Académique Documents
Professionnel Documents
Culture Documents
net/publication/283299448
CITATIONS READS
0 207
1 author:
Jason Ongpeng
De La Salle University
66 PUBLICATIONS 95 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Theory, Experiment, and Modeling of Partial FRP-Confined Concrete Cylinders View project
All content following this page was uploaded by Jason Ongpeng on 29 October 2015.
This chapter covers the data yielded from the series of experimental
procedures conducted in this study as well as its analysis which includes the
crack evaluation of mortar cubes after the 28th day of compressive testing.
In this portion of the paper, the researchers studied the strength of the
eight (8) plastering materials with the use of Compression Testing Machine.
There were three (3) trial specimens allotted for each testing date per material
wherein there were a total of 96 cube specimens experimented on. The said
testing dates were taken at time intervals of 24 th Hour, 3rd Day, 8th Day, and
28th Day. It should be noted that the third testing date was supposed to be at
7th Day as specified in ASTM C109. However, due to some limitations in the
strength of Skimcoat plasters with respect to time. It could be seen from the
graph that the compressive strength is directly proportional to the age of the
54
Skimcoat plasters. The curves as could be observed are relatively different
and distant from each other. This indicates that each of the Skimcoat material
fail. This can be primarily associated to the fact that the Skimcoats will behave
differently because they are made up of properties which are unique from
each other.
Compressive Strength in Mpa
18
16
14
12
10
8
6
4
2
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Skimcoat A Skimcoat B Skimcoat C Skimcoat D
Age in Days
among the Skimcoat plasters. Its early and late strength development
continued to become the highest among the others up to the last testing date.
Skimcoat B on the other hand had the lowest compressive strength among
the others. This behavior was observed even at the start of early strength
55
development and it continued to attain the lowest compressive strength up to
have a similar compressive strength but it could be observed from Figure 5.1
that upon reaching the 10th up to the 28th day, their strengths started to vary
from one another. As could be observed, the strength values of the said
plaster were close to each other during the 24th Hour and 3rd Day Testing,
wherein Skimcoat C’s strength is slightly higher than Skimcoat A’s strength.
But upon reaching the 10th day, the strength of Skimcoat A started to increase
slowly and surpassed the strength of Skimcoat C. One could infer out of this
at the third day except for Skimcoat B which took more days to develop and
increased at 8th day. One could infer out of these results that the strength
development of all the plasters experimented on is higher during its early age
than late age. Please refer to Appendix C for the complete compressive
the mortar plasters. It could be observed that the compressive strength of the
mortar plasters increased with time as well. As could be seen, the graphical
56
curves of the mortar plasters are similar in behavior. The trends have shown
that their strength development are slightly similar which was already
expected since they are all made up of the same material and only the water-
cement-sand ratio were varied. Despite of the said similarity, one cannot fail
to notice the curve intersection of some of the graphs, which tells us the
some mortar plasters would perform better than the others then later on will
compressive load until failure because their water cement and cement-sand
ratios were varied. It could also be observed from the Figure 5.2 that the
curves were not widely spread from each other which means that the
compressive strength of the mortar plasters were just a little higher and lower
40
35
30
25
20
15
10
5
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
MORTAR A MORTAR B MORTAR C MORTAR D
Age in Days
Figure 5.2 Compressive Strength Comparison of Mortar Plasters
57
Despite of the minor differences in strength, it is still evident from the
illustration which among the four (4) mortar plasters acquired the highest and
lowest strength. Mortar A had the highest compressive strength among the
others. In the 24th hour testing, it acquired a strength of 12.27 MPa. However
it was not consistent since it could be observed from Appendix C that at the
3rd Curing Day, the strength of Mortar Mix A was surpassed by Mortar Mix D.
among the others. However one cannot fail to notice that this behavior was
not consistent because at the 8th day, it was able to surpass the compressive
strength of Mortar D.
Mortars B and D were the two mortar plasters that were observed in
between the highest and lowest performing mortar mix. During the 24 th and 3rd
Mortar B but upon reaching the 8th day until the 28th day, Mortar D’s
the mortar plasters which showed that there could be a problem in the
uniformity of the mix which is the downside of the said plastering material. It is
hard to control the uniformity since the mortar mix involves 3 different
58
It could be generalized that during the 24th hour testing, it was Mortar A
which got the highest compressive strength equal to 12.27 MPa, followed by
Mortar D’s strength of 9.76 MPa and then Mortar B and C’s strength which
were equal to 7.82 MPa and 7.16 MPa, respectively. Starting on the 3 rd day,
the compressive strength of the mortar plasters greatly developed and their
8th day, the compressive strength of the Mortar plasters varied by 2 to 4 MPa.
value equal to 33.87 MPa, followed by Mortar B with a strength of 31.57 MPa,
succeeded by Mortar D with a strength of 28.05 MPa and lastly Mortar C with
strength of the mortar plasters are higher compare to the Skimcoat plasters.
