3 18
20
29
F25SX R1 19
BU 4
41 F27 R4
R2 6
30
F59
R3 5
F81 >
R5 15
F81 < R4 17
UL
16
14 C/B
SCM21 PROGR. BF
44 R5 SX2 3
INT. FAULT 2
SX1
1
C 34/38
BU L/+ 12 KEYBORD S- 23
S+ 24
N/- 13
9 PIN MALE IEC 255

RRS

+ -
- 15
G MEDIA
AVERAGE + 14 To other RRS Relays
12
R1
3
INCREASE
4 13
Operation
-
SETTINGS

1 T +
VOIOCOS
R2 1
7

6 2 DECREASE
OPTO OPTO 17
+ R3
8 - OVER POWER
-
+ 18
9
(.) (.)
Lood Shedding Freq. control

22 21 11 10
2 3 Lood 3 Freq. control
1 2
Shedding
Open Open Yes Open Yes
Open Open Yes Close No
Open Open Yes
Open Open Yes

18
Synchronising Relays
Generator Synchronising /
Synchrocheck Relays
Loadl sharing Relays

• Display of various parameters,


event count & event data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

• Four user programmable

158mm
output relays

• Built in self supervision &


self testing feature help maintainance

• Easy operation by 5 push buttons


m
4m m
20 24m
• RS 485 Port for 2
serial communication with “MSCOM”
User friendly software
121mm

Model SPM21 SCM21 RRS


Description Auto Synchronising Relay Synchronising Check Relay Generator load sharing

Device Code 25 25 95
Design Numeric Numeric Solid starter
Functions Available Auto Synchronising with Synchro Check with Active / reactive power
Adjustable Voltage, Adjustable Voltage, Over power
Adjustable Frequency, Adjustable Frequency, Load sharing
Adjustable Phase angle Adjustable Phase angle Frequency control
Adjustable Reclose time, Adjustable Reclose time, Check Synch/
Bus Live / Dead operation, Dead line / Dead bus modes of operation,
Speed Regular Control, Over voltage protection, Under voltage
Voltage Regulator Control, protection, Over Frequency Protection,
Digital inputs to monitor Under frequency protection,
CB position Digital inputs to monitor CB position

Rating 110V - 125V PT input 110V - 125V PT input 110V PT input


Other Features Display of Parameters, Display of Parameters, 1 A / 5 A CT input
Built in self supervision, Built in self supervision,
RS485 Port RS485 Port
Burden on PT 0.04 VA 0.04 VA < 5VA
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg <1.5kg
Burden on Auxiliary 8.5 VA 8.5 VA 8.5 VA
Output Contacts 5 C/O 5 C/O 3 N/O
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 71 x 158 x 224
Panel Cutout 113 x 142 113 x 142 62 x 142

O R D E R I N G I N F O R M AT I O N

Auxiliary Supply 20-110V AC / DC or 20-110V AC / DC or 20-110V AC / DC or


88-264V AC / DC 88-264V AC / DC 88-264V AC / DC
Upto 380V AC
1A /5A

19
UFD34 / UM30A / DM33
Wiring Diagrams

UFD34

(21)
25 R1 21
A DISPLAY 10
N.O.
26 11
MICROP. 22
R2 7 N.C.
27 9
B UFD34 (10)
28 8
FUNCTION 18 N.O.
39 R3
20
29 F81 - 1 R1
C N.C.
F81 - 2 19
R2 R4 4
41 6
F81 - 3
30
F81 - 4 R3 5
Fdf / dt R5 15
R4 17
F27 / 59
16
PROGR. 14 14
R5
INT. FAULT BI<
3
BI> 2
1
_ C
34/38
L/+ 12 S-
˜ ˜ =
KEYBOARD S+
23
24
N/- 13 ˜
IEC 255 9 PIN MALE

UM30A

(21)
25 R1 21
A DISPLAY 10
N.O.
26 11
MICROP. 22
27 R2 7 N.C.
B UM30A 9 (10)
28 8
FUNCTION 18 N.O.
39 R3
29 F27 / 59 20
C R1
F27d / 59d 19 N.C.
41 R2 R4 4
30 F59s 6
F59U R3 5
EA F81 R5 15
R4 17
F59 / 81

