ABSTRACT: This paper presents an experimental and analytical study on the behavior of short, concrete-filled
steel tube columns concentrically loaded in compression to failure. Fourteen specimens were tested to investigate
the effect of the steel tube shape and wall thickness on the ultimate strength of the composite column. Con-
finement of the concrete core provided by the tube shape was also addressed. Depth-to-tube wall thickness ratios
between 17 < D/t < 50, and the length-to-tube depth ratios of 4 < LID < 5 were investigated. Ultimate strength
results were compared to current specifications governing the design of concrete-filled steel tube columns.
Nonlinear finite-element models were developed and verified using experimental results. The analytical models
were further used to investigate the adequacy of design specifications. Experimental results suggest that circular
tubes offer substantial post-yield strength and stiffness, not available in most square or rectangular cross sections.
Downloaded from ascelibrary.org by Iowa State University on 01/18/19. Copyright ASCE. For personal use only; all rights reserved.
Also observed by these results was that current design specifications were adequate to predict the yield load
under most conditions for a variety of structural shapes.
INTRODUCTION failure. The shape of the steel tube and the wall thickness were
the primary parameters in the test program. These factors were
In the mid-1980s several buildings constructed in Seattle,
studied to determine their influence on the ultimate strength
Wash., became well known for their use of concrete-filled tube
of the CFT and the confinement offered by the steel tube. Yield
[CFT] columns. Most of these buildings were high-rises that
strength results were compared to applicable design specifi-
utilized CFTs as primary columns in the lateral load-resisting
cations governing CFT behavior. The analytical portion of this
frame. The notoriety of these building systems was due to the
study was needed to develop calibrated nonlinear finite-ele-
large diameter CFTs used, ranging from 2.3 to 3.2 m, and to
ment models of CFT specimens and to further investigate the
the use of high-performance concrete, with target strengths of
adequacy of the design provisions. The primary purpose of the
96 MPa and cylinder strengths of 130 MPa. The depth-to-wall
analytical investigation was to investigate the effect of the D/t
thickness (Dlt) ratios of these large dimension columns ranged
ratio on the axial compressive strength of the CFT and to
from 180 to 250 and length-to-depth (LID) ratios ranging from
extrapolate these effects to the large dimension columns used
2 to -14. Although stiffness was the primary concern for these
in construction. Depending on the shape of the steel tube,
large columns, the calculated strength of these CFTs was ex-
CFTs can offer substantial post-yield axial ductility. Experi-
trapolated from results of small-scale test specimens with quite
mental results suggested that all circular tubes exhibited sig-
different material and column properties. Although these large
nificant strain-hardening behavior; however, the post-yield be-
composite columns are beyond the scope of current design
havior for the square and rectangular tubes depended on the
specifications, smaller CFTs were also used in low- to mid-
D/t ratio. Current design specifications offer a reasonable pre-
rise construction projects. Circular CFTs were used in braced
diction of the strength of the CFT column, although it pro-
frames, and a smaller percentage were used in moment-resist-
duced conservative results for some small-dimension tube col-
ing frames. Compared to the extremely large CFTs, the steel
umns.
tube dimensions used in the low- to mid-rise buildings were
in a more practical range of 0.36-0.76 m. Depth-to-wall thick- PREVIOUS RESEARCH
ness ratios for the smaller diameter CFTs ranged from 26 to
48 and LID ratios from 5 to 9. These smaller size CFTs have Tests to investigate the axial strength of CFT columns have
the most common application in current building construction been performed on a variety of cross-sectional shapes and D/t
and are the focus of this research. and LID ra~s. Furlong (1967) investigated 13 specimens
Although the use of CFT columns is becoming more com- with D/t ratios ranging from 29 to 98. Results indicated that
monplace, concrete core confinement is not well understood. each component of the composite column resisted load inde-
The prevailing attitude is that the steel tube can be used for pendent of each other, and consequently there was no increase
longitudinal and confining reinforcement. Confinement in a in the load-resisting capacity due to confinement of the con-
CFT is continuous, unlike the conventional spiral reinforced crete core. Gardner and Jacobson (1967) investigated 22 com-
concrete column. Therefore, CFTs are generally considered to posite columns with Dlt ratios between 30 and 40. These re-
posses favorable characteristics for use in regions at high seis- sults suggested that at ultimate load the steel tube was at
mic risk. However, if the concrete core and the steel tube are failure but the concrete core was not. However, an increased
loaded simultaneously, the steel tube expands more than the strain level was noted for the steel tube without local buckling,
concrete core under moderate loads, since Poisson's ratio is suggesting that the concrete stabilized the tube wall.