However this does not automatically lead to a notion that the mortars
are better than the Skimcoat. One of the references of this study which came
from the site, Masonry Advisory, tells us that ideally the background must be
stronger than the render. The said research claimed that it would be
remove it. If by chance that the failure takes place first at the walls and other
59
structural members being protected, removing the said plaster layer would
take time and it might cause further damage to the structural member
40
Compressive Strength in Mpa
35
30
25
20
15
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Figure 5.3 28th Day Compressive Strength Comparison of the Eight (8)
Plastering Materials
mostly happened during the third day except for Skimcoat B which greatly
developed its strength at 8th day. This goes to show that both the Skimcoat
and Mortar plasters are good for protecting the structural members because it
already started to develop its compressive strength as early as 3rd to 8th day.
and the actual compressive strength of the eight (8) plastering materials. This
60
is to verify whether the plasters were able to meet the strengths set by the
for the Skimcoat plasters were acquired from the technical data given by the
manufacturers. The said data came from their own laboratory tests which
latter part of this paper. It could be observed from the graph that there are no
data.
As for the target strength of the mortar plasters, they were all based
from the Journal: “Optimization Mix Proportion of High Performance Mortar for
Structural Application”. It could be seen that the strengths obtained did not
surpassed the target strengths. However this does not automatically leads to
the idea that the data gathered are erroneous. One has to consider that the
target strengths set by the manufacturers and researchers of the eight (8)
plasters were tested in different sample size. It can be recalled that this study
made use of smaller sample size which is the main reason why the obtained
strengths were smaller. Take for example, the journal where the mortar
design mix was patterned from made use of a 100x100x100 mm mortar cubes
that the data were gathered under the testing conditions in their respective
61
role in the testing procedures not only for plasters but in other materials alike.
45
40
35
30
25
20
15
10
5
0
It can be recalled that during the mixing and casting of the specimens,
really tell whether this exposure had caused a decrease or increase of the
water content of the specimen because there’s no way to verify this except for
the fact that the temperature change pattern was fluctuating for the rest of the
62
materials. The researchers’ stand about this matter is that the target strengths
serve just a guide but not applicable for this study because of the
aforementioned reasons.
Table 5.1 shows the actual strength of the eight (8) plastering materials
Table 4.3 for the different types of plastering classification). For the Skimcoat
they were classified into types N and S while the Mortar plaster were
Table 5.1 Comparison of Actual 28th Day Strength with Minimum Required
Compressive Strength
ACTUAL Plaster Type Based
PLASTER
STRENGTH (MPa) from ASTM
SKIMCOAT A 12.15 N
SKIMCOAT B 6.2 N
SKIMCOAT C 7.77 N
SKIMCOAT D 15.97 S
MORTAR A 33.87 M
MORTAR B 31.57 M
MORTAR C 26.75 M
MORTAR D 28.05 M
Skimcoat A acquired a strength 12.15 MPa during its 28th Day. Its
strength falls in between the range of 5.17 MPa to 12.40 MPa which is the
keep it from drying. This information just verified that Skimcoat A can be truly
63
categorized as Type N plaster because it can be used both in interior and
exterior application.
Skimcoat B acquired a strength of 6.2 MPa during its 28th day. Its
strength falls in between the range of 5.17 MPa to 12.40 MPa which is the
technical data of Skimcoat B, it was indicated there that it can be used for
interior and exterior application. This information verifies that Skimcoat B can
its strength falls in between the range of 5.17 MPa to 12.40 MPa which is the
its strength falls in between the range of 12.41 MPa to 17.23 MPa during its
28th Day which is the reason why it was classified as Type S of plaster. No
technical data verifies the said categorization. However upon preparing the
mostly for below grade work meaning to say any plaster application below the
ground.
64
In general, we could see the differences in application of the eight (8)
plasters. The classification made does not mean that the Mortar plasters have
intended to show the difference in application of the eight (8) plasters basing
their strength from the ASTM standards. For the mortar plasters, they were all
categorized under type M plaster because they are all made up of the same
properties and materials. For Skimcoat plasters, not all of them are in the
same category. Only Skimcoats A, B, and C falls under the type N plasters
wherein they are generally used for both exterior and interior application.
also computed by the group which were all graphically presented in Appendix
L-1 to L-8. Wherein, one could observe that generally most but not all of the
testing dates of the plastering materials had 1 out of the 3 trials specimen
outside the boundary and the rest were within the boundary. The mean as
well as the upper and lower limits of the standard deviation are presented.
Standard deviation is a value representing the limits from the mean wherein
the data points enveloped in it are considered sound data. This means that
the data points not exceeding the limits are within the standard. Thus, data
points outside the boundaries are considered either too high or too low from
the mean. The upper limit was obtained through the addition of the standard
65
deviation to the mean while the lower limit was obtained through the
5.1.1 Density
The densities of the plaster specimen were derived with the use of the
formula:
(Equation 2)
The mass of the specimens were weighed during the experiment while
the volume was computed with the use of the dimensions measured by a 0.05
The density data from all the different testing dates were averaged
which are all summarized in Figure 5.5. It could be observed that the densities
of the mortar plasters are all higher than the Skimcoat plasters. Generally,
when the density is high, it would mean lesser presence of voids. However
this does not automatically mean that the mortar plasters have lesser voids
than the Skimcoat plasters. The researchers’ stand about the said matter is
that the density of the mortar plasters are hard to evaluate when being
denser than the Skimcoat plasters because its properties are heavier (Refer
to Appendix A for the weights of the plaster specimens). This is due to the
66
presence of fine aggregates, which is sand. Primarily, the mass of the
were able to observe by visual inspection that the surfaces of the mortar
plaster are more porous compared to the surfaces of the Skimcoat plaster
specimens. By judging their appearances, one cannot totally say that the
mortars have lesser voids compared to the Skimcoat because only the
influences the density values. One could expect higher density when the
weight is high because the volumes of the mortar specimens in this research
are more or less similar to each other (Taking into account that the volume of
the specimens would be a little bit higher or lower than 125,000 mm 3 since the
supported by the weight results obtained that are summarized and graphically
For the mortar plasters, the comparison of the density can be made
because they are all made out of the same materials. It could be generalized
that Mortar A had the least voids among the four (4) mortar plasters being
observed because it has the highest density. While Mortar D can be inferred
67
to have the most voids since it had the smallest density among the mortar
plasters.