˜˜
Uo
UC UA ˜
BT 2 50 PROGR.
R5 14
16
14
44 INT. FAULT BI< 3
BI> 2
EC EB 1
UB _ C
34/38
L/+ 12 KEYBOARD S-
N/- 13 ˜ ˜= S+ 23
24
˜ 9 PIN MALE

IEC 255

24(-20%) - 110(+20%)Vac 24(-20%) - 125(+20%)Vdc 80(-20%) - 220(+20%)Vac 90(-20%) - 250(+20%)Vdc

DM33

A B C A B C
29 29
R1 21 (21)
1/5A DISPLAY 10
30 30 11 N.O.
41 41 1/5A MICROP. 22
31 31 R2 7
9 N.C.
42 42 1/5A DM33
32 32 8 (10)
FUNZION R3 18
43 43
33 33
1/5A Io
˜˜˜
50-60
FUNCTION 20
19
N.O.
28 28 R4 4
F50 6 N.C.
39 39 R1
27 27 F51 5
F67(1) R2 R5 15
26 26 17
F67(2)
F67N(1) 16
25 25 R3
F67N(2) B4 14
R4 3
F27 B3

˜˜
Uo B2 2
In=5A
50-60
1
In=1A PROGR. R5
INT.FAULT

12 _ C 38
AUXILIARY
SUPPLY 13 ˜˜ ˜ = KEYBOARD
TASTIERA RS485
S-
S+ 23
24
MS - SCE 1621 - R1

20
Voltage / Frequency Relays
Directional O/C, E/F Relay
3 Phase voltage / frequency and Load shedding Relay
3 Phase voltage / frequency & zero sequence voltage Relay

• Display of various parameters,


trip count & trip data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

158mm
• Four user programmable
output relays

• Built in self supervision &


self testing feature help maintainance
m
4m m
• Easy operation by 5 push buttons 20 24m
2

• RS 485 Port for


serial communication with “MSCOM” 121mm
User friendly software

Model UFD34 UM30A UM30A


Description 3 Ph Voltage & Freq. Relay 3 Ph Voltage & Freq. Relay 3 Ph Dir O/C & E/F + Highset
Device Code 81, 27, 59, df/dt, de/dt 81, 27, 59, V/Hz, 59d, 59s, 59Uo 50/67 RYBN, 50 LBB
Design Numeric Numeric Numeric
Functions Available Frequency-4 stages selectable Over exitation-2 stages Low Set Dir O/C
as under or over or under/over Frequency-2 stages selectable Highset Dir O/C
Voltages - 2 stages selectable as under or over or under/over Low Set Dir E/F
Rate of change of frequency Voltages - 2 stages selectable Trip time Char : NI, VI, EI, Def time
protection df / dt - 2 Stages as under or over CB Failure Function
Rate of change of voltage Direct Sequence Auto Doubling of Highset
protection de /dt - 1 Stage Negative Sequence Blocking Function
Blocking function Zero Sequence - 2 Stages MTA Setting = 0-359°
Blocking function 1 A or 5 A site selectable
Rating 100 - 125V PT input 100 - 125V PT input 100 - 125V PT input
Other Features Display of Parameters Display of Parameters Display of Parameters
Built in self supervision Built in self supervision Built in Self supervision
RS485 Port Communication RS485 Port Communication RS485 Port Communication
Burden on CT Not applicable Not applicable 0.2 VA for 5 A, 0.01 VA for 1 A
Burden on PT 0.04 VA 0.04 VA 8.5 VA
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 2kg
BurdenonAuxiliary 8.5 VA 8.5 VA 0.04 VA
Output Contacts 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time del 4 C/O, S/R or H/R or Time Del
1 C/O for self supervision 1 C/O for self supervision 1 C/O for self supervision
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142