higher for the steel section. This suggests that the steel tube Knowles and Park (1969) studied 12 circular and seven
may offer little confinement under certain conditions. square columns with D/t ratios of 15, 22, and 59, and LID
This paper presents an experimental and analytical study on ratios ranging from 2 to 21. Results indicated that the tangent
the behavior of the CFTs loaded in compression. Test results modulus method accurately predicted the capacity for columns
include data from 14 CFT specimens concentrically loaded to with LID ratios >11 but was slightly conservative for columns
with small slenderness ratios. It was concluded that this larger
1Asst. Prof., Dept. of Civ. Engrg., Univ. of I1Iinois at Urbana-Cham- than expected capacity for composite columns with LID < 11
paign, 205 N. Mathews Ave., Urbana, IL 61801-2352. was due to the increase of concrete strength resulting from
Note. Associate Editor: W. Samuel Easterling. Discussion open until triaxial confinement effects. It was observed that for certain
March I, 1999. To extend the closing date one month, a written request
must be filed with the ASCE Manager of Journals. The manuscript for
values of longitudinal strain the concrete began to increase in
this paper was submitted for review and possible publication on March volume due to microcracking, which induced concrete con-
4, 1996. This paper is part of the JOUT1UlI of Structural Engineering, finement by the steel tube. This confinement increased the
Vol. 124, No. 10, October, 1998. ©ASCE, ISSN 0733-9445/98/0010- overall load-resisting capacity of the CFT column. However,
1125-1138/$8.00 + $.50 per page. Paper No. 12776. this increase was noted for circular tubes only, not for square
JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998/1125
tions, which explained the strain-hardening characteristics for design of composite members, which were adopted by the
these specimens. Square tubes provided very little confinement LRFD specification. This specification provides design guide-
of the concrete because the wall of the square tube resisted lines for elements in which the area of the steel tube comprises
the concrete pressure by plate bending, instead of the mem- at least 4% of the total composite cross-sectional area. The
brane-type hoop stresses. Consequently, there was no axial axial strength of a composite element is computed similar to
load increase due to the triaxial compression effects for the that of a structural steel column, except the material yield
square tubes. strength and stiffness are modified to account for the steel and
Sakino et al. (1985) tested 18 circular specimens with Dlt concrete components in the composite column. The AISCI
ratios ranging between 18 and 192. In this investigation, three LRFD defines the square of the column slenderness parameter
otherwise identical specimens were subjected to different load as
conditions. Axial load was applied to the concrete and the steel
( 1)
tube simultaneously for the first specimen group. The load was
applied exclusively to the concrete core in the second speci- where FE = Euler buckling stress for a column; r m = radius of
men group, and the load application was similar to this in the gyration of the steel tube only; and KL = effective simply
third group except the inside tube wall was greased before supported column length. Em is the modified elastic modulus
casting the concrete. Results indicated that when the steel tube and Fmy is the modified yield strength of the CFT column
and the concrete core were loaded simultaneously, the tube which are defined by the equations
provided no confinement until post-yield behavior. In the con-
crete loaded only specimens, some longitudinal stresses were Em = Es + OAOEe(AeIA s) (2)
noted in the steel tube even for the columns with the greased
wall. Therefore, regardless of the loading condition, the wall F my = Fy + O.85f;(AJA s ) (3)
of the steel tube appeared to be primarily in a biaxial stress En An and Fy = elastic modulus, cross-sectional area, and the
state. Although test results indicated that the axial stiffness of yield strength of the steel tube, respectively; E e , A e , and f; =
the concrete loaded only columns were about half that of the elastic modulus, area, and strength of the concrete core, re-
other CFTs tested, the concrete loaded only columns obtained spectively. Once the column slenderness parameter is known
a greater yield and ultimate axial load capacity. the critical stress Fer is computed from
Lundberg (1993) assembled available experimental data for
axially loaded column and beam-column tests on CFTs. The Fer =(O.658'~)Fmy for Ae:S 1.5 (4)
ultimate strength was compared to current strength specifica-
tions of composite columns according to the AISC's Manual Fer = (O.877/h~)Fmy for Ae > 1.5 (5)
of Steel Construction: Load and Resistance Factor Design The ultimate strength of the CFT is determined by multi-
(LRFD) (Manual 1994). The ultimate strength for the CFTs plying the critical stress by the cross-sectional area of the steel
exhibited a large variation compared to predicted strengths ob- tube
tained by the LRFD. The average strength of the axially loaded
CFTs was about 1.32 times the LRFD predicted strength, with (6)
a standard deviation of 0.23. More scatter, and higher actual-
to-predicted strength ratios, were observed for stub CFT col- TEST SPECIMENS
umns compared to the relatively slender columns. Stub col-
umns were defined by the column slenderness parameter be- A total of 14 test specimens were constructed and tested
ing he < 0.20. This overstrength was generally explained by under concentric axial compression (Ito 1990; Masada 1990).