increases (Chee & Ban, 2010). Given that the Mortars A and B have the same
cement-sand ratio, Mortar A was proven to have higher density since it has
smaller water-cement ratio (Refer Table 4 for the water-cement ratio values of
mortar plasters). Likewise, in Mortars C and D, the same behavior was also
observed wherein Mortar C had higher density since it has smaller water-
cement ratio.
evaluate the voids by just comparing their density values because they are
made out of different materials. It cannot be generally inferred out of the data
that since Skimcoat A is the densest among the Skimcoat plasters, it has the
least voids. And likewise with Skimcoat D, it doesn’t directly mean that it has
the most voids among the plasters since it acquired the smallest density
values. It cannot be generalized which among the plasters had the best result
in terms of observing the density values because of the reasons pointed out
previously.
68
2500.00
Density (kg/m3)
2000.00
1500.00
1000.00
500.00
0.00
PLASTER MATERIAL
Skimcoat A 1880.17
Skimcoat B 1766.72
Skimcoat C 1789.03
Skimcoat D 1740.09
MORTAR A 2205.77
MORTAR B 2122.53
MORTAR C 2138.61
MORTAR D 2120.70
5.1.2 Workability
tabulate the different consistencies of the eight (8) plasters based on the
69
300.00
250.00
Weight (grams)
200.00
150.00
100.00
50.00
0.00
PLASTER
SKIMCOAT A 246.07
SKIMCOAT B 228.03
SKIMCOAT C 232.88
SKIMCOAT D 232.60
MORTAR A 278.38
MORTAR B 271.65
MORTAR C 272.97
MORTAR D 274.56
consistencies and workability of the plasters can be point to the fact that each
of them has its own specific mix ratios. It could be seen from Figures 5.7 to
5.16 that some of the plasters exhibited high workability but there are others
The water content influences the workability of the plaster mix (Refer to
Table 4.4 and Table 4.7 for the water-plaster, water-cement, and water-sand
70
ratio). It could be observed that Skimcoat A is a highly workable material. It is
added in the mix was not followed because of the consistency observed. It
could be seen from Figure 5.7 that the mix was too flowy and practically
speaking, if all of the water was added, the plaster would tend to slide down
Skimcoat B was the easiest to mix. As could be seen in Figure 5.8, its
71
Skimcoat C had very low workability. It stuck to the trowel as it was
being mixed. It is actually the hardest to mix among all of the eight plasters.
Its color is light grey. There was a need to add water to the mix in excess of
the specified 6-7 liters because of the dry and poor consistency of the
material. Figure 5.9 is an image to show how the mix looked like before the
addition of water. A total of 1 liter of water was added to the mix in order to
On the other hand, Skimcoat D also had very low workability. It was,
however, super fine white in color and smooth in consistency after the
addition of water. There was also a need to add water to the mix in excess of
the specified 7 liters. Figure 5.11 is an image to show how the mix looked like
before the addition of water. A total of 75 milliliters of water was added to the
mix in achieving the desired workability which can be seen in Figure 5.12.
For the mortar plasters, the researchers strictly followed the water
consistency as shown in Figures 5.13 and 5.15. The workability of these mix
plaster. It can be said that no matter how high the compressive strength of a
72
workability. In real practice, the consistency will matter because workers just
do estimates for the amount of water to be added in the plaster mix and doing
that simply alters the strength of plasters. This simply tells us that strength
alone is not the sole basis for evaluating whether the plaster is good or not.
Skimcoat A, Mortar B and Mortar D were the top 3 plasters which had high
plaster for actual application on walls and structural members because the
desired workability for the said plasters is easy to achieve without adjusting
73
Figure 5.11 Skimcoat D Consistency Figure 5.12 Skimcoat D Consistency
Before Addition of Water After Addition of Water
74
of 0.05mm and 0.02mm precisions were used for the two clusters of
specimen. For each specimen, there were a total of six faces of the prism,
whose sides were measured in three portions (top, middle and bottom).
Appendix D shows the averaged reading measurements taken for each face
better represent the length measurements for each face. There were a total of
three averaged readings for each testing, which are the length, the depth and
the height. Measurements were taken for four test ages, namely 4 th day, 8th
day, 11th day and 25th day excluding the initial reading taken as the
The change in length of each specimen was taken as the final reading
in the testing age subtracted from the initial reading. Appendix E shows a
summary of the length changes for each test age. The negative values
indicate that the final reading for the specified curing age is greater than the
reduction in volume.