O R D E R I N G I N F O R M AT I O N

Auxiliary Supply 20-110V AC / DC or 20-110V AC / DC or 20-110V AC / DC or


88-264V AC / DC 88-264V AC / DC 88-264V AC / DC

21
MD32T, IM30T, UM30SV
Wiring Diagrams

MD32T

A B C
(21)
I1A 25 R1 21
87T + 87N 10
DISPLAY
1/5A N.O.
I1B
In1 11
I1C 26 MICROP. 22
R2 7 N.C.
1/5A
MD32T 9 (10)
27
8
1/5A
V1 28 R3 18 N.O.
39 FUNCTION 20
V2 V1
á V1 19 N.C.
Kv =
V2 V2 F187T R1 R4 4
F287T 6
29 F87N R2
5
1/5A R3 15
I2A R5
R4 17
30
R = Stabilising resistor
I2B 41 16
Z = Protection surge 1/5A
arrester (if required) I2C 31 B3 14
42 1/5A
PROGR. R5 B2 3
32 INT. FAULT
43 B1 2
Z 1

R
33
1/5A
˜˜˜
50-60
KEYBOARD
C
S-
S+
34/38
23
24
L/+ 12
IEC 255 ˜ ˜ = 9 PIN MALE
N/- 13
˜

IM30T

A B C A B C A B C
(21)
25 25 25 R1 21
DISPLAY 10
1/5A N.O.
26 26 26 11
MICROP. 22
N.C.
27 27 27 R2 7
9 (10)
1/5A IM30T
28 28 28 8 N.O.
39 39 39 R3 18
FUNCTION 20
29 29 29 N.C.
19
1/5A
41 41 41 R4 4
F46 R1 6
30 30 30 F49
F50 R2
32 32 32 F51 5
43 43 43 15
1/5A
˜
˜
F50N
F51N R3
R5
17
31
42
31
42
31
42
˜
BT 2 50
F51BF
2
It=K R4 16

33 33 33 RT 14

BIO 3
PROGR. R5 2
44 INT.FAULT BIF
1
In = 5A In = 1A
C 34/38
_ S-
L/+ 12 23
N/- 13 ˜ ˜= KEYBOARD S+
24

IEC 255
PRESA/TAP 31 Ion = 5A
PRESA/TAP 33 Ion = 1A ˜ 9 PIN MALE

UM30SV

21 (21)
A 25 R1
DISPLAY 10
N.O.
26 11
MICROP. 22
27 7 N.C.
B UM30SV R2
9 (10)
FUNZIONI
28 8
FUNCTION
39 R3 18 N.O.
29 20
C F27/59 R1 19 N.C.
41 F27d/59d R4 4
R2
30 F59s 6
F59Uo 5
R3
EA F81 R5 15
17
R4

UC UA
Uo ˜˜˜
BT 2 50
F59/81

14
16
14
PROGR. BI< 3
R5
INT.FAULT BI> 2
EC EB
UB 1
KEYBOARD C 38
12 _ S-
TASTIERA 23
AUXILIARY
SUPPLY 13 ˜˜ ˜ = RS485
S+
24

22
Transformer Protection
and Vector Shift Relay
Percentage Biased Transformer Differential Relay
3 Phase Thermal + Over Current + Earth Fault Relay
for transformer protection

• Display of various parameters,


trip count & trip data on 8 digit
alphanumeric display

• Separate LEDs for


individual fault indication

158mm
• Four user programmable
output relays

• Built in self supervision &


self testing feature help maintainance m
4m m
20 24m
• Easy operation by 5 push buttons 2

