SIVANANDA ELECTRONICS

Oil Insulation (Breakdown Voltage) Test Set


Model : OTS-PR-CG (100 KV)

The oil insulation test kit is intended to be used for testing of dielectric strength of insulating oil used in
Transformer, Circuit breaker, CTs, PTs, etc. The test kit is fully automatic and has the facility for Auto /
Manual selections. The operator simply feeds the sample in the test vessel & selects the required test.
Testing can be done as per many international (IEC & European standards) which are programmed
into the instrument memory. Stand time, stir times & rate of rise of applied voltage can be selected in
Custom Mode, One set of such selected modes can also be stored in the memory. In addition to the
above, the set can also perform withstand test (proof) tests. In this test the set allows the set voltage to
pre-set value & hold for one minute to see if breakdown occurs.
The backlit LCD is used for user friendly operations during the test process. It also displays fault
condition messages such as open ground cover open. All the user selected programmes are chosen
through the 4 x 3 keypad. The test results can be printed along with test type, date, time, breakdown
test voltage, averages and deviations.
Voltage value can be measured & printed with a resolution of 0.1 kV. In reprint option it is possible to
have number of printouts for the last test. For each test the readings are recorded and stored in
memory. All stored readings can be transferred via the RS-232 interface to PC.
A safety interlock prevents access to the high voltage terminals during testing. The design ensures a
high level of safety for the operator. The high voltage chamber is covered by a polycarbonate door.

 Fully automatic microcontroller operation


 Pre-programmed international standards: IEC
156, ASTMD877, ASTMD1816, UNE21, IS:
6792
 Custom Mode
 Withstand A and Withstand B 5 Minute Test
 User programmable Withstand (Proof) Test
 Backlit LCD Display
 Built in printer for test results

Specifications :
Features Microprocessor controlled with following features and fully automatic
option to set:
a) Stand Time
b) Stir Time
c) Rate of Rise of Voltage (0.5 KV to 5 KV adjustable)
d) d) No. of tests carried out as per the selected standard
Voltage Range 0 to 100 KV AC (50 KV – 0 – 50 KV)
Also available Model: OTS-PR-CG-60 KV for 0 to 60 KV and Model: OTS-
PR-CG-80 KV for 0 to 80 KV
Trip Current 10 mA
Resolution 0.1 KV in Manual Mode and 0.4 KV in Auto Mode
Accuracy ± 3% of the FSD ± 2 digits
Indication 3 ½ digit panel meter in Manual Mode and alpha numeric LCD display in
Auto Mode
HV Transformer a) 50-0-50 KV with midpoint earth
b) Double wound
c) Air cooled
d) Epoxy moulded
Variac Motorised
Shut Down Sensitivity 5 mA
Shut Down Time < 20 milli seconds
Oil Test Cell Transparent polycarbonate moulded
Gap Gauge 1 mm, 2 mm, 2.5 mm, 4 mm
Cabinet Powder coated sheet metal table top cabinet with lifting handles
Controls Mains ON / OFF, HT ON / OFF, Hold, Stirrer ON / OFF, Timer ON / OFF,
Auto / Manual Mode, Reset
Printer Built in alpha-numeric, 24 column, dot matrix printer. Time & dated results
with standard deviation printed
Port RS232C port interface to download data to PC
Software Windows based Data Acquisition Software
Keypad 12 keys soft touch keypad for quick test selection
Display Large backlit LCD display to show Test Menu, Setup Screens, Test
Result
Indications a) Cover Open
b) Wait Time
c) HT On
d) KV Rise
e) Stir Time
f) Stand (Settle) Time
g) Temperature
h) Breakdown
i) Audible beep on breakdown
j) Long beep on completion of test
Test Standards a) IEC 156
b) IS 6792
c) ASTM D1816
d) ASTM D877
e) UNE 21
f) Withstand
g) Proof
h) Custom Mode
Storage Memory 100 test results
Safety Features a) Interlock on high voltage test chamber
b) Zero start protection
c) Double ground protection
d) All safety interlocks to avoid shocks with indications
e) Protected against overload
Safety Standard Meets IEC 61010
EMI / EMC Standard Meets IEC / EN 61326
Accessories a) Mains cord
b) Oil test vessel with adjustable electrodes
c) GO / No GO gauge for adjusting gap
d) Suitable calibrator
e) Stirrer
f) Pairs of mushroom, spherical and cylindrical electrodes
g) Transportation case
Power Supply 220V AC ± 10%, 50 Hz, single phase
Temperature Range Operating 0 to 50 °C, Storage -5 to 70 °C
Humidity Range 80% RH at 40 °C
Dimensions 700 mm (L) x 320 mm (B) x 325 mm (H) ± 10 mm
Weight 50 kg (Approx.)
To keep pace with the latest technology, Sivananda Electronics reserves the right to update its systems. Hence, information in the catalogue is likely to change
without prior notice.

Authorised Sales and Service Representative

S P B E N G I N E E R S ( I N D I A )
LG-009, V. I. P. MARKET, P-187, SCHEME : VI-M, C. I. T. ROAD, KOLKATA – 700 054, INDIA
PHONE : +91-33-23200759 / +91-33-32930008 / +91-9331294406
E-MAIL : spb.cal@gmail.com / WEBSITE: www.spbengineers.com