the largest length change while zero was the smallest. On the other hand, an
absolute value of 0.87 mm was obtained as the largest length change for the
mortar plasters. The smallest length change was zero. Comparing the two
clusters of plaster, both were able to have zero shrinkage but the maximum
recorded length change in mortar plasters is double the value from the
75
commercial plasters. This observation means that in terms of the maximum
Further, the percent change in length was also calculated. This is also
in sample length with the original length. The shrinkage percentage was
L = initial length in mm
lowest was 0% for the individual data. The average shrinkage percentages of
plasters was 3.49% while the lowest was 0%. The average shrinkage
76
percentages of Mortars A, B, C and D were 0.11, 0.32, 0.23 and 0.17%,
each specimen was also calculated as well as the shrinkage percentage with
summary of the volume changes while Tables 5.5 and 5.6 show a summary of
Similar to length change, the negative values from the table indicate
that there was an increase in volume. The largest volume change recorded for
77
Table 5.3 Volume Change of Commercial Plasters
Change in Volume (mm3)
Specimen
25th
No. 4th Day 11th Day 18th Day
Day
1 289.71 85.81 360.74 184.07
SKIMCOAT A
2 -619.59 -234.36 -297.20 -287.96
6484.17 cubic millimeters while the lowest was 0.54 cubic millimeters. By
comparing the two clusters of plaster, it is quantified that the highest volume
plasters.
78
Table 5.4 Volume Change of Mortar Plasters
Change in Volume (mm3)
Specimen No.
4th Day 11th Day 18th Day 25th Day
1 107.21 412.09 479.73 -283.18
MORTAR A
2 925.56 -389.23 -109.52 -398.84
5.5, the lowest was 0.04% while the greatest was 1.55%. The averaged over-
79
Table 5.5 Percent Change in Volume of Commercial Plasters
Percent Change in Volume (%)
Specimen No.
4th Day 11th Day 18th Day 25th Day
1 0.15 0.04 0.18 0.09
SKIMCOAT A 2 0.32 0.12 0.16 0.15
A and C followed the same pattern until the 18 th day of testing but Skimcoat C
increased during the 25th day while Skimcoat A remained the same. Skimcoat
until the 25th day. The behavior of Skimcoat D is opposite to that of Skimcoat
80
B wherein it increased on the 11th day and continuously decreased until the
25th day. The four commercial plasters showed fluctuating change in volume
0.70
0.60
Over-all Shrinkage
Percentage (%)
0.50
0.40 Skimcoat A
0.30 Skimcoat B
0.20 Skimcoat C
0.10 Skimcoat D
0.00
4th Day 11th Day 18th Day 25th Day
Test Age (Days)
On the other hand, the over-all shrinkage of mortar plasters had the
lowest value of 0% while the greatest was recorded to be 3.57%. The largest
between the two clusters. This means that in terms of the over-all shrinkage,
mortar plasters exhibited greater values than the commercial plasters. The
81
Table 5.6 Percent Change in Volume of Mortar Plasters
Percent Change in Volume (%)
Specimen No. th
4 Day 11th Day 18th Day 25th Day
1 0.06 0.21 0.25 0.15
MORTAR A 2 0.50 0.21 0.06 0.22
each other, the trend of mortar plasters is less intersecting. All the mortar
plasters are almost horizontally flat except for Mortar B. Mortar B increased
until the 18th day and decreased on the 25th day. It could be seen from the bar
graph that the shrinkage percentage of Mortar B has a great deviation from
82
day. Mortar C, on the other hand, had higher shrinkage percentages for all the
over-all shrinkage percentage for mortars A, B, C and D were 0.23, 0.99, 0.64
1.60
1.40
Over-all Shrinkage
Percentage (%)
1.20
1.00
0.80 Mortar A
0.60 Mortar B
0.40 Mortar C
0.20 Mortar D
0.00
4th Day 11th Day 18th Day 25th Day
Test Age (Days)
Figure 5.18 Averaged Over-all Shrinkage Percentage vs Test Age Graph for
From Figure 5.19 it is evident that the mortar plasters are generally
the rest of the plasters. This means that Mortar B has the greatest shrinkage
percentage for all the test ages except for the 4 th day. The rest of the plasters
were interlinked with each other such that the trends could not be specifically
determined.
83
Over-all Shrinkage Percentage (%)
1.60
1.40
1.20
1.00
0.80
0.60
0.40
0.20
0.00
4th Day 11th Day 18th Day 25th Day
Test Age (Days)
Skimcoat A Skimcoat B Skimcoat C Skimcoat D
Mortar A Mortar B Mortar C Mortar D
Figure 5.19 Averaged Over-all Shrinkage Percentage vs Test Age Graph for
Different Plastering Materials
Generally, the researchers have assessed that for each of the different
plasters, each material has its respective shrinkage percentage along with its
change pattern. Based from theory, materials that have greater water cement
ratio (w/c) tend to have greater shrinkage. In the case of mortar plasters, this
materials were calculated as follows: 0.20, 0.32, 0.40 and 0.35 for Skimcoats
wherein the addition and reduction of water in the mix proportions was
84
respectively. In summary, Skimcoat C had the greatest over-all shrinkage
percentage of 0.75% having the largest w/p of 0.40. Skimcoat D followed with
0.32. The commercial plaster that had the least shrinkage was Skimcoat A
For the mortar plasters, however, Mortars B and D have a w/c of 0.50
while Mortars A and C have a w/c of 0.475. It was previously analyzed that
0.23, 0.99, 0.64 and 0.32%, respectively. The data showed that Mortar B had
the greatest shrinkage of 0.99% and w/c of 0.500. On the contrary, Mortar D
had 0.32% shrinkage and w/c of 0.500. This could be true to the fact that
there are also other factors affecting shrinkage besides the water cement
ratio. Factors of environmental conditions could have also affected the results.
mortar plasters, results indicated that not all of the mortar plasters have
greater shrinkage percentages than the rest of the commercial plasters. This
could mean that although mortar plasters are generally conceived to attain
properties.
