Académique Documents
Professionnel Documents
Culture Documents
Leyte
form the central mountain spine of the island. Hot springs and fumarolic
Electric Power needs to be carried over long distances from the point
of generation to the point of consumption. This Transmission is done either
through overhead lines or Underground cables. Each of these two methods
of transmission has its own advantages and disadvantages.
In this design, the overall Electrical System Design used was overhead
transmission line because of its lesser cost compare to the underground
cables.
be able to supply different areas in the region. The substations are expanded
load. The generation plant are designed to provide the required demand for
Geothermal Power Plant Investment Cost (2,400 MW) = 6.44 Billion Pesos
Transmission Cost:
2 = 46.2 Billion
Capital Cost for Double Circuit Line = 44.14 Million x 2 = 88.28 Billion
Pesos
maximum return from the system. Some very commonly used bus bar
Single Bus System is simplest and cheapest one. In this scheme all
the feeders and transformer bay are connected to only one single bus as
show.
Advantages
Disadvantages
- The indoor 11KV switchboards have quite often single bus bar
arrangement.
-
7.1.2 Single Bus System with Bus Sectionalizer
Some advantages are realized if a single bus bar is sectionalized with circuit
breaker. If there are more than one incoming and the incoming sources and
Advantages
If any of the sources is out of system, still all loads can be fed by switching
on the sectional circuit breaker or bus coupler breaker. If one section of the
bus bar system is under maintenance, part load of the substation can be fed
Disadvantages
to that bay.
- The use of isolator for bus sectionalizing does not fulfill the purpose. The
isolators have to be operated ‘off circuit’ and which is not possible without
total interruption of busbar. So investment for bus-coupler breaker is
required.
In double bus bar system two identical bus bars are used in such a way that
any outgoing or incoming feeder can be taken from any of the bus. Actually
isolator as shown in the figure. By closing any of the isolators one can put
the feeder to associated bus. Both of the buses are energized and total
feeders are divided into two groups, one group is fed from one bus and other
from other bus. But any feeder at any time can be transferred from one bus
to other. There is one bus coupler breaker which should be kept close during
bus transfer operation. For transfer operation, one should first close the bus
coupler circuit breaker then close the isolator associated with the bus to
where the feeder would be transferred and then open the isolator associated
with the bus from where feeder is transferred. Lastly after this transfer
Advantages
Disadvantages
interruption.
7.1.4 Double Breaker Bus Bar System
In double breaker bus bar system two identical bus bars are used in such a
way that any outgoing or incoming feeder can be taken from any of the bus
similar to double bus bar system. Only difference is that here every feeder is
only isolator as shown in the figure. By closing any of the breakers and its
associated isolators, one can put the feeder to respective bus. Both of the
buses are energized and total feeders are divided into two groups, one group
is fed from one bus and other from other bus similar to previous case. But
any feeder at any time can be transferred from one bus to other. There is no
isolator. For transfer operation, one should first close the isolators and then
the breaker associated with the bus to where the feeder would be
transferred and then he or she opens the breaker and then isolators
This is an alternative of double bus system. The main conception of Main and
Transfer Bus System is, here every feeder line is directly connected through
an isolator to a second bus called transfer bus. The said isolator in between
transfer bus and feeder line is generally called bypass isolator. The main bus
breaker and associated isolators at both side of the breaker. There is one
bus coupler bay which couples transfer bus and main bus through a circuit
the transfer bus can be energized by main bus power by closing the transfer
bus coupler isolators and then breaker. Then the power in transfer bus can
directly be fed to the feeder line by closing the bypass isolator. If the main
bus.