• RS 485 Port for 121mm


serial communication with “MSCOM”
User friendly software

Model MD32T IM30T UM30SV


Description Transformer Differential + 3 Ph O/C, E/F + Thermal 3 ph voltage and frequency relay
Restricted E/F
2
Device Code 87 RYB, 87N 50/51 RYBN, 49, 46, I t 24, 27d/59d, 47, 59, 59Uo, 78, 81
Design Numeric Numeric Over Fluxing
Functions Available Lowset Differential Lowset O/C O/V + U/V
Lowset Op time : <=30mS Highset O/C O/F + U/F
Highset Differential Lowset E/F Zero seq. voltage
Highset Op time : 6-20mS Highset E/F Voltage unbalanced
Restricted Earth Fault Thermal Overload Vector surge
Dual slope Bias Lowset current unbalance with
Highset can be Biased / Unbiased Definate / Inverse time tripping
2nd harmonic restraint setting Highset current unbalance
5th harmonic restraint setting Inrush Energy protection
Auto correction of CT Ratio CB Failure function
Zero sequence compensation Blocking function
Blocking Function
Other Features Display of parameters Display of Parameters Display of parameter
Built in self supervision Built in self supervision Built in self supervision
RS485 Port RS485 Port RS485 Port
1 A OR 5 A site selectable 1 A OR 5 A site selectable
Waveform capture feature
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 2kg
Burden on Auxiliary supply 8.5 VA 8.5 VA 8.5VA
Output Contacts 5 C/O, S/R or H/R or Time del 5 C/O, S/R or H/R or Time del 5%
Construction Draw out Draw out Panel monitoring
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142
O R D E R I N G I N F O R M AT I O N
Auxilary Supply 20-110V AC / DC 20-110V AC / DC 20-110V AC / DC

23
MW33, MU30, IM30-DRE
Wiring Diagrams

MW33

25 R1 21 (21)
DISPLAY 10
26
1/5A
11 N.O.
MICROP. 22
27 R2 7 N.C.
MW33 9
28
1/5A 8 (10)
FUNZIONI R3 18
39 FINCTION
29 20 N.O.
19
1/5A 4 N.C.
41 F32 W R1 R4
30 R2 6
F32 VAR 5
32 R5 15
43 Wh R3 17
Un VARh R4
31 16
42 14 14
Un 3
33 PROGR. R5 3
INT.FAULT 2 2
44 1
C 34/38
KEYBOARD S-
23
_ S+
L/+12 TASTIERA 24
L/- 13 ˜˜ ˜ = 9 PIN MALE
In = 5A In = 1A Un = 100V

IEC 255

MU30
(21)
29 R1 21
DISPLAY 10
1/5A
11 N.O.
30 MICROP. 22
41 R2 7
1/5A MU30 9 N.C.
31 8 (10)
42 1/5A R3 18
32 FUNCTION 20 N.O.
43
19
U R1 4 N.C.
I R4
R2 6
F
P.F. 5
25 P/E 15
R5
S R3 17
Un Q/R R4
26 16
14 14
Un
27 3 3
PROGR. R5
OMT.FAULT 2 2
28 1
42 C
S-
34/38
_ KEYBOARD S+ 23
L/+ 12 24
L/- 13 ˜ ˜=
In = 5A In = 1A Un = 100V ˜ 9 PIN MALE

IEC 255

IM30-DRE

A B C A B C A B C
(21)
25 25 25 R1 21
DISPLAY 10
1/5A N.O.
26 26 26 11
MICROP. 22
27 27 27 R2 7 N.C.

1/5A
IM30-DRE 9
(10)
28 28 28 8
FUNZIONI 18 N.O.
39 39 39 FUNCTION R3
20
29 29 29
19
1/5A N.C.
30 30 30 R4 4
F50 R1 6
41 41 41
F51 R2 5
1/5A F67N R3 R5 15
31 31 31 17
R4
42 42 42 BT 2 50 16
32 32 32 14
BIR
43 43 43 3
1/5A PROGR. BI
33 33 33 BT 2 50 R5 2
INT.FAULT C/B
1
C 38
S–
KEYBOARD S+
23
TASTIERA 24
12
13 9 PIN MALE

CE In=5A Ion=5A

MS-SCE 1573-R0 In=1A Ion=1A Un=100V

24
Control & Supervision Relays
Power Management Relay
Multifunction 3 Phase Measuring Instrument

• Display of various parameters,


event count & event data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

158mm
• Four user programmable
output relays

• Built in self supervision &


self testing feature help maintainance

• Easy operation by 5 push buttons m


4m m
20 24m
2
• RS 485 Port for
serial communication with “MSCOM”
User friendly software 121mm