85
In order to assess the validity of the data points gathered from the
experiment, statistical analysis was applied with the use of standard deviation.
Generally, this statistical parameter best describes the limits of the standards
in the data with respect to all of the data points gathered. Similarly, the data
points that would be enveloped by the said limits (or boundaries) are those
data that are belonging to the “standard” of the set. Likewise, the data points
that are outside of the limits would only mean that either those data points are
too high or too low from the mean depending on where they belong in the
graph.
most of the data points are scattered in the graphs, meaning to say that the
individual data points are not consistently approaching the mean. Generally,
at least 2 out of 4 data points are within the range of standard deviation. This
that the data points beyond the boundaries are mostly on the upper limit side,
which means that there are mostly data that are deviating largely from the
mean. Thus, this was an indication of the obtained high over-all shrinkage
determined by Health and Roesler to be within the range of 800 and 2000
86
allowable. Microstrain is computed as the change in length over the initial
Table 5.7 below shows the summary of the microstrains obtained for all the
test ages for each plastering material with a total of 4 specimens each.
From the table, it is seen that the highest strain obtained was 1416
microstrain for Skimcoat D and the lowest was zero microstrain, which meant
that there was no change in length at all. By comparing the shrinkage strain
87
MICROSTRAIN (mm/mm)
SPECIMEN NO.
4th day 11th day 18th day 25th day
MORTAR A
1 146 233 175 58
2 87 52 122 262
3 29 160 87 436
4 58 0 29 204
MORTAR B
1 87 233 291 233
2 29 262 291 408
3 58 58 58 87
4 0 1107 1049 991
MORTAR C
1 366 44 161 351
2 73 234 468 673
3 132 241 585 702
4 388 22 344 475
MORTAR D
1 102 44 366 380
2 0 219 570 468
3 270 365 380 438
4 321 358 519 636
through the theoretical values of 800 to 2000 microstrain whether the obtained
shrinkage is passing the allowable values. Since the highest value obtained
was 1416 microstrain, it means that the obtained shrinkage values from the
88
the specimens from outside conditions. The containers were only opened
equipment, it was found out that the thermocouple available in the campus
specimens.
One can also recall from Bai’s journal that the temperature of the
plasters was monitored every minute which cannot be adopted in this thesis
due to time constraints. Instead, the group just monitored the temperature
taken 12 hours after the demoulding of the shrinkage specimens. For better
12, 36, 60, 84, 108, 132, and 156 were temperature readings taken during the
night. While testing hours, 24, 48, 72, 96, 120, 144, and 168 were all taken
during the morning. It should be noted also that testing hours 12 and 24, 36
89
and 48, 60 and 72, 84 and 96, 108 and 120, 132 and 144, and lastly 156 and
169 each represents the 1st, 2nd, 3rd, 4th, 5th, 6th, and 7th day of temperature
reading respectively.
while the mortar plasters include four mortar mix designs namely Mortar A,
Skimcoat B, C, and D.
90
32
30
29
28
27
26
25
24
23
12 24 36 48 60 72 84 96 108 120 132 144 156 168
Skimcoat A 26.383 28.583 26.758 29.342 29.792 30.683 30.492 28.917 27.492 29.325 28.375 28.85 28.383 28.35
Skimcoat B 28.475 25.517 28.35 29.367 29.75 29.783 28.317 26.142 28.308 28.133 28.183 27.633 27.775 30.408
Skimcoat C 28.283 25.367 28.608 29.383 30.108 29.962 28.633 26.083 28.875 28.133 27.592 28.25 27.708 29.858
Skimcoat D 28.242 26.308 28.683 29.5 29.958 29.983 28.2 26.842 28.925 28.183 27.958 27.967 27.892 29.5
Time, in hours
91
By referring to Figure 5.21, it could be generalized that the temperature
Skimcoat plasters did. As seen from the graph, the temperature of Skimcoat A
32
Temperature, in degrees Celsius
31
30
29
28
27
26
25
24
23
12 24 36 48 60 72 84 96 108 120 132 144 156 168
Time, in hours
Skimcoat A Skimcoat B
Skimcoat C Skimcoat D
It could be observed from Figure 5.22 that Mortars A and B have the
92
temperature change pattern as well. As noticed in the graph when Mortars A
the opposite and vice versa. Generally, both Mortar A and B experienced a
range of both A and B is from 26.2oC to 31.2oC while C and D is from 26.8oC
to 30.2 oC.