This is combination of the double bus system and main and transfer bus
system. In Double Bus System with Bypass Isolators either bus can act as
main bus and second bus as transfer bus. It permits breaker maintenance
without interruption of power which is not possible in double bus system but
it provides all the advantages of double bus system. It however requires one
additional isolator (bypass isolator) for each feeder circuit and introduces
slight complication in system layout. Still this scheme is best for optimum
economy of system and it is best optimum choice for 220KV system. Ring
Bus System
7.1.7. Breaker-and-a-Half
Figure 7-1. In this arrangement, three circuit breakers are used for two
independent circuits; hence, each circuit shares the common center circuit
since any breaker can be removed from service without interrupting any
common breaker fails and only one circuit if an outside breaker fails.
the additional flexibility and reliability required with the additional circuits.
Advantages:
- Flexible Operation
- High Reliability
the service
Disadvantages:
- Each circuit should have its own potential source for relaying.
- Each circuit should have its own potential source for relaying.
Distribution System
a. Voltage
Voltage is probably the largest single factor that affects the strength of an
and cost impacts caused by the corona effect. Corona effect decreases when
Conductors can be physically arranged in ways that will change the EMF’s
d. Width of Right-of-Way
The width of the right of way for power lines is typically determined by the
cost of the land and the amount of space required for the construction,
with lateral distance from the centreline, the wider the right of way the
Air provides the required insulation between conductors, as does air between
the conductors and ground. Air and specially designed insulators provide
insulation between the conductors and the towers. The higher the voltage,
the larger the spacing and insulator length are required to be. All air spacing
to carry out their work safely during live-line maintenance activity. If placing
all three phase conductors in the same physical space were electrically
possible, the electric fields from the conductors would completely cancel
each other out. Although close or compact placement reduces field strength,
maintenance.
8.2 Sizing of the Transmission Lines
a. Transmission Substation 1
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
700𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (500𝐾𝑉)
b. Transmission Substation 2
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
800𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (500𝐾𝑉)
c. Transmission Substation 3
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
800𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (500𝐾𝑉)
d. Transmission Substation 4
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
600𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (500𝐾𝑉)
e. Transmission Substation 5
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
500𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (500𝐾𝑉)
a. Distribution Substation 1
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
200𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (230𝐾𝑉)
b. Distribution Substation 2
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
300𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (230𝐾𝑉)
c. Distribution Substation 3
𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
300𝑀𝑉𝐴
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 =
√3 (230𝐾𝑉)
𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 = 753.07 = 755𝐴
VOLTAGE
8.3 Transmission Line Parameters
For higher amount of current, bundle conductors are used for several
reasons. Due to skin effect, for larger conductors, the current capacity does
not increase proportional to the cross sectional area instead, it is only with
Ds = 26.31 mm
GMR = 10.7 mm
4
3 √𝐺𝑀𝑅
𝑑=√ 4
(1. 𝑂09) (𝐷𝑠)
𝑑 = 0.2615𝑚𝑚
b. Spacing of bundled conductor in Transmission Line 2
Ds = 29 mm
GMR = 12 mm
4
3 √𝐺𝑀𝑅
𝑑=√ 4
(1. 𝑂09) (𝐷𝑠)
𝑑 = 0.2556𝑚𝑚
c. Spacing of bundled conductor in Transmission Line 3
Ds = 29 mm
GMR = 12 mm
4
3 √𝐺𝑀𝑅
𝑑=√ 4
(1. 𝑂09) (𝐷𝑠)
𝑑 = 0.2556𝑚𝑚
Ds = 23.55 mm
GMR = 9.54 mm
4
3 √𝐺𝑀𝑅
𝑑=√ 4
(1. 𝑂09) (𝐷𝑠)
𝑑 = 0.3753𝑚𝑚
e. Spacing of bundled conductor in Transmission Line 5
Ds = 19.61 mm
GMR = 7.89 mm
Table 8.1: Transmission Line Data
CHAPTER 9
operating coil causes the normally open contacts to close. When the relay
contacts close, the trip coil of the circuit breaker is energized which then
causes the circuit breaker to open. System protection components have the
following criteria:
Figure 9.1: Excitation curves for a multiratio bushing CT with a C100 ANSI
accuracy classification
Table 9.2: Ratings for CTs with one or two ratios
Table 9.3: Typical tap ranges and settings of time-overcurrent relays