Model MW33 MU30 IM30-DRE (AUTO RECLOSING)


Description Power management Measurment 3 ph voltage / frequency relay
with auto reclosing
Device Code 81, 27, 59, PF, P, QL, QC Measure 46, 50/51, 50N/51N, 51BF,
67N, 68, 79
Design Numeric Numeric O/C protection
Functions Available Frequence 2 stages, Actual measurements of E/F protection
Voltage 2 stage, Freq, I, V, PF, 4 stage A/R
Power factor 2 stage, Power - Active / Reactive / -
Active power 2 stage, Apparent
Capacitor reactive power 2 stage. Energy - Active / Reactive
Actual measurement of Freq, Maximum Demand
Other Features V, I, PF, active power, reactive power. Display of Parameters Display of Parameters
Display of parameters Record of last event Last trip data
MD recording & data logging RS485 Port, Event recording, RS485 Port
RS485 Port, Event recording Event counter, MD recording, 0.2 VA
Oscillographic wave form capture Not Applicable

Burden on CT
\ O.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A
Burden on PT 0.04 VA 0.04 VA
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 2kg
Burden on Auxiliary supply 8.5 VA max 8.5 VA max 8.5 VA
Output Contacts 5 C/O 5 C/O 5 C/O
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142
O R D E R I N G I N F O R M AT I O N
Auxiliary supply Type 1 20-110V AC / DC 20-110V AC / DC 20-110V AC / DC
Type 2 88-264V AC / DC 88-264V AC / DC 88-264V AC / DC

25
MC30, MC20-R, RPM-8
Wiring Diagrams

MC30

4 DISPLAY R1 R1
16 16
1/5A MICROP.
5 OUTPUT
R2 R2 18 RELAYS
6 MC30 18
FUNZION 17 OUTPUT 17 RELE
7
1/5A
FUNCTIONS
R3 14 RELAYS R3 14 DI USCITA
RELE
F50 15 15
8 R1 DI USCITA
R4 13
F51
1/5A
F50N R2 12 D3 20 DIGITAL
9
F51N D2 21 INPUT
D3 20 DIGITAL INGRESS
R3 19
21 INPUTS
D1
1/5A
D2 22 DIGITAL
R4 D1 19 INCRESSI
22 TO I/0 RELAY
PROGR. DIGITAL
L
In= 1A 5A H 13 EXPANSION
INT.FAULT 12 ALL ESPANSIONE
DI I/0
3 COMUNE
C
C
A (S+)
3 COMUNE
AUXILARY SUPPLY 10 RS485
RS232 B (S-) 2 A (S+)
11 1 B (S-)
2 RS485
KEYBOARD 1
TASTIERA
BPMC

MS-SCE1895-R2 MS -SCE1924-R2
STANDARD OUTPUT I/O Output

MC20-R

6 6 DISPLAY R1
R1 15 16
1/5A MICROP.
7 7 OUTPUT
R2 R2
MC20-R 18 18
RELAYS
FUNZIONI 17 OUTAUT 17 RELE
R3 RELAYS R3
FUNCTIONS 14 14 DI USCITA
4 4 RELE
F50 15 DI USCITA 15
1/5A
5 5 R1 R4 13
F51
F50N R2 12
8 8 D3 20 DIGITAL
F51N
1/5A D3 20 DIGITAL D2 21 INPUTS
9 9 F79
D2 21 INPUT D1 19 INGRESS
R3 19 INGRESS 22 DIGITAL
PROGR. D1
INT, FAULT R4 22 DIGITAL
1A TO I/O RELAY
In = 5A H 13 EXPANSION
L 12 ALL EXPANTION
Ion = 1A 5A
D I/O
C
C
A (S+)
3 3 COMUNE
Auxilariy supply10 RS232 B (S-)
2 RS-485 COMUNE
1 A (S+)
11 KEYBOARD 2 RS485
B (S-)
TASTIERA 1
MS-SCE2021-RO BPMC