more confinement of the concrete core exhibited by the stub Of these 14 CFT specimens, three were circular, five were
columns than observed for more slender columns. It was square, and six were rectangular steel tube shapes. Cross-sec-
suggested that this concrete-steel interaction was not fully tional properties of all test specimens are listed in Table 1. For
addressed by the current composite column strength specifi- convenience, circular tubes were designated with C, S for
cations. Finally, a Monte Carlo simulation was performed on square, and R for rectangular. For each tube profile, specimens
all of these CFT columns to determine the overall reliability were arranged in order of increasing wall thickness. As shown
of the design specifications. Although the steel ratio had large by this table, Dlt ratios in this study ranged from 17 to -50,
variation, the reliability index was within target values for el- and the steel to total composite area ratio AslA tolai ranged from
ements designed according to the LRFD specifications. 8 to 22%. For the rectangular shapes, D/t was listed for the
This previous research demonstrated that slender columns broad face. Although the nominal dimension of each tube was
did not exhibit the beneficial effects of composite behavior, in given, outside dimensions and wall thickness were measured
which the concrete strength increased over that of the cylinder at several locations. These measured values were used in de-
strength due to core confinement. Thus, it was concluded that termining the cross-sectional properties listed. Since it was de-
1126/ JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998
• LOCATION OF LVDTs
compacted by a steel rod. This process was similar to that used
• LOCATION OF LONGITUDINAL & for the concrete cylinders. After allowing the composite col-
PERIMETER STRAIN GAUGES
umn to cure for one day, the top surface was roughened with
'V PERIMETER GAUGES ON SPECIMEN R5
a wire brush. A thin layer of hydrostone was poured on the
roughened surface to eliminate voids, and another stiffened
end cap was attached to the top of the CFT. This ensured that
I
~
I the concrete core and the steel tube were loaded simultane-
I I
I I ously.
1 1 The test specimen and location of the instrumentation are
I I shown in Fig. 1. Specimens were placed in a 9-MN fixed load
frame. A spherical bearing was placed on the top of the CPr
to ensure the applied load was concentric. Linear variable dif-
STRAIN ferential transducers (LVDTs) were placed inside the top and
r
GAUGES < bottom end caps to monitor overall deformation. These LVDTs
PLACEMENT 0
were also monitored in the early stages of loading to ensure
'", ;;?
w
o ~ that a uniform compression was imposed on the composite
'"3 =' ! ~
m
:> specimen. Axial deformations were obtained from the average
3
0
I of the LVDTs at each corner; however, very little variation
0
a was observed in displacement readings among the four LVDTs
:u for any specimen. Strain gauges were placed on the exterior
z
m
:u of the CPr to measure vertical deformations and perimeter
expansion of the steel tube wall. Column load, as measured
I I by the test machine load cell, was applied at a very slow rate
I I such that local buckling behavior of the CPr could be care-
I
~
111 1
t\ fully observed.
I : r 1\
l EXPERIMENTAL RESULTS
FIG. 1. CFT Test Specimen and Instrument Location
Load-displacement relations for all specimens are shown in
Fig. 2. For clarity, test results have been separated by tube
sired to keep tube depths approximately the same, the LID shape, and therefore these graphs show behavior for the cir-
ratios ranged between 4 and 5. cular, square, and rectangular steel tubes separately. The stor-
All steel tubes were cold-formed carbon steel with a spec- age capacity needed for the test data of Specimen C3 was
ified yield strength of 317 MPa. All tubes were seam welded underestimated; data beyond a load of 1,850 kN was not re-
and annealed to relieve residual stresses. Each tube was sup- corded. Testing continued, however, and the yield strength of
plied longer than needed for the CPr test to provide enough the specimen was approximated at 2,010 kN during the test.
material for a tensile coupon test. Type I portland cement, The fixed load frame accurately recorded the maximum load
sand, and a maximum aggregate size of 9.5 mm were mixed for the specimen, which was measured at 2,715 kN.
to obtain a 28-day target concrete strength of 20 MPa and a Fig. 2 shows the post-yield behavior of each tube shape. In
75-mm slump. The concrete for the composite columns was general, circular tube shapes exhibited strain-hardening char-
mixed in four batches, and four standard concrete cylinders acteristics long after the CPr reached yield. Square and rec-
were cast for each batch. Cylinders were tested within 2 days tangular tube shapes exhibited various post-yield behavior de-
of the compressive test for the composite column. Material pending on the tube wall thickness. Specimen S5 was
properties listed for the composite column specimens were the classified as strain-hardening, and R6 exhibited signs of mod-
average values obtained from the cylinder tests. The elastic est strain-hardening. Specimen S4 was classified as elastic,
modulus listed in Table 1 was the tangent modulus at one- perfectly plastic, and Specimen R5 appeared to be in transition
third the ultimate strength of the cylinder tests. between elastic-plastic and degrading stiffness. Behavior of the
A stiffened end cap was attached at the base of each steel remaining cross sections were classified as degrading stiffness
tube. Concrete was placed in five layers, and each layer was type, or strain-softening, behavior. These plots clearly show
JOURNAL OF STRUCTURAL ENGINEERING I OCTOBER 1998/1127
,, i
I ,I C2!
