Académique Documents
Professionnel Documents
Culture Documents
Date : 24/6/2019 To :
Telephone no. :
Fluid properties :
Density : 1.225 [kg/m^3] Temperature : 15 [deg. C]
Impeller properties :
Diameter : 500 [mm] Tip clearance (%R) : 1 Blade : D Angle : 50°
Rotation speed : 1440 [RPM] Material : PAG Hub-Blade : 10-5
Working point :
Q[m^3/h] Pst[Pa] Pdyn[Pa] Ptot[Pa] Pshaft[kW] Eff(t) [%] Lwt[dB(A)]
10400 10.92 132.6 143.5 0.6404 64.8 81.14
Mechanical info :
Axial force[N] Shaft torque[N*m] Tip speed[m/s] Air speed[m/s]
28.19 4.247 37.7 14.71
System curve [Pa] Pst [Pa] Pshaft [kW] Eff(t) [%] Eff(s) [%]
140 0.8 100
[Pa] [kW] [%]
126 0.72 90
Pst Pshaft Eff
112 0.64 80
98 0.56 70
84 0.48 60
70 0.4 50
56 0.32 40
42 0.24 30
28 0.16 20
14 0.08 10
0 0 0
6000 6500 7000 7500 8000 8500 9000 9500 10000 10500 11000
Q [m^3/h]
50.6 39.6
62 125 250 500 1000 2000 4000 8000 Hz Lwtot (A) 62 125 250 500 1000 2000 4000 8000 Hz Lptot (A)
GEOMETRY OF SOUND PROPAGATION : Full sphere Distance : 1 [m]
Warning : different applications may have a different impact on the air performance and sound performance of the impellers.
HW Ventilation is an ISO 9001 certified company