MS- SCE2021-R0 MS-SCE2022-RO


Standard Output I/O Expansion module Output

RPM-8

Ph
230V AC
1 13 50 Hz
N
2 14

3 15
4 16
ALARM

5 R8 17

6 R7 18
S1(5A)
+ R6 19
BANK #8
7
S1(1A) 8 + R5 20

S2 9
- R4 21

10 R3 22
11 R2 23

12 R1 24

BANK #1

Y TO

B LOAD

N
26
158mm m
4m m
20 24m
2

121mm

Model IM30AB MC30 MC20-R


Description 3 Phase OC + EF relay with thermal 3 Phase OC + EF relay with
image element Autoreclosing
Device Code 50/51, 50N/51N, 51BF 50/51, 50N/51N, 51BF, 79

Design Numeric Numeric


Functions Available 3 Phase fault levels 3 Phase fault levels
3 Earth fault levels 3 Earth fault levels
1 Thermal image element 4 Shots programmable reclosing
breaker failure protection (LBB) Reclosure sequence coordination
breaker failure protection (LBB)

Rating 1 A or 5 A site selectable 1 A or 5 A site selectable


Other Features Time tagged multiple event recording Time tagged multiple event recording
Oscillographic wave form capture Oscillographic wave form capture
Blocking O/P’s and Inputs for better Blocking O/P’s and Inputs for better
coordination coordination

16 (8x2) character LCD display 16 (8x2) character LCD display


1 Rip circuit breaker control via serial
port
Do not change
RS232 and RS485 Ports available RS232 and RS485 Ports available
Modbus RTU / IEC 870-5-103 Modbus RTU / IEC 870-5-103
communication protocol communication protocol

Burden on CT 0.1VA for 1 A CT & 0.3VA for 5 A CT 0.1VA for 1 A CT & 0.3VA for 5 A CT
Burden on PT NA NA
Burden on Aux. Supply < 7VA < 7VA
Operating Temp -100C to 550C -100C to 550C
Weight
Output Contacts 4 N/O 4 N/O

Construction Draw out Draw out


Dim 83 x 164 x 225 83 x 164 x 225
Panel Cutout 62 x 142 62 x 142
O R D E R I N G I N F O R M AT I O N
Aux. Supply Type 1 24-110V AC or 24-125V DC 24-110V AC or 24-125V DC
Type 2 80-220V AC or 90-250V DC 80-220V AC or 90-250V DC

