G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 1 de 2

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3520C GENERATOR SET GZM
Configuration: G3520C Generator Set GZM00001-UP

Systems Operation
Caterpillar Digital Voltage Regulator (CDVR)
Media Number -RENR7941-06 Publication Date -07/01/2010 Date Updated -07/07/2010

i02847614

Line Loss Compensation


SMCS - 4467

In some installations where a single generator is used with long feeder lines to the load, it may be
advantageous to provide line loss compensation. Line loss compensation is commonly referred to as
IR compensation. In this mode, a CT must be provided in order to measure the generator current.

The parameters that are related to line loss compensation are listed below.

 Rated Generator Voltage

 Generator PT Primary Voltage Rating

 Generator PT Secondary Voltage Rating

 Voltage Set point

 Generator Frequency

 Knee Frequency

 Integral Gain

 Derivative Gain

 Proportional Gain

 Loop Gain

 Generator CT Current Primary Rating

 Generator CT Current Secondary Rating

 Load Compensation Mode

 IR Compensation

 Rated Generator Current

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 01/08/2010
G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 2 de 2

Current flowing through a long conductor causes a voltage drop due to the resistance of the wire.
Therefore, the voltage at the load end of the conductor will be lower than the voltage at the generator
end due to the voltage drop along the conductor. This condition is commonly referred to as line
losses. In order to improve the power quality, the digital voltage regulator can compensate for this
phenomenon. As generator load increases, the regulator will cause the output voltage to rise slightly
at the generator terminals in order to compensate for line losses. Line drop percentage controls the
amount of compensation. It should be adjusted to yield a constant voltage at the location of the load.

Line loss compensation is mutually exclusive to reactive voltage droop. These two functions work
opposite of one another and can not be used at the same time. If a CT is provided but line loss
compensation is not desired, the set point percent must be set to zero.