From Figure 5.23, it could be observed that both Mortars A and B have
the same temperature change pattern. On the other hand, Mortars C and D
also have the same temperature change pattern. Considering Mortars A and
B as one and Mortars C and D as one, we can say both have different
behaviors. The only close reading they experienced was during the 12 th hour,
60th, 84th, 120th and 156th hour where there temperatures are intersecting. For
the rest, they have completely the opposite temperatures. Both A and B
Figure 5.24, the trends are erratic. No similar pattern can be distinguished
from the Mortar plasters and Skimcoat plasters. By comparing the mortar
samples to the Skimcoat, it can be generalized that the samples are behaving
93
32
Time, in hours
94
For the first 36 hours of temperature monitoring of Mortars A and B and
Skimcoat A, the same pattern is observed and after that they completely
32
Temperature, in degrees Celsius
31
30
29
28
27
26
25
24
23
12 24 36 48 60 72 84 96 108 120 132 144 156 168
Time, in hours
On the other hand, Mortars C and D have the same behavior with
its 24th hour and increases again on its 36th hour. After the 36th hour, the
Skimcoat plasters and mortar plasters acted differently. Overall, the mortars
analyzing the graph, one can notice that both mortars A and B experienced
the highest temperature on the 24th hour while skim coats A and B
95
experienced its lowest temperature on its 24th hour. By looking at the
32
Temperature, in degrees
31
30
29
Celsius
28
27
26
25
24
23
12 24 36 48 60 72 84 96 108 120 132 144 156 168
Time, in hours
Skimcoat A Skimcoat B Skimcoat C Skimcoat D
Mortar A Mortar B Mortar C Mortar D
specimen as it failed when induced load was applied on it. Photographs were
96
taken for each side of each specimen to be able to evaluate the cracks that
formed on its surfaces. For each specimen, there are 6 faces and for each
evaluated in this section similar to the previous ones namely commercial and
For the case of commercial plasters, the materials are different while for the
conventional plasters, the materials are the same but only differ in mix design.
There are different modes of failure that were identified from the
Tension failure is indicated by the cracks in the sample. Shear cracks are
direction.
Cracks have a wide range of classifications. There are cracks that are
thin while there are some that are deep and severe in appearance. However,
it should be noted that these are cracks that were produced from crushing
cracks are products of scaling, or that wherein a thin layer of the plaster is
scraped off.
As can be seen from the photos, the labels are not the same as the
category or the type of material under which it belongs to. For specific
97
purposes, it was intended to label the materials in random letters rather than
The main objective of this study is to interlink the results of the different
tests on the plaster properties and evaluate its effect on surface cracking.
plastering material among all the other materials considered. The evaluation
of the cracks in this portion of the study did not base on length measurements
but rather on mere observations and identification of the types of cracks that
taken immediately after the specimens were subject to crushing for the 28 th
analyzed individually. Further, the three specimens for each material were
produced for the commercial plasters was that it had lower compressive
change than the mortar plasters. These results were based from the
98
5.4.1.1 Skimcoat A (Figure 5.25)
specimen did not fail in total crushing. Instead, minor cracks manifested.
Photo 1 showed scaling in the bottom portion and thin cracks on the left edge.
The cracks observed were purely vertical in this face. In one face (Photo 3),
portions of the specimen specifically on the top were detached while a clearly
defined crack is seen at the middle portion. There could be different factors
the material. The crack along the neutral axis is partially inclined due to shear
concerned. Only two faces of the specimen have shown the effect of
compressive load resistance (See photos 1 and 5 from Figure 5.25b). Photo 5
showed a detached portion from the specimen at the upper part. Thin cracks
among the 3. In fact, it almost didn’t even manifest that it had undergone a
compression test considering the fact that a maximum load of 33.5 kN was
applied on it. There are, however thin cracks that are almost invisible to the
naked eye. Encircled are the portions where these cracks were identified.
99
The averaged total maximum load that Skimcoat A was able to resist is
30.37 kN. Specimen 1 was able to resist 28.8 kN same with specimen 2, both
showing more definite cracks than specimen 3 which resisted a higher load of
33.5 kN but having minimal thin cracks. This means that Skimcoat A is able to
resist such magnitude of force without manifesting total crushing and rupture
specimen 1 where generally, minor cracks are observed. However, there are
faces of the cube that are still intact (Photos 1,2 and 4). For one face (Photo
3), the cracks starting from the bottom are parallel to the applied load and
started at the bottom. Probably, this is due to the resistance of the material to
neutral axis. It should be noted that shear stress is maximum at this point. It
may have been that the shear stress was greater than the stress induced by
The crack widths are very minimal. Photo 5 shows a greater crack
width that is more defined. It can be seen that there is one major crack
leaning towards the right and branched out with a hairline crack leaning
100
towards the left. The orientation of the crack manifested shear failure. The last
photo shows thin thin cracks at different locations on the face. Over-all, this
specimen did not manifest complete specimen crushing even after load
application.
obtained cracks for this specimen is the same with the location of cracks in
Specimen 1 (Photos 3,5 and 6). The 3rd photo shows the different directions
of crack. There is a main vertical crack that branched out into horizontal ones
inclined towards the left. A more defined crack is seen on the 5th photo with
thin cracks surrounding it all in the vertical orientation. For the 6 th photo,
scaling as well as thin thin cracks are observed. The cracks started singularly
at the bottom and leaned towards the left until it reached the top edge. The
third specimen is that which achieved the least cracks. Most of its faces are
intact. However, minor cracks are observed from photos 3 and 6. There is a
single crack seen in the 3rd photo in a curved form concaving to the right
edge.
The averaged total maximum load applied to Skimcoat B was 15.5 kN.
Among the three specimens, specimen 3 obtained the highest maximum load,
which is 17.7 kN at the same time having the least cracks. Specimen 1
101
shrinkage percentage previously calculated from Skimcoat B was 0.38%
percentage.