27
Notes
Notes
For selection and product demonstration, please contact any of our branch offices listed below:

REGISTERED OFFICE AND L&T House A28,Indira Nagar


HEAD OFFICE Group MIG - 5 Faizabad Road
L&T House, Ballard Estate Padmanabhpur Lucknow 226 016
P. O. Box 278 Durg 491 001 Uttar Pradesh
Mumbai 400 001 Tel: 0788-2213833 / 14 / 28 / 29 Tel: 0522-4040905 / 903 / 904
Tel: 022-67525656 Fax: 0788-2213820 Fax: 0522-2311671
Fax: 022-67525858 e-mail: esp-Lko@Lntebg.com
Website: www.Larsentoubro.com A1/11, Astronauts Avenue
Bidhan Nagar Plot No. 518
ELECTRICAL STANDARD PRODUCTS (ESP) Durgapur 713 212 4th Main Road
501, Sakar Complex Tel: 0343-2536493 / 39 K. K. Nagar
Opp. Gandhigram Rly. Station Fax: 0343-2536493 Madurai 625 020
Ashram Road e-mail: esp-dgp@Lntebg.com Tel: 0452-2537404 / 303
Ahmedabad 380 009 Fax: 0452-2537552
Tel: 079-66304007-11, 55304000/1 (Faridabad Switchgear Works) e-mail: esp-mdu@Lntebg.com
Fax: 079-26580491 12/4, Delhi-Mathura Road
e-mail: esp-ahm@Lntebg.com Faridabad 121 003 North Wing, Level II,
Tel: 0129-2565147 / 8 Gate 7, Powai
38, Cubbon Road, Post Box 5098 Fax: 0129-2275405 Mumbai 400 072
Bangalore 560 001 e-mail: esp-fbd@Lntebg.com Tel: 022-67050505
Tel: 080-25020100 / 25583613 Fax: 022-67051112
Fax: 080-25580525 Milanpur Road, Bamuni Maidan e-mail: esp-bom@Lntebg.com
e-mail: esp-blr@Lntebg.com Guwahati 781 021
Tel: 0361-2550565 8B, Farmland, Ramdaspeth
131/1, Zone II Fax: 0361-2551308 Behind Hotel Radhika
Maharana Pratap Nagar e-mail: esp-gau@Lntebg.com Nagpur 440 010
Bhopal 462 011 Tel: 0712-2420641 / 24
Tel: 0755-6454906 / 7 / 8 / 9 5-10-173, Fateh Maidan Road Fax: 0712-2420619
Fax: 0755-2769264 P. O. Box 12 e-mail: esp-ngp@Lntebg.com
e-mail: esp-bho@Lntebg.com Hyderabad 500 004
Tel: 040-66720251 32, Shivaji Marg, P.O. Box 6223
Plot No. 559, Annapurna Complex Fax: 040-23242356 New Delhi 110 015
Lewis Road e-mail: esp-hyd@Lntebg.com Tel: 011-51419500 / 1 , 51419515
Bhubaneswar 751 014 Fax: 011-51419600
Tel: 0674-2537301, 2436696 D-24, Prithvi Raj Road e-mail: esp-del@Lntebg.com
Fax: 0674-2537309 C-Scheme
e-mail: esp-bbi@Lntebg.com Jaipur 302 001 L&T House, P.O. Box 119
Tel: 0141-2377374 / 2361064 191/1, Dhole Patil Road
SCO 32, Sector 26-D Fax: 0141-2373280 Pune 411 001
Madhya Marg, P. O. Box 14 e-mail: esp-jai@Lntebg.com Tel: 020-66033395 / 88 / 89
Chandigarh 160 026 Fax: 020-26129586
Tel: 0172-4646841 / 2 / 3 / 4 / 5 / 6 / 7 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@Lntebg.com
Fax: 0172-4646802 P. O. Golmuri
e-mail: esp-chd@Lntebg.com Jamshedpur 831 003 3rd Floor, Vishwakarma Chambers
Jharkhand Majura Gate, Ring Road
10, Club House Road Tel: 0657-2340864, 2340308 Surat 395 002
Chennai 600 002 Fax: 0657-2341250 Tel: 0261-2473726
Tel: 044-28462072 / 4 e-mail: esp-jam@Lntebg.com Fax: 0261-2477078
Fax: 044-28462102 e-mail: esp-sur@Lntebg.com
e-mail: esp-maa@Lntebg.com Skybright Bldg.
M. G. Road Radhadaya Complex
67, Appuswamy Road Ravipuram Junction Old Padra Road
Post Bag 7156 Ernakulam Near Charotar Society
Opp. Nirmala College Kochi 682 016 Vadodara 390 015
Coimbatore 641 045 Tel: 0484-4409422 / 23 / 24 / 25 / 26 / 27 Tel: 0265-6613611
Tel: 0422-2588120, 2588121 / 3 Fax: 0484-4409430 Fax: 0265-2336184
Fax: 0422-2588148, e-mail: esp-cok@Lntebg.com e-mail: esp-bar@Lntebg.com
e-mail: esp-cbe@Lntebg.com
3-B, Shakespeare Sarani 48-8-16, Dwarakanagar
Kolkata 700 071 Visakhapatnam 530 016
Tel: 033-44002301 / 2 / 3 / 4 / 5, 44002572 Tel: 0891-2755493, 2704928
Fax: 033-22821025 Fax: 0891-2746075
e-mail: esp-ccu@Lntebg.com e-mail: esp-viz@Lntebg.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Tel: 022-6705 0505
Fax: 022-67051324 / 1746
E-mail: esp@LNTEBG.com
Website: www.LNTEBG.com

SP 50297 R1 210507