I I
•••••••••••••••(..........
.••...•...········r··
I
C2
1 I- 1
'000 /
, / I
I
i
' Cl l" C1
o
~ , I
I
I
I
, i
I I I
i T INDICATES LOCAL TUBE WALL BUCKLING
I I
o0~------,l-----1,l,0-----;1L:-S-----:!-20=------2~S,------::3'=-0...
(8) AXIAL DEFORMATIONS (mm)
2,000 SQUARE
...z 1,SOO .. I
I
z
o
Ci5
(J)
!i~ 1,000
-----4-_
---.-.~_._ •• _.~, ••_-_._ .•-_._-_. ---.---"---.- .•.•J
oo I ---"SI3
! I
S1 I
;;l 1
~ i
j.
I
II
I
I
T INDICATES LOCAL TUBE WAL,L BUCKLING
O~O- - - - - - JS!-------,J;10,-----'1!rS-----;!20..--------;h2S,----'3!;;0·
R6
____ 1-- - ~
I
- - - - . ., - - -R6
"
I - - ;
I-~---I
...z 1,SOO
!
z
f·,-·~'~l"·_··_··.J--··_..-··-1.-..-
•• _ : R5' ,
.. _."lRS
'
t
0
Ci5 _ _--..,. R3 I ,
(J)
w ~~-=----_!
r
I i
a:
0.. 1,000 l I
- o;...t,R4 , . '"-
' _
R4 ---oi.-"R3
' ','
::::E
0
0
/1 R2 ·················r R2 :
...J
:$
I "
~ I R1
SOO
I
FIG. 2. Comparison of CFT Behavior with Respect to Tube Shape: (a) Circular Tubes; (b) Square Tubes; (c) Rectangular Tubes
~ 1.00
~
o
~ 0.75
z
o
entn
~ 0.50
11.
:::E
o
()
g
Downloaded from ascelibrary.org by Iowa State University on 01/18/19. Copyright ASCE. For personal use only; all rights reserved.
~ 0.25
(8)
'25-,
3O<DIt<40
I r i IIT-T-i
f 1.00 <~~-:::::-jJ=:=---------i--
2 .~•••••••• ~l....... 1---,...---~R3
j - _--ji ------i---l----~
I I i
R1 Iii
i
o i R4·········r·············+R2;
FIG. 3. Comparison of CFT Behavior with Respect to OltRatlo: (a) Olt< 25; (b) 25 < Olt< 30; (c) 30 < Olt< 40; (d) 40 < Olt
~... 1.00
a:
o
~
0:: 0.75
z
o
en
II)
~ 0.50
~
(.)
~
Downloaded from ascelibrary.org by Iowa State University on 01/18/19. Copyright ASCE. For personal use only; all rights reserved.
FIG. 3. (Continued)
that post-yield characteristics approached strain-hardening be- strain-hardening even though the Dlt ratio was quite large
havior for the square and rectangular shapes with large wall compared to other specimens tested in this study.
thickness. Also shown in Fig. 2 is the approximate location of Local wall buckling, shown in Fig. 3, for all CFfs with
observed local wall buckling of the steel tube. Local wall strain-softening post-yield behavior occurred at an axial duc-
buckling did not occur for any specimen prior to yield of the tility between 2 and 6. For the square and rectangular strain-
CFf. Furthermore, higher axial deformations were obtained, hardening specimens local wall buckling occurred at a ductil-
prior to local wall buckling, for the thicker tubes of each shape ity between 6 and 8, while wall buckling did not occur for the
type. circular tube until a ductility of -10 or larger.
Fig. 3 shows nondimensional force-displacement behavior The yield and ultimate loads for each specimen are listed
for each specimen. If a definite yield point was not evident, a in Table 2. The ultimate load was the maximum axial load
0.2% offset was used to estimate the yield load. In Fig. 3, observed during each test. For most of the strain-softening
specimens were arranged by Dlt ratios. These plots indicated type specimens the ultimate load occurred within an axial duc-
that there was a correlation between Dlt and the post-yield tility of -2. Thus the strain-softening CFfs had very little
behavior for the square and rectangular tubes. Specimens C2 ductility before the ultimate load was reached, while the strain-
and S5 exhibited clear signs of strain-hardening behavior, with hardening CFfs had a ductility of 10 or more before reaching
an ultimate strength of >25% of the yield strength. Specimens the ultimate load. Furthermore, except for the specimens with
55 and 54 exhibited distinctly different behavior for cross sec- strain-hardening characteristics, the maximum value of ulti-
tions with a 31 % difference in the Dlt ratio. Specimens R5 mate load was 1.07 times the yield strength. Specimens that
and R6 showed a similar pattern, in that the post-yield behav- possessed strain-hardening characteristics had an ultimate
ior exhibited a significant transition from strain-hardening to strength that ranged up to a maximum of 1.41 times the yield
mildly elastic-plastic with a 27% increase in the Dlt ratio. strength.