102
1 2
3 4
5 6
103
1 2
3 4
5 6
104
1 2
3 4
5 6
105
1 2
3 4
5 6
106
1 2
3 4
5 6
107
1 2
3 4
5 6
108
1 2
3 4
5 6
109
1
2
3
4
5 6
110
1 2
3 4
5 6
111
5.4.1.2 Skimcoat C (Figure 5.27)
formations as opposed to the two previous materials. For the first specimen,
definite vertical cracks were observed in its faces (Photos 1,5 and 6 of Figure
5.27a). Specimen 2 shows the presence of moderate cracks that are almost
unseen due to the porous surfaces. The third specimen is also shows great
crack formation. The 5th photo (Figure 5.27c) shows webbing or intersecting
cracks at different orientations. The 3rd photo (Figure 5.27c) illustrates the big
chunk that was detached from its form. Lastly, the 6th photo manifested a
The maximum load resisted by Specimens 1,2 and 3 were 22.7, 16.7
and 18.9 kN, respectively. Likewise, the extent of cracking among the three
which is true to the fact that it obtained the the highest over-all shrinkage
percentage of 0.75%.
Smooth in texture and pure white in color, the cracks that manifested in
specimen 1 are minimal. Most of its faces were intact except for the 6 th photo
where scaling was observed. Thin cracks are seen progressing upwards
112
The crack formation in the second specimen (Figure 5.28b) is highly
different from the previous one. The cracks were more defined and severe. A
big chunk was detached from the main body (See Photo 3) and horizontal
cracks manifesting shear failure (See photo 4) have also appeared. For two
faces, however (Photos 5 and 6), vertical cracks existed, all ending at the
edges.
However, it showed definite vertical cracks. Scaling was also seen on the top
portion. Scaling is an indication that the material’s surface is brittle enough for
maximum load with an averaged value of 39.93 kN. From the crack
evaluation, the cracks that manifested in this material are minimal. The first
specimen, that manifested minimal scaling, was able to resist a load of 46.7
kN. Specimen 2 had more cracks than the other two specimens, whose
maximum load resisted was 37.6 kN. Specimen 3 on the other hand, resisted
35.5 kN and was the most intact specimen. No cracking was visible to the
113
1 2
3 4
5 6
114
1 2
3 4
5 6
115
1 2
3 4
5 6
116
5.4.2 Crack Evaluation of Conventional Plasters
The same method was adapted in analyzing the crack formation in this
cluster. However, spider webs are seen on the faces of the samples.
Comparing the two clusters, the surfaces of the specimens in this group are
generally rougher in texture. More so, these are denser materials due to the
towards each other thus creating collision providing more room for cracking.
Whereas, smoother particles tend to slide towards each other such as the
on commercial plasters, this material showed crushing like that seen on the
last photo from Figure 5.29a. There are also portions that were detached from
the form. Vertical cracks are evident also on the 5 th photo ranging from bigger
great chunks were disengaged from the formation specifically the exterior
portions of the cube. Diagonal cracks were also seen. Thin cracks weren’t
visible from the faces since the failures were mostly caused by the
117
cohesion of the material particles since it tends to break apart from each other
also disintegrated into pieces although majority of the volume remained intact.
the three specimens while the individual data for maximum load are 84.2, 73.3
and 96.5 kN for the three specimens respectively. Despite having resisted the
the three. With respect to the over-all shrinkage percentage obtained, Mortar
A had a value of 0.23%, having the least magnitude from its cluster.
there are many voids on the surfaces. However, no much cracks emanated.
Vertical, thin cracks were seen on faces 5 and 6. This specimen was able to
block of mortar was detached from the main body. Bigger, vertical cracks
were also evident (Photo 1 and 3). Thin, thin cracks are seen in the 5th photo.
118
The third specimen (Figure 5.30c) reached a maximum load of 85.2
kN. Vertical cracks were mostly observed and little amount of thin, thin cracks.
Partial scaling was also manifested. Two faces however (Photo 2 and 4)
remained intact.
For the shrinkage percentage of this material, the largest value was
yielded with a magnitude of 0.99%. This value is not only the largest in its
119
1 2
3 4
5 6
120
1 2
3 4
5 6
121
1 2
3 4
5 6
122
1 2
3 4
5 6
123
1 2
3 4
5 6
124
1 2
3 4
5 6
125
5.4.2.3 Mortar C (Figure 5.31)
Detachment from the body characterizes the first specimen. More so,
thin thin cracks are evident. The detachment of portions from the mortar could
maximum load. The projection of the detachment is leaned outwards. For this
specimen, the maximum load was 72.3 kN, which is the largest among the
previous although the extent is to a lesser degree. The first photo (Figure
vertically oriented. An inclined crack was also present in the last photo leaning
towards the left across the neutral axis. A magnitude of 58.3 kN was the
The last specimen (Figure 5.31c) showed scaling and thin thin cracks.
In addition, vertical cracks are also seen. A load of 70 kN was resisted by the
sample.
kN, which is the lowest among its cluster. A shrinkage percentage of 0.64%
was recorded for this material. Although Mortar C was second in rank in
126
having the greatest shrinkage among conventional plasters, the crack
127
1 2
3 4
5 6
128
1 2
3 4
5 6
129
1 2
3 4
5 6
130
5.4.2.3 Mortar D (Figure 5.32)
over-all shrinkage percentage was 0.32% being second to the lowest. The
the last photo. This specimen was able to resist an 81.3 kN load without
crushing failure.
formation wherein a big portion of one side detached as a whole unit (Photos
3 and 6). This specimen resisted the least maximum load of 46.5 kN however,
showing total crushing in the sample. Wider crack widths (Photo 1) and
(Figure 5.32c Photo 6) and vertical cracks. The shear crack can be described
as producing burst effect thus showing the specimen resistance to the load
applied on it.
