Service Information System Página 1 de 2

Operação dos Sistemas


Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines
Número de Mídia -RENR1200-01 Data de Publicação -10/01/1999 Data de Atualização -10/09/2001

i01175107

AC Factory Calibration Setpoint Viewing OP2-2


SMCS - 4490; 7451

The option for the AC factory calibration setpoint viewing is OP2-2. OP2-2 is also used for viewing
other specific data. None of these items are programmable by service personnel.

The following information is shown on the display.

GSC+ Serial umber - The serial number of the GSC+ has ten digits. This number is unique for
each GSC+. The serial number is stamped on a label on the back of the GSC+. The displayed serial
number will always match the number on the label.

GSC+ Software Level Identifier - The software level identifier indicates the level of the software
that is included within the GSC+. The identifier has nine characters. "XXXXXXX-XX" is the form
of the identifier.

Setpoints P201 through P222 - The setpoints are the AC factory calibration setpoints. The AC
factory calibration setpoints contain information that is used during the factory calibration
procedures. These setpoints are not programmable by service personnel.

Procedure To View The Setpoints


ote: The engine may be running or the engine may be stopped while the operator is viewing the
setpoints.

ote: Service mode cannot be entered when the engine control switch (ECS) is in the AUTO
position.

ote: An active shutdown fault must be made inactive in order to access service mode. To
temporarily change a shutdown fault from an active shutdown fault to an inactive shutdown fault,
turn the ECS to the OFF/RESET position. The shutdown fault must be corrected, and the ECS must
be turned to the OFF/RESET position in order to permanently change a shutdown fault from an
active shutdown fault to an inactive shutdown fault. If the jumper from terminal 6 to terminal 9 is not
installed on the ECS, the GSC+ does not power up in OFF/RESET and any active shutdown fault
must be corrected before entering service mode.

1. Press "SERVICE MODE" key in order to enter service mode. "OP 1" is showing on the lower
display. See System Operation, "Service Mode" for more information.

2. Press "SCROLL UP" key. "OP2-0" is showing.

a. Go to Step 3 in order to view the setpoints that are within OP2-0.

b. Press the "SCROLL UP" key once or press the "SCROLL UP" key twice in order to
view OP2-1 or OP2-2. The display will show OP2-1 or OP2-2. Go to Step 3.

https://sisweb.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/... 31/08/2010
Service Information System Página 2 de 2

3. Press "SELECT" key. "P001" is showing for OP2-0 which is followed by the value of the
setpoint. "P101" is showing for OP2-1 which is followed by the value of the setpoint. The ten
digit serial number is showing on the display for OP2-2.

4. Press the "SCROLL UP" key or the "SCROLL DOWN" key. The next setpoint value is
showing. Repeat this step until all the desired setpoints and the setpoint values are viewed.

5. Press "EXIT" key. "OP1" is showing on the lower display.

6. Press "EXIT" key. The display returns to the normal mode.