Post-yield behavior for the remaining noncircular CFf shapes Calculated values of strength, according to the LRFD spec-
was clearly strain-softening. On the other hand, C I was clearly ifications, are also listed in Table 2. The modified yield
length of the specimen. The elastic stiffness was determined less compact cross sections.
and the measured modified elastic modulus of each specimen Fig. 6 illustrates the portion of the total CFT load shared
was listed under the Test Data heading in Table 2. Comparison by the steel section. The load shared by the steel tube P, was
between the measured and the LRFD computed elastic moduli computed by averaging the values of the longitudinal strain
illustrated substantial scatter in the ability to predict the stiff- gauges times the measured elastic modulus of the steel tube.
ness of the composite column. However, Per was recomputed Elastic, perfectly plastic strength was assumed for the steel
1.25
--- - - ----1- --- - ------1-- -.-- ---- r---- r--------1------ -----1
~-
cE
-... 1.20 ---·-------T - !-- -- - T - -- - --- _.1 -- - L_ - - - -- ----1
0..'"'
o 1.15
~
~ 1.10
...
Q
W
t; 1.05 ---
1---- I -----~--- t3 -~---------j
I-----r----i-l
2i
w
-----~-----!-----~\s2--r-1:
a::
ll.
oI- 1.00
~
:=I
0.95
I I
----------r-----------t--------- i----·--- I ; i S1 '
.[I
~
I iI
I
0 ----.~------;;0~.1~0------=-0.~15:-------;:0,...j.2"'"0------;:"-b-------:--!-=--
0.90:-
FIG. 4. Yield Load-to-Crltlcal Load Ratio with Respect to Column Slenderness Parameter
0..'"'
~
1.15 ----- - - - - -- -
~---t~3 ---I~-; +- -~4- -~
,
t-----._.---1
IIR8. !
- ----.
:
- -- - -- - -
I I
Q I I
1.10 -·-----·------I·~---·----·-- ---t--84-------------
f-------------- -1"--'
I - ---·---T-....---..-
...~ 1
Q
II • 1 R2
!I I
W
I-
u
2i
1.05 --- --- -c- .--.--. l. --
'
j--
I
I -- - -1-- ---- -- - --
w
a::
" I I R3 I I :
ll.
0
1.00
-----1 -----r----~~--I---t----~-~-----~
...
-.. I i - + f
I-
<
:=I
I-
~
0.95
i .... ~
I I
0.90
0 20 30 40 50 80
DIAMETER TO WALL THICKNESS RATIO (D I t)
FIG. 5. Yield Load-ta-Crltlcal Load with Respect to Oft Ratio
a.""
.....
a. 10
l-
LL
(..)
UJ 2
:I: 0.8
l-
LL
'1I
0
0
i=
I
I
0.6
~ I
z I
0
Ci5
en
\ I
UJ 0.4
a:: J
0-
Downloaded from ascelibrary.org by Iowa State University on 01/18/19. Copyright ASCE. For personal use only; all rights reserved.
:< I
0
(..)
0.2 I
I
...J
« I
~ /'
0% .0 0.2 0.4 0.6 0.8 1.0 12
STEEL TUBE TO TOTAL AXIAL LOAD RATIO ( Ps / P)
FIG. 6. Axlal-to-Vleld Load RatIo Compared to Load Shared by the Steel Tube
1.2
82 C1
R2
R6 81
R1 R5
84,R4
~ 1.0
a."" YIELD 8TRN -'---"---"--~-- -- -.. ---- -- ----- -- - - --- - -- - - - - - --Ci
..... . "T- ....__ 1--- --- ------. ,,-----
a. \ /R3
0 0.8 I t-.J
i= I
I
I
~ I
z
0 0.6
!
r I
/
Ci5
en
UJ
I
I
I
a:: I
0-
:<
0 0.4
!I I I
(..)
...J
«
I
I
I I
X
« 0.2
I
\
I
I
,/
.-'
0.0
0.0 01 0.2 0.3 04 0.5 0.6 0.7 0.8 0.9 1.0
STRAIN RATIO
tube once the yield strain was exceeded. In Fig. 6, specimens of any steel tube in the longitudinal direction. Table 2 lists
with the smallest and largest wall thickness are shown explic- whether the average longitudinal strain in the steel tube
itly, while the remaining data was bounded by the area shaded yielded before, simultaneously with, or after Py was imposed
in gray. Fig. 6 shows that steel sections with thicker walls on the CFT. In all cases in which the tube yielded after P y , it
maintained about the same portion of total load throughout occurred within a ductility fL of <1.3.
most of the load history. Sections with thinner walls exhibited An increase in the perimeter strains relative to the longitu-
an increase in the total shared by the steel tube as the load dinal strains, for the behavior shown in Fig. 7, would indicate
approached the yield strength of the CFT. On the other hand, confinement of the concrete core offered by the steel tube.
the contribution of the steel tube for CFTs with strain-hard- Except for the specimens shown explicitly, the strain ratio was
ening behavior decreased once the CFT yield strength was nearly constant and approximately equivalent to that of Pois-
reached. son's ratio, for an axial compression ratio <O.92Py • Beyond
Fig. 7 shows a comparison of the strain ratio of the steel this load ratio level, the strain ratios increased -15% as the
tube wall to the axially load ratio applied to the CFT. The load approached P y • Specimen C2 was the only column that
strain ratio was the absolute value of the perimeter strain di- appeared to yield in the lateral direction prior to yield of the
vided by the longitudinal strain. Strain values were averaged CFT. It should be noted that strains were difficult to measure
for the longitudinal and the lateral strain gauges on the spec- accurately after the steel tube yielded, particularly if the tube
imen. Strain ratio behavior for most specimens was bounded wall buckled locally. Therefore, at very high loads the strain
by the gray shaded region, with the location of the extreme readings became slightly erratic. However, these curves do il-
value for most specimens indicated. The specimens with strain lustrate trends in the tube wall behavior as the steel tube
ratio behavior well outside this bounded region were shown yielded about the longitudinal axis and the perimeter.
independently. Also shown by these plots was the earliest yield Fig. 8 shows examples of typical wall buckling that oc-
1132/ JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998
(a) (b)
FIG. 8. Typical Local Suckling of Steel Tube Wall: (a) Circular Tubes; (b) Square and Rectangular Tubes
curred for these specimens. Rectangular and square tubes had alytical models for simple axial CFT behavior, so that behavior
very similar local buckling behavior, and therefore only S3 is can be expanded to specimen sizes that are likely to be used
shown for an example. Clearly, most of the local wall buckling in construction. ABAQUS (ABAQUS 1994) was used for all
of the circular cross section was due to a radial expansion of nonlinear analytical modeling.
the tube. The square and rectangular tubes, however, showed The concrete core of the CFT was modeled using 20-node
clear signs of wall bulging. Local buckling occurred equally brick elements, with three translation degrees of freedom at
on every face for the square tube. For the rectangular CFT, each node. The three-dimensional concrete material model
local buckling was more extensive for the broad face than for available in ABAQUS was developed to simulate conditions
the narrow face. Fig. 8 illustrates how ineffective the flat tube with uniaxial strain and relatively low confining pressure.
wall was in confining the concrete core. In general, tubes with Therefore, reasonable results were expected with confinement
large Dlt ratios had more local wall buckling, with higher ap- on the order of one-fourth the uniaxial compressive stress or
parent distortions, compared to the sections with small Dlt less. Since the experimental results suggested that little con-
ratios. This behavior accounted for the differences observed in finement was observed for the concrete core prior to yield, this
the strain-hardening and strain-softening characteristics of the material model for the concrete was considered adequate. The
steel tube shapes. unconfined uniaxial stress-strain curve for the concrete used
At the end of the test, S3 was cut open in the vicinity of in this analysis is shown in Fig. 10. The stiffness beyond the
the locally buckled tube wall. Fig. 9 shows the condition of ultimate strength of the concrete was indicative of the amount
the tube wall and the concrete after failure of the specimen. of confinement expected. This portion of the curve was ad-
Although diagonal cracks were observed in the concrete core, justed according to the experimental results. The values listed
there were few gaps between the concrete and steel tube wall in Fig. 10 represent the concrete model used for all of the
near the locally buckled region. Furthermore, the concrete near finite-element analyses.
the severe tube wall distortions was usually not granulated. The steel tube was modeled using an 8-node shell element,
Consequently, it appeared that the concrete flowed plastically with five degrees of freedom at each node. Inelastic material
to fill the buckled shape of the tube wall and yet remained and geometric nonlinear behavior were used for this element.
cohesive. von Mises yield criteria defined the yield surface, and the
Prandtl-Reuss flow rule was used to determine inelastic de-
ANALYTICAL STUDY formations. No strain-hardening was assumed for the steel
tube. Therefore, if strain-hardening characteristics were ob-
Three-dimensional nonlinear finite-element models were de- served in CFT behavior, it was due primarily to the interaction
veloped to further study the axial load behavior of CFTs. Cal- between the steel and concrete components.
ibrated nonlinear models were needed to investigate behavior The interface, or gap, element, also available in ABAQUS,
of CFTs with dimensions that were different from the speci- was used for the interface between the concrete and the steel
mens tested. Therefore, this study focused on calibrating an- components. A schematic of the gap element is illustrated in
JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998/1133
en
en
w
a::
I-
f en
e
STRAIN
TENSION
2.000p& 90.000p&
Fig. 11. As shown, the element has two faces denoted as A sequently, the yield strength of the analytical model was ob-
and B. When the faces were in contact, normal forces devel- tained using a 0.2% offset. For this condition, the strength of
oped between the two materials resulting in frictional forces. the analytical model was -1.05 times the yield strength of the
A coefficient of friction of 0.25 was used in all of these ana- experimental specimen. While the strength of the CFf speci-
lytical models. On the other hand, if the gap element experi- men was slightly larger, it was clear the behavior of the ana-
enced tension, face A separated from face B, resulting in no lytical model was close to that of the experimental specimen,
contact between the concrete and steel, and consequently no thereby providing an opportunity to investigate trends in be-
bond developed. havior for larger size CFf columns. It is of interest to note
Fig. 12 shows the results obtained using this analytical fi- that local buckling of the tube wall in the analytical model
nite-element model compared to the results of experimental was similar to that observed from the experimental specimen.
Specimen C 1. Although elastic and inelastic behavior were To investigate the behavior of the Dlt ratio on larger di-
closely predicted, the yield strength was not as well defined ameter pipes, 15 finite-element models were analyzed. The cir-
for the analytical model as it was for the test specimen. Con- cular tube was investigated since this shape exhibited favora-
1134/ JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998
~ ~ LJA ISTEEL
B
and were equivalent to the values obtained in the test program.
The concrete strength was f: = 31 MPa, and the steel strength
( was F y = 317 MPa.
Three different circular tube diameters were investigated
with the finite-element analysis. The low end reflected the di-
mension of the tube used in the experimental study, while the
large diameters represented pipe sizes used in previous low-
to mid-rise building construction. Pipe lengths were selected
to obtain LID values of 5 and approximate KLirm values of
15. These LID values were consistent with the dimensions of
the test specimen used in the experimental study. As shown,
8-NODE SHELL KLirm was not sensitive to the tube wall thickness, and thus
Downloaded from ascelibrary.org by Iowa State University on 01/18/19. Copyright ASCE. For personal use only; all rights reserved.
~NT all of these tubes had approximately the same column slen-
derness of Ac "" 0.2.
It was desired to investigate a broad range of Dlt ratios for
each different tube diameter, so that values ranged from 10
11
LOAD
to 85 by increments of 15. This was accomplished by adjust-
ing the steel tube wall thickness to obtain the needed Dlt
FIG. 11. Finite-Element Modeling ratio. The LRFD specifies that the minimum wall thickness
I I:
i
~. J
00 3 6 9 12 15 18
AXIAL DEFORMAnONS (mm)
FIG. 12. Comparison between Numerical and Experimental Results
sive strength; however, the steel tube did not obtain its full
strength in compression. This was due to the biaxial stress
state, which reduced the compression strength once the tube
was confining the concrete core at later stages of loading.
Analytical results suggested that the trends observed in the
small dimensional tube columns, compared to the LRFD pre-
dicted values, diminish for larger diameter pipes. A compari-
son between the analytical finite-element strength and the val-
ues obtained from the LRFD specification is listed in Table 3.
For the 120-mm-diameter pipes the values of PylPcr decreased
with increasing Dlt ratios. This was similar to trends exhibited
by the experimental data. For the larger diameter tubes, how-
ever, analytical results suggest that the LRFD estimated the
yield load reasonably well for small values of Dlt, while
slightly unconservative values were obtained for large Dlt ra-
tios. The Dlt = 85 used in this analytical study would not be
allowed by the present restriction on the tube wall thickness.
However, for the nO-mm-diameter pipe the LRFD underes-
timated the strength of the Dlt = 55 and 70 CFTs by ~4%.
Approximate distributions of the concrete stresses at yield
and at ultimate are shown in Fig. 14 for all three diameter
tubes for Dlt = 25. Fig. 14 shows that for the small diameter
tube, the concrete stresses for most of the concrete core were
near the cylinder strength. At ultimate load for the 120-mm-
diameter pipe, the concrete stresses were almost 30% more
than the cylinder strength. This was due to the confinement of
the small concrete core provided by the steel tube. The mag-
nitude of stress in the concrete core for the large diameter
tubes at ultimate load was much less, with a maximum in-
crease of only 1.15!;.
IMPLICATION OF RESULTS
In general, the circular eFT columns offered more axial
ductility than the square or rectangular shapes. All of the cir-
FIG. 13. Analytical Force-Displacement Behavior for Dlf =25 cular pipes tested in this experimental study were categorized
1136/ JOURNAL OF STRUCTURAL ENGINEERING / OCTOBER 1998
distributed to the concrete core. Most CFTs with strain-soft- compressive strength is an essential component in the equation
ening characteristics showed an increase in load distributed to to determine the CFT strength for tubes larger than 600 mID
the steel tube once the CFT yielded. This was also an example in depth.
of the lack of confinement offered by the steel tube for CFTs
that exhibited strain-softening characteristics. An increase in CONCLUSIONS
the axial load distributed to the steel tube beyond the yield
strength of the composite column was detrimental to the post- This paper presents an experimental study on short, con-
yield performance of the square and rectangular tubes with centrically loaded, concrete-filled steel tube columns. Param-
thin walls. eters for this study included the shape of the steel tube and
Many buildings constructed with CFTs utilized the com- the D/t ratio. The influence of these parameters on the con-
posite column in braced frame structural systems. Results from finement of the concrete core and the compression shared by
this study suggested that circular CFT columns offer more the steel tube was investigated. An analytical investigation was
ductility than the square and rectangular columns. For exam- used to further study the effect of the D/t ratio on the load
ple, the ultimate load for the strain-hardening specimens oc- sharing between the concrete core and the steel tube. Several
curred at a ductility IJ. of 2:10, while the ultimate strength of aspects from these studies are worth noting.
strain-softening specimens occurred within IJ. < 2. Conse-
quently, square and rectangular tubes should be avoided for 1. Circular steel tubes offer much more post-yield axial
buildings constructed in regions of moderate-to-high seismic ductility than the square or rectangular tube sections. All
risk if CFT columns are desired. This will ensure that the circular tubes in this experimental study was classified
gravity load resisting elements have sufficient ductility in a as strain-hardening, while only the small D/t ratios, ap-
severe seismic event. It is possible, however, that depending proximately D/t < 20 for this study, exhibited strain-hard-
on the alternative cross sections, CFT behavior of square and ening characteristics for the square or rectangular tubes.
rectangular sections is an improvement compared to conven- 2. Measured perimeter-to-longitudinal strains of the steel
tional reinforced concrete, or perhaps even structure steel, col- tube suggest significant confinement is not present for
umns. most specimens until the axial load reaches almost 92%
Behavior exhibited by the test specimens also suggests pos- of the yield strength of the column. Furthermore, the
sible requirements for connection details to CFT columns. The square and rectangular tube walls, in most cases, did not
tube will unlikely provide confinement for the concrete core offer significant concrete core confinement beyond the
if the connection attaches to the steel tube only. For specimens yield load of the composite column.
in which the steel tube and concrete core were loaded simul- 3. Local wall buckling for the circular tubes occurred at an
taneously, these test results suggest that very little concrete axial ductility of 10 or more, while most local wall buck-
confinement occurred before 0.92Py • Even for loads above ling of the square and rectangular tubes occurred at a
0.92Py the increased confinement offered by the steel tube was ductility between 2 and 8.
minimal for most specimens until the yield strength was 4. For small dimensional concrete-filled steel tube columns,
reached. This study suggests that an optimum connection de- smaller D/t ratios provide a significant increase in yield
sign distributes load to the concrete core. For square and rec- load compared to the computed AISCILRFD Specifica-
tangular tubes, however, the load transferred to the CFT should tions (Manual 1994). Furthermore, the small D/t ratios
not be distributed exclusively to the core since they provide exhibited more favorable post-yield behavior. However,
much less confinement than the circular tube counterpart. these effects diminished for large diameter concrete-filled
Loads distributed primarily to the core in a square or rectan- tube columns.
gular tube may induce early local wall buckling of the steel 5. In almost all cases the AISCILRFD Specification pro-
tube. vides a reasonable, conservative estimate for the axial
Finally, the AISCILRFD predicted the yield capacity of the strength of the concrete-filled steel tube column. In the
CFT column reasonably well for this range of column slen- few cases that the LRFD predicted load underestimated
derness values. Compared to the test data, the LRFD specifi- the actual yield load, the predicted load was unconser-
cations predicted conservative strengths for tubes with small vative by only 5%.
D/t ratios, but closer estimates were obtained for tubes with
large D/t ratios. It should be noted, however, that experimental ACKNOWLEDGMENTS
data from this, and previous, studies were generally based on
data for small dimensional CFTs. Testing large dimensional Experimental results used in this paper are based on tests conducted
by Noburu Ito and Masakazu Masada at the University of Washington
CFTs has been prohibited due to the large forces needed to under the guidance of Prof. Neil M. Hawkins. who provided consent for
test the column to failure. The analytical study suggested that the use of this test data. His encouragement to consolidate this data is
the trends noted for the small CFTs diminish for large-size gratefully appreciated.