131
1 2
3 4
5 6
132
1 2
3 4
5 6
133
1 2
3 4
5 6
134
5.5 Integration of Results: Point System
the researchers came up with a point system that gives quantitative ranking
The pointing system shall comprise of six (6) categories such as cost,
equal weight of 16.67% in order to remove the biases for each property. The
weight value shall serve as a multiplier to the total points earned for each
category.
Cost
Crack Evaluation
Table 5.7 is the summarized rating, ranking and visual judgment of the
plasters. Table 5.8 shows the tally of the points earned for each property of
135
each material and the best plastering product was determined as well as the
over-all ranking.
strength value, the better since it has a higher capacity to withstand greater
loadings in application. Therefore, more points are given for plasters which
ranking. Wherein, a rank of 1 is given to the plaster which has the lowest
compressive strength and a rank of 8 to the plaster which has the highest
the weight value of 0.167 and then product of which, served as the points
researchers that the lower the shrinkage value, the better since shrinkage
136
The point system adapted for shrinkage was based on ranking from1 to
5. Wherein, a rating of 1 is given for shrinkage values that range from 0.81 to
1.0; a rating of 2 is given for shrinkage values that range from 0.61 to 0.8; a
rating of 3 is given for shrinkage values that range from 0.41 to 0.6; a rating of
4 is given for values that range from 0.21 to 0.4 shrinkage percentage.
Finally, a rating of 5 is given for shrinkage values that range from 0.0 to 0.2.
The rating given to the plaster is multiplied to the weight value of 0.167 and
the product served as the points earned by the plaster for the drying
shrinkage category.
It was generalized by the group that the lower the density, the better
more points are given for plasters which have lower density.
A rank of 1 is given to the plaster which has the lowest density and a rank of 8
is given to the plaster with the highest density. The rank given to the plaster is
multiplied to the weight value of 0.167 and the product served as the points
137
5.5.4 Cost Point System
to purchase at lower cost. Therefore, more points are given for plasters which
the plastering material. The different costs of the eight (8) plastering materials
were summed up and used as a divisor for all of the computed price per 20 kg
of the plastering materials. The quotient value was deducted to 1. For better
The computed costing rate for each material is multiplied to the weight
value of 0.167 and the product served as the points earned by the plaster for
is, the better since a more workable plaster would entail less labor and
138
increase the convenience of usage. Therefore, more points are given for
rating. Table 5.8 below shows the rating system used to describe the
The rating given to the plaster was multiplied to the weight value of
0.167 and the product served as the points earned by the plaster for the
workability category.
16.67%. This percentage is further divided into four (4) sub-categories. Figure
5.34 shows the weight distribution of the four (4) sub-categories. It could be
observed from the sub-categories that each has its respective weights where
more importance was given to the crack length and width. In the paper
139
and Japan” by Baccay et. al., the crack length and width were the two
data for the permissible crack width in concrete structures. These provisions
this study, the crack length and the crack width were not measured but rather
the equivalent points is briefly described to support the basis for the
researcher’s judgment.
Number of Sides
20.00% with Cracks
20.00%
Degree of Failure
20.00%
20.00% Crack Length
Crack Width
Similar trend from the previous point systems in other categories could
be observed wherein higher point values can be expected for plasters which
140
It should be noted that the averaging of the three (3) trials per
plastering material was done after getting their total equivalent points wherein
The rating given to the plasters under this category was 1 to 6. Table
5.9 below shows the points given according to how many faces of the plaster
cube specimens had evident cracks on its surface. One could see that more
points are given to plaster specimens which have fewer sides with cracks
while lesser points for plaster specimens with more sides that have cracks.
The respective points given for each of the specimens were multiplied
141
5.5.6.2 Degree of Failure in Plasters
doing the crack evaluation for this category, the group compared the different
Table 5.10 shows the rating system used in describing the plasters’ degree of
142
Degree of
Rating Failure Figure Reference Remarks
Description
The respective points given for each of the specimens was multiplied to
0.2 in order to obtain the equivalent points with respect to the degree of
failure.
In this category, the point classification for the rating system used for
143
It should be noted that in evaluating the crack length of the specimens,
there was no crack comparator used but just the visual judgment of the
evaluation is that not all of the cracks in the specimen can be generally
treated to be long or short because each of the faces of the specimens have
varying crack lengths. Hence, the group evaluated each face of the
specimens and accumulated the points earned based from the crack length
The formula used in order to compute for the total equivalent point of
(Equation 6)
Each face of the specimen was observed in order to obtain the value
for the accumulated points for the crack lengths seen. In general, the higher
the value earned in this category means that more long cracks were observed
in the specimen. A perfect score of 100 was set wherein the total
With the use of Equation 6, the resulting points earned means that a
higher point is earned when less accumulated points is subtracted from it.
144
Likewise, less accumulated points mean that shorter crack lengths are
specimens and the respective points given are all included in Table 5.12
below.
The rating system used in this category was very much similar to that
of the crack length. Wherein, visual judgment was applied. Similar concept of
point designation was also used, where the highest value obtained would be
8 was also used in solving for the equivalent points of